BS 7354 Substation Layout
BS 7354 Substation Layout
Incorporating
Amendment No. 1
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Design of high-voltage
open-terminal
stations —
Confirmed
October 2008
BS 7354:1990
The preparation of this British Standard was entrusted by the Power Electrical
Engineering Standards Policy Committee (PEL/-) to Technical Committee
PEL/92, upon which the following bodies were represented:
The following bodies were also represented in the drafting of the standard,
through subcommittees and panels:
Contents
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Page
Committees responsible Inside front cover
Foreword iii
Section 1. General
1.1 Scope 1
1.2 Definitions 1
1.3 Relevant acts and regulations 4
Section 2. Switching arrangements
2.1 General 5
2.2 Service continuity 5
2.3 Choice of switching arrangements 5
Section 3. Busbar connection and structures
3.1 General 8
3.2 Design parameters 8
3.3 Factor of safety 9
3.4 Insulators 9
3.5 Busbars and connections 10
3.6 Terminal fittings and clamps 10
3.7 Supporting structures 10
Section 4. Main switching equipment
4.1 General 11
4.2 Circuit-breakers 11
4.3 Disconnectors 11
4.4 Current transformers 11
4.5 Capacitive couplers and voltage transformers 11
4.6 Surge arresters 12
Section 5. Layout
5.1 General 13
5.2 Clearances 13
5.3 Access for maintenance 16
Section 6. Auxiliary equipment
6.1 Battery systems 17
6.2 Pressurized air systems for operation of equipment 17
6.3 Mobile gas handling plant 17
6.4 A.C. supplies 18
Section 7. Earthing
7.1 Symbols 20
7.2 General 20
7.3 Earthing 20
7.4 Design considerations 23
7.5 Interconnecting two station grids 28
Section 8. Control, indication and interlocking
8.1 Control 31
8.2 Indication 31
8.3 Interlocking 31
Section 9. Marking and identification
9.1 General 33
9.2 Phase marking of busbars and main connections 33
9.3 Equipment identification 33
© BSI 07-1999 i
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Page
9.4 Labels 33
Section 10. Insulation co-ordination
10.1 General 34
10.2 Selection of BIL 34
10.3 The location and use of rod-gap protection 34
10.4 Station direct lightning strike protection 35
10.5 Selection of SIL (for highest voltage for
equipment of 300 kV and above) 35
Appendix A Limitation of work areas 39
Appendix B Application of safety clearances 39
Appendix C Notes on the provision of safety clearances and work sections 39
Appendix D Example of an equipment item numbering system 42
Figure 1 — Commonly used switching arrangements 6
Figure 2 — Step voltage coefficient Cs 29
Figure 3 — Allowance touch and step voltages 30
Figure 4 — Protection zones 36
Figure 5 — Station shielding for 0.1 % failure rate for inner zones only 37
Figure 6 — Outer type protective zones (for a single spike,
for the outboard side of a row of spikes and for the outboard
side of an array of earthwires) 38
Figure 7 — Application of safety clearances 40
Figure 8 — Tertiary connected shunt reactor
numbering and nomenclature 47
Figure 9 — Equipment numbering system 48
Table 1 — Relevant standards and documents 2
Table 2 — Analysis of service continuity 7
Table 3 — Clearances: practice used within UK 15
Table 4 — Clearances: international practice 16
Table 5 — Typical loads 19
Table 6 — Maximum current density for earthing conductors and rods 21
Table 7 — Formulae for the calculation of the current to
ground from metallic sheathed cables 26
Table 8 — Reduction of touch voltage due to interconnecting grids A and B,
referred to the new station (B) touch voltage 28
Table 9 — Station BIL 35
Table 10 — Summary of numbering system for 400 kV
equipment, designated X 46
Publication(s) referred to Inside back cover
ii © BSI 07-1999
BS 7354:1990
Foreword
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
This British Standard has been prepared under the direction of the Power
Electrical Engineering Standards Policy Committee. It supersedes BS 162:1961,
which is withdrawn.
This code of practice represents a standard of good practice and takes the form of
recommendations.
Attention is drawn to the following Regulations:
a) The Health and Safety at Work etc. Act 1974;
b) The Factories Act 1961;
c) The Electricity at Work Regulations 1989;
d) The Electricity Supply Regulations 1988.
In a limited number of locations the Mines and Quarries Act 1954 may apply. It
is essential that all persons responsible for electrical work or operation make
themselves acquainted with the appropriate standing regulations and statutory
regulations.
It has been assumed in the drafting of this British Standard that the execution of
its provisions will be entrusted to appropriately qualified and experienced people
for whose guidance it has been prepared.
A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.
Compliance with a British Standard does not of itself confer immunity
from legal obligations.
Summary of pages
This document comprises a front cover, an inside front cover, pages i to iv,
pages 1 to 54, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on
the inside front cover.
iv
blank
BS 7354:1990
Section 1. General
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
1.2.1 1.2.10
switchgear clearance between poles
a general term covering switching devices and their the clearance between any conductive parts of
combination with associated control, measuring, adjacent poles
protective and regulating equipment and also 1.2.11
assemblies of such devices and equipment with clearance between connections of the same
associated interconnections, accessories, enclosures pole
and supporting structures, intended in principle for the total clearance between parts of the same pole
use in connection with generation, transmission, separable electrically from each other by a
distribution, and conversion of electric power mechanical switching device in the open position or
1.2.2 by any other means
open-type switchgear 1.2.12
switchgear in which the live parts are not provided short-circuit
with protective covers the connection of two or more points of different
1.2.3 poles or parts of a circuit through a negligible
outdoor open-type switchgear impedance
open-type switchgear suitable for installation in the 1.2.13
open air, i.e. capable of withstanding wind, rain, short-circuit current
snow, dirt deposits, condensation, ice and hoar-frost an overcurrent resulting from a short-circuit due to
1.2.4 a fault or an incorrect connection in an electric
indoor open-type switchgear circuit
open-type switchgear designed solely for 1.2.14
installation within a building or other housing, short-time withstand current (of a circuit)
where the open-type switchgear is protected against the current that a circuit or a switching device in the
wind, rain, snow, abnormal dirt deposits, abnormal closed position can carry during a specified short
condensation, ice and hoar-frost time under prescribed conditions of use and
behaviour
© BSI 07-1999 1
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
2 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 3
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
1.2.18
switching impulse level (SIL)
the voltage of the standard switching impulse
waveform that, under specified conditions, the
insulation of a device is designed to withstand
4 © BSI 07-1999
BS 7354:1990
© BSI 07-1999 5
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
6
BS 7354:1990
© BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
A Single busbar 3 4
B Single busbar with bus section circuit-breaker 3 3
C Double busbar 3 2 (see note 1)
D Double busbar with by-pass facilities 2 (see note 1) 2 (see note 1)
E Double busbar with double circuit-breaker 1 or 2 1 or 2
F Single busbar with transfer bar 2 (see note 1) 3
G Double busbar with 1½ circuit-breaker 1 or 2 (see note 2) 1 or 3 (see note 3)
H Mesh 1 or 2 3
I Three switch with by-pass 1 or 2 3
J One switch with by-pass 1 or 2 3
NOTE 1 To achieve these stated categories requires the inclusion of a bus coupler switch.
NOTE 2 Category 1 applies for maintenance conditions. Category 2 applies for fault conditions.
NOTE 3 Category 1 applies if maintenance is required on the busbars. Category 3 applies if a fault occurs or maintenance is
required on circuit connections identified with an asterisk in Figure 1.
© BSI 07-1999 7
BS 7354:1990
(1)
8 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
When multiple conductors are employed for a single 3.2.4 Force due to deadweight
phase, allowance should be made for the short time When calculating the deadweight of conductor or
“snatch” force produced by the mutual attraction other items, the mass of an even thickness of ice
between parallel conductors. This force is a function should be included where applicable.
of the conductor spacing and distance between
spacers. Tests have shown that this force is not The thickness of ice should be stated by the user and
coincident with the maximum short-circuit forces its mass per unit volume calculated at 912 kg/m3.
between phases.
3.3 Factor of safety
It has been found in practice that structures
designed for normal working and dynamic load due Since the method described in 3.2 provides forces
to short-circuit forces between phases have been which are known maxima then the resultant
adequate to meet the impulse forces due to multiple stresses can be up to the maximum
conductors. allowable, e.g.:
3.2.3 Force due to wind loading a) porcelain: guaranteed cantilever breaking
strength;
It is essential that a maximum wind speed is stated
by the user, and for calculation purposes this will be b) drawn or extruded metals: guaranteed
assumed to be acting normal to the axis of the minimum proof stress;
conductor or item of equipment. c) cast metals: manufacturer’s recommendation
If the wind speed varies with height, this fact should and/or manufacturer’s experience.
be included in the information supplied. For UK
practice, CP 3: Chapter V-2 gives further 3.4 Insulators
information. This document indicates that wind 3.4.1 Post-type insulators for use as busbar or
force is affected by height, type of ground and size of connection supports
obstacles, e.g. buildings. Normally of porcelain construction, the location of
For a typical open-type station, the wind pressure P post-type insulators for use as busbar or connection
(in N/m2) for a nominal height of 10.0 m is given by: supports is largely dictated by the form of layout
(3) adopted and the maximum permissible conductor
P = 0.613V2
span between adjacent supports.
where In selecting the correct insulator for a particular
V is the windspeed (in m/s). application, it is necessary for the designer to
determine the following.
The force F (in N) applied to the conductor or item of
equipment is given by: a) The mechanical strength required. This can be
readily determined by the method described
F = PA (4)
in 3.2.
where b) The electrical requirements. This data will
A is the projected surface area (in m2). determine the overall height of the insulator, the
minimum height being dictated by the clearance
The force obtained from equation (4) is affected by
requirements of 5.2.
the shape of the item concerned. CP 3: Chapter V-2
provides force coefficients (Cf) for this purpose, and c) The minimum surface creepage. This will
equation (4) becomes: normally be specified to suit the pollution
conditions prevailing on site.
F = PACf (5)
3.4.2 Tension insulators
For items of equipment normally found in open-type Tension insulators are normally of the cap and pin
substations the value of Cf rarely exceeds 1.0 and type and it is common practice to use overhead line
for practical design purposes the following values insulators since these are established designs.
can be applied: Appropriate insulators should be selected having
a) all cylindrical shapes including regard to the mechanical strength and the number
insulators, Cf = 0.7; required in series for the electrical requirements.
b) rectangular shapes, Cf = 1.0. Units with different profiles are available and this
enables selection to suit the specified creepage
When applying the above, allowance should be
length.
made for increase in dimensions due to ice where
appropriate. Lattice structures should be treated as
a special case in accordance with CP 3: Chapter V-2.
© BSI 07-1999 9
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
3.5 Busbars and connections Since joint faces between clamps and conductors are
subject to deterioration, steps should be taken to
The conductors used for busbars and connections
ensure their effective longevity by preparation of
will in general be of either rigid, tubular or flexible
the surfaces immediately prior to making the joint.
form, the choice largely being determined by the
type of substation construction adopted. Preparation is particularly important where high
resistance oxides form quickly, as in the case of
The materials used should preferably be either aluminium, and where electrolytic action takes
copper or aluminium, to provide the highest
place, as in the case of dissimilar metals.
current-carrying capacity for a given size.
All joints should be protected against the ingress of
Where flexible tensioned conductors are applied the
moisture, where this would cause corrosive action,
size should be determined for both the mechanical
by the application of appropriate greases or sealants
strength and electrical requirements. immediately after the joint has been made and in
The size of tubular conductors can be determined in accordance with manufacturer’s recommendations
a similar manner and, particularly when applied to or instructions.
busbars, the maximum possible length or span
Manufacturer’s recommended procedures should be
should be utilized since this requires the minimum
followed.
number of supporting insulators. These rigid forms
of connection are prone to wind induced vibration 3.7 Supporting structures
and care should be taken to ensure that the
maximum span determined from mechanical Structures for busbar supports should provide the
strength is adjusted as necessary to avoid this minimum insulation clearance given in Table 3 and
phenomenon. Table 4, and be designed to withstand static and
As a guide, a tubular conductor rigidly fixed at one dynamic loads. The latter can be determined from
end and supported at the other is generally the method described in 3.2 but they should also
insensitive to vibration if the material frequency of comply with appropriate national standards.
oscillation is greater than 2.75 Hz.
10 © BSI 07-1999
BS 7354:1990
© BSI 07-1999 11
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
12 © BSI 07-1999
BS 7354:1990
Section 5. Layout
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 13
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
14 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
5.2.4 Increased switching impulse level (SlL) 5.2.7 Effect of hand held tool
safety clearance A hand held tool can increase the reach of a person.
Where the switching impulse level (SIL) is the An addition to the personal reach values (both
determining overvoltage, an additional clearance vertical and horizontal) of 300 mm is included by
may be added to those given in 5.2.3 as a provision some UK authorities.
against the infrequent tendency for switching surge 5.2.8 Operational access clearance
flashovers not to occur across the shortest gap,
(anomalous flashover). The distance from ground level to the nearest point
of any live metal or connections, necessary to permit
5.2.5 Personal reach pedestrian access for operational purposes should
The vertical reach of a person with upstretched be not less than the safety clearance given in 5.2.6.
hand should be taken as 2.4 m. The horizontal reach The same clearance is necessary to the top of
should be taken as 1.4 m. vehicles accessing the operational areas.
5.2.6 Safety clearance 5.2.9 Insulation height
The safety clearances given in Table 3, columns 3 The lowest part of any high-voltage insulation
and 4 represent practice in the UK and are derived should be not less than 2.1 m above ground level to
by adding the basic electrical clearance (see 5.2.3) provide for pedestrian access, e.g. the pedestal
and the personal reach (see 5.2.5). The safety insulator bases. Table 3 and Table 4 give the
clearances in Table 4, columns 4 and 5 represent the recommended clearances from the lowest insulation
clearances recommended for constructions outside part of a support insulator to ground with respect to
the UK and are derived similarly up to 750 kV BIL the insulation withstand level.
but include an increased SIL safety clearance
(see 5.2.4) at appropriate levels as a provision
against anomalous flashover.
© BSI 07-1999 15
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
16 © BSI 07-1999
BS 7354:1990
1)
1 mmHg = 0.133 kPa.
© BSI 07-1999 17
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Where smaller quantities of gas are used and 6.4.2 Typical a.c. supply loads and rating
retrieval is not required a small gas handling plant A list of the more common a.c. loads to be supplied
may be specified to enable the equipment to be is given in Table 5 which also indicates the normal
safely filled and vented. range of power requirements, although these are
The plant should be capable of evacuating the dependent upon the size of the station and the type
largest volume specified and filtering the gas of equipment installed. The rating of the a.c. supply
extracted to ensure the expelled gas is safe, should take account of the diversity factors for each
i.e. non-toxic. load. This factor may be a matter of judgement and
The plant should be capable of evacuating air at for guidance an overall diversity factor
atmospheric pressure from the equipment and of 0.7 applied to the sum of the individual loads
replenishing the gas at the end of a maintenance typically can be used in determining the supply
operation at ambient temperatures greater rating.
than – 20 °C. The extraction and filling times Where there are large motor loads, cognizance of the
should be as for a large gas handling plant. voltage drop due to motor starting current should be
The plant should be mobile and able to be taken into account to ensure the voltage remains
manoeuvred on a concrete surface by one person. over 80 % of nominal. It may be preferable to err on
the high side for the supply rating to ensure that
6.4 A.C. supplies there is no undue excessive voltage drop due to
regulation and for unforeseen future loads.
6.4.1 General
6.4.3 Essential supplies
Station a.c. supplies may be categorized into
essential and non-essential groups. Some supplies Supplies which should always be available, such as
should be continuously available without any break the supply to a computerized SCADA system which
whilst others can operate with a brief or long break. can give incorrect signals with a transient loss of
For example, system control and data acquisition supply, should be fed by an uninterruptable power
(SCADA) computerized systems are intolerable of a supply (UPS), i.e. an inverted a.c. supply in
break whereas transformer tap-changers requiring combination with a battery.
a firm supply can tolerate a brief loss without Other supplies, such as to the transformer
danger to the equipment. These two examples are tap-change and cooling fans or pump motors, can
quite common and the status of other supplies to a accept a limited supply interruption not exceeding a
large extent is a matter of custom. few minutes. A diesel generator automatically
The sources of the a.c. supplies should be selected run-up and connected in the event of the main
with due regard to the level of integrity required; supply failure is adequate for this purpose. The
alternative costs may vary and therefore due rating of the diesel generator can be limited to that
consideration of economics, security of supply and necessary for only these types of essential loads.
the integrity required should be made when Alternatively, duplicate auxiliary transformers, or
selecting the preferred sources. Duplicate power one auxiliary transformer together with a local
sources should not be paralleled and interlocking of distribution network supply with automatic
switchgear to prevent this occurrence should be changeover facilities, may adequately provide an
provided. acceptable level of risk for these loads. If it is
deemed that the risk should be minimal a standby
For security of supply, it is good practice to have two
generator should also be provided.
independent sources of supply with the failure of
one supply automatically initiating changeover to
the alternative.
The equipment for a.c. supplies should comply with
PD 6499 for insulation co-ordination, BS 5420 for
the degree of protection, and with the relevant
National Practice and Specifications.
18 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 19
BS 7354:1990
Section 7. Earthing
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
A area occupied by the grid The design of the earthing installation should
m2
ensure that when current is conducted to earth
a cross-sectional area of m2 either during a fault to earth of the system or
conductors particularly when the fault to earth is within the
Cs step voltage coefficient — station, the voltage difference between parts with
D spacing between parallel m which a person may be in simultaneous contact is
conductors kept to a safe value. Current paths through the body
d diameter of buried conductor m are generally those between the hand and one or
E system voltage V both feet, usually referred to as touch voltage or
h depth of burial of grid m between one foot and the other usually referred to as
hr depth of rock/stone covering m step voltage. A procedure for these calculations is
given in 7.4.
IC cable fault current A
During fault conditions the voltage difference
IL line fault current A between equipment and the main body of earth
It tolerable body current for current A should be controlled, to ensure that insulation
duration breakdown or burning does not occur on apparatus
K two layer reflection coefficient — connected to points outside the substation. Cable
ki current distribution factor — sheaths, metallic pipes, etc. which are connected to
KR constant dependent on number, — a remotely earthed structure but isolated from the
position and length of earth station earth by insulation will transfer the
rods connected to the grid potential of that structure into the station.
Similarly, the voltage difference between earth
L total length of buried grid m
points within the switching station should be
conductors
controlled.
n number of parallel —
conductors/cables/lines 7.3 Earthing
nR total effective number of rods —
7.3.1 General
R resistance of grid to earth 7
RT lower footing resistance 7 In order to satisfy 7.2 the structures, equipment and
metalwork in a station should be electrically
r equivalent circular plate radius m connected by permanent connections to electrodes in
t duration of earth fault s contact with the general body of earth, so as to
V grid potential rise (GPR) V present a sufficiently low impedance path for fault
Vs step voltage V currents. This should ensure that the potential of
VT touch voltage V the station as a whole rises uniformly with respect
Vx voltage at x metres from grid V to the general body of earth during fault conditions
edge and dangerous potential differences will not appear
between individual items of equipment.
x distance from grid m
ZC cable sheath impedance to earth 7
Zg earthwire impedance to ground 7
per span
ZL line earthwire chain impedance 7
to earth
ZT overall impedance to earth 7
20 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 21
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
b) independently earthing the fence and placing it 7.3.6 Incoming overhead lines
outside the grid area at a convenient place where Where the earthwires of overhead transmission
the potential gradient from the grid edge is lines end at the terminal towers and are not
acceptably low. connected to a point on the station structure, the
In the first of the above procedures, the fence base of the terminal tower should be tied solidly to
potential rises with that of the earth grid and may the station earth grid. By so doing, a substantial
assist in reducing the station earth resistance by proportion of the ground current may be diverted
increasing the effective area and due to the addition away from the station earth grid, and advantage can
of fence earth rods. It also obviates any risk of be taken of this situation in the design of the grid. If
inadvertent electrical connection between the fence the tower lies outside the station fence, the
and the earth grid. A perimeter conductor connected connections between the station grid and the base of
to the earth grid can with advantage be laid a short the tower should be buried and insulated where
distance (approximately 1 m) outside the fence and they pass under an independently earthed fence, to
parallel to it, thus decreasing the possible touch ensure isolation from the fence.
potential to which a person or animal outside the It should be realized, however, that connecting the
fence may be subjected. This perimeter conductor station grid to the transmission line earthwires will
may incur significant cost and there may be usually have the overall effect of increasing the
problems of land ownership or pilfering of the buried hazard at the tower bases, while lessening it at the
conductor which degrades an otherwise sound station. This is due to the fact that each of the
engineering procedure. The fence should be bonded nearby towers will share in each voltage rise of the
electrically to the grid on each side. The connections station grid whatever the cause, instead of being
should be located adjacent to each corner and at affected only by a local insulation failure or
each crossing of the fence by overhead lines, and flashover at one of the towers. On the other hand,
their maximum spacing in metres should not when such a tower fault occurs, the effect of the
exceed 0.25r (where r is the equivalent circular connected station grid should decrease the
plate radius). Gate posts forming part of the fence magnitude of gradients near the tower bases.
should be connected together below ground.
7.3.7 Services
Where the fence and the attached earth rods are
connected to the grid they become the edge of the For excessive potential rises of the station with
grid. The area within the fence should be used to respect to the outside surrounding earth which may
determine the radius r (see 7.4.2). However, the ensue during earth fault conditions, special care is
fence should not be taken into account when necessary with services such as water pipes, railway
determining the number of parallel buried lines, and telephone or pilot cables which enter the
conductors, or for the total length of conductor when station. Water pipes and cable sheaths or armour
determining the resistance. (which are more or less in direct contact with soil)
should be tied to one station grid, to avoid hazards
Where the fence and the associated earth rods are
within the station area.
not connected to the grid, the fence voltage may
typically be taken to be 70 % of that of the grid Where it is thought desirable to prevent transferred
potential rise (GPR). Care should be exercised in potentials outside the grid boundary, insulating
making this assumption, as it is true only when all sections can be inserted. It is essential, however,
metalwork in the ground connected to the grid is that these insulating sections are a minimum
insulated for 2 m each side of the fence and when no of 4 m, to avoid shunting by the adjacent soil.
local large differences of soil resistivity, compared Cement or plastics piping is often suitable for water
with the average value, could cause a closer voltage pipes. With railway lines, two sets of insulating
coupling of the fence and the grid. joints will be necessary to provide against the
shunting of a single set by the adjacent soil or a
Particular care should be taken with water pipes,
metal waggon passing over the track.
cables, etc., and these should be insulated where
they pass below or close to the fence. This insulation In severe cases, isolating transformers may be
need only be nominal, so a few layers of PVC tape necessary for telephone connections. It may be
covering can be a good safeguard. Where necessary to treat pilot cables as live conductors and
disconnecting links and connections are provided to they should be insulated from the station earth
allow the fence to be connected, the link box should system by insulation adequate to withstand the
be located 2 m from the fence and the connection maximum grid potential rise. In the case of
between it and the fence insulated to maintain non-cross-bonded flat formation power cables, it is
separation of the fence and grid when they are the practice to run an earth conductor along with
required to be independent. the cables.
22 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 23
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
7.4.3 Calculation of electrode resistance 7.4.4 Calculation of grid potential rise (GPR)
An approximate simple expression for the Each of the overhead line earthwires and
resistance R (in 7) of a thin solid circular plate continuously earthed cable sheaths which are
buried to a depth of 0.5 m in soil having a uniform connected to the grid will assist in reducing the sum
resistivity Ô (in 7 m) is: impedance to earth. As well as determining the grid
resistance, using the expressions given in 7.4.3, the
(8) effective impedance of each overhead line and cable
sheath has to be established. It is necessary that all
As a grid is not a solid circular plate but typically is these are summated as parallel impedances in the
made up of a grid of buried conductors having a general expression for the overall impedance to
combined length of L metres, a simple approximate earth (in 7) as follows:
expression which does not take into account the
burial depth h is: (12)
(9)
where the symbols are as defined in 7.1.
A more accurate expression which incorporates h The effective impedance of an overhead line
and also the effect of earth rods connected to the grid earthwire and its connections to earth via the
is: towers is given by the expression:
ZL = {0.5 Zg + (ZgRT)0.5} (13)
(10)
where the symbols are as defined in 7.1.
The impedance of a cable sheath to earth is not very
where sensitive to the size of the cable or the depth of its
burial. It varies with the length of the cable l and
KR is a constant dependent upon the number, eventually attains a constant value. The impedance
position and length of earth rods connected ZC (in 7) can be obtained from published data or
to the grid given by the following equation: from the following:
(11) (14)
KR = (1 + nRlR2/10r2)
where or
lR is the length of the earth rods (in m). (15)
24 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
The GPR is the product of ZT and the sum of the NOTE For flat strip conductor use an equivalent diameter,
currents from each line and/or cable circuit. Each d = (width/ ;).
source current should be taken as the foreseen The resistance R is dependent upon the grid depth
ultimate development source current at its position h (in m) and on any earth rods connected to it, as
in the system. Each source current has then to be shown in 7.4.3.
reduced to take account of the current which will be There are limitations which apply to both national
induced in the overhead earthwire or cable sheath, practices, as follows:
as these currents do not pass through the grid. Thus n # 25
GPR (in V) is given by:
0.25 m # h # 2.5 m
GPR = Z T { I L1 ( 1 – È 1 )… I Ln ( 1 – È n ) +
d < 0.25 h
+ I C1 ¶ 1 + … I Cn ¶ n } (16) D > 2.5 m
(21)
(17)
or
(18)
© BSI 07-1999 25
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Table 7 — Formulae for the calculation of the current to ground from metallic sheathed cables
Cable circuit Type of cable C Formulae for per unit ground current " = Igr/If
Key
a is the conductor cross-sectional area (in mm2)
E is the system voltage (in kV)
l is the length of the cable (in km)
Igr is the ground return current (in A)
Isr is the sheath return current (in A)
If is the fault current (in A)
R AB = R A + R B
PILCSWA paper insulated lead cables steel wire armoured
PICAS paper insulated corrugated aluminium sheath
PILC paper insulated lead cables
The constant C reflects the physical construction of the sheath; it may vary ± 15 % depending on the manufacturer. For cross-linked
polyethylene (XLPE) or synthetic insulation cables use 0.9C for the equivalent construction paper insulated cable, for steel wire
armoured (SWA) copper screened cables use 1.5C, and for unarmoured copper screened cables use a C value of 450.
2)
Publications available from International Telecommunications Union (ITU), Place des Nations, CH 1211 Geneva 20,
Switzerland.
26 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
The expression usually adopted to calculate the hot The general expression for allowable touch voltage
zone boundary Vx (in V) (measured from the grid VT, for which the two feet are in parallel in the
edge) is derived from: conceived circuit is:
(22) VT = I t body resistance +
© BSI 07-1999 27
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
28 © BSI 07-1999
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999
Figure 2 — Step voltage coefficient Cs
29
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
30
BS 7354:1990
© BSI 07-1999
BS 7354:1990
© BSI 07-1999 31
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
32 © BSI 07-1999
BS 7354:1990
© BSI 07-1999 33
BS 7354:1990
10.1 General For equipment rated 123 kV and above there are a
varying number of choices of BIL, although these
The main objectives of insulation co-ordination are
are restricted by compatibility with a switching
to minimize the interruptions to the supply and at
impulse level (SIL) at 300 kV and above. Other
the same time to confine those unavoidable
constraints in the choice of BIL are the frequency of
insulation failures to the least damaging location. lightning (IKL level) and airborne pollution, both of
Outdoor high-voltage switchgear installed in a which mitigate against choosing the lower values.
station may be subjected to the following. Table 9 shows the most commonly specified BIL
a) Lightning overvoltages: by a direct strike to the levels for system voltages of 123 kV and above.
station overhead connections or from the When surge arresters are installed at each line
occurrence of a strike to the overhead line towers, entry to the station, a BIL of one level lower than
overhead earthwires or the main conductors. some of the values shown in Table 9 could be
Voltages can also be induced on the main selected; however studies should be made showing
conductor from strikes to ground in the vicinity of the amplitudes of reflected voltages on the station
the lines but it is generally accepted that these connections to confirm the choice.
induced voltages are of significance only to lines All the equipment for use at the same operating
of 66 kV and below. voltage in a station should normally have the same
b) Switching overvoltages: occurring when the BIL. An exception to this is that equipment directly
operation of the switchgear creates an protected by a surge arrester, e.g. transformers,
overvoltage, e.g. due to energizing a line or by may have a lower BIL commensurate with the
chopping low inductive currents. protection afforded by the surge arrester. Usually
c) Temporary power frequency overvoltages: one BIL level lower is used.
caused by a sudden reduction of load impedance,
usually due to switching at another station. 10.3 The location and use of rod-gap
protection
10.2 Selection of BIL Rod-gap flashover causes an earth fault. The
In general terms, the exposure to lightning strike is current is limited only by the system impedance and
a function of the ground area of the station plus a will initiate tripping of the circuit-breakers by the
ground area which is equivalent to four times the protective relay system of the zone in which the
line tower height times the line length, for each line. rod-gap is situated. Preferably rod-gaps should be
Due to attenuation of the travelling voltage wave on located at the terminal tower tension insulators, in
a line, the pertinent length of line usually is the path of incoming lightning overvoltage surges. If
from 2 km to 5 km, as the voltage is reduced to a the connection distance from the terminal tower
harmless amplitude after travelling more than this location to the line disconnector is too great to
distance. Even so, the area of significant exposure of prevent an excessive voltage occurring at the latter,
the lines usually is many times greater than that of rod-gaps should be located at the disconnector as
the station, hence the greatest danger is a line strike well. For the terminal tower located rod-gap to
rather than a direct strike to a station. effectively protect the line disconnector, the
connection distance (in m) should not exceed the
The probability of line insulation failure due to a
length determined from the following empirical
direct strike can be reduced to an acceptably low
equation:
value by the application of overhead earthwires to
the lines and wires or structure spikes to a station Separation distance = 0.6 (BIL – rod-gap
as discussed in 10.4. flashover voltage in kV) (29)
The probability of a station insulation failure can
Rod-gaps elsewhere in the station are unnecessary
also be reduced to an acceptable value by the choice
unless they are required by the manufacturer for
of BIL and the application of surge arresters and
the insulation co-ordination of equipment, e.g. to
rod-gaps. ensure any flashover occurs externally rather than
For system voltages of highest voltage for internally on oil or gas filled equipment.
equipment up to 36 kV, BS 5622-1 allows two
alternative BILs nominated as list 1 and list 2. Only
if rigorous studies are made confirming the lower
value of list 1 will be adequate should this lower
value be selected, otherwise the higher list 2 value
should be selected. For values of 52 kV and 72.5 kV
there is only one recommended value of BIL in
BS 5622-2.
34 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
IKL 0 to 30 and light pollution 450 550 650 850 1 050 1 175 1 300 1 425
IKL 30 to 90 or heavy pollution 550 550 650 950 1 050 1 175 1 300 1 425
IKL > 90 or very heavy polution 550 650 750 1 050 1 050 1 300a 1 425 1 550b
a A significant proportion of special cases require a BIL greater than the maximum level of 1 175 kV.
b In some cases of extreme pollution, a level of 1 800 kV may be appropriate.
© BSI 07-1999 35
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
36
BS 7354:1990
© BSI 07-1999
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999
Figure 5 — Station shielding for 0.1 % failure rate for inner zones only
37
BS 7354:1990
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Figure 6 — Outer type protective zones (for a single spike, for the outboard side of a row of
spikes and for the outboard side of an array of earthwires)
38 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 39
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
40
BS 7354:1990
© BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Any work, therefore, that can be done from these In the simplest case where no provision is made for
positions and with the provisos given in items a) the sub-division of a station for the purpose of work,
to c) may be carried out without the necessity for the the whole of the station, including any incoming
further precautions referred to in C.3. Such work circuits, should be made dead and earthed before it
normally includes: is safe to do work on any of the equipment. This
1) local operation of the equipment on site, procedure is seldom convenient operationally and
e.g. disconnector, earth switches, on-load provision is usually made for sub-division of the
tap-changers of transformers and station equipment by disconnector and the creation
circuit-breakers; of work sections. The nature and extent of this
sub-division will depend on how much of the station
2) inspection of the equipment from ground level
can, for operational reasons, be taken out of
or permanent access ways;
commission at any one time, having regard also to
3) painting (with a normal brush) the equipment, the frequency of the particular maintenance work
supporting steelwork and other parts, as far as a required. The extent of sub-division provided in the
man can reach from the ground or permitted design of the station is therefore normally a matter
access; for agreement between purchaser and
4) normal testing and adjustment of switchgear manufacturer.
operating and transformer tap-changing Consideration should be given to providing for the
mechanism; following work without the necessity for
5) testing of control cables, protective gear and interruption of any circuit other than that
compressed air systems. containing the equipment upon which it is
It is recommended that, unless otherwise required necessary to work:
by the purchaser, the disposition of equipment a) drawing off and replenishment of insulating
should be such as to provide the necessary medium in circuit-breakers and transformers;
clearances throughout the station which would b) inspection or replacement of circuit-breaker
enable the above work to be done in safety while all contacts and interrupting parts;
the equipment is live.
c) inspection and maintenance of transformer
The occupier should make his own arrangements for tap-changing equipment;
special conditions such as the carrying of ladders
d) cleaning of bushings or insulators associated
and other long objects in live stations.
with circuit-breakers or transformers.
C.3 Work requiring isolation of apparatus
It is necessary to provide for work areas of sufficient
Work which involves leaving ground level, deviating dimensions to cover not only the positions that a
from permitted access ways or infringing the man may occupy in carrying out the work, but also
provisos set out in items a) to c) of C.2 makes it the means of access to these positions. The
necessary that at least some of the apparatus is conductors of circuits other than that containing the
made dead and earthed. equipment worked on, which it is desired to retain
The extent to which the substation equipment has live and in service during the work, should then be
to be made dead is dictated by the space required to so arranged as to provide the safety clearances from
do the work intended, and the preservation of safety them to the boundary of the work area.
clearances around this space. It should be noted that the whole of the equipment
on which work is being done need not be within the
limits of the work area, provided that the parts lying
outside it can be satisfactorily reached by a man
standing at a point within these limits, and provided
that he is prevented from moving beyond that point
in the direction of live conductors.
© BSI 07-1999 41
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
42 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999 43
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
44 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
D.5.3 The second number should be used to denote **7 circuit-breaker disconnector, busbar side
the class of switch group as given in the following **8 main bus disconnector (2nd choice)
list (the first and third number are represented by reactor tie bus disconnector
asterisks):
**9 reserve bus disconector (2nd choice)
*0* line Where more than one item in a group qualifies for a
particular number the number should be suffixed by
*1* transformer high-voltage side main busbar
consecutive letters, commencing from the circuit
section
termination inwards to the busbar selector
*2* mesh busbar interconnector (within a disconnectors.
station) In the case of banked circuits the numbers should be
*3* bus coupler suffixed by the identification letter of the
*4* static series compensators, e.g. reactors, appropriate circuit in those instances where the
capacitors items are not common to all the circuits of the bank.
In general, a suffix should not be used for items
*5* static shunt compensators, e.g. reactors, common to all circuits for the bank except in those
capacitors instances where the number is repeated, when an
*6* reserve busbar section appropriate letter suffix should be added.
*7* (spare)
*8* transformer low-voltage side generator
*9* synchronous compensator
© BSI 07-1999 45
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
46 © BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
Generator circuit breaker (where two per generator, main busbar) Xa90
Generator transformer earthing switch Xa91
Generator by-pass disconnector Xa92
Generator transformer disconnector Xa93
Main bus disconnector Xa94
Generator circuit-breaker where two per generator (reserve busbar) or switching disconnector Xa95
Reserve bus disconnector Xa96
Circuit-breaker disconnector (busbar side) Xa97
a
Denotes sequence of switch groups (see D.5.2).
NOTE Suitable suffix to be added to 4 ATI if supergrid transformer voltage lower than 132 kV.
Figure 8 — Tertiary connected shunt reactor numbering and nomenclature
© BSI 07-1999 47
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
48
BS 7354:1990
© BSI 07-1999
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999
Figure 9 — Equipment numbering system
49
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
50
BS 7354:1990
© BSI 07-1999
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
© BSI 07-1999
Figure 9 — Equipment numbering system
51
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
52
BS 7354:1990
© BSI 07-1999
BS 7354:1990
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
NOTE The three switch mesh is as shown, for the one switch mesh omit 110 and 210.
(i) One or three switch mesh with by-pass
Figure 9 — Equipment numbering system
© BSI 07-1999 53
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
54
blank
BS 7354:1990
Publication(s) referred to
Licensed copy: [email protected] [email protected], Mott Macdonald, Version correct as of 25/03/2013 05:06, (c) The British Standards Institution 2013
3)
Published by and available from Electric Power Research Institute, 1019 19th Street, Washington DC 98201, USA.
4)
Published by and available from Institute of Electrical and Electronic Engineers, Service Centre, 445 Hoes Lane, Piscataway,
New Jersey 088 54, USA.
© BSI 07-1999
BS 7354:1990
Revisions
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: 020 8996 9000. Fax: 020 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.
Information on standards
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the internationalstandardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.
This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.