F 3349 (1133)

F 3349

F 3349: 8-channel output module


safety-related, applicable up to SIL 3 according to IEC 61508
• resistive or inductive load up to 500 mA (at L+ 24 V or 48 V)
• lamp load up to 10 W
• with integrated safety shutdown
• with safe isolation, with line monitoring

Front
cable plug

Figure 1: Block diagram and front cable plug

Appertaining function block: HB-BLD-3 or HB-BLD-4

The module is automatically tested during operation. The main test routines are:
• Reading back of the output signals. The operating point of the 0-signal read back
is ≤ 6.5 V,
• Switching capability of the safety shutdown, cross-talking (walking-bit test),
• Line monitoring.

Nominal output voltage 24 V or 48 V, acc. to supply of L+ via cable plug,


500 mA, short-circuit-proof
Space requirement 4 SU
Operating data 5 VDC / 0.15 A,
24 VDC / 200 mA (via rear bus system)
24/48 VDC / 50 mA plus load (via cable plug)

All rights reserved. Equipment subject to change without notice: 1/6


HIMA Paul Hildebrandt GmbH + Co KG, P.O. Box 1261, 68777 Brühl
F 3349 (1133)

Cable plug for outputs 24 VDC


Channel Connection Color
1 b2 BN
b18 WH
2 b4 YE
b20 GN
3 b6 PK
b22 GY
4 b8 RD
b24 BU
5 b10 VT Cable
b26 BK LiYY 16 x 0.5 mm2
6 b12 WHGN
b28 WHBN
7 b14 WHGY
b30 WHYE
8 b16 WHBU
b32 WHPK
L- 24 V z2 BK Flat pin plug 6.3 x 0.8 mm
L+ 24 V z12 RD
Wire: q = 1 mm2, l = 750 mm

Lead marking of the cable plug Z 7150 / 3349 / C5 / 24P2


2-pole connection of the load
Figure 2: Lead marking of the cable plug for outputs 24 VDC

Cable plug for outputs 48 VDC


Channel Connection Color
1 b2 BN
b18 WH
2 b4 YE
b20 GN
3 b6 PK
b22 GY
4 b8 RD
b24 BU
5 b10 VT Cable
b26 BK LiYY 16 x 0.5 mm2
6 b12 WHGN
b28 WHBN
7 b14 WHGY
b30 WHYE
8 b16 WHBU
b32 WHPK
-48 V z2 BN Cable
+48 V z12 WH
LiYY 2 x 1 mm2

Lead marking of the cable plug Z 7150 / 3349 / C5 / 48P2


2-pole connection of the load
Figure 3: Lead marking of the cable plug for outputs 48 VDC

2/6
F 3349 (1133)

2-pole connection of the loads required!


Figure 4: 2-pole connection

Additional technical data


Current input WD 1 mA
Monitored switching time max. 230 μs (without extension by
the function block)

Internal voltage drop max. 2 V at 500 mA load


Admissible line resistance max. 11 Ω
max. lamp load 10 W
max. inductivity 1H
max. capacity 100 μF
Output leakage current max. 500 μA
Operating points of the line moinitoring
Line short-circuit 0.7...0.8 A
Line break 2...8 mA

Reaction of the module to errors


• Module error:
All outputs are switched off.
• Line error:
If an external line break or a short-circuit is detected, the module only makes an annun-
ciation to the corresponding central module.
At a short-circuit and an overcurrent (> 2 A per channel) the overcurrent tripping is acti-
vated after 50 ms at the latest. For smaller overloads (> 0.7 A per channel) the reaction
time can last up to several seconds.
At line errors the channel of the module is reconnected again after approx. 4.5 se-
conds.
• The error codes for the module are shown in the display of the corresponding central
module. For further information see operating system manual.

3/6
F 3349 (1133)

Planning notes

The function block HB-BLD-3 (for single channel operation) or HB-


BLD-4 (for redundant operation) must be used for all applications with
the module.

• In case of line monitoring the appertaining function blocks HB-BLD-3 (for single chan-
nel operation) or HB-BLD-4 (for redundant operation) enable enhanced configuration
possibilities for the module.
• The extension of the time for the inrush current for lamp loads by the appertaining func-
tion block is valid for all channels. So inductive and lamp loads may not be operated on
one module at the same time.
• The line break monitoring requires an output load of at least 10 mA.
• The short-circuit and line break can be evaluated in the user program as line faults by
means of the function blocks HB-BLD-3 or HB-BLD-4. The evaluation of the signal “line
break” is made up to SIL 1.
• The outputs of the module and their supply voltage must be connected with two poles.
The use of common lines can produce coupling loops with interferences, leading to a
module fault or a failure of the safety shutdown of the outputs.
• The outputs can be connected in parallel without additional external decoupling diodes.
• An external short-circuit of a channel does not trigger the integrated safety shutdown,
i.e. the remaining channels continue their function.
• If the line is longer than 10 m or if a power supply unit not manufactured by HIMA is
used, for a faultless operation with 48 V the supply voltage must be filtered with an
additional module Z 6019.
• Lines for outputs not used may not be extended to the plant without any terminal loads.
• In one I/O subrack max. 10 output modules with nominal load may be used at the same
time.
• At maximum power dissipation a forced cooling with a fan module is required.

Note for the redundant use of modules


• In case of a line short-circuit the double current can flow, until this line short-circuit is
diagnosed.
• In case of a line break the required minimum current is twice the value (20 mA) to pre-
vent an indication of a line break.

Note The connection of capacitive loads is not permitted. A length of the


connection line up to 3 km is possible. The line capacity, however, is
limited to a maximum of 1 μF.
With an interruption of the supply line L- the safe shutdown of the out-
puts is no longer ensured.

4/6
F 3349 (1133)

Edition Revisions Type of Change


technical editorial
(1133) Value of "Monitored switching time" corrected, X

5/6
F 3349 (1133)