0304DS6 20KB User Manual
0304DS6 20KB User Manual
CISPR 22
NOTICE: Pursuant to CISPR 22 rules, this product has been tested and thereby complies
with the conditions of a Class A digital device, which have been established for offering
sufficient protection against dangerous interference for installation in a residential area.
User Guide Installation and use of the equipment should comply with the instructions provided in order
to avoid such interference due to the amount of radio frequency energy that is radiated and
generated by the equipment. In spite of this, we cannot assure that a certain amount of
interference may not occur in some installations. If, by turning on and off, it can be deduced
that your radio or television reception is found to be influenced by harmful interference from
the equipment, it is recommended to use one of the following preventive measures:
z Place the receiving antenna in a separate location or orientation.
z Ensure a greater distance is achieved between the receiver and the equipment.
z Ensure that your equipment is connected to an outlet on a separate circuit than the
receiver.
z Contact a technician experienced with radio and TV or a dealer for further assistance.
Declaration of Conformity Request
Units labeled with a CE mark comply with the following standards and directives:
z Harmonic Standards: EN 50091-1-1 and EN 50091-2
z EU Directives:73/23/EEC, Council Directive on equipment designed for use within
certain voltage limits
Durable Series
6KVA~20KVA
I
CONTENTS
1. Introduction ...........................................................................................2
IMPORTANT SAFETY INSTRUCTIONS
2. System description...............................................................................3 SAVE THESE INSTRUCTION
2.1 General description ..............................................................................3 ● CAUTION (UPS Having Internal Batteries): Risk of electric shock -
2.2 System configuration ...........................................................................5 Hazardous live parts inside this unit are energized from the battery supply
even when the input AC power is disconnected.
3. Safety information ................................................................................6
● CAUTION (No User serviceable Parts): Risk of electric
4. Storage...................................................................................................7 shock, do not remove cover. No user serviceable parts inside. Refer
5. Installation .............................................................................................7 servicing to qualified service personnel.
7.1 Starting and shutting down the UPS ................................................18 ● CAUTION: Do not open or mutilate the battery, released electrolyte is
harmful to the skin and eyes.
7.2 Button operation .................................................................................20
7.3 Control panel functions......................................................................20
● CAUTION: A battery can present a risk of electric shock and high short
circuit current. The following precaution should be observed when working
7.4 Interpreting UPS messages ...............................................................26 on batteries
7.5 Trouble shooting.................................................................................27 Remove watches, rings or other metal objects.
II 1
The instructions contained within this safety manual are deemed important and should be Only detailed requirements of the UPS units are described herein, and installation must be
closely followed at all times during installation and follow-up maintenance of the UPS and carried out in accordance with this manual. Electrical installations must also carefully follow
batteries. local legislation and regulations. Only qualified personnel should conduct these installations
as failure to acknowledge electrical hazards could prove to be fatal.
CAUTION
The unit has a dangerous amount of voltage. If the UPS indicator is on, the unit’s 2. System description
outlets may have a dangerous amount of voltage even when not plugged into the Several different kinds of sensitive electrical equipment stay protected by a UPS
wall outlet because the battery may continue to supply power. (Uninterruptible Power System) including computers, workstations, process control systems,
Care should be taken to undertake installation indoors free from telecommunications systems, sales terminals, other critical instrumentation, etc. The purpose
electrically-conductive particles which is under temperature and humidity control of the UPS is to protect these systems from poor quality utility power, complete loss of
in order to reduce the risk of electric shock. power, or other associated problems.
It is best to disconnect the device using the power supply cord. Ensure that the Electrical interference abounds in many forms causing problems in AC power, from
equipment is placed in a position near the outlet where easily accessible. lightning, power company accidents and radio transmissions to motors, air conditioners, and
vending machines, among others. So protection of sensitive electrical equipment is vital to
Except replacing the batteries, all servicing on this equipment must be carried out
protect against power outages, low or high voltage, slow voltage fluctuations, frequency
by qualified service personnel.
variations, differential and common-mode noises, transients, etc.
Before conducting any maintenance, repair or shipment, first ensure that
In order to prevent power line problems reaching critical systems causing damage to
everything is turned off completely and disconnected.
software, hardware and causing equipment to malfunction, the UPS helps by maintaining
For additional safety instructions, please use the Safety Manual as reference. constant voltage, isolating critical load output if needed, and cleaning the utility AC power.
Special Symbols 2.1 General description
The following symbols used on the UPS warn you of precautions:
As a double conversion on-line UPS, it is able to supply uninterrupted, clean single-phase
RISK OF ELECTRIC SHOCK – Please observe the warning that a risk of electric power to your critical systems while keeping batteries charged continuously, regardless of
shock is present. whether utility power fails or not.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to the operator’s In event that a power failure lasts longer than a UPS backup time, it will shut down avoiding
manual for additional information, such as important operating and maintenance battery discharge, and as soon as voltage comes back, the UPS will automatically charge up
instructions. and start recharging the batteries.
SAFE GROUNDING TERMINAL - Indicates primary safe ground As shown in fig.1 block diagram:
z An input filter reduces transients on the mains
LOAD ON/OFF - Pressing this button turns on/off the output receptacles and the z For maintaining full battery charge, AC-power is rectified and regulated in the rectifier
Indicator light. feeding power to the inverter and battery converter.
Please do not discard the UPS or UPS batteries as the UPS may have valve z DC power is converted to AC in the inverter passing it on to the load.
regulated, lead–acid batteries. Please recycle batteries.
z Power is maintained from the battery during a power failure.
z The converter increases voltage appropriately for the inverter.
1. Introduction
The information provided in this manual covers single phase 5000 – 20000 VA,
uninterruptible power systems, their basic functions, operating procedures, and emergency
situations, also including information on how to ship, store, handle and install the equipment.
2 3
2.2 System configuration
PFC&Booster Inverter By-pass The UPS device and the internal backup battery make up the system. Depending on the site
Filter Filter and load requirements of the installation, certain additional options are available as a tailored
switch
solution.
Charger & Monitoring Planning a UPS system, the following should be taken into consideration:
panel
Battery Battery Control z The total demand of the protected system shall dictate the output power rating (VA).
switch RS232 or
& USB
Allow a margin for future expansion or calculation inaccuracies from measuring power
requirements.
Monitoring
Slot z Backup time needed will indicate the battery size needed. If load is less than the UPS
nominal power rating then actual backup time is longer.
z The following options are available:
Fig.1. Block diagram
z External Battery Cabinets
Efficiency Optimizer function
z Transformer cabinets
The Efficiency Optimizer function is a new feature for the UPS adding cost effectiveness, z Maintenance bypass switches
minimizing power loss and reducing power consumption. Alternating between bypass and
on-line modes is achieved automatically and in accordance with the conditions of the utility z Connectivity options (relay card, SNMP/WEB card)
power. On-line mode may be used during times of intermittent power supply, and bypass The following UPS models are available
mode when power flows smoothly in order to obtain greatest efficiency. Irregularities can be
detected in less than a second, and on-line mode reactivated immediately. Switching back to Backup time
online mode occurs when input voltage is outside ±10% or nominal (±15% selectable), when Model Recharge time to 90% capacity
Internal batteries
input frequency is outside of ±3Hz or when no input line is available.
UPS 6000VA 6min 4 hours
Although high efficiency is standard, the default operation is in on-line mode. Bypass can be
activated in the LCD panel, though on-line can be run permanently if preferred. UPS 8000VA 6min 4 hours
UPS 10000VA 6min 4 hours
Free Run Mode
UPS 12000VA 6min 4 hours
The UPS operates in free run mode when input frequency is outside of the selected input
frequency range. Free run mode is when output frequency does not match input frequency. UPS 15000VA 4min 4 hours
When starting the UPS, the frequency regulation detected is 50 or 60 Hz ±0.25Hz. Please UPS 20000VA 5min 4 hours
refer to chapter 7.2 if you want bypass available while running in free run mode.
Additional External Battery Cabinets are available if more back-up time is needed.
Diagnostic tests
When you start the UPS, a diagnostic test is automatically executed that checks electronics,
battery, and reports any problems on the LCD display.
An advanced battery management system always monitors the conditions of the batteries
sends any forewarnings if replacement is needed. Otherwise every 30 days of normal mode
operation, a battery discharge test is performed and any problems reported on the LCD
display.
Except during the first 24 hours after startup while the UPS is in charging mode (please see
chapter 7.2), diagnostic tests can be performed manually from the front panel at any time.
4 5
3. Safety information 4. Storage
Information presented here is vital to all personnel and please also read the UPS safety Please adhere to the following instructions if the UPS is not installed immediately:
manual.
z Store the equipment as is in its original packing and shipping carton
Storage and Transportation z Do not store in temperatures outside the range of +15°C to +25°C.
Please handle with extreme caution since a high amount of energy is contained with the z Ensure that the equipment is fully protected from wet or damp areas and from moist air.
batteries. Always keep the unit in position as marked on the packaging and never drop the In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6
unit. months for at least 8 hours.
Installation
If flammable substances such as gases or fumes are present or if the room is airtight, a safety 5. Installation
hazard situation exists, in which no electrical equipment should be operated.
5.1 Environment
The instructions in this manual explain how to install the UPS safely. Not acknowledging
such electrical hazards may be fatal, so keep this manual for all future reference. Ensure that all environmental concerns and requirements are met according to these
technical specifications, otherwise the safety of installation personnel cannot be
guaranteed and the unit may malfunction.
WARNING!
Ensure that you remember the following when locating the UPS system and battery options:
It is strongly advisable not to open the UPS cabinet as the components have very z Avoid extremes of temperature and humidity. Maximal battery life can be attained with a
high voltage and touching them may be fatal. Only a technician from the recommended temperature range of 15 °C to 25 °C.
manufacturer or an authorized agent may service the unit.
z Provide protection for the equipment from moisture.
This UPS unit’s output receptacles carry live voltage even when not connected to a
power supply as it has its own energy source. z Space and ventilation requirements must be met. Ensure there is 100mm behind and
50mm on the sides of the UPS for ventilation.
z Ensure that the front of the UPS remains clear for user operation.
User’s operations
The External Battery Cabinets has to be installed next to the UPS or under the UPS.
The only operations that users are permitted to do are:
z Turning the UPS unit on and off
z Operating the users interface
z Connecting data interface cables
All such operations are to be performed exactly as instructed in this manual. The greatest
care possible must be taken for any of these operations and any change thereof may prove
very hazardous to the operator.
6 7
5.2 Rear panel views
5K~6KVA 5K~6KVA
Rear panel Rear panel
(STANDARD) (With ISO)
8 9
8K~10KVA Rear panel
(STANDARD)
10 11
15/20 KVA Rear panel
(STANDARD & With ISO)
12 KVA Rear panel
(STANDARD & With ISO)
12 13
which when open will immediately shut down the logic circuit output of
the UPS as in figure 2 and 3. Wiring the EPO signal is optional.
z Caution! Local safety requirements may require a separate external
Emergency Power Off that opens output circuit breakers, and if so, use
5.3 Connection to mains and loads (6000 - 20000 VA) figures 2 and 3 for proper installation. Refer to local wiring rules.
z Should computer or alarm connections be used, use connections
Only qualified specialists or technicians who conform to applicable safety according to chapter 6 of the manual provided with that option. The
standards may carry out the installation of this equipment. The installation must connections can be referred to on the rear panel.
further comply with all local legislation and regulations.
Follow all installation and safety instructions very carefully, otherwise those z The installation is now complete.
performing installation may suffer from a hazardous situation and the UPS or b*) removable jumper when dual input used
load connections may also be damaged.
Bypass
input J Static L N PE
L Bypass
The high voltage and current contained within the UPS equipment can injure N
PE
L N PE
or kill personnel and damage equipment. A 1 L ~ = L
1
N = ~ N
PE PE
Rectifier
input
For electrical installation, closely observe the nominal current rating of the source.
Installing External battery cabinets
Fig. 2
z First disconnect the UPS from mains and loads before attempting an
External Battery Cabinet installation.
z Use the battery cable provided with the External Battery Cabinet to
connect the External Battery Cabinet to the UPS. Connect a second
battery cabinet to the first one with the cable provided if more than one is
to be installed.
z Be aware of UPS parameters and changing the Battery pack quantity
when using the external battery cabinets (see chapter 7.2)
Installing UPS
z Ensure that the installation site has all electrical connections properly Fig. 3.
carried out. In addition, refer to figures 2 and 3 to check the fuse and z Only required if demanded by that of local wiring rules.
cable dimensions. The information listed on the table is for reference only .
z Isolate and secure the source against reclosing. Both input and output 1Φ2W(110V) 1Φ2W(220V) 1Φ3W(220V) 3Φ4W(380/220V)
circuit breakers (located in the back) must be “OFF”.
8KVA 6AWG(min.) 8AWG(min.) 8AWG(min.) 8AWG(min.)
z Refer to figure 2 for single cable input and figure 3 for dual cable input.
Connect the UPS according to these diagrams. If installing dual cables, 10KVA 6AWG(min.) 8AWG(min.) 8AWG(min.) 8AWG(min.)
the interconnection jumper (b*) needs to be removed as in figure 2. Fuse
and cable sizes are given in figure 3. 12KVA 6AWG(min.) 8AWG(min.) 8AWG(min.) 8AWG(min.)
z During installation, if it cannot be determined that neutral is grounded or 15KVA 4AWG(min.) 6AWG(min.) 6AWG(min.) 6AWG(min.)
the identification of the neutral status of the mains supply is unreliable,
an additional two pole disconnect device is necessary in the building 20KVA 4AWG(min.) 6AWG(min.) 6AWG(min.) 6AWG(min.)
installation.
2 2 2
z At the back of the unit you will find the Emergency Power Off (EPO), 8AWG=16mm , 6AWG=25mm , 4AWG=35mm
14 15
5.4 Default settings at the factory 6. Computer and alarm connections
On the LCD display you will find several of the UPS parameters to select. At the back of the UPS is an interface allowing direct communication with your computer
Default settings are as follows: system, the location of which can be found in figure 4. There is a RS232 serial data
interface, one USB data interface and an emergency power off switch supplied. However,
Settings Selection Factory default the RS232 port cannot be used when the USB interface is in use.
In addition there is an optional interface slot that allows you to install different
Output Voltage Setting 208/220/230/240 Vac 230V (FOR HV series) communications cards. It can be used parallel with either the RS232 or USB ports.
Currently there are two cards available for the optional interface slot. An SNMP/WEB
±10% card allows management and monitoring over a network or internet, and the AS/400 card
Input/Bypass Voltage +10/-15% +10/-15% allows voltage free relay contacts. Your local dealer will have more information about
+15/-20% these option cards.
Fig.4
16 17
USB port (option) z During this inspection, the LCD will display “Ready on”. The LED shall light up
when output power has commenced and the LCD will display “Line mode”.
Connecting the UPS to your computer is accomplished through the USB port on the back z Switch on the loads.
of your computer. USB compliant hardware and operating system will be necessary
including installation of a UPS driver. The serial port cannot be used when using the USB Shutting down the UPS
port. The USB cable is standard and can be bought separately.
z Shut down and turn off the loads.
6.1 EPO port (emergency power off)
z Push the “ON/OFF” button on the front panel for two seconds. The alarm will sound
A customer-supplied switch located remotely can be used to open the EPO connection and the UPS will shut down.
and allows UPS output receptacles to be switched off. Since the EPO shuts down the z The LCD will display UPS OFF for a few seconds.
equipment immediately, orderly shutdown procedures are not followed and not by any
power management software. The UPS will have to be manually restarted in order to z In emergency situations, the EPO located on the back of the unit should be used.
regain power to the outlets.
z Ensure that installation was correct and successful and that the input power cable is
connected to a well-grounded outlet.
z The UPS can be started by pushing the “ON/OFF” button on the front panel.
z The UPS should now start its inspection of: internal functions, main synchronization
and inverter startup. Then power should start to be supplied via the terminal block.
18 19
7.2 Button operation Operation of the UPS is indicated on the monitor panel with five LED indicators and an
LCD screen. This display is also capable of alerting the user with audible alarms.
Please note the five operating buttons on the front panel:
ON:This green LED is lit when UPS has been turned on.
1. “ON/OFF” button: ON-LINE:When the UPS is in normal or static bypass modes, there is voltage at the
output terminals and this LED will light up in green.
(a) Push “ON/OFF” button (at least 1 seconds) to turn on the UPS.
ON-BAT:While operating in battery mode.
(b) When UPS is working, push the “ON/OFF” button(at least 2 seconds) to turn
BYPASS:While operating in bypass mode, this LED will light up in yellow.
off the UPS. FAULT:If any internal error occurs in the UPS, this LED will light up in red and give off
an audible alarm. Press any of the buttons on the front panel to turn off the
2. “STATUS” button:
alarm.
Use this button to check content of UPS and the method is listed below:
(a) Push the “STATUS” button (at least 2 seconds) to check content of UPS.
Each content can be displayed by pressing at once, and it has fifteen kinds of
function to be checked.
3. “FUNC” button:
Each function can be enabled by pressing this button & “ENTER” button.
(a) Push the “FUNC ” button (at least 2 seconds) to choose which function that
you want. Each content can be displayed by pressing at once, and it has
(b) After choosing the function, push the “ENTER” button to enter the function
(e) Push the “ENTER” button to confirm and enable your function.
4. “ENTER” button:
Use this button to enter、enable or confirm the function that you want.
5. “ESCAPE” button:
20 21
Status of the UPS, measurements and alarms are all indicated on the LCD screen. UPS configurations
1. Various settings that have been chosen are shown in the UPS setting display.
2. To enter configuration mode, press the “FUNC” button for one second. The first
configuration parameter will be shown on the LCD display.
3. Press the “FUNC” button to scroll through the parameters.
4. Press the “ENTER” button to select the parameter.
RM- LCD PANEL TOWER- LCD PANEL 5. Press the “FUNC” button to scroll through the options for the selected parameter.
22 23
**) Note: In order for the UPS and power management software to operate normally,
Manual Bypass should always be set to OFF as the load will not be protected by the unit
LCD Factory when Manual Bypass is ON. This is aimed for operating an external maintenance bypass
Settings Explanation Selection
display default
switch.
O/P V ***) Note: You should turn UPS off and keep the AC power before you use “Generator”
Output Volt.Setting Select Nominal Voltage 208/220/230/240 V 230V
Setting function. (even you want to select “\Generator\OFF” to back to normal mode).
Select input frequency ±2%
Input/Frequency I/P F Setting range when UPS goes into ±5% ±5%
free run mode ±7%
±10%
Input/Bypass I/P Bypass Select Input Voltage range
+10/-15% +10/-15%
Voltage Set when bypass is available
+15/-20%
Select if UPS can run in
Free Run
Free Run Mode Free run mode ON/OFF ON
Set
(unsynchronized)
Bypass If Enable is chosen, the
Bypass
Enable/Disable at UPS can go to bypass when Disable/Enable Disable
disable
Free run mode unsynchronized.
HE Mode Select if UPS runs in high
He mode Setting ON/OFF OFF
Set efficiency mode
Manual UPS or Manual Battery tests can be conducted from the UPS configuration as well
and are functional even when the UPS is not charging the battery.
Manual Battery test: Scroll the parameters until Manual Bat test displays on the LCD.
Press the “ENTER” button twice.
24 25
7.4 Interpreting UPS messages 7.5 Trouble shooting
Displayed on LCD Audible Alarm Alarm Description What You Should Do
Troubleshooting procedures described here give simple instructions in determining UPS
The UPS is overloaded (in Shut off the least important
malfunctions.
Line Mode). Your equipment connected to the
Start the troubleshooting procedure if you witness any alarm indication on the control panel. Two Beeps per equipment needs more UPS. If this solves the
Output Overload
second power than the UPS can overload problem, the UPS
Alarm indicators provide. The UPS operates will switch from bypass back
in bypass. to normal operation.
The UPS gives the following audible alarms: No action needed. The UPS
z If UPS is on battery and the ON BATTERY LED is on, UPS will beep every 5 seconds. The UPS is doing a battery will return to normal operation
Battery Test No Beeps
test. when it successfully completes
z If the battery capacity is low and the ON BATTERY LED is flashing, the UPS will beep the battery test.
twice every 5 seconds. Turn off protected loads. Turn
Batteries are
z If UPS is on bypass and the BYPASSED LED is on, UPS will no beep. Over-Charge Constant beep off UPS and call your local
overcharged.
dealer
z If UPS has an internal fault and the ALARM LED is on, the UPS will give a constant The unit is operating on
The unit will restart
audible alarm displaying the cause on the LCD display. 2 beeps every Battery Power and will shut
Low Battery Automatically when
5seconds down soon due to very low
acceptable power returns.
Silencing an alarm battery voltage
Once every 5 The unit is operating on Save your data and perform a
By pressing any of the three buttons on the front panel, the alarm can be turned off, except On-Battery
seconds Battery Power. controlled shutdown.
when the battery is low, which will cause the alarm to resound. Charger Failure Constant beep Charger has failed. Phone the local dealer
Make sure the unit’s fans and
On the LCD display, you can also choose silent alarm mode which will not warn you of any
vent holes are not blocked, and
malfunction audibly. make sure the ambient
surrounding temperature is not
Over-Temperature Constant beep High ambient Temperature.
above 40 degree C. If these
conditions did not solve the
problem, call your service
representative.
Output Short Constant beep Output short circuit Call the Local dealer
High output Voltage Constant beep High output voltage Call the Local dealer
Low Output Voltage Constant beep Low output voltage Call the Local dealer
Turn off protected loads. Turn
2 Beeps per High internal DC bus
Bus Fault off UPS and call your local
second Voltage.
dealer
UPS mains connector polarity
Wrong. Rotate the connector
1 Beep per Voltage detected Between (Schuko). UPS installed to
Site wiring Fault
second Neutral and Ground mains supply without ground.
See page 15 on how to disable
the Site wiring alarm
1 Beep per Wrong AC Line backed up
Line abnormal
second during auto restart
26 27
8. Maintenance 10. Technical Specifications
With a minimal amount of maintenance, you can expect the UPS to application, otherwise GENERAL
consider changing the batteries. have a long life free of trouble. The most critical issues for Rated power 6000 VA, 8000 VA, 10000 VA, 12000VA,15000VA, 20000VA
the reliability of the UPS are environmental issues. Ensure that the temperature and humidity at p.f 0.7
are always according to specifications and keep the area around the unit clean and dust free. Technology On-line, double conversion topology with automatic bypass
At a temperature of 25°C, the typical battery lifetime is 4 years. INPUT
Phase Single phase with ground or Three phase with netural+ground
Also check at regular intervals of 6 to 12 months whether the back-up time of the battery is
Bypass Voltage: 184-265 VAC (user selectable)
adequate for its
Input Voltage range: 120/140/160/180 VAC-276 VAC (Single phase)
208/242/277/312 VAC-478 VAC (Three phase)
Frequency: 50/60 Hz. Auto selection
WARNING!
Frequency window from mains 45-65 Hz
Batteries may cause electrical shock or burn from high short circuit Synchronization window ± 3Hz.
currents. Please observe the following precautions: 1. Remove jewelry and metal
Input current 6000 VA 23.0A, 8000 VA 30.7A, 10000 VA 38.3A,
objects such as watches and rings. 2. Use tools that have insulated handles. 3. Keep
tools and other metal objects from contacting and away from the batteries. 12000VA 46.0A, 15000VA 57.5A, 20000VA 76.6A (Single phase)
8K VA 10.2A, 10K VA 12.8A, 12K VA 15.3A,
ELECTRIC ENERGY HAZARD. Do not attempt to rewire, alter, or change any
15 KVA 19.2A, 20 KVA 25.5A (Three phase)
battery wiring or connectors. Attempting to make such alterations can cause
injury. Input Power factor: 0.97(Single phase) ; >0.95 (Three phase)
Replace the batteries with the same number and type as originally installed OUTPUT
batteries.
Output Voltage: 208/220/230/240 VAC, selectable from LCD panel
DO NOT DISCONNECT the batteries while UPS is in Battery mode. Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation ± 0.25 Hz (battery or free running mode)
9. Warranty * 120V at 25% load, 140V at 50%, 160V at 75%, 180V at 100%.
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Warranty on this product is valid against defects in material and workmanship
for a period of 24 months from its original date of purchase. Overload capacity: 110-125% 1 min, 126-150% 10 sec (Line mode)
110-130% 10 sec, 131-150% 1.5 sec (Battery mode)
Efficiency: greater than 88%
ENVIRONMENTAL
Ambient temperature: +0 °C to +40 °C
Recommended temperature: +15 °C to +25 °C
Storage temperature: -15 °C to +50 °C
Cooling: Forced air-cooling
Humidity: 0-95%, non-condensing
Audible noise: < 55 db normal and battery mode (5000-6000 VA)
< 65 db normal and battery mode (8000-20000 VA)
STANDARDS
Safety: EN50091-1-1
Emissions: EN50091-2 class B
Immunity: EN50091-2
28 29
HV Model 6K TB 6K-ISO TB
Without Lead-acid
Lead-acid Lead-acid Lead-acid Lead-acid
Battery type Internal
7.2 Ah/12V Battery 7.2 Ah/12V 9 Ah/12V 5 Ah/12V
9 Ah/12V 8/10/12K TB 8/10/12K-3O TB
Number of batteries 20 - 20 20 40 40
<4 hours <4 hours <4 hours <4 hours <4 hours <4 hours to
Recharge time
to 90% to 90% to 90% to 90% to 90% 90%
Without
257x590x570 428*597*130 257*690*700 257*690*700 342*690*878 342*755*905
Dimensions ISOTR
W*D*H 6/8/10/12K-ISO TB 8/10/12K-ISO-3Ø TB
mm With
257*590*700 - 342*690*715 342*690*715 342*690*878 342*755*905
ISOTR
Without
87 20 108 110 130 212.5
ISOTR
Weight kg
With
123 - 130 130 180 287.5
ISOTR
30 31
(2) UPS REAR PANEL COMPONENTS:
11. DS6000B-RM (3U+3U) Mechanical
H. TERMINAL BLOCK
A. DS6000B-RM RACK-MOUNT(3U+3U) DESIGN: I. BREAKER
(1) BASIC COMPONENT: INCLUDING 3U-UPS & 3U-BATT. CABINET J. EXTERNAL BATTERY CONNECTOR
FRONT VIEW K. BYPASS SWITCH
L. SNMP SLOT
M. RS232 + EPO
N. TVSS
O. USB
P. REMOTE CONTROL PORT
O P L
H
K
I
REAR VIEW
N M J
32 33
(4) FEATURE of REMOTE CONTROL FUNCTION: c. Running the remote-control function.
a. Remove the original right side panel and take apart the control panel unit. Then
assemble the blank right side panel.
b. Connect the Control panel unit and Remote control port from rear side.
34 35
(1) 19” Rack installation: (3) Tower installation:
Mount the 3U rack-mount in a 19-inch EIA 310 C standard rack. a. Move the mounting brackets from the front to the side and attach the brackets by
screws. Then let the UPS stand with the vertical direction as the below pictures
shown.
b. Rotate the control panel unit from horizontal to vertical direction.
36 37
(5) Installation with rear Bracket:
We can use bracket to support the rear side of UPS or battery cabinet.
38