Electrical Design System Study
Electrical Design System Study
BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION Date 7 Aug 2012
PFMAP SDN BHD Page 1 of 8
CLIENT:
PROJECT TITLE:
DOCUMENT TITLE:
CONTRACT NO:
CHO/2011/DAC/630
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 2 of 8
RECORDS OF AMENDMENT
3.0 Change total 120V AC UPS loads with 20% future loads 4
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 3 of 8
1.0 OBJECTIVE 4
9.0 CONCLUSION 8
10.0 APPENDICES 8
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 4 of 8
1.0 OBJECTIVE
The purpose of this document is to determine the load consumption and size the
battery and charger system to meet the operational requirement of 120V AC, 60Hz,
Uninterruptible Power Supply (UPS) System for Instrumentation Loads and HVAC
Panel in Bekok-C platform.
1. The rating of UPS shall be finalized based on 120V AC UPS Load Summary
(refer Appendix B).
2. The AC UPS System shall have 20% spare capacity for future use.
3. The AC UPS System power factor of 0.8 is considered.
4. Inverter efficiency is considered 88%.
5. The AC UPS System configuration shall be 2 x 100% as shown on the 120V AC
UPS Single Line Diagram (Appendix A).
6. Design temperature is considered as 36°C, as the battery is located indoor
inside forced ventilated battery room, temperature correction factor is
considered as 1.00.
7. Battery ageing factor is considered as 10% for Nickel Cadmium Batteries.
8. Battery nominal voltage is considered as 220V DC in the battery sizing
calculations. The number of cells shall be selected based on 15% negative
tolerance and 10% positive tolerance on the battery nominal voltage (110V
DC). The battery end cell voltage shall be 1.10V per cell.
9. Battery Autonomy times for the UPS System shall be as shown on the UPS
Load Summary (Appendix B).
10. Battery type shall be Valve Regulated, Nickel-Cadmium Gas Recombination
Type.
11. The capacity rating factor, Kt, is the ratio of rated ampere-hour capacity (at
a standard time rate, at 25°C, and to a standard end-of-discharge voltage)
of a cell, to the amperes that can be supplied by that cell for t minutes at
25°C and to a given end-of-discharge voltage. Kt factors are available from
the battery manufacturer, or may be calculated using this formula.
Kt = Kt2 - (Kt2 - Kt1 ) x (t2 – t)
(t2 – t1)
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 5 of 8
Specification requirements:
Battery Type : Low Maintenance, Nickel-Cadmium
Gas Recombination Type
Nominal System Voltage: Un : 220V DC
Cell Voltage at the end of discharge (ECV) : 1.10V
Therefore the Battery Voltage range shall be 187V, 243.1 V ~ 246.5 V with 170
number of cells and ECV = 1.10V
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 6 of 8
Refer Appendix B
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 7 of 8
Charger/Rectifier for UPS System: The rated current of a UPS rectifier shall be
computed by the following equation:
Inv.kVA x 1000 x PF
A = SF + BIF AhBatt
Inv.EffBattFloat x VBatt RechargeTime
Float
Where:
A = Ampere rating of the rectifier output
SF = Service factor(considered as 20% spare of UPS load)
PF = Power factor of UPS load (use PF = 0.8 lagging)
Inv.EffBatt Float = Known efficiency of the inverter at battery float voltage
VBatt Float = Overall battery float voltage
(Float charge voltage x No. of cells)
Inv. kVA = Rated kVA of the UPS inverter
Ahbatt = Battery capacity (Ampere Hour) for nickel cadmium
battery
Recharge Time = Required Recharge time of the system battery
BIF = Battery inefficiency factor is considered as 1.0
Therefore:
Current to the inverter = (Inv.kVA x 1000 x power factor)
(Vbatt.Float x inverter efficiency)
= (40 x 1000 x 0.8) / (243.1 x 0.88)
= 149.58 A
Therefore total rectifier current required to supply the load and charging the
battery:
= Load current + battery charging current
= 149.58 + 30
= 179.58 A
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD
Page 8 of 8
9.0 CONCLUSION
10.0 APPENDICES
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD Page APPENDIX A
APPENDIX A
PFMAP - CALCULATION
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD Page APPENDIX B
APPENDIX B
PFMAP - CALCULATION
Doc.No. BEKP-C-ELE-DAT-5004
Revision 0
AC UPS LOAD LIST
Date 7 Aug 2012
CLIENT:
PROJECT TITLE:
ENGINEERING, PROCUREMENT, CONSTRUCTION,
INSTALLATION AND COMMISSIONING (EPCIC) FOR
BEKOK-C RESTORATION PROJECT
DOCUMENT TITLE:
AC UPS LOAD LIST
CONTRACT NO:
CHO/2011/DAC/630
LOAD IN kW
No LOAD DESCRIPTION TAG NO. REMARKS 1
30 MINS 45 MINS 180 MINS
2
120V UPS LOAD - MAIN CONTROL ROOM (FEED FROM ACP-430B) 3
23
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
LOAD LIST SUMMARY Doc.No. BEKP-C-ELE-DAT-5004
Revision 0
7RC-405 120V AC UPS LOADS
Date 7 Aug 2012
PFMAP SDN BHD EPCIC FOR BEKOK-C RESTORATION PROJECT Page 3 of 4
LOAD IN kW
No LOAD DESCRIPTION TAG NO. REMARKS 1
30 MINS 45 MINS 180 MINS
2
120V UPS LOAD - OTHERS (FEED FROM ACP-430) 3
17
18
20
22
24
26
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
LOAD LIST SUMMARY Doc.No. BEKP-C-ELE-DAT-5004
Revision 0
7RC-405 120V AC UPS LOADS
Date 7 Aug 2012
PFMAP SDN BHD EPCIC FOR BEKOK-C RESTORATION PROJECT Page 4 of 4
LOAD PROFILE
35.00
30.00
25.00
20.00
15.00
UPS Load in kW
10.00
5.00
0.00
15 30 45 60 75 90 105 120 135 150 165 180 195 210 225 240 255 270 285
Autonomy time in minutes
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD Page APPENDIX C
APPENDIX C
PFMAP - CALCULATION
1) GENERAL INFO
4) BATTERY SIZING
Cell AH Checking
APPENDIX D
PFMAP - CALCULATION
M Range Cell performance
Performance after prolonged float charge of fully charged cells
Available amperes at +20ºC ± 5ºC (+68ºF ± 9ºF) Final voltage: 1.10 V/cell
HOURS MINUTES SECONDS
Vantex C5
type Ah 10 h 8h 5h 3h 2h 1.5 h 1h 45 min 30 min 20 min 15 min 10 min 5 min 1 min 30 s 5s 1s
VTX1 M 8 8 0.81 1.00 1.55 2.48 3.34 4.01 4.94 5.64 6.36 7.39 7.98 8.76 10.2 11.9 13.2 16.3 18.8
VTX1 M 16 16 1.62 2.00 3.10 4.96 6.69 8.03 9.88 11.3 12.7 14.8 16.0 17.5 20.4 23.9 26.5 32.7 37.5
VTX1 M 24 24 2.42 3.00 4.66 7.44 10.0 12.0 14.8 16.9 19.1 22.2 23.9 26.3 30.6 35.8 39.7 49.0 56.3
VTX1 M 32 32 3.23 4.00 6.21 9.92 13.4 16.1 19.8 22.6 25.5 29.6 31.9 35.0 40.9 47.8 52.9 65.3 75.0
VTX1 M 40 40 4.04 5.00 7.76 12.4 16.7 20.1 24.7 28.2 31.8 37.0 39.9 43.8 51.1 59.7 66.2 81.7 93.8
VTX1 M 48 48 4.85 6.00 9.31 14.9 20.1 24.1 29.6 33.9 38.2 44.4 47.9 52.5 61.3 71.6 79.4 98.0 113
VTX1 M 65 65 6.57 8.13 12.6 20.2 27.2 32.6 40.2 45.9 51.7 60.1 64.8 71.1 83.0 97.0 107 133 152
VTX1 M 75 75 7.58 9.38 14.7 23.3 31.7 38.2 47.0 52.9 59.1 65.9 70.7 75.2 82.1 91.6 98.8 117 127
VTX1 M 100 100 10.1 12.5 19.6 31.0 42.3 50.9 62.6 70.6 78.8 87.9 94.2 100 109 122 132 156 169
VTX1 M 125 125 12.6 15.6 24.5 38.8 52.8 63.6 78.3 88.2 98.5 110 118 125 137 153 165 195 212
VTX1 M 150 150 15.2 18.8 29.4 46.5 63.4 76.4 94.0 106 118 132 141 150 164 183 198 234 254
VTX1 M 170 170 17.2 21.3 33.3 52.7 71.9 86.5 106 120 134 149 160 171 186 208 224 265 288
VTX1 M 195 195 19.7 24.4 38.2 60.5 82.4 99.3 122 138 154 171 184 196 213 238 257 304 330
VTX1 M 220 220 22.2 27.5 43.1 68.2 93.4 112 138 155 173 193 207 221 241 269 290 343 372
VTX1 M 245 245 24.7 30.6 48.0 76.0 104 125 153 173 193 215 231 246 268 299 323 381 415
VTX1 M 270 270 27.3 33.8 52.9 83.7 114 137 169 191 213 237 254 271 295 330 356 420 457
VTX1 M 295 295 29.8 36.9 57.8 91.5 125 150 185 208 232 259 278 296 323 360 389 459 499
VTX1 M 320 320 32.3 40.0 62.7 99.2 135 163 200 226 252 281 302 321 350 391 422 498 542
VTX1 M 345 345 34.8 43.1 67.6 107 146 176 216 243 272 303 325 346 378 421 455 537 584
VTX1 M 370 370 37.4 46.3 72.5 115 156 188 232 261 291 325 349 371 405 452 488 576 626
VTX1 M 395 395 39.9 49.4 77.4 122 167 201 247 279 311 347 372 396 432 482 521 615 669
VTX1 M 420 420 42.4 52.5 82.3 130 178 214 263 296 331 369 396 421 460 513 553 654 711
VTX1 M 445 445 44.9 55.6 87.2 138 188 227 279 314 351 391 419 446 487 543 586 693 753
VTX1 M 490 490 49.5 61.3 96.0 152 207 249 307 346 386 431 462 492 536 598 646 763 829
VTX1 M 540 540 54.5 67.5 106 167 228 275 338 381 425 475 509 542 591 659 712 841 914
VTX1 M 590 590 59.6 73.8 116 183 249 300 370 416 465 518 556 592 646 720 778 919 999
VTX1 M 640 640 64.6 80.0 125 198 271 326 401 452 504 562 603 642 700 781 843 996 1083
VTX1 M 690 690 69.7 86.3 135 214 292 351 432 487 544 606 650 692 755 842 909 1074 1168
VTX1 M 740 740 74.7 92.5 145 229 313 377 464 522 583 650 697 742 810 903 975 1152 1252
VTX1 M 785 785 79.3 98.1 154 243 332 400 492 554 618 690 740 788 859 958 1035 1222 1329
VTX1 M 835 835 84.3 104 164 259 353 425 523 589 658 734 787 838 914 1019 1100 1300 1413
VTX1 M 885 885 89.4 111 173 274 374 451 554 624 697 778 834 888 969 1081 1166 1378 1498
VTX1 M 935 935 94.4 117 183 290 395 476 586 660 737 822 881 938 1023 1142 1232 1456 1583
VTX1 M 985 985 99.5 123 193 305 416 501 617 695 776 866 928 988 1078 1203 1298 1534 1667
VTX1 M 1030 1030 104 129 202 319 435 524 645 727 811 905 971 1033 1127 1258 1357 1604 1743
VTX1 M 1130 1130 114 141 221 350 478 575 708 797 890 993 1065 1134 1237 1380 1489 1759 1913
VTX1 M 1230 1230 124 154 241 381 520 626 770 868 969 1081 1159 1234 1346 1502 1621 1915 2082
VTX1 M 1330 1330 134 166 261 412 562 677 833 938 1048 1169 1253 1334 1456 1624 1753 2071 2251
14
Doc. No. BEKP-C-ELE-CAL-5004
Revision 0
AC UPS SIZING CALCULATION
Date 7 Aug 2012
PFMAP SDN BHD Page APPENDIX E
APPENDIX E
UPS CATALOGUE
(32 Pages)
PFMAP - CALCULATION
Industrial Power for
Business-Critical ContinuityTM
Scope 4
General requirements 4
Range overview 5
System description 6
Monitoring and control interfaces 9
Mechanical data 14
Environmental conditions 14
Technical data 15
Parallel operation 22
Options 24
General arrangement drawings 29
Chloride Apodys AC UPS 316P-1ph
4
Chloride Apodys AC UPS 316P-1ph
3 Range overview
The system described is a static 3.1. The system The UPS uses today’s most
UPS system as shown in Figure 1. The UPS provides high quality AC reliable topology: the double
The system operates on a power for electronic equipment conversion. It converts AC power
microprocessor-based thyristors loads. It offers the following from an AC source in to DC power
charger and microprocessor- features: to charge a battery and
based IGBTs inverter. By means reconverts it into AC power to
of digital vector control • Increased AC power quality provide a clean and reliable AC
technology the performance of • Full compatibility with all types output to power the AC load.
the UPS are enhanced. By adding of loads 3.2. Models available
system components, such as • Power blackout protection (for The Apodys AC UPS 1-ph range
paralleling kits, safety and systems associated with includes several kVA ratings
disconnecting devices, battery) output models as specified in
distribution cubicles, as well as • Lifetime of, at least, 20 years, paragraph 8. It is of the single-
software and communications combined with an appropriate phase output type.
solutions, it is possible to set up preventive maintenance
elaborated systems ensuring • Operation temperature of 0 to
complete AC load protection. 40°C permanent.
UPS cubicle
BYPASS SUPPLY
1Ph
-V21 -Q22
Charger Inverter
-V18 -Q21
-Q3 -Q24
AC SUPPLY -Q23 AC LOAD
3Ph 1Ph
-Q 21 22 23
AUTO XX
TRANSITION X XX
TEST XX
MAINTENANCE X
-F5
Battery -Q3 : UPS INPUT ISOLATOR
fuse -V18/V21 : STATIC SWITCH
BATTERY * -Q21 : BYPASS SWITCH
-Q24 : UPS OUTPUT ISOLATOR
Legend:
5
Chloride Apodys AC UPS 316P-1ph
4 System description
In this section, the main power 4.2. Components
electronic features and the The UPS consists of the following The inverter converts the DC
operating modes of the Apodys major components: power into clean and regulated
AC UPS range are described. • One input isolator AC power to supply the critical
4.1. General description • One main transformer load through the static transfer
The three-phase current taken • 6-Thyristors bridge rectifier / switch. The power loading can
from the AC source is converter battery charger reach up to 105% of the inverter
to a regulated DC voltage by a 6- • IGBTs bridge inverter nominal rating without
pulse rectifier. • One output transformer considering the inverter in
• Electronic static switches overload conditions.
In order to protect the power • Manual bypass switch
components within the system, While supplying the load, the
• Two control units, each based
the rectifier bridge is fused with a inverter and static switch control
on one microprocessor and one
fast acting fuse. A transformer is unit monitors the reserve supply
Digital Signal Processor-DSP
provided at the input of the signal and ensures that the
• One control and visualisation
rectifying bridge. inverter bridge tracks the reserve
unit
supply frequency. Thus, any
4.3. Operating modes automatic transfer to the reserve
The DC current taken from the
The Apodys AC UPS operates as supply (e.g. when an overload is
rectifier is converted to a
follow: detected) is frequency
sinusoidal and regulated AC
voltage by an IGBTs inverter 4.3.1. Normal operation synchronised and does not cause
(Insulated Gate Bipolar The critical AC load is an interruption to the load.
Transistor), using PWM (Pulse continuously supplied by the UPS 4.3.2. Overload operation
Width Modulation). This means inverter. The rectifier-charger The UPS inverter is considered in
that the digital signal processor derives power from the AC overload conditions when the
controls the IGBTs so that the DC source and converts it into DC load is beyond 105% of the
input voltage is divided into power for the inverter whilst inverter nominal rating.
pulsed voltage to generate a low simultaneously maintaining the
distortion sinewave AC output battery in a fully charged and Two cases are considered:
voltage with good transient optimum operational condition Case 1: Reserve supply is
response voltage regulation. (floating mode). available:
A transformer is provided at the • Upon overload detection by the
output of the inverter bridge. UPS inverter (above 105% of
the inverter nominal rating),
the static switch automatically
time (s) transfers the load to reserve
1000 supply. The static switch
automatically switches back
800 the load to inverter 10 seconds
600
after the UPS inverter is back to
normal conditions.
400
The reserve supply withstands
200 overload as shown on Figure 2.
6
Chloride Apodys AC UPS 316P-1ph
Case 2: Reserve supply is not 4.3.3. Input supply failure 4.3.4. Battery recharge
available: operation
Upon fault of the input AC
• Upon overload detection by the
source, the rectifier-charger After an AC input failure and
UPS inverter (above 110% and
stops while the load remains upon its restoration, the rectifier-
up to 125% of the inverter
supplied by the UPS inverter. charger can be pre-set (according
nominal rating):
Upon Mains input fault detection, to customer’s specification) to
− The system initiates a timer for
the inverter immediately draws automatically restart in 2 ways:
a 10 minutes period.
its power from the associated
− The AC load remains powered battery without switching. While 1) Timer Recharge Mode:
by the UPS inverter for this 10 the inverter is powered by the If the Mains input failure was
minutes period. battery, indication is provided of longer than 5 minutes, the
− Upon expiration of the 10 the actual autonomy percentage rectifier charger automatically
minutes delay, the UPS remaining. restarts in recharge mode for the
inverter shuts down. pre-set recharge time. If the
• Upon overload detection by the When reaching the end of battery Mains input failure was less than
UPS inverter (above 125% and autonomy, an alarm occurs and 5 minutes, the rectifier-charger
up to 150% of the inverter the static switch immediately automatically restarts in floating
nominal rating): switches the load onto reserve mode.
− The system initiates a timer for supply, without interruption. If 2) Current Recharge Mode:
a 1 minute period. for any reason, the reserve supply For any Mains input failure
− The AC load remains powered is not present or faulty and the duration, the rectifier-charger
by the UPS inverter for this 1 battery is no longer available, the restarts in recharge mode until
minute period. UPS automatically shuts down. the battery current is below a
− Upon expiration of this minute pre-set value. Then, the rectifier-
delay, the inverter shuts down. charger automatically turns to
• Upon overload detection by the floating mode.
UPS inverter above 150% of the 3) Boost mode
inverter nominal rating: This operating mode is a specific
− The UPS inverter keeps mode dedicated to vented type
powering the AC load for 5 batteries. It is used when boost
seconds after which it charge or commissioning charge
automatically shuts down. is requested. During Boost mode,
the voltage limitation is increased
This overload operation mode is (up to 2.65V per cell for a Lead
shown in Figure 3. Acid battery and up to 1.7V per
time (s) cell for a Nickel Cadmium
10 min battery). Restoration of the
Floating mode is automatic after
a preset typical time of 5 hours,
unless the Floating mode is
100 s
1 min
manually initiated by the
operator through the control
10 s unit.
5s
4.3.5. Maintenance bypass
operation
100 125 150 Overload (in %) • If for any reason the UPS has to
be taken out of service for
Figure 3: Apodys AC overload curve
7
Chloride Apodys AC UPS 316P-1ph
maintenance or repair, the 4.4. Electrical features 4.4.4. Over voltage protection
Apodys UPS is provided with a
4.4.1. Total harmonic The rectifier-charger of the UPS is
manual bypass switch. The
distortion of input automatically turned off if the DC
bypass switch enables a load
voltage voltage exceeds the maximum
transfer to reserve supply
The maximum voltage THD value associated to its
without power interruption for
allowed on the rectifier input is operational status.
the load. Bypass isolation is
then complete, all serviceable 8% to guarantee the correct 4.4.5. Output voltage harmonic
components such as fuses, operation of the system (either distortion
power modules etc. are from utility or from generator). The inverter provides harmonic
isolated. 4.4.2. Rectifier current neutralisation and filtering to
• The transfer/retransfer is based limitation limit the total harmonic
on the make-before-break The rectifier-charger current of distortion on the voltage to less
principle in order to secure the the UPS is limited to the nominal than 3% with a linear load. For
critical load: the value either in floating, charge reference non-linear load (as
transfer/retransfer operation is and boost mode. defined by EN62040-3) the total
automatically accomplished by harmonic distortion is limited to
4.4.3. Battery current
paralleling and synchronising less than 5%.
limitation
the inverter output to the 4.4.6. Inverter short-circuit
reserve supply, before closing The battery current is limited to
capacity
or opening the bypass switch as 0,1C (Pb) or 0,2C (NiCd) of the
associated battery, in floating or The inverter short-circuit capacity
appropriate.
charge modes. In Boost mode, of Apodys UPS is detailed in
the battery current is limited to Figure 4.
0,05C (Pb) or 0,1C (NiCd). 4.4.7. Static Switch short-
circuit capacity
The electronic static switch is
capable of supporting the short-
circuit currents as shown on
Figure 5.
t (ms) time
1s
5s
Ph-N
100 ms
100 ms
10 ms
1 2 3 4 11 2 3 4 5 6 7 8 9
1.75 2.5 In (A) 10 In (A)
Figure 4: Apodys AC UPS 1-ph inverter short circuit Figure 5: Apodys AC UPS reserve supply short circuit
capacity capacity
8
Chloride Apodys AC UPS 316P-1ph
STOP
C UPS “Inverter
ON/OFF”
Push button
OK Inverter
9
Chloride Apodys AC UPS 316P-1ph
5.3. Display 5.3.2. Active mimic diagram menu to provide the user with
A graphical (64 x 128 pixels) The active mimic diagram detailed information, such as:
illuminated Liquid Crystal Display displays the following • Block status
(LCD) is provided to enable the information: • Block measures
operating parameters, all the • Graphical view of the • Block faults
measurements and the active connected load • Block warnings
mimic diagram of the UPS to be • Graphical view of the power
monitored. The LCD messages flow By using these menus, the user
are accessed by navigation • Graphical view of the status of can access to detailed
buttons (see Figure 7). The text is each functional block information about each following
available in English, unless The Figure 9 provides an example component:
otherwise mentioned. of an active mimic situation: • Rectifier-charger
• AC Mains input failure • Battery
By using the appropriate push- • Rectifier-charger stopped • Inverter
buttons it is possible to display • Battery discharging • Reserve supply
the information described • AC load still supplied by reserve • AC Load
hereafter. 5.3.5. Rectifier-charger
5.3.1. Default page information
The default page displays the Status indications:
active mimic diagram of the UPS Charger off
(see Figure 8). Initialisation
Charger Stop
Equalisation mode*
Equalisation imposed*
Figure 9: Active mimic panel, example of Floating mode
situation Battery test mode*
5.3.3. General menu Battery test imposed*
Boost mode*
Pressing any key from the default
Measurements indications:
page (active mimic diagram)
UDC (charger output voltage)
allows the user to access to the
IDC (charger output current)
Figure 8: mimic default page. following general menu:
U12 (Input voltage ph 1 and 2)
• Charger U23 (Input voltage ph 2 and 3)
By pressing the “OK”, “UP”, or • Battery U31 (Input voltage ph 3 and 1)
“DOWN” buttons, the user enters • Inverter I1 (input line current)
the general menu. If the user is • Reserve supply I2 (input line current)
navigating in the menus, he may • AC load I3 (input line current)
return to the active mimic • Reset Freq (input frequency)
diagram by pressing the “C” • Black Start (option) Number of Mains failures
button. • Event log * Optional messages (according to
If the user does not request any • Display setting specification and system configuration)
action (such as pressing a button) • Contact
for 5 minutes while displaying the
menus, the system will 5.3.4. Menus of functional
automatically return to the blocks
display of the default page active Each functional block (charger,
mimic diagram. battery, inverter, reserve static
switch, load) includes its own
10
Chloride Apodys AC UPS 316P-1ph
11
Chloride Apodys AC UPS 316P-1ph
12
Chloride Apodys AC UPS 316P-1ph
12
34
5
6
13
Chloride Apodys AC UPS 316P-1ph
6 Mechanical data
6.1. Enclosure 6.3. Cable entry 6.6. Internal cables
The Apodys UPS is housed in a Cable entry is achieved via the connection
space-saving modular enclosure bottom of the cabinet. Top cable Connection of cables is achieved
including front doors and entry is also available in option. by inserting cables directly in
removable panels (standard 6.4. Enclosure design screw-clamps.
external protection IP 20). The All the surfaces of the enclosure 6.7. Access to integrated
enclosure is made of sheet steel. are finished with an
The doors can be locked. The
subassemblies
electrostatically applied powder- All internal subassemblies are
enclosure is of the floor mounted epoxy-polyester coat, cured at
type. accessible for typical and most
high temperature. Colour of the frequent maintenance from the
For harsh environmental enclosure is RAL 7032 (pebble
conditions (dust, water), a higher front of the unit. Top access is
grey) textured semi-gloss. available for replacement of
degree of protection, of up to For uniformity of the UPS with
IP42 is available in option. cooling fans. Rear access is not
other equipments in electrical required for installation or
Specific system design can be rooms, the surface finishing and
achieved up to IP54. In such servicing. In any case and if side
the colour of the enclosure may or rear access is required, the side
extreme cases, technical be available according to the
characteristics mentioned in this and rear panels are removable.
customer’s specification and
document are not maintained. upon request.
6.8. Installation
6.2. Ventilation The UPS is forkliftable from the
6.5. Components front. Upon request, it can be
Fan-assisted air cooling is identification
standard on the Apodys AC UPS equipped with lifting lugs to
Main components are identified facilitate its installation on site.
range. The cooling air entry is in by self-adhesive vinyl labels. In
the base and the air exit at the option, Apodys UPS offers the
top of the device. It is possibility to include specific
recommended that the enclosure component identification by
is installed with at least 400 mm engraved traffolyte labels.
of free space between device and
ceiling at the top in order to allow
an unhindered cooling air exit.
7 Environmental conditions
The Apodys UPS is capable of 7.1. Ambient temperature 7.3. Altitude
withstanding any combination of The UPS is capable of operating The maximum altitude without
the following environmental permanently from 0° to 40°C. derating is 1000 metres above
conditions. It operates without 7.2. Relative humidity sea level.
mechanical or electrical damage The UPS is capable of Please consult us for operating
or degradation of operating withstanding up to 90% humidity the system above 1000 metres.
characteristics. level (non-condensing) for an
ambient temperature of 20°C.
14
Chloride Apodys AC UPS 316P-1ph
8 Technical data
Data common to the complete Apodys AC UPS 31 range
Rectifier input
Nominal input voltage (V) 400 [380 / 415]
Input phases 3 ph + N
Input voltage tolerance (%) +10 / -10
Nominal frequency (Hz) 50 / 60 (factory setting selectable)
Tolerance on frequency (%) +5 / -5
Rectifier type 6-pulses SCR (thyristors)
soft start (s) 5
Isolation transformer Standard
Maximum recommended voltage distortion (THD) from Mains (or
(%) 8
generator) on the input of the rectifier
Rectifier output
DC voltage stability (%) < +/- 1
DC voltage ripple in float (disconnected battery) (% rms) 1
Rectifier-charger current limitation (in floating, charge or boost) I nominal
Inverter output
Nominal output voltage See tables on the following pages
Nominal output frequency (Hz) 50 / 60 [factory setting selectable]
Overload at cos phi = 0.8 (%) 125 (10 min) / 150 (1 min)
Short circuit capacity (%) 250 (100 ms) / 175 (5 s)
Isolating transformer Standard on the complete range
Voltage stability (for 100% load variation):
Static (%) +/- 1
Dynamic (%) Complies with IEC/EN 62040-3, class 1
Frequency response (Hz/s) 0.1
Frequency stability:
with own oscillator (%) +/- 0.05
with reserve supply synchronisation (%) +/- 4 [adjustable from 1.2 to 6]
Harmonic voltage distortion:
with 100% linear load (%) <3
with 100% non linear load (%) Complies with IEC 62040-1-2
Output crest factor admissible 3/1
Load power factor 0.5 lag to 0.5 lead
Reserve supply input
Reserve input voltage (V) See tables on the following pages
Reserve input voltage tolerance (%) +/- 10 [adjustable from +/-5% to +/-20%]
Reserve input frequency (Hz) 50 / 60 [factory setting selectable]
Reserve input frequency tolerance (%) +/- 3 [adjustable from +/-0.2% to +/-5%]
System data
External protection degree IP 20
Internal protection degree IP 20
Cable entry Bottom
Access Front
System design life (years) 20
Environmental data
Operating temperature (°C) 0 to 40 (permanent operation)
Storage temperature (°C) -20 to +70
Maximum relative humidity (non condensing) (%) <90
Operating altitude 1000 m (without system derating)
15
Chloride Apodys AC UPS 316P-1ph
Data for 1 x 110 VAC output / 120 VDC (110 VDC) intermediate circuit
Input voltage: 400 VAC [380, 415] three phase
Intermediate voltage: 120 VDC [110 VDC]
Output voltage: 110 VAC [115, 120] single phase
Ratings (kVA) 2.5 5 7.5 10 15 20 25 30 40 50 60
UPS input
Nominal input voltage, frequency,
See page 15
tolerances
Maximum current consumption at
(A) 9 23 23 29 45 70 70 89 112 140 176
full load (°)
Recommended type for UPS input
D curve (circuit breakers) or gL (fuses)
protection
Rectifier-charger output
Nominal voltage (V) 120
Output voltage in floating (V) 136.2
Max DC current (A) 32 80 80 100 160 250 250 320 400 500 630
Battery
Battery output power (W) 2410 4819 7143 9524 14118 18823 23529 28235 37647 46512 55814
UPS output
Nominal output voltage AC (V) 110 [115, 120] — 1 phase + neutral
Nominal output current(*) (A) 22.7 45.5 68.2 90.9 136.4 182 227 273 364 454 545
Reserve static switch
Nominal voltage AC (V) 110 [115, 120] — 1 phase + neutral
Recommended type for reserve
D curve (circuit breakers) or gL (fuses)
input protection
UPS System data
Heat dissipation system(**) F F F F F F F F F F F
UPS system losses(*) (W) 707 1415 1937 2582 3345 4460 5575 6691 8921 10556 12667
UPS system efficiency(***) (%) 74 74 76 76 78 78 78 78 78 79 79
UPS system noise (dBA) 61 61 62 62 68 68 70 70 71 73 73
Height (mm) 1852 1852 1852 1852 1852 1852 1852 1852 1852 1852 1852(°°)
Width (mm) 800 800 800 800 800 800 1200 1200 1200 1600 1600(°°)
Depth (mm) 808 808 808 808 808 808 808 808 808 808 808(°°)
Footprint (m²) 0.64 0.64 0.64 0.64 0.64 0.64 0.96 0.96 0.96 1.28 1.28(°°)
Mass(****) (kg) 300 300 375 375 585 585 735 735 865 1015 1070(°°)
Drawing (See paragraph 11)
on
Code for general arrangement B0 B0 B0 B0 B0 B0 C0 C0 C0 E0
project
NOTA:
-These data are typical and are valid in the following conditions: Sealed lead acid battery (60 cells) operated at Ufloat=2,27V per cell and at 20°C, with
a 3x400VAC Mains input. The system can also be designed and pre-set for use with any other type of stationary battery.
-Full customized technical specification is provided at the bidding stage of project.
-(*) at full load (cos phi 0.8), battery in floating, and at 1x110 VAC nominal output voltage.
-(**) F: Fan cooling.
-(***) For tolerance, see IEC 60146-1-1
-(****) For information only. Mass may vary according to configurations and options
-(°) at inverter full load (cos phi 0.8), battery in recharge, low input voltage level (400Vac -10%) and with charger input power factor 0.85.
-(°°) external bypass cabinet mandatory and not included in this description.
16
Chloride Apodys AC UPS 316P-1ph
Data for 1 x 110 VAC output / 240 VDC (220 VDC) intermediate circuit
Input voltage: 400 VAC [380, 415] three phase
Intermediate voltage: 240 VDC [220 VDC]
Output voltage: 110 VAC [115, 120] single phase
Ratings (kVA) 10 15 20 25 30 40 50 60 80 100
UPS input
Nominal input voltage, frequency,
See page 15
tolerances
Maximum current consumption at
(A) 32 42 53 66 83 104 130 165 206 257
full load (°)
Recommended type for UPS input
D curve (circuit breakers) or gL (fuses)
protection
Rectifier-charger output
Nominal voltage (V) 228
Output voltage in floating (V) 258.8
Max DC current (A) 60 80 100 125 160 200 250 320 400 500
Battery
Battery output power (W) 9302 13953 18605 22988 27586 36782 45977 54545 71111 87912
UPS output
Nominal output voltage AC (V) 110 [115, 120] — 1 phase + neutral
Nominal output current(*) (A) 91 136 182 227 273 364 454 545 727 909
Reserve static switch
Nominal voltage AC (V) 110 [115, 120] — 1 phase + neutral
Recommended type for reserve
D curve (circuit breakers) or gL (fuses)
input protection
UPS System data
Heat dissipation system(**) F F F F F F F F F F
UPS system losses(*) (W) 2111 3004 4005 4456 5347 7129 8912 9416 10854 12539
UPS system efficiency(***) (%) 79 80 80 82 82 82 82 84 86 86
UPS system noise (dBA) 62 64 64 65 65 70 70 70 73 73
Height (mm) 1852 1852 1852 1852 1852 1852 1852 1852(°°) 1852(°°) 1852(°°)
Width (mm) 800 800 800 800 800 1200 1200 1200(°°) 1600(°°) 1600(°°)
Depth (mm) 808 808 808 808 808 808 808 808(°°) 808(°°) 808(°°)
Footprint (m²) 0.64 0.64 0.64 0.64 0.64 0.96 0.96 0.96(°°) 1.28(°°) 1.92(°°)
Mass(****) (kg) 385 540 540 665 665 780 870 940(°°) 1175(°°) 1300(°°)
Drawing (See paragraph 11)
on on
Code for general arrangement B0 B0 B0 B0 B0 C0 C0 C0
project project
NOTA:
-These data are typical and are valid in the following conditions: Sealed lead acid battery (114 cells) operated at Ufloat=2,27V per cell and at 20°C,
with a 3x400VAC Mains input. The system can also be designed and pre-set for use with any other type of stationary battery.
-Full customized technical specification is provided at the bidding stage of project.
-(*) at full load (cos phi 0.8), battery in floating, and at 1x110 VAC nominal output voltage.
-(**) F: Fan cooling.
-(***) For tolerance, see IEC 60146-1-1
-(****) For information only. Mass may vary according to configurations and options
-(°) at inverter full load (cos phi 0.8), battery in recharge, low input voltage level (400Vac -10%) and with charger input power factor 0.85.
-(°°) external bypass cabinet mandatory and not included in this description.
17
Chloride Apodys AC UPS 316P-1ph
NOTA:
-These data are typical and are valid in the following conditions: Sealed lead acid battery (192 cells) operated at Ufloat=2,27V per cell and at 20°C,
with a 3x400VAC Mains input. The system can also be designed and pre-set for use with any other type of stationary battery.
-Full customized technical specification is provided at the bidding stage of project.
-(*) at full load (cos phi 0.8), battery in floating, and at 1x110 VAC nominal output voltage.
-(**) F: Fan cooling.
-(***) For tolerance, see IEC 60146-1-1
-(****) For information only. Mass may vary according to configurations and options
-(°) at inverter full load (cos phi 0.8), battery in recharge, low input voltage level (400Vac -10%) and with charger input power factor 0.85.
-(°°) external bypass cabinet mandatory and not included in this description.
18
Chloride Apodys AC UPS 316P-1ph
Data for 1 x 230 VAC output / 120 VDC (110 VDC) intermediate circuit
Input voltage: 400 VAC [380, 415] three phase
Intermediate voltage: 120 VDC [110 VDC]
Output voltage: 230 VAC [220, 240] single phase
Ratings (kVA) 2.5 5 7.5 10 15 20 25 30 40 50 60
UPS input
Nominal input voltage, frequency,
See page 15
tolerances
Maximum current consumption at
(A) 9 23 23 29 45 70 70 89 112 140 176
full load (°)
Recommended type for UPS input
D curve (circuit breakers) or gL (fuses)
protection
Rectifier-charger output
Nominal voltage (V) 120
Output voltage in floating (V) 136.2
Max DC current (A) 32 80 80 100 160 250 250 320 400 500 630
Battery
Battery output power (W) 2410 4819 7143 9524 14118 18823 23529 28235 37647 46511 55814
UPS output
Nominal output voltage AC (V) 230 [220, 240] — 1 phase + neutral
Nominal output current(*) (A) 10.9 21.7 32.6 43.5 65.2 87 109 130 174 217 261
Reserve static switch
Nominal voltage AC (V) 230 [220, 240] — 1 phase + neutral
Recommended type for reserve
D curve (circuit breakers) or gL (fuses)
input protection
UPS System data
Heat dissipation system(**) F F F F F F F F F F F
UPS system losses(*) (W) 707 1415 1937 2582 3345 4460 5575 6691 8921 10556 12667
UPS system efficiency(***) (%) 74 74 76 76 78 78 78 78 78 79 79
UPS system noise (dBA) 61 61 62 62 68 68 70 70 71 71 73
Height (mm) 1852 1852 1852 1852 1852 1852 1852 1852 1852 1852 1852
Width (mm) 800 800 800 800 800 800 1200 1200 1200 1600 1600
Depth (mm) 808 808 808 808 808 808 808 808 808 808 808
Footprint (m²) 0.64 0.64 0.64 0.64 0.64 0.64 0.96 0.96 0.96 1.28 1.28
Mass(****) (kg) 300 300 370 370 575 575 725 725 850 1000 1050
Drawing (See paragraph 11)
Code for general arrangement B0 B0 B0 B0 B0 B0 C0 C0 C0 E0 E0
NOTA:
-These data are typical and are valid in the following conditions: Sealed lead acid battery (60 cells) operated at Ufloat=2,27V per cell and at 20°C, with
a 3x400VAC Mains input. The system can also be designed and pre-set for use with any other type of stationary battery.
-Full customized technical specification is provided at the bidding stage of project.
-(*) at full load (cos phi 0.8), battery in floating, and at 1x230 VAC nominal output voltage.
-(**) F: Fan cooling.
-(***) For tolerance, see IEC 60146-1-1
-(****) For information only. Mass may vary according to configurations and options
-(°) at inverter full load (cos phi 0.8), battery in recharge, low input voltage level (400Vac -10%) and with charger input power factor 0.85.
19
Chloride Apodys AC UPS 316P-1ph
Data for 1 x 230 VAC output / 240 VDC (220 VDC) intermediate circuit
Input voltage: 400 VAC [380, 415] three phase
Intermediate voltage: 240 VDC [220 VDC]
Output voltage: 230 VAC [220, 240] single phase
Ratings (kVA) 10 15 20 25 30 40 50 60 80 100 120
UPS input
Nominal input voltage, frequency,
See page 15
tolerances
Maximum current consumption at
(A) 32 42 53 65 83 104 130 165 206 257 324
full load (°)
Recommended type for UPS input
D curve (circuit breakers) or gL (fuses)
protection
Rectifier-charger output
Nominal voltage (V) 228
Output voltage in floating (V) 258.8
Max DC current (A) 60 80 100 125 160 200 250 320 400 500 630
Battery
Battery output power (W) 9302 13953 18605 22988 27586 36782 45977 54545 71111 87912 105495
UPS output
Nominal output voltage AC (V) 230 [220, 240] — 1 phase + neutral
Nominal output current(*) (A) 43.5 65.2 87 109 130 174 217 261 348 435 522
Reserve static switch
Nominal voltage AC (V) 230 [220, 240] — 1 phase + neutral
Recommended type for reserve
D curve (circuit breakers) or gL (fuses)
input protection
UPS System data
Heat dissipation system(**) F F F F F F F F F F
UPS system losses(*) (W) 2111 3004 4005 4456 5347 7129 8912 9416 10854 12539 15047
UPS system efficiency(***) (%) 79 80 80 82 82 82 82 84 86 86 86
UPS system noise (dBA) 62 64 64 65 65 68 70 70 73 73 73
Height (mm) 1852 1852 1852 1852 1852 1852 1852 1852 1852 1852 1852(°°)
Width (mm) 800 800 800 800 800 1200 1200 1200 1600 1600 1600(°°)
Depth (mm) 808 808 808 808 808 808 808 808 808 808 1008(°°)
Footprint (m²) 0.64 0.64 0.64 0.64 0.64 0.96 0.96 0.96 1.28 1.28 1.60(°°)
Mass(****) (kg) 380 535 535 660 660 760 850 920 1150 1270 1470(°°)
Drawing (See paragraph 11)
on
Code for general arrangement B0 B0 B0 B0 B0 C0 C0 C0 E0 E0
project
NOTA:
-These data are typical and are valid in the following conditions: Sealed lead acid battery (114 cells) operated at Ufloat=2,27V per cell and at 20°C,
with a 3x400VAC Mains input. The system can also be designed and pre-set for use with any other type of stationary battery.
-Full customized technical specification is provided at the bidding stage of project.
-(*) at full load (cos phi 0.8), battery in floating, and at 1x230 VAC nominal output voltage.
-(**) F: Fan cooling.
-(***) For tolerance, see IEC 60146-1-1
-(****) For information only. Mass may vary according to configurations and options
-(°) at inverter full load (cos phi 0.8), battery in recharge, low input voltage level (400Vac -10%) and with charger input power factor 0.85.
-(°°) external bypass cabinet mandatory and not included in this description.
20
Chloride Apodys AC UPS 316P-1ph
NOTA:
-These data are typical and are valid in the following conditions: Sealed lead acid battery (192 cells) operated at Ufloat=2,27V per cell and at 20°C,
with a 3x400VAC Mains input. The system can also be designed and pre-set for use with any other type of stationary battery.
-Full customized technical specification is provided at the bidding stage of project.
-(*) at full load (cos phi 0.8), battery in floating, and at 1x230 VAC nominal output voltage.
-(**) F: Fan cooling.
-(***) For tolerance, see IEC 60146-1-1
-(****) For information only. Mass may vary according to configurations and options
-(°) at inverter full load (cos phi 0.8), battery in recharge, low input voltage level (400Vac -10%) and with charger input power factor 0.85.
-(°°) external bypass cabinet mandatory and not included in this description.
21
Chloride Apodys AC UPS 316P-1ph
9 Parallel operation
The Apodys UPS systems have Each Apodys UPS is supplied with If one of the UPS fails, the
the capability to be connected in the parallel kit option, which remaining UPS keeps supplying
parallel for Dual configurations consists in one printed circuit the load.
between units of the same rating. board POB (Parallel Operation In such configuration, the
The parallel connection of Board) and one 25 poles, paralleled UPSs must share the
Apodys UPS increases reliability screened data line to the same reserve supply.
for the AC load. neighbouring UPS system. A dual 9.1.3. Benefits
9.1. Distributed parallel parallel system is controlled and
• Very simple system
configuration monitored automatically by
• Thanks to the vector control,
controlling each individual UPS.
9.1.1. System description there is no master and no slave.
All reserve lines and UPS included
The Apodys UPS range is capable • No single point of failure as
share the load.
of operating in Dual distributed each UPS includes its own
9.1.2. Operating principle parallel operation board
parallel configuration as shown
on Figure 12. In this configuration, the 2 UPSs • The available overload current
are connected in parallel so that is doubled
they continuously share the load.
Bypass cabinet1
BYPASS SUPPLY
1Ph
-Q5-1 I
BATTERY1 *
-Q21 Contact
Position A B C
AUTO 1 0 1
-Q5-2
TRANSITION 1 0 1
BATTERY2 * TEST 0 1 1
MAINTENANCE 0 1 0
I
BYPASS SWITCH OPERATION
UPS 2 cabinet APODYS
DISPLAY
U,I,F U,I U,F
CHARGER2 INVERTER2
Bypass 2 cabinet
BYPASS SUPPLY
1Ph
Legend:
22
Chloride Apodys AC UPS 316P-1ph
9.2. Centralised parallel Each Apodys UPS is supplied with All the UPS continuously share
configuration the parallel kit option, which the load. If one of the UPS fails,
includes one printed circuit board the remaining UPS keeps
9.2.1. System description POB (Parallel Operation Board) supplying the load.
The centralised paralleling and one 25 poles, screened data 9.2.3. Benefits
philosophy enables UPSs without line to the neighbouring UPS
reserve static switches to be • Thanks to the vector control,
system.
connected in parallel. Hereby the there is no master and no slave.
Each UPS is monitored and
reserve supply to the loads works • No single point of failure as
controlled individually. Each UPS
with one central reserve cubicle each UPS includes its own
includes only one inverter static
(see Figure 13). parallel operation board
switch, which is paralleled with
• The available overload current
the single reserve static switch.
Again, UPSs of the same rating is doubled
9.2.2. Operating principle • Perfect load sharing
are connected in parallel.
In this configuration, each UPS • 3 simple static switches instead
does not include its own reserve of 2 double static switches,
supply anymore. The reserve which increases overall
supply is externally centralised in reliability through higher MTBF
a COC (Common Output • Only one single reserve supply
Cubicle). input is present.
Bypass cabinet
BYPASS SUPPLY
1Ph
UPS1 cabinet
DISPLAY
U, I, F U, I U U, F
CHARGER 1 INVERTER 1
U
AC SUPPLY 1
3Ph
BATTERY 1 *
U, F
U, F
C
B
BATTERY 2 * U, F, I, W
A AC LOAD
I 1Ph
U, F, I, W
Contact
Position A B C
UPS2 cabinet
DISPLAY AUTO 1 0 1
U, F TRANSITION 1 0 1
U, I, F U, I U TEST 0 1 1
MAINTENANCE 0 1 0
CHARGER 2 INVERTER 2
U BYPASS SWITCH OPERATION
AC SUPPLY 2
3Ph
23
Chloride Apodys AC UPS 316P-1ph
10 Options
10.1. Main electrical options
The list of options described in this section is non-exhaustive. Please consult us for any other requirement.
DISPLAY
1 U, I, F U, I I U U, F U, F
16
-Q22
6 -V21
CHARGER INVERTER
U, F, I, W -Q21 AC Distribution
-T3 -T11 -V18
-Q3 -Q24 -Q001
AC SUPPLY -Q23
AC LOAD
3Ph
1Ph
-K10 -K1
14 CIC 11
-Q5 -Q5
BATTERY * *
13 -Q5
Legend:
* -Q3 : INPUT ISOLATOR -T11 : OUTPUT ISOLATING TRANSFORMER
Interconnection cables not supplied by Chloride
-K10 : 2-STEPS START-UP CONTACTOR -V18/V21 : STATIC SWITCH
Optional part, available upon request -T3 : INPUT ISOLATING TRANSFORMER -K101 : AC EARTH FAULT ALARM RELAY
-Q5 : BATTERY PROTECTION -Q21 : BYPASS SWITCH
1 Option number -K5 : LOW VOLTAGE DISCONNECT CONTACTOR -Q24 : INVERTER OUTPUT ISOLATOR
-CIC : DC EARTH FAULT ALARM RELAY -Q31 : RESERVE INPUT ISOLATOR
-A01 : LOW VOLTAGE DETECTION RELAY -T31 : RESERVE TRANSFORMER
-S02 : BLACK START KEY SWITCH -U31 : RESERVE STABILIZER
-K1 : PRE-CHARGE CONTACTOR -Q34 : STABILISER OUTPUT ISOLATOR
24
Chloride Apodys AC UPS 316P-1ph
Physical Isolate physically the reserve supply from the UPS System.
7
segregation
The reserve bypass supply can be physically apart from the main parts of the UPS system to increase people’s safety
when maintaining the UPS system. This option is achieved by cabling the reserve supply components (e.g. circuit
breaker, transformer, stabilizer) in a separate By-Pass cabinet.
25
Chloride Apodys AC UPS 316P-1ph
This option is made of a key switch to force the battery circuit breaker Q5 to close. In this way, the battery circuit is
powered, thus allowing the inverter to start thanks to the battery current.
External Protect the battery circuit as for option 12, but can not be used in conjunction with option N°12.
14
battery
protection The battery protection device is housed in a wall-mounted metal box for battery systems mounted on racks and it is
supplied with the battery cabinet, when the battery is fitted in a matching cubicle. Furthermore, this device serves as
a safety element for the cross section of the power cable between the UPS and the remotely placed battery system.
Therefore, the wall-mounted box must be installed as close as possible to the battery and the length of cables
between battery and UPS system must be the shortest.
Low THDi Reduce the harmonic currents rejected on the Mains.
15
The standard 6-pulse rectifier is replaced by the standard 12-pulse rectifier, with or without additional filter,
according to the THDi requirements.
26
Chloride Apodys AC UPS 316P-1ph
27
Chloride Apodys AC UPS 316P-1ph
10.3. Remote monitoring (embedded into the system) and 10.4. Other options
options fully detailed protocol coding
10.4.1. Special identification of
documentation.
10.3.1. Customer interface internal components
relays As standard, Apodys UPS includes
NOTE:
The communication cable internal sub-assemblies
between the UPS and the identification with self-adhesive
monitoring station is not part of vinyl labels. As an option, it is
Chloride’s supply. possible to change these labels to
engraved traffolyte labels, black
10.3.3. Monitoring software signs on white background.
PPVis 10.4.2. Top cable entry
It is possible to increase the Software solution is available to The option allows power cable
number of inputs/outputs remotely monitor all Chloride’s entry from the top of the UPS, by
described in paragraph 5.4 by UPS from the Apodys range (DC adding an external cabinet to
providing an additional board and AC systems). drive the cables down to the
with corresponding output The PPVis software (windows bottom of the UPS.
relays. These input/outputs can based) offers several features,
be used to monitor several such as: IMPORTANT NOTE
parameters specified by the user. Current state of components This option affects the overall
dimensions of the system.
Each board includes: Display of output voltage, UPS
3 inputs (from voltage free performances, load current 10.4.3. Internal lighting
contacts — Not provided) Number of input failures
Twenty outputs to drive voltage Data storage function
free contacts (provided). The
The figure hereafter shows a
requested number of output
PPVis screenshot for a UPS
information will be made
system.
available on double-pole change-
over (dpco) contacts (8A/250V
AC1; 8A/30V DC1; 1A/60V DC1).
Internal lighting is available upon
request to improve internal
10.3.2. Modbus / Jbus visibility of the system.
Upon request, Apodys UPS is able
to remotely deliver information 10.4.4. Lifting eyes
through Modbus/Jbus protocol (2
or 4 wires).
28
Chloride Apodys AC UPS 316P-1ph
1982
1852
1852
100
100
0 mini 0 mini
WALL WALL
800 1200
0 mini
0 mini
808
808
800
1852
100
0 mini
WALL
1600
0 mini
808
29
Chloride Apodys AC UPS 316P-1ph
Notes
30
Chloride Apodys AC UPS 316P-1ph
Notes
31
Chloride Apodys AC UPS 316P-1ph
Asia Pacific
Chloride - Emerson Network Power
371, Beach Road, #17-03, Keypoint
Singapore 199597
Singapore
Tel: +65 6336 699
[email protected]
This publication is issued to provide outline information only and is not deemed Central and Latin America
to form part of any offer and/or contract. The company has a policy of continuous Chloride - Emerson Network Power
product development and improvement, and we therefore reserve the right to
1300 Concord Terrace, Suite 400
vary any information without prior notice.
Sunrise, Florida 33323
Tel: +1 954 984 3452
[email protected]
UPS APODYS 6P-31-CATALOGUE-UK-Rev3-01-2012