Section 26_05_53_00_IEC(16075)

Identification for Electrical Systems

Rev 1.1 Description of Change Author WP # Date


16075 (European)
1.0 K2 Baseline 04/30/01
1.1 Reviewed to “unexpire” this specification. No M.McGovern 06/16/04
changes.
2.0 Published C. Bustos 07/07/04
2.1 Cable and wire core labeling details updated. M McGovern n/a 02/10/05
3.0 Published C. Bustos 02/10/05
3.1 Israeli codes referenced, Israeli label and wire ,M McGovern 10/04/05
colours added and Israeli sample labels added .
4.0 Published C. Bustos 10/07/05
26_05_53_00_European(16075)
4.1 Conversion of spec number 16075 (European) to R. Lucius 11/09/05
MF04 number 26_05_53_00_European(16075)
5.0 Published(MF95) R. Lucius 03/27/06
5.1 Changed “European” to “IEC” due to European C. Bustos 06/04/08
being geographically incorrect where as IEC is
more International
6.0 Published C. Bustos 06/10/08
6.1 Update to cable marker type to Miltex type CM M McGovern 05/21/10
(formally referred to as “M10”) and deletion
inferior label not used anymore (i.e. F-10B-L & F-
10B-S). And an update on core colour table. Also
to align with proposed 50/60Hz merge wrt
attachment method of label’s.
7.0 Published C. Bustos 06/02/10

1. General

1.1. Work Included

A. Nameplates and tape labels.

B. Wire and cable markers.

C. Conduit colour coding.

D. Cable tray/rack labels.

1.2. Related Work

A. Section 26_00_10_00_IEC(16010) - Basic Electrical Requirements

B. Israeli codes, regulations and standards shall apply for projects in Israel and these
shall supersede sections contained within this specification where a conflict arises.

IMCS Rev. 7.0 dated 06/02/10 Page 1 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
2. Products

2.1. Materials

A. Nameplates: engraved three-layer laminated plastic, minimum 5-mm-high black


letters on a white background. Emergency equipment nameplates: white letters on a
red background.
1) Israeli specific details:
a. White letters on Black background - Normal power
b. White letters on Red background - Emergency power
c. White letters on Brown background - CPS Critical power
d. White letters on Yellow background - CPS Non-Critical power

B. Tape Labels: embossed adhesive tape with minimum 5 mm white letters on black
background.

C. Wire and Cable Markers (all regions except as noted):


1) Ireland: All cables shall be identified by means of non-deteriorating type cable
tags, ferrules, strap-on type supplied by CSI and manufactured by Miltex type
CM (formally referred to as M10) range of labels fitted on each termination
point. Labels shall be UV stabilized, halogen free, self extinguishing, oil
resistant, IPA (cleaning fluid) resistant and weather resistant.
2) Israel and other regions: All cables shall be identified by means of non-
deteriorating type, UV stabilized, oil-resistant, IPA (cleaning fluid) resistant and
weather resistant cable tags, strap-on type, as manufactured by Miltex, Critchley
Brothers or equal and approved. To be tied to cable using plastic tie-wrap.

D. Cable Core Markers: Wire core labels shall be a non-deteriorating type marker:
a. For Ireland site: as supplied CSI, type “C10” (heat-shrink tube by Raychem
Tyco) or “I 10” (push-on transparent sleeve by Brady).
b. For Isreal and other region’s: as types used for Ireland except supplied by
local agent.

E. Conductor-Colour Tape: coloured heat shrink sleeves or vinyl electrical tape. Refer
to clause 3.2.F for appropriate colours.

F. Cable Tray/Rack Labels: pressure-sensitive numbers manufactured from adhesive-


backed polyester film. Numbers are to be black on white background and 25 mm
high.

3. Execution

3.1. Installation for under 690 Volts AC:

A. Degrease and clean surfaces to receive nameplates or labels.

IMCS Rev. 7.0 dated 06/02/10 Page 2 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
B. Install nameplates and/or labels parallel to equipment lines.

C. Secure nameplates to equipment fronts using industrial grade double sided adhesive
tape. Where approved, only stainless steel set screws shall be used as an alternative
Use of self-tapping screws is not allowed.

D. Use embossed tape for identification of power source for individual wall switches
and receptacles, and for all fire alarm, security/access control, and CCTV systems
devices, such as strobe lights, evacuation speakers, emergency telephones, smoke
detectors, etc. Device identification tag to match system programming tag.
Coordinate with Contractor.

E. Wire and cable markers shall be fitted on each cable and termination point.

F. Branch circuit panelboard MCB labels shall be:-


1) All regions - computer printer stick-on label
2) Isreal - P-Touch tape

G. Wire and cable markers (labels) shall be fitted on each cable at each termination
point. In addition, labels shall be fitted to the cables at both sides of a PopOut where
it enters the Cleanroom.

3.2. Wire Identification

A. Power and lighting circuits: Provide wire markers on multi-core cables and on each
phase conductor and neutral in panelboards, switchboards, motor control centers,
gutters, multi circuit pull boxes, pull boxes wit parallel runs of the same circuit, outlet
and junction boxes, and at load connection.

B. Identify with branch circuit or feeder number for power and lighting circuits, and
with control wire number as indicated on schematic and interconnection diagrams for
control wiring.

C. Provide wire markers at each termination point of fire alarm, security/access control,
and CCTV systems cable. Identify cables in accordance with the wiring schedule on
the Drawing. Coordinate with the Contractor.

D. Cable tag’s shall the following information:-


1) Both the source and destination of the supply.
2) Branch circuit or feeder number.

E. Wire tags inside enclosures or panels:


1) Phase conductor  Feeder or circuit number and phase number.
2) Neutral conductor  Feeder or circuit number.
3) Ground conductor  Feeder or circuit number.

IMCS Rev. 7.0 dated 06/02/10 Page 3 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
F. Conductors for power circuits shall be identified per the following schedule:
1) Intel Ireland campus (690V and below):

Conductor Colour
Phase A (R) Red (or Brown core sleeved Red)
Phase B (S) Yellow (or Grey core sleeved Yellow)
Phase C (T) Blue
Neutral Black
Grounding Green/Yellow
Switchleg (lighting) Phase colour
Dc Positive Red
Dc Negative Black

2) IEC region (690V and below):

Conductor Colour
Phase A (R) Brown
Phase B (S) Black
Phase C (T) Grey
Neutral Blue
Grounding Green/Yellow
Switchleg (lighting) Phase colour
Dc Positive Red
Dc Negative Black

3) Israel:

Conductor
208/120V 400/230V Above 690V
Phase R (A) Brown Brown Red sleeve +R
Phase S (B) Brown with orange line Brown with orange line Yellow sleeve +S
Phase T (C) Brown with black line Brown with black line Blue sleeve +T
Neutral Blue Blue
Ground Green/Yellow Green/Yellow
Iso Ground Green/Yellow + label Green/Yellow + label
PEN Blue and sleeve Blue and sleeve
Green/Yellow Green/Yellow
Switch-leg Phase color Phase color

IMCS Rev. 7.0 dated 06/02/10 Page 4 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
(lighting)
Dc Positive Red Red
Dc Negative Black Black

3.3. Nameplate Engraving Schedule

A. Provide nameplates to identify all electrical distribution and control equipment, and
loads served. Letter height: 3 mm for individual switches and loads served, 6 mm for
distribution and control equipment identification.

B. Panelboards, Switchboards, and Motor Control Centres: 6 mm, identify equipment by


designation; 3 mm, identify voltage rating and source.

C. Individual Circuit Breakers, Switches, and Motor Starters in Panelboards,


Switchboards, and Motor Control Centres: 3 mm, identify source to device and the
load it services, including location.

D. Individual Circuit Breakers, Enclosed Switches, and Motor Starters: 3 mm, identify
load served and source.

E. Transformers: 6 mm, identify equipment designation; 3 mm, identify primary and


secondary voltages, primary source, and secondary load and location.

F. Fire Alarm, Security/Access Control, and CCTV Systems Panels: 12 mm, identify
equipment designation.

G. The following nameplate details are specific to Israel:


Figure 1 :- SAMPLE SWITCHBOARD / PANEL LEGEND PLATE

IMCS Rev. 7.0 dated 06/02/10 Page 5 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
Figure 2

IMCS Rev. 7.0 dated 06/02/10 Page 6 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
Figure 3

IMCS Rev. 7.0 dated 06/02/10 Page 7 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
Figure 4

IMCS Rev. 7.0 dated 06/02/10 Page 8 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
Figure 5

120mm
5mm

CDOMN01 CELL 2/1 UP12000


5mm letters

50mm TO PMP 110-1-110

BOILER ROOM G12/3.5

5mm

INDIVIDUAL MOTOR STARTERS, VARIABLE SPEED DRIVES, SWITCHES, INDIVIDUAL


BREAKERS

Figure 6

300mm

Letters 50mm

CELL AM
200mm SOURCE CELL B8 Letters
30mm

FROM SWGR-4 –B3

3.3KV OR 22KV SWITCHGEAR TIE CELL

IMCS Rev. 7.0 dated 06/02/10 Page 9 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
Figure 7

300mm

Letters 30mm

CELL# 4
200mm TIE Letters
50mm

SWITCH

3.3KV OR 22KV SWITCHGEAR TIE CELL

IMCS Rev. 7.0 dated 06/02/10 Page 10 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
Figure 8

300mm

Letters 30mm

SWITCHGEAR

# 5 Letters 50mm
200mm
CELL B6
TO SUB 18A

3.3KV OR 22KV SWITCHGEAR OUTGOING CELL

Figure 9

Examples:

a) 1st line (10mm high text) - TOOL CODE: AMS408


2nd line (5mm high text) - SUPPLIED FROM: FF0NS08- C6
3rd line (5mm high text) - PANEL LOCATION: BASEMENT @ K/40

100mm

TOOL CODE: AMS408


50mm
SUPPLIED FROM: FF0NS08-C6
PANEL LOCATION: BASEMENT @ K/40

Figure 10

IMCS Rev. 7.0 dated 06/02/10 Page 11 of 13


Section 26_05_53_00_European(16075)
Identification for Electrical Systems
b) 1st line (10mm high text) - TOOL CODE: AMS408
2nd line (5mm high text) - SUPPLIED FROM: REMOTE AC PANEL CIRC. BKR.
# C1
3rd line (5mm high text) - PANEL LOCATION: SUBFAB @ M/40

125mm

TOOL CODE: AMS408


50mm
SUPPLIED FROM: REMOTE AC PANEL CIRC. BKR. # C1
PANEL LOCATION: SUBFAB @ M/40

Figure 11

c) 1st line (10mm high text) - TOOL CODE: AMS408


2nd line (5mm high text) - SUPPLIED FROM: FF0NS08 circ.# 1,3,5
3rd line (5mm high text) - PANEL LOCATION: BASEMENT @ N/41

100mm

TOOL CODE: AMS408


50mm SUPPLIED FROM: FF0NS08-1,3,5
PANEL LOCATION: BASEMENT @ N/41

3.4. Conduit and Wireway Colour Coding

A. Exposed conduit, including conduit above lay-in or accessible ceilings, together with
associated pull and junction boxes, shall be banded at intervals of not over 3 meters
and at all direction changes. Bands shall be different contrasting colours. Obtain
approval for colour of banding for systems not listed below.

B. Grounding: Green.

C. 400/230-Volt, Single- or Three-Phase System: Blue.

D. 110-Volt, Single-Phase System: Black.

E. Fire Alarm System: Red.

F. Building Management System (BMS): Blue and Black.


IMCS Rev. 7.0 dated 06/02/10 Page 12 of 13
Section 26_05_53_00_European(16075)
Identification for Electrical Systems
G. Telephone System: Yellow.

H. Emergency 400/230-Volt, Single- or Three-Phase System: Orange/Blue.

I. Emergency 110-Volt, Single-Phase System: Orange/Black.

J. Security/Access Control: Grey.

K. Closed-Circuit Television: White.

L. Gas Monitoring: Black/White.

M. Medium Voltage: Purple.

N. Non-FMS Controls: Brown.

O. Clean Power: Pink.

P. All BMS wireway, junction boxes, and conduit shall be labeled BMS USE ONLY.
All lettering shall be blue on a white background with lettering 25 mm high. In
addition, BMS raceway containing 230V control wiring shall be labeled CAUTION
230V.

3.5. Cable Tray/Rack Identification

A. Provide cable tray/rack markers on each independently identified section of cable


tray/rack as indicated on Drawings. Identify cable tray/rack numbers at all tees,
crossings, risers, and changes of direction as indicated on the Drawings.

End of Section