Operating Instructions
Operating Instructions
CROUSE-HINDS
SERIES
Explosion-protected distributions
GHG 619
1 Technical Data���������������������������������������������������� 27
1.1 Complete distribution......................................... 27
1.2 Bus-bar system up to max. 180 A...................... 28
1.2.1 Bus-bar system GHG758 up to max.
250 A / 315 A...................................................... 28
1.3.a Circuit breaker,
1-, 2-, 3-, 4-pole GHG 61..................................... 28
1.3.b Circuit breaker,
1-, 2-, 3-, 4-pole GHG 62..................................... 29
1.3.b.1 Circuit breaker,
1-, 2-, 3-, 4-pole................................................... 30
1.3.b.2 Signal contact GHG 622...................................... 30
1.3.b.3 Auxiliary contact multi pole GHG 622................ 30
1.3.b.4 Auxiliary contact 1 pole GHG 622....................... 30
1.3.b.5 Under-voltage release GHG 622......................... 31
1.3.b.6 Overload release GHG 622................................. 31
1.4 ELCB (RCD), 2- and 4-pole GHG61..................... 32
1.4 a Circuit breaker, 1-pole+N, with
ELCB (RCD) GHG61............................................ 32
1.5 ELCB (RCCB), 2 and 4-pole;
GHG624 ............................................................. 33
1.5a RCBO with Circuit breaker;
GHG625.............................................................. 33
1.5.1 Max. permissible contact voltage UL
for RCCB, RCBO ................................................ 33
1.5.2 Interface Relais R1561........................................ 33
1.6 Current surge switch.......................................... 34
1.7 20 A installation contactor............................... 34
1.8 24 A installation contactor............................... 34
1.9 40 A installation contactor.................................. 35
1.10 20 A air-break contactor...................................... 35
1.11 Star-delta time relay............................................ 35
1.12 Overvoltage arrester........................................... 36
1.13 Multi-function relay............................................. 36
1.14 Motor starter 4 kW............................................. 36
1.15 Thermal overcurrent relay................................... 37
1.16 Main current switch, 4-pole,
40 A, 80 A, 125 A and 180 A............................... 37
1.17 NH 00 main fuse, 3-pole..................................... 37
1.18 Manual motor starter up to 25 A........................ 38
1.18.1 Aux. contact........................................................ 38
1.18.2 Under voltage trip............................................... 38
1.19 Operating flap..................................................... 39
1.20 Signal lamp......................................................... 39
1.21 Actuator general................................................. 40
1.21.1 Actuator 2 pole for push button,
Mushroom head p.b., switch and
Key-operated pushbutton................................... 40
1.21.2 Actuator 4 pole for
push button, Mushroom head p.b., switch and
Key-operated pushbutton................................... 40
1.22 Potentiometer..................................................... 42
1.23 AM45/AM72 measuring instrument:.................. 42
1.24 Intrinsically safe circuits...................................... 42
1.25 Ex 23 control switch.......................................... 43
1.26 Ex 28 control switch........................................... 43
1.27 Ex 29 control switch........................................... 43
1.28 Flange socket 16 A.............................................. 44
1.29 Flange socket 32 A............................................. 44
2 Safety instructions��������������������������������������������� 46
3 Conformity with standards�������������������������������� 46
4 Field of application��������������������������������������������� 46
5 Application / Properties�������������������������������������� 47
5.1 Application / Properties
Flange sockets.................................................... 47
6 Installation���������������������������������������������������������� 47
6.1 Mounting............................................................ 47
6.2 Opening apparatus/
Electrical connection............................................... 48
6.3 Cable entries (KLE);
blanking plugs..................................................... 49
6.4 Flanges and metal plates.................................... 50
6.5 Closing apparatus............................................... 50
6.6 Putting into operation.......................................... 50
7 Maintenance / Servicing������������������������������������ 50
8 Repairs /
Modifications����������������������������������������������������� 50
9 Disposal / Recycling������������������������������������������� 50
10 Test torques
for terminal rows������������������������������������������������ 75
11 Cable gland�������������������������������������������������������� 75
11.1 Capri ADE 1F2.................................................... 75
11.2 Capri ADE 4F....................................................... 76
11.3 Plastic cable entries............................................ 77
12 Dimensional drawings��������������������������������������� 78
13 Dimensional drawings GHG 61������������������������� 79
14 Tripping characteristic of circuit breaker������������ 80
2
Explosion-protected distributions GHG 619 GB
1 Technical Data
1.1 Complete distribution
ATEX type examination certificate: BVS 22 ATEX E 006
Marking acc� to 2014/34/EU and standard:
EN 60079-0 D II 2 G Ex d e ia/ib mb [ia/ib] IIC T6/T5/T4 Gb
D II 2 D Ex tb IIIC T80°C, T95°C1) Db
1)
Limited selection
IECEx type examination certificate: IECEx BVS 22.0008
Category of application:
IEC60079-0 Ex d e ia/ib m [ia/ib] IIC (IIB)T6/T5/T4
Ex tD A21 IP66/IP65 T80°C, T95°C1)
27
Explosion-protected distributions GHG 619 GB
Fig. 1.3.a Connection Main-; 1.3.a Circuit breaker, 1-, 2-, 3-, 4-pole GHG 61
Aux.-/Signal contact
EC-Type Examination Certificate: PTB 98 ATEX 1087U
A B Explosion protection: Ex de II C
Temperature range: for use in temperature classes T4-T6
Main contact Aux. contact
Rated voltage: up to 400 V AC up to 240 V AC
Maximumvoltage acc. NEC for
"p" Type GHG 612 11.. R0013 - 27
GHG 612 21.. R0013 - 27
up to 480 V AC up to 240 V AC
GHG 612 31.. R0013 - 27
GHG 612 41.. R0013 - 27
Main contact Aux./Signal contact
Rated current:
Contact arrangement 0.5 A up to 40 A up to 5 A
Rated switching capacity: 6 kA
Back-up fuse: dep. on rated current, up to 100A
Terminal cross section Main contact: 1x 2.5 mm² up to 2x 10 mm² (Fig. 1.3a A oder B)
with fork-type cable lug: max. 2x 16 mm² (Fig. 1.3a B)
Aux./Signal contact: 1x 1.5 mm² up to 2x 2.5 mm² (Fig. 1.3a A)
Test torques Main contacts 3.0 Nm
1-pole 2-pole
Aux. contacts 1.5 Nm
1 2 3 4
Component size:
0.58 kg 0.96 kg 1.24 kg 1.62 kg
Weight: approx.
1-pole * 2-pole * 3-pole * 3-pol.+N
Contact arrangement:
Tripping characteristic of circuit breaker see capital 12
* Circuit breakers with signal contacts are built into component enclosures in the next size.
3-pole 4-pole
28
Explosion-protected distributions GHG 619 GB
Fig. 1.3.b 1.3.b Circuit breaker, 1-, 2-, 3-, 4-pole GHG 62
Series A Series E
Ambient temperature range 1): GHG 622 .... R 0... GHG 622 .... R 2...
IIC size 1 to size 4: -20 °C ... +55 °C -20 °C ... +50 °C
IIB size 1 to size 2: -45 °C ... +55 °C -45 °C ... +50 °C
Contact arrangement - Circuit breaker
IIB size 3 to size 4: -20 °C ... +55 °C -20 °C ... +50 °C
2) The operating temperature range refers to the adherence to the explosion protection parameters and defines
the maximum permissible temperatures of the materials of the flameproof enclosure.
The technical data relates to standard built-in apparatus. Terminal cross section:
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed. Main terminal module size 1-4
fine wire with cable lug: 1 x 1.5 mm² ... 1 x 16 mm²
2 x 1.5 mm² .. 2 x 4.0 mm²
with pin lug: to 2 x 16 mm²
with pin lug GHG GHG 510 1916 R0001: to 1 x 25 mm²
Aux. Terminals:
1 x 1.0 mm² ... 1 x 2.5 mm²
2 x 1.5 mm²
Quantity terminals for the module size: 1 2 3 4
Main terminals: 1 2 3 4
Aux. terminals: 2 3 4 5
Test torques
Main terminals: 2.4 Nm
Aux. terminals: 1.0 Nm
Mounting screws: 2.5 Nm
Enclosure material: Polyamide
29
Explosion-protected distributions GHG 619 GB
7 Series A Series E
Rated voltage: up to 230 V up to 250 V
Rated current: 5A 4A
Min. switching capacity: 5 mA at 24 V 10 mA at 5 V
Making/breaking capacity Ie/Ue (EN62019):
AC 13 -- 3 A / 250 V
8
1 A / 400 V
AC 14
3-pole 4-pole 2 A / 230 V
AC 15 3 A / 250 V
1 A / 220 V
DC 12 0,5 A/ 110 V
1,5 A/ 110 V
2 A / 60 V
DC 13 --
4 A / 24 V
Contact arrangement
additional devices
1.3.b.3 Auxiliary contact multi pole GHG 622
S
Series A Series E
Signal contact Rated voltage: up to 400 V up to 250 V
Rated current: 5A 4A
8 mA at 12 V
Min. switching capacity: 10 mA at 5 V
4 mA at 24 V
Making/breaking capacity Ie/Ue (EN62019):
AC 13 - 3 A / 250 V
1A / 400 V
H AC 14 -
2A / 230 V
AC 15 - 3 A / 250 V
Aux. contact 1A / 220 V
DC 12 0.5 A/ 110 V
1.5 A / 110 V
2A / 60 V
DC 13 -
4A / 24 V
30
Explosion-protected distributions GHG 619 GB
31
Explosion-protected distributions GHG 619 GB
32
Explosion-protected distributions GHG 619 GB
"TEST"
Rated voltage: Main contact 230/400 V AC up to 240/415 V AC
Pos. 1
Aux. contact up to 230V AC
Rated current: Main contakt up to 63A
Aux.contakt max. 5A
Short-circuit protection: 10 kA
Back-up fuse: max. 100 A gG
Tripping current: 30 mA up to 500 mA
Component size: 2* 3* 4
Weight: approx. 0,96kg 1,24kg 1,62kg
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.
Component size: 2* 3* 4
Weight: approx. 0,96kg 1,24kg 1,62kg
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.
2/1 N
Fig. 1.5.2 Contact Arrangement
1-pole + N ELCB with circuit breaker
and Interface Relais R1561
1/2 3/4
2/1 4/3
2-pole
33
Explosion-protected distributions GHG 619 GB
34
Explosion-protected distributions GHG 619 GB
35
Explosion-protected distributions GHG 619 GB
36
Explosion-protected distributions GHG 619 GB
Dimensions in mm
X = Fixing dimensions 1.16 Main current switch, 4-pole, 40 A, 80 A, 125 A and 180 A
37
Explosion-protected distributions GHG 619 GB
1= thermal trip
2= electromagnetic trip
38
Explosion-protected distributions GHG 619 GB
Size 1 MCB flap for GHG 61 Size 2 MCB flap for GHG 61 Click Frame 2 for GHG 61
29,5
29,5
Size 1 MCB flap for GHG 62 Size 2 MCB flap for GHG 62
40
Explosion-protected distributions GHG 619 GB
2 NC 2 NO 1 NO + 1NC
2 NC 2 NO 1 NO + 1NC
Circuity Code
.061
6060
.063
6062
.067
6065
Switch mechanism
4 5 6
Special switch
mechanism
7 8 9
2 NC 2 NO 1 NO + 1 NC
2 NC 2 NO 1 NO + 1 NC
41
Explosion-protected distributions GHG 619 GB
42
Explosion-protected distributions GHG 619 GB
6062
1.26 Ex 28 control switch
EC type examination certificate: BVS 14 ATEX E 076 U
6065 Rated voltage up to max. 500 V
Rated current: max. 20 A (up > 12 A wiring >=2,5 mm²)
Switching capacity AC 15: 230 V / 8 A 400 V / 6,0 A
6033 Switching capacity DC 13: 24 V / 6 A 230 V / 0,4 A
Perm. short-circuit back-up fuse: 25 A gG at 500 V
With gold-tipped contact: max. 400 mA
6170 Connection terminals: 2x 0,5 - 4,0 mm² 1 x 1,0 - 6,0 mm² 2,5 Nm
1 level 2 levels 3 levels
Weight:
approx. 0.25 kg approx. 0.40 kg approx. 0.55 kg
. 021
. 067
. 049
. 037
. 191
Switch mechanism
4 5 6
Special switch
mechanism
7 8 9 Switch actuator Ex 23 Switch actuator Ex 28 / Ex 29
43
Explosion-protected distributions GHG 619 GB
3 pôl. + N + PE
44
Explosion-protected distributions GHG 619 GB
110-130V 110-130V
45
Explosion-protected distributions GHG 619 GB
The apparatus shall be used for the In case of use in an extremely aggressive
intended purpose and shall be in a perfect atmosphere, please refer to manufacturer.
and clean state.
46
Explosion-protected distributions GHG 619 GB
When required, the Ex 28 and Ex 29 control The apparatus connected to the plug shall
Fig. 4
switches are provided with a locking facility that be suitable for the applied mains voltage.
1 also allows them to be locked with a padlock.
In order to switch on the socket, the plug is
Details of the electric contacts are given on the inserted, pushed fully home and then turned
base of the component. through approx. 45° to the right. Thereby the
plug is locked in the socket.
The version with gold-tipped contacts is marked
2 with a ”G” or with colour (see Technical Data, For switching off and pulling the plug, proceed
for max. current load). in inverse Order.
To ensure reliable isolation, the normally closed
contacts are designed as forced break contacts After a short in the circuit, the functioning of
Fig. 5
(optional Ex 28/Ex 29 with forced make the plug and socket system and of the plugs
Stainless steel contacts). has to be checked.
enclosure
Wall fixing Where required, the bases are fitted with 0.6 W
lugs
resistors, fine-wire fuses and diodes (max. pow-
er dissipation 1 W). 6 Installation
Screw M6 x 16
Spring washer The measuring instruments AM 72 and AM 45 The relevant national regulations(e.g. Betr.Si.V,
are used for the local indication of electrical the equipment safety law for Germany), the
Fig. 6 Mounting of fixing lugs values. (See Technical Data, for the type of generally recognized rules of engineering and
movement, accuracy and connections). the IEC/EN 60079-14 apply for the installation
and operation.
With measuring instruments for c.t. connection
n/1A (fig. 4, item 2), the interchangeable scales
6.1 Mounting
(fig. 4, page 28) can be exchanged via a flap on
right underneath the upper part of the measuring instrument. The distribution enclosures can be mounted
without opening the cover.
5 Application / Properties Observe the rated diversity factors accordance
to IEC/EN 60439 4.7 when equip the When the boxes are mounted directly onto the
The distributions are used for safeguarding, distributions. wall, they shall rest evenly only on the fastening
controlling, switching and distributing electric points provided for this purpose, and they shall
power, e.g. main, lighting, heating, control and Information on the safe use of third-party be fixed in such a way that they cannot twist or
intrinsically safe circuits, etc. (see Technical products, unless non specified in these turn.
Data for temperature classes, explosion groups, operating instructions, have to be requested
permissible ambient temperatures). from the respective manufacturer of the The screw used shall match the fixing hole (see
equipment. dimension drawings) and must not damage the
For controlling electric machines and installa- opening (e.g. use of a washer).
tions in potentially explosive atmospheres, the The data according to sections 3 and 4 shall
enclosures can be fitted with control and be taken into account during use. Distributions in the sizes 1 + 2 shall be fixed
indicating components that have been certified with a minimum of two diagonally opposed
for this purpose within the scope of the Applications other than those described are screws.
approvals. not permissible without a written declaration
of consent from the manufacturer. Distributions in the sizes 3 + 4 shall be fixed
Specially marked control unit components can with a minimum of 4 screws.
be operated in ”intrinsically safe circuits”. During operation the instructions stated in
The mounting of wall fixing lugs on stainless
section 7 of the operating instructions shall
The electric limiting values applicable to steel distribution boxes is shown on Figs. 5 + 6.
be observed. These operating instructions
”intrinsic safety” shall be observed. The fixing lugs are not be loaded with more
also apply as instructions for the replacement
than 50 kg.
or addition to individual flameproof compo-
The function of circuit breakers and ELCBs
nents. Excessive tightening can result in damage to
(RCDs) with circuit breakers shall be checked
after several short circuits. the flameproof enclosure or the terminal or
The sole responsibility with respect to the bus bar box.
An ELCB (RCD) does not prevent the sensation suitability and proper use of these boxes lies
caused by an electric shock, but it limits the with the operator. See the drawings and Figs. 1 - 3 for the
duration of the current flow through the human mounting of the bus bar connections.
body to such a short time that the probability of 5.1 Application / Properties The individual parts are enclosed loose in a bag.
a fatal effect is reduced to a negligible amount. Flange sockets
The MCB flap Size 2 is mounted with six
Once the cause for the tripping of the ELCB The flange sockets are used for the power screws. The clickframe is catched in the holders
(RCD) has been eliminated, it is reset by supply of local controls with varying locations, of the flap. Only with the clickframe the degree
switching the toggle to the ”ON” position. as well as of electrical installations, mobile of protection is IP66.
machinery and driving gear in hazardous areas.
By cutting out the switch collar in the respec- Warning: The connections for the incoming
tive locking position, the small control switches The low-voltage plugs and sockets are fitted and outgoing leads of the bus bar systems
can be locked with a padlocking facility. (Ø lock with a load switch and can be used up to max. shall be fitted in such a way that the current
shackle 5mm). 16 A / 32 A (see technical data). The plugs and load of the copper rails is distributed evenly.
The front actuators of the Ex 23 control sockets can generally be used for the voltage
switches feature a drilled hole, Ø 5.5mm, in the range laid down in IEC/EN 60309 (e.g. UN 400V All minimum clearances of the bus bar
respective locking position on the switch collar that corresponds to the voltage range 380-415V). systems to the enclosure wall and between
and can, therefore, be locked with a padlocking the connections shall be maintained in
facility of the type mentioned above. accordance with figs. 2-3.
47
Explosion-protected distributions GHG 619 GB
Individual moulded plastic distribution boxes are The built-in standard terminal is designed for
Fig. 7
suited for mounting on Size 3 apparatus holders the direct connection of conductors with copper
using self-tapping screws (see figs. 7 and 7a). wires.
Apparatus holder for pipe mounting, size 3
The mounting instructions for the apparatus DIN cable lugs shall be used to connect the
holder shall be observed. built-in bus bars and bolt terminals.
The insulation shall reach up to the terminal. The instructions for the installation of
The conductor itself must not be damaged. intrinsically safe electrical apparatus shall be
observed.
The minimum and maximum connectable
conductor cross sections are to be observed. It is necessary to ensure that the permissible
external capacitance and inductance for the
The test torques are specified by the manufac-
specific intrinsically safe circuit are not
turer in cap. 10 have to be observed.
exceeded.
A= F
ixing holes for size 1 All screws and/or nuts of the connection
When the apparatus is open, it is necessary
distribution enclosures terminals, including those not in use, shall be
to ensure (isolate voltage) that there is no
tightened down securely.
voltage transmission to the connected
Apparatus holder for wall and trellis mounting, intrinsically safe circuits.
size 3
Fig. 7a 2 x apparatus holders, size 3, for pipe mounting, horizontal
A
X
48
Explosion-protected distributions GHG 619 GB
The circuit diagram for the built-in components The relevant mounting directives for the
Fig. 8
is either shown on the components, enclosed built-in cables entries shall be observed.
Assembly pieces of the with the switch unit, or shown in the operating
double cable end box instructions. In the case of wired control units, See figs. 8 and 9 for how to assemble
1 the connection diagram included with the double cable end boxes:
apparatus is to be observed.
Undo the 2 fixing screws, Item 4, and the 3
When using multi- or fine-wire connection fixing screws, Item 12, of the top, Item 10, and
2 5 remove the top.
cables, the wire ends shall be treated in
accordance with the valid national and
Loosen the semicircular clamping pieces, Item
international regulations (e.g. use of cable end
3 14, of the strain relief. Adapt the cable sleeves,
sleeves).
Item 13, to suit the cable diameter and pull over
4
! In the case of building up the electrical the connection cable.
equipment in the "protective insulation" version,
Then screw the semicircular clamping pieces,
appropriate sticker
Item 14, of the strain relief securely onto the
( ) GHG 905 1002 P0005 can be requested
strain relief clamp again.
by the manufacturer.
! If the inserted terminal rail is not equipped Once the cable has been fitted, secure the
cable sleeve with the respective cable clamp,
completely with line-up terminals, the terminal
Item 8.
rail must be included in the equipotential earth
6 7 connection also. Finally, replace the top, Item 10, and fix
securely in position with the fixing screws,
To ensure that the distribution enclosure closes
Items 4 and 12, and refit the strain relief, Item 14.
properly and to avoid damage, switching at the
switch shafts of the switch inserts is prohibited Seal the unused entry opening of the double
8
when the apparatus is open or the cover is only cable end box with a blanking plug, Item 5,
1 Fixing lug replaced loosely. (Order No. GHG 740 1993 R0003).
2 Self-cutting screws
3 M5 fixing set If a flameproof component is disassembled, Warning: To guarantee the IP degree of
4 Fixing screws before it is connected to the electric power protection, it is necessary to ensure that the
5 Sealing plug supply, it is necessary to ensure that the seal, Item 6, is fitted correctly.
6 Seal components are put back into the distribution
7 Punched metal piece enclosure correctly. When using cable entries with a degree of
8 Cable clamps protection that is lower than the IP protection of
9 Enclosure base For actuating the flameproof protective
the apparatus (see Technical Data, pages 26),
10 Double cable end box – top components (circuit breakers / ELCBs RCDs),
the degree of IP protection for the complete
11 Double cable end box, bottom the actuating flap may also be opened while the
unit is reduced.
12 Fixing screws for top circuit is live.
13 Cable entry sleeve The colour-coded (light blue) cable entries shall
14 Cable clamp for strain relief Overtightening can damage the enclosure or
be used for leading-in the intrinsically safe
impair the sealing effect.
circuits.
Fig. 9 6.3 Cable entries (KLE); In order to ensure the minimum degree of
blanking plugs protection, any unused entry holes shall be
Assembly of double cable end box
sealed with certified blanking plugs.
Generally only certified cable entries and
9 14 blanking plugs may be used. When fitting cable entries, it is necessary to
ensure that the sealing inserts used are suitable
Trumpet-shaped cable glands or other for the cable diameter.
1/2 suitable entries with additional pull relief shall
be used for flexible cables . ! When using apparatus or cable entries for
the connection to or into the apparatus, when
6 applicable, the relevant special conditions for
safe use given in the individual certificates shall
be considered.
11
In the case of sealing inserts that are cut to
4 8 size, it is necessary to ensure that the insert is
properly adapted to the cable diameter.
49
Explosion-protected distributions GHG 619 GB
Overtightening can impair the degree of The ELCB (RCD) shall release when the test
Fig. 10
protection. button is actuated. If this is not the case, the
Connection of bolt terminals up to 240 mm² protective function is no longer guaranteed
Warning: and the ELCB (RCD) shall be replaced.
To ensure the minimum protection category,
the MCB flap shall be closed with a suitable During servicing, above all the correct working
socket-head spanner (M8). (Marking of lock order of parts on which the explosion protection
position indicator shall be set to Zu/Closed) depends, (e.g. intactness and efficiency of the
flameproof components, the enclosure, the
6.6 Putting into operation seals and cable entries), and the switch
mechanism function of the control switches
Before putting the apparatus into operation, shall be checked.
the tests specified in the individual national
regulations shall be performed. If, in the course of servicing, it is ascertained,
that repairs are necessary, section 8 of these
In addition to this, before being put into operating instructions shall be observed.
operation, the correct functioning of the
apparatus and of the built-in components
(measuring instruments, signal lamps,
pushbuttons, etc.) shall be checked in
8 Repairs / Modifications
accordance with these operating instructions
and other applicable regulations. Only original Cooper Crouse-Hinds / CEAG
Any unused metric Cooper Crouse-Hinds / parts shall be used for carrying out repairs.
At temperatures below -20° C it is important
CEAG cable entries shall be sealed with the
to make sure that their is no explosive In the event of damage to the flameproof
certified blanking plug for metric cable entries.
atmosphere in the surrounding of the encapsulation, replacement of the respective
distributions. Observe relevant labels on the components is mandatory. In case of doubt,
6.4 Flanges and metal plates distributions. For distributions with internal the respective apparatus shall be sent back
If flange plates of moulded plastic enclosures heating, the switch on standby is signaled by to the manufacturer for repair.
are to be mounted (e.g. after drilling entry the thermostat.
holes), to maintain the minimum protection Repairs that affect the explosion protection
category it is necessary to ensure that the The zero setting of the measuring instrument may only be carried out by Cooper Crouse-
flange plate and the fixing clamp are fixed needle shall be checked before putting it into Hinds / CEAG or by a qualified electrician in
correctly. operation. If necessary, the measuring compliance with the respective national
instrument needle shall be set to zero using the regulations (EN/IEC 60079-19).
The flange plates of stainless enclosures shall adjustment screw.
be mounted in such a way that the IP degree of Ex-d components in Ex-e distribution boxes may
protection is maintained. Here it is necessary to The incorrect installation and operation only be replaced by components of the same
pay attention to the exact fit of the sealing of distributions can result in the invalidation type (electrical ratings and mechanical size).
element. of the guarantee.
When replacing these individual built-in
PE conductors fed from outside are to be components (flameproof circuit breakers,
connected to the PE terminal provided on the contactors, measuring instruments, pushbut-
flange. The maximum terminal cross section tons, etc.), section 6.2 ”Opening apparatus /
7 Maintenance / Servicing
is 50 mm². Electrical connection” shall be observed.
The valid regulations EN/IEC 60079-17 for the
Warning: Metal enclosures, metal flanges, servicing / maintenance of electrical Apparatus modifications or design changes are
metal plates and metal glands shall be apparatus for use in potentially explosive not permitted; excepted from this are the fitting
incorporated in the potential equalization. atmospheres shall be observed. of additional cable entries and the installation of
connection terminals within the scope of the
Prior to opening the enclosure, it is necessary approvals for the respective apparatus or
6.5 Closing apparatus
to ensure that the voltage supply has been according to details laid down by the manu
Any foreign matter shall be removed from isolated or to take suitable protective facturer.
the apparatus. measures.
When replacing the enclosure cover, it is In the case of intrinsically safe circuits, it is
necessary to ensure that the switch shafts of permissible to carry out work while the circuit is 9 Disposal / Recycling
the switch inserts are fitted correctly into the live.
carrier openings of the switch handles. In The respective valid national regulations for
addition to this, it is also necessary to ensure The user is responsible for stipulating the waste disposal shall be observed when
that the front actuator elements match the necessary maintenance intervals specific to disposing of apparatus.
built-in components. the application depending on the conditions
of use, national directives and standards. To facilitate recycling of individual parts, parts
To ensure the minimum protection category, Should the maintenance interval for the made of moulded plastic shall bear the marking
the cover screws shall be tightened down function test of an RCB (ELCB) not be for the type of plastic used.
securely. defined, the manufacturer of the ECD (ELCB)
The product range is subject to changes and
recommends to test the function by the test
additions.
button twice yearly.
50
12 Dimensional drawings
Dimension drawings for moulded plastic Dimension drawings for stainless steel
enclosures enclosures
Size
Size 2
Size 3 Taille 3
Size 4
Dimensions in mm
X = Fixing dimensions
78
13 Dimensional drawings GHG 61
X = Fixing dimensions
Ø 5,5
x 166
177
x 166
177
36
54
132 132
114 114
x 61 102 x 97 102
Ø 5,5
Ø 5,5
x 166
x 166
177
177
72 108
79
14 Tripping characteristic of
circuit breaker
Min
Min
Grenzkennlinieaus
1 = Grenzkennlinie 1 = Grenzkennlinie 1 =Grenzkennlinie
Min
Grenzkennlinie aus
20 auskalten
dem dem Zustand 20 auskalten
dem dem Zustand 20 aus kalten
dem Zustand
Auslösezeit / Tripping time / Temps de déclenchement
dem
Sek
Sek
10 10 10
Sek
6 6 6
4 4 4
2 2 2
1 1 1
0.6 0.6 0.6
0.4 0.4 0.4
AC
0.2 AC 0.2 AC 0.2
0.1 DC 0.1 0.1 DC
DC
0.06 0.06 0.06
0.04 0.04 0.04
0.02 0.02 0.02
0.01 0.01 0.01
1 1.5 2 3 5 6 8 10 15 20 30 1 1.5 2 3 5 6 8 10 15 20 30 1 1.5 2 3 5 6 8 10 15 20 30
3 5 8 3 10 16 10 14 22.
kalten Zustand
Auslösezeit / Tripping time / Temps de déclenchement
kalten
dem Zustand
kalten Zustand dem kalten Zustand kalten
dem Zustand
kalten Zustand
10 1 10 1 10 1
Min
6 6 6
Min
Min
1 1 1
4 4 4
2 2 2
1 1 1
40 40 40
20 20 20
10 10 10
Sek
Sek
Sek
6 6 6
4 4 4
2 2 2
1 1 1
0.6 0.6 0.6
0.4 0.4 0.4
AC
0.2 AC 0.2 AC 0.2
0.1 DC 0.1 DC 0.1 DC
0.06 0.06 0.06
0.04 0.04 0.04
0.02 0.02 0.02
0.01 0.01 0.01
1 1.5 2 3 5 6 8 10 15 20 30 1 1.5 2 3 5 6 8 10 15 20 30 1 1.5 2 3 5 6 8 10 15 20 30
2 3 4,5 3 5 7,5 10 14 21
Vielfaches des Bemessungsstromes / Vielfaches des Bemessungsstromes / Vielfaches des Bemessungsstromes /
Multiple of rated current / Multiple of rated current / Multiple of rated current /
Multiples du courant mesuré
Z
Multiples du courant mesuré
S 280 UC S 280 UC K
Multiples du courant mesuré
80