myPLV

myPLV is an improvement on the recognized IPLV performance measurement. IPLV is a poor indicator of
™ actual chiller efficiency because of variations in actual job operating conditions. myPLV allows the engineer
to create job specific chiller application conditions and testing criteria that provide a much better indication of
various chillers' value.

calculator Units of Measure IP 


Region Middle East 
Country United Arab Emirates (ARE) 
State / Territory 
City / Location Dubai (0B) 
Building Type and Airside Economizer Office w/o Econ 
Chiller Condenser Type Air Cooled Chiller 
Building Peak Load 856 tons
Number of Chillers in Plant 2 **Assumes equal size chillers in parallel**
Size of Each Chiller 428 tons
Plant Capacity (calculated point) 856 tons
ASHRAE 90.1 Appx. G Oversize Factor (calculated point) 0%

myPLV™ Test and Submittal Points


Enter chiller performance values for four submittal points.
% Full Load tons ton-hrs weighting ODDB Chiller EER
25% 107 119,516 4.5% 74.2° F 14.3
50% 214 713,560 27.0% 85.4° F 12.5
75% 321 1,289,679 48.8% 92.0° F 10.6
94% 402 519,562 19.7% 94.7° F 8.9
design 428 0% 115.0° F 8.4
Total ton-hrs 2,642,316 myPLV™ 10.946
Chilled Water Setpoint: 44.0° F Annualized kWh 2,945,857