LOADING CALCULATIONS FOR LOWER CIRCUIT

TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 132.57
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 165.63
Wind direction 30 Weight Span(Min) 0 -200 Insulator - - - 191.97
MAX(SIN2Ω) 0.933 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 4386
Tension 0.15 2.715 2 250 125 Earth Wire 2453
Pilot 0.15 1.63 0 0 0

LOAD CASE - 1 : WIND DIRECTION 30deg. - RELIABILITY CONDITION (30deg.) - EVERYDAY TEMP. 100% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 350 x 165.63 x 0.00945 x 1 = 548
Due To Deviation = 2 x 1 x SIN (15) x 2453 = 1270
TOTAL = 1818
Vertical Load
Weight Of Wire = 0.428 x 1 x 525 (0) = 225 0
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 235 10
Longitudinal Load
= 0
TOTAL = 0

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x COS (30) = 136
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x COS (30) = 0
Wind On Wire = 350 x 132.57 x 0.021 x 1 = 975
Due To Deviation = 2 x 1 x SIN (15) x 4386 = 2271
TOTAL = 3382
Vertical Load
Weight Of Wire = 1 x 0.974 x 525 (0) = 512 0
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 1012 250
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x SIN (30) = 79
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x SIN (30) = 0
TOTAL = 79

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 106.57
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 133.14
Wind direction 45 Weight Span(Min) 0 -200 Insulator - - - 191.97
MAX(SIN2Ω) 0.750 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 3846
Tension 0.15 2.715 2 250 125 Earth Wire 2152
Pilot 0.15 1.63 0 0 0

LOAD CASE - 2 : WIND DIRECTION 45deg. - RELIABILITY CONDITION (30deg.) - EVERYDAY TEMP. 100% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 350 x 133.14 x 0.00945 x 1 = 441
Due To Deviation = 2 x 1 x SIN (15) x 2152 = 1114
TOTAL = 1555
Vertical Load
Weight Of Wire = 0.428 x 1 x 525 (0) = 225 0
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 235 10
Longitudinal Load
= 0
TOTAL = 0

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x COS (45) = 111
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x COS (45) = 0
Wind On Wire = 350 x 106.57 x 0.021 x 1 = 784
Due To Deviation = 2 x 1 x SIN (15) x 3846 = 1991
TOTAL = 2886
Vertical Load
Weight Of Wire = 1 x 0.974 x 525 (0) = 512 0
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 1012 250
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x SIN (45) = 111
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x SIN (45) = 0
TOTAL = 111

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 142.09
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 177.52
Wind direction 0 Weight Span(Min) 0 -200 Insulator - - - 191.97
MAX(SIN2Ω) 1.000 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 4579
Tension 0.15 2.715 2 250 125 Earth Wire 2560
Pilot 0.15 1.63 0 0 0

LOAD CASE - 3 : WIND DIRECTION 0deg. - RELIABILITY CONDITION(15deg.) - EVERYDAY TEMP. 100% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 350 x 177.52 x 9.45 x 1 = 588
Due To Deviation = 2 x 1 x SIN (7.5) x 2560 = 669
TOTAL = 1257
Vertical Load
Weight Of Wire = 0.428 x 1 x 525 (0) = 225 0
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 235 10
Longitudinal Load
= 0
TOTAL = 0

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x COS (0) = 157
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x COS (0) = 0
Wind On Wire = 350 x 142.09 x 21 x 1 = 1045
Due To Deviation = 2 x 1 x SIN (7.5) x 4579 = 1196
TOTAL = 2398
Vertical Load
Weight Of Wire = 1 x 0.974 x 525 (0) = 512 0
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 1012 250
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x SIN (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x SIN (0) = 0
TOTAL = 0

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 106.57
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 133.14
Wind direction 0 Weight Span(Min) 0 -200 Insulator - - - 143.98
MAX(SIN2Ω) 0.750 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 3846 4579
Tension 0.15 2.715 2 250 125 Earth Wire 2152 2560
Pilot 0.15 1.63 0 0 0

LOAD CASE - 4 : WIND DIRECTION 0deg. - INTACT CONDITION(15deg.) - EVERYDAY TEMP. 75% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 350 x 133.14 x 9.45 x 1 = 441
Due To Deviation = 2 x 1 x SIN (7.5) x 2560 = 669
TOTAL = 1110
Vertical Load
Weight Of Wire = 0.428 x 1 x 525 (0) = 225 0
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 235 10
Longitudinal Load
= 0
TOTAL = 0

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x COS (0) = 118
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x COS (0) = 0
Wind On Wire = 350 x 106.57 x 21 x 1 = 784
Due To Deviation = 2 x 1 x SIN (7.5) x 4579 = 1196
TOTAL = 2098
Vertical Load
Weight Of Wire = 1 x 0.974 x 525 (0) = 512 0
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 1012 250
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x SIN (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x SIN (0) = 0
TOTAL = 0

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 106.57
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 133.14
Wind direction 0 Weight Span(Min) 0 -200 Insulator - - - 143.98
MAX(SIN2Ω) 0.750 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 3846 4579
Tension 0.15 2.715 2 250 125 Earth Wire 2152 2560
Pilot 0.15 1.63 0 0 0

LOAD CASE - 5 : WIND DIRECTION 0deg. - BROKEN CONDITION(15deg.) - EVERYDAY TEMP. 75% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 210 x 133.14 x 9.45 x 1 = 265
Due To Deviation = 1 x 1 x SIN (7.5) x 2560 = 335
TOTAL = 600
Vertical Load
Weight Of Wire = 0.428 x 1 x 315 (-200) = 135 -86
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 145 -76
Longitudinal Load
Due To Deviation = 1 x 1 x COS (7.5) x 2152 = 2134
TOTAL = 2134

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x COS (0) = 118
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x COS (0) = 0
Wind On Wire = 210 x 106.57 x 21 x 1 = 470
Due To Deviation = 1 x 1 x SIN (7.5) x 4579 = 598
TOTAL = 1186
Vertical Load
Weight Of Wire = 1 x 0.974 x 315 (-200) = 307 -195
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 807 55
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x SIN (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x SIN (0) = 0
Due To Deviation = 1 x 1 x COS (7.5) x 3846 3814
TOTAL = 3814

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(m) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 142.09
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 177.52
Wind direction 0 Weight Span(Min) 0 -200 Insulator - - - 191.97
MAX(SIN2Ω) 1.000 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 4579
Tension 0.15 2.715 2 250 125 Earth Wire 2560
Pilot 0.15 1.63 0 0 0

LOAD CASE - 6 : WIND DIRECTION 0deg. - RELIABILITY CONDITION(30deg.) - EVERYDAY TEMP. 100% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 350 x 177.52 x 9.45 x 1 = 588
Due To Deviation = 2 x 1 x SIN (15) x 2560 = 1326
TOTAL = 1914
Vertical Load
Weight Of Wire = 0.428 x 1 x 525 (0) = 225 0
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 235 10
Longitudinal Load
= 0
TOTAL = 0

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x COS (0) = 157
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x COS (0) = 0
Wind On Wire = 350 x 142.09 x 21 x 1 = 1045
Due To Deviation = 2 x 1 x SIN (15) x 4579 = 2371
TOTAL = 3573
Vertical Load
Weight Of Wire = 1 x 0.974 x 525 (0) = 512 0
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 1012 250
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 191.97 x SIN (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 191.97 x SIN (0) = 0
TOTAL = 0

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 106.57
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 133.14
Wind direction 0 Weight Span(Min) 0 -200 Insulator - - - 143.98
MAX(SIN2Ω) 0.750 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 3846 4579
Tension 0.15 2.715 2 250 125 Earth Wire 2152 2560
Pilot 0.15 1.63 0 0 0

LOAD CASE - 7 : WIND DIRECTION 0deg. - INTACT CONDITION(30deg.) - EVERYDAY TEMP. 75% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 350 x 133.14 x 9.45 x 1 = 441
Due To Deviation = 2 x 1 x SIN (15) x 2560 = 1326
TOTAL = 1767
Vertical Load
Weight Of Wire = 0.428 x 1 x 525 (0) = 225 0
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 235 10
Longitudinal Load
= 0
TOTAL = 0

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x COS (0) = 118
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x COS (0) = 0
Wind On Wire = 350 x 106.57 x 21 x 1 = 784
Due To Deviation = 2 x 1 x SIN (15) x 4579 = 2371
TOTAL = 3273
Vertical Load
Weight Of Wire = 1 x 0.974 x 525 (0) = 512 0
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 1012 250
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x SIN (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x SIN (0) = 0
TOTAL = 0

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 106.57
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 133.14
Wind direction 0 Weight Span(Min) 0 -200 Insulator - - - 143.98
MAX(SIN2Ω) 0.750 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 3846 4579
Tension 0.15 2.715 2 250 125 Earth Wire 2152 2560
Pilot 0.15 1.63 0 0 0

LOAD CASE - 8 : WIND DIRECTION 0deg. - BROKEN CONDITION(30deg.) - EVERYDAY TEMP. 75% WIND
1) GROUNDWIRE
MAX MIN
Transverse Load
Wind On Wire = 210 x 133.14 x 9.45 x 1 = 265
Due To Deviation = 1 x 1 x SIN (15) x 2560 = 663
TOTAL = 928
Vertical Load
Weight Of Wire = 1 x 0.428 x 315(-200) = 135 -86
Wt. Of GW Clamp = 10 = 10 10
TOTAL = 145 -76
Longitudinal Load
Due To Deviation = 1 x 1 x COS (15) x 2152 = 2079
TOTAL = 2079

2) CONDUCTOR
MAX MIN
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x COS (0) = 118
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x COS (0) = 0
Wind On Wire = 210 x 106.57 x 21 x 1 = 470
Due To Deviation = 1 x 1 x SIN (15) x 4579 = 1186
TOTAL = 1774
Vertical Load
Weight Of Wire = 1 x 0.974 x 315 (-200) = 307 -195
Weight Of Insulator = 2 x 250 (125) = 500 250
Weight Of Pilot Insulator = 0 (0) = 0 0
TOTAL = 807 55
Longitudinal Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 143.98 x SIN (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 143.98 x SIN (0) = 0
Due To Deviation = 1 x 1 x COS (15) x 3846 = 3715
TOTAL = 3715

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 0.00
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 0.00
Wind direction 0 Weight Span(Min) - - Insulator - - - 0.00
MAX(SIN2Ω) 1.000 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 2012
Tension 0.15 2.715 2 250 125 Earth Wire 1028
Pilot 0.15 1.63 0 0 0

LOAD CASE - 9 : WIND DIRECTION 0deg. - SAFETY NORMAL CONDITION(30deg.) - EVERYDAY TEMP. NIL WIND
1) GROUNDWIRE
MAX INTACT
Transverse Load
Wind On Wire = 350 x 0 x 9.45 x 1 = 0
Due To Deviation = 2 x 1 x SIN (15) x 1028 = 533
TOTAL = 533
Vertical Load
Weight Of Wire = 2 x 525 x 0.428 x 1 = 450
Wt. Of GW Clamp = 10 x 2 = 20
Wt. Of man with tools = 153 = 153
Errection Load = 357 = 357
TOTAL = 980
Longitudinal Load
Due To Deviation = 1.5 x 1028 x 0.5 x 1 = 0 771
TOTAL = 0 771

2) CONDUCTOR
MAX
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 0 x COS (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 0 x COS (0) = 0
Wind On Wire = 350 x 0 x 21 x 1 = 0
Due To Deviation = 2 x 1 x SIN (15) x 2012 = 1042
TOTAL = 1042
Vertical Load
Weight Of Wire = 2 x 1 x 0.974 x 525 = 1023
Weight Of Insulator = 2 x 2 x 250 = 1000
Weight Of Pilot Insulator =2x0 = 0
Wt. Of man with tools = 153 = 153
Errection Load = 357 = 357
TOTAL = 2533
Longitudinal Load
Due To Deviation = 1.5 x 2012 x 0.5 x 1 = 0 1509
TOTAL = 0 1509

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 0.00
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 0.00
Wind direction 0 Weight Span(Min) - - Insulator - - - 0.00
MAX(SIN2Ω) 0.000 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 2012
Tension 0.15 2.715 2 250 125 Earth Wire 1028
Pilot 0.15 1.63 0 0 0

LOAD CASE - 10 : WIND DIRECTION 0deg. - SAFETY BROKEN CONDITION(30deg.) - EVERYDAY TEMP. NIL WIND
1) GROUNDWIRE
MAX
Transverse Load
Wind On Wire = 210 x 0 x 9.45 x 1 = 0
Due To Deviation = 1 x 1 x SIN (15) x 1028 = 267
TOTAL = 267
Vertical Load
Weight Of Wire = 2 x 315 x 0.428 x 1 = 270
Wt. Of GW Clamp = 10 x 2 = 20
Wt. Of man with tools = 153 = 153
Errection Load = 357 = 357
TOTAL = 800
Longitudinal Load
Due To Deviation = 2.0 x 1028 x 0.5 x 1 = 1028
TOTAL = 1028

2) CONDUCTOR
MAX
Transverse Load
Wind On Insulator = 2 x 0.15 x 2.715 x 2 x 0.5 x 0 x COS (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 0 x COS (0) = 0
Wind On Wire = 210 x 0 x 21 x 1 = 0
Due To Deviation = 1 x 1 x SIN (15) x 2012 = 521
TOTAL = 521
Vertical Load
Weight Of Wire = 2 x 1 x 0.974 x 315 = 614
Weight Of Insulator = 2 x 2 x 250 = 1000
Weight Of Pilot Insulator =2x0 = 0
Wt. Of man with tools = 153 = 153
Errection Load = 357 = 357
TOTAL = 2124
Longitudinal Load
Due To Deviation = 2.0 x 2012 x 0.5 x 1 = 2012
TOTAL = 2012

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors
LOADING CALCULATIONS FOR LOWER CIRCUIT
TENSION POLE ''PC (15 - 30 deg.)''

Design Span = 350 m Span Detail (m) NC BWC Wire Details Dia.(mm) Wt.(Kg) Nos. Wind Pressure
Devation Angle (Max) 30 Wind Span 350 210 Conductor 21 0.974 1 0.00
Devation Angle (Min) 15 Weight Span(Max) 525 315 Earth Wire 9.45 0.428 1 0.00
Wind direction 0 Weight Span(Min) - - Insulator - - - 0.00
MAX(SIN2Ω) 0.000 Kg/m2

Insulator Detail Dia.(m) Length (m) Nos Wt.Max Wt.Min Wire Tension (Kg)
Suspension 0.15 2.64 2 200 100 Conductor 2012
Tension 0.15 2.715 2 250 125 Earth Wire 1028
Pilot 0.15 1.63 0 0 0

LOAD CASE - 11 : WIND DIRECTION 0deg. - ANTI-CASCADING CONDITION(30deg.) - EVERYDAY TEMP. NIL WIND
1) GROUNDWIRE
MAX
Transverse Load
Wind On Wire = 210 x 0 x 9.45 x 1 = 0
Due To Deviation = 1 x 1 x SIN (15) x 1028 = 267
TOTAL = 267
Vertical Load
Weight Of Wire = 315 x 0.428 x 1 = 135
Wt. Of GW Clamp = 10 = 10
Wt. Of man with tools =0 = 0
TOTAL = 145
Longitudinal Load
Due To Deviation = 1 x 1028 x COS (0) = 1028
TOTAL = 1028

2) CONDUCTOR
MAX
Transverse Load
Wind On Insulator = 1 x 0.15 x 2.715 x 2 x 0.5 x 0 x COS (0) = 0
Wind On Pilot Insulator = 0.15 x 1.63 x 0 x 0.5 x 0 x COS (0) = 0
Wind On Wire = 210 x 0 x 21 x 1 = 0
Due To Deviation = 1 x 1 x SIN (15) x 2012 = 521
TOTAL = 521
Vertical Load
Weight Of Wire = 1 x 0.974 x 315 = 307
Weight Of Insulator = 2 x 250 = 500
Weight Of Pilot Insulator =0 = 0
Wt. Of man with tools =0 = 0
TOTAL = 807
Longitudinal Load
Due To Deviation = 1 x 2012 x COS (0) = 2012
TOTAL = 2012

Notes :
1. All above loads are Unfactored loads in Kg.
2. Factor of Safety for monopole Design = 1.02
3. Apart from the above loads, monopole body wind & self weight of monopole is considered in analysis.
4. Wind Pressure on Wires & Insulators includes Drag & Gust factors as per IS 802 Part 1 Sec 2 : 2015.
5. Broken Wire Condition : Earth Wire + Any One Conductor (or) Any Two Conductors