Applications: Trip Relay
Applications: Trip Relay
High Burden Application The HV breaker may be expected to trip more quickly than the LV
breaker so the tripping signal is maintained by the delayed reset.
These relays, supplied as high burden, are suitable for use in high This ensures complete clearance by the LV circuit-breaker, even
security circuit-breaker tripping circuits. The high burden provides though the fault may have been cleared largely by the HV breaker
greater immunity to capacitance discharge currents, which can and the protection has started to reset.
result at the inception of an earth fault on battery wiring. This
makes the relays particularly suitable for use in distributed Low Burden Application
tripping or control relay contact logic schemes, where the
initiating contact may be remote from the relay. These relays are suitable for general applications where the
initiating contact is located close to the relay. When configured
MVAJ 05 for low burden applications, by removing the external link from
terminals 22 and 24, the burden is either cut off during operation
When configured for high burden applications, the burden is or is economised to a low figure instantaneously.
either cut off at operation or is economised to a low figure
instantaneously.