MVAJ 05/10/20 Tripping and Control Relays

Applications Type MVAJ 102 relay is specifically designed for applications


requiring a tripping relay which is self-resetting after a nominal
Self-reset relays reset when the initiating signal is removed, delay of 2.5 seconds. This relay may be used, for example, for
making them suitable for use as trip relays in auto-reclose inter-tripping between higher voltage and low voltage circuit-
schemes and also for general flagging purposes. Hand-reset relays breakers of a large 3-phase power transformer.
require manual resetting, making them effective lockout relays
which are commonly used to trip circuit-breakers associated with This may become necessary when the high voltage circuit-
transformers. Electrical-reset relays require a voltage to be breaker is tripped after a heavy internal fault by protection
applied to the unit to reset the contacts. These relays may be which cannot conveniently provide an auxiliary contact with a
used in auto-reclose schemes, or where remote resetting of the dwell time long enough to ensure correct tripping of the low
relay is required. voltage circuit-breaker.

Trip Relay Typically, the relay is initiated by transformer protection, such as


With the exception of the MVAJ 102 time delayed self-reset overall protection, restricted earth fault and Bucholz relays, in
relays, all trip relays are suitable for either low burden or high arrangements where both the HV and LV circuit-breakers are to
burden applications. be tripped simultaneously.

High Burden Application The HV breaker may be expected to trip more quickly than the LV
breaker so the tripping signal is maintained by the delayed reset.
These relays, supplied as high burden, are suitable for use in high This ensures complete clearance by the LV circuit-breaker, even
security circuit-breaker tripping circuits. The high burden provides though the fault may have been cleared largely by the HV breaker
greater immunity to capacitance discharge currents, which can and the protection has started to reset.
result at the inception of an earth fault on battery wiring. This
makes the relays particularly suitable for use in distributed Low Burden Application
tripping or control relay contact logic schemes, where the
initiating contact may be remote from the relay. These relays are suitable for general applications where the
initiating contact is located close to the relay. When configured
MVAJ 05 for low burden applications, by removing the external link from
terminals 22 and 24, the burden is either cut off during operation
When configured for high burden applications, the burden is or is economised to a low figure instantaneously.
either cut off at operation or is economised to a low figure
instantaneously.

MVAJ 10, MVAJ 20


When configured for high burden applications, the burden is
either cut off or is economised to a low figure after a 40-60 ms
time delay. Due to the greater minimum operating current, the
high burden application also permits the use of supervision relays
such as type MVAX 11, where the wiring is at risk. The 40- 60 ms
time delay ensures reliable operation of series elements such as
type MCAA repeat relays.