Commissioning Service Department

Commissioning Standard Test Formats

Description: (50+62BF) CBF RELAY REF615 Record No. :


Equip. No. Drawing ref.: Page 1 of 5
Contractor : Contract no.: Substation No :

1. GENERAL DATA AND INFORMATION:


Panel No. Designation
Serial No. Rated Voltage 125 VDC
Make Aux. Voltage 48 – 250 VAC/DC
DWG. & SH. No. Frequency 50 – 60 Hz
CT Ratio 1200/1A

2. MECHANICAL CHECKS AND VISUAL INSPECTION:


ITEM DESCRIPTION CHECKED
1 Inspect for physical damage / defects.
2 Verify Connections as per approved drawings.
3 Check tightness of all connections.
5 Check apparatus lists.
6 Check ferrules
7 Test Switch checked for correct function.
8 Check case earthing.

3. ELECTRICAL TESTS: With relay energized condition

ITEM DESCRIPTION CHECKED


1 Measured auxiliary supply.
2 Clock set at local time.
3 Time maintained when auxiliary supply removed.
5 Relay healthy (green) LED working.
6 Trip (red) LED working.

3.1 OPERATING DC SUPPLY CURRENT:


DC Current DC Current
DC Volt (V) Calculated WATT (W)
Without Fault (mA) During Fault (mA)

125 VDC

(Relays /energized): < 12.0 W (nominal)/< 18.0 W (max) Technical Data page: 809

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: (50+62BF) CBF RELAY REF615 Record No. :


Equip. No. Drawing ref.: Page 2 of 5
Contractor : Contract no.: Substation No :

4. INPUTS AND OUTPUTS TESTS:

INPUT OPTO-ISOLATORS CHECKS (With Relay Energized):

Test Procedure:
Go to CONFIGURATION - MONITORING,
I/O STATUS,
then go to BINARY INPUTS VALUES ( X120 (AIM) – X110 (BIO) )
to check the values after giving pulse on each BI.

TEST METHOD RESULT


OPTO
(Energize only one at a time with Display FALSE REMARKS
INPUT NO.
125V DC Station Battery voltage) to TURE

X120

BI 1 ENERGIZE TB NO. X120 : 1 – 2C SPARE

BI 2 ENERGIZE TB NO. X120 : 3 – 2C SPARE

BI 3 ENERGIZE TB NO. X120 : 4 – 2C SPARE

BI 4 ENERGIZE TB NO. X120 : 5 – 6 SPARE

X110

BI 1 ENERGIZE TB NO. X110 : 1 – 2 CBF INITIATION

BI 2 ENERGIZE TB NO. X110 : 3 – 4 SPARE

BI 3 ENERGIZE TB NO. X110 : 5 – 6C SPARE

BI 4 ENERGIZE TB NO. X110 : 7 – 6C SPARE

BI 5 ENERGIZE TB NO. X110 : 8 – 9C SPARE

BI 6 ENERGIZE TB NO. X110 : 10 – 9C SPARE

BI 7 ENERGIZE TB NO. X110 : 11 – 12C SPARE

BI 8 ENERGIZE TB NO. X110 : 13 – 12C SPARE

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: (50+62BF) CBF RELAY REF615 Record No. :


Equip. No. Drawing ref.: Page 3 of 5
Contractor : Contract no.: Substation No :

OUTPUT RELAYS CHECKS (With Relay Energized):

Test Procedure:
Go to IED CONFIGURATION,
TESTS, IED TEST, TEST MODE : ON,
then go to BINARY OUTPUTS-CHANGE THE POSITION OF EACH BO FROM FULSE TO TURE FROM HMI,
then check contact resistance.

TEST METHOD RESULT


OUTPUT
(Energize only one relay at a time by Contact Checked REMARKS
RELAY No.
Test ON in ‘IED TEST’) ≤ 0.2Ω

X100

PO1 CONTACT OPERATED X100 : 6 – 7 (N/O) CBF OPTD(86CBF)

PO2 CONTACT OPERATED X100 : 8 – 9 (N/O) CBF OPTD(86CBF)

SO1 CONTACT OPERATED X100 : 10 – 11 /10 - 12 (C/O) SPARE

SO2 CONTACT OPERATED X100 : 13 – 14 (N/O) CBF OPTD(FR)

PO3 CONTACT OPERATED X100 : 16 – 17 (N/O) SPARE

PO4 CONTACT OPERATED X100 : 21 – 22 (N/O) SPARE

IRF CONTACT OPERATED X100 : 3 – 4 (N/O) WATCHDOG

X110

SO1 CONTACT OPERATED X110 : 14 – 16 /14 - 15 (C/O) SPARE

SO2 CONTACT OPERATED X110 : 17 – 19 /17 - 18 (C/O) SPARE

SO3 CONTACT OPERATED X110 : 20 – 22 /20 - 21 (C/O) SPARE

SO4 CONTACT OPERATED X110 : 23 – 24 (N/O) SPARE

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: (50+62BF) CBF RELAY REF615 Record No. :


Equip. No. Drawing ref.: Page 4 of 5
Contractor : Contract no.: Substation No :

INDICATION LED TEST


LED Checks:

Go to MONITORING,
PROGRAMMABLE LEDS to view the physical position of the LED.

OPTO Input Number Result Display On or Off Function

LED 1 CBF INITIATION

LED 2 CBF OPTD

LED 3 DIST. TRIGGERED

LED 4 SPARE

LED 5 SPARE

LED 6 SPARE

LED 7 SPARE

LED 8 SPARE

5. MEASUREMENTS ACCURACY CHECKS:

Displayed value ( A )
Applied Value Expected Value ( A )
R Y B
0.1 In 120
0.5 In 600
1 In 1200
1.5 In 1800

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date:


Commissioning Service Department
Commissioning Standard Test Formats

Description: (50+62BF) CBF RELAY REF615 Record No. :


Equip. No. Drawing ref.: Page 5 of 5
Contractor : Contract no.: Substation No :
6. BREAKER FAILURE PROTECTION (50+62BF) PICK UP & DROP OFF
Current ( A ) Stage 1 Stage 2
Phase
Set Pickup Drop-off Set OPTD (ms) Set OPTD (ms)
R
Y 5% In 50 ms 100 ms
B
R
Y 15% In 100 ms 200 ms
B
R
Y 20% In 200ms 400 ms
B

Operation accuracy:
±1.5% of the set value or ±0.002 x In Technical Data page : 499

Operate time accuracy:


±1.0% of the set value or ±20 ms Technical Data page : 499
refer to manual page : 26/132

1 Communication with PC
2 Event Record Check
3 Disturbance Record Check

Tested by: ENG. Witnessed by: ENG.

Signature & Date: Signature & Date: