PX series

digital temperature
controller
MICRO-CONTROLLER X (48 × 48 mm)
DATA SHEET PXG4
PXG4 is a compact size temperature controller of front panel
size 48 × 48 mm. To cope with any of versatile uses as a
temperature controller, it has many input/output points and
sophisticated control functions.

FEATURES
1. Wide variety and number of input / output
1. Digital input: Up to 2 points (Up to 3 points for motor-
ized valve control)
2. Digital output: Up to 3 points
3. Control output: 4 types
Relay contact, SSR drive, voltage linear, current linear
4. Universal inputs: Thermocouple, resistance bulb, cur-
rent, voltage, mV linear
5. Remote SV input function
6. Analog re-transmission output function (for current or
voltage)
7. Motorized valve control output
2. User interface of easy-to-see indication and easy-to-use
SPECIFICATIONS
operation method
1. General Specifications
1. Easy-to-see, large display section
2. Parameters grouped by functions (1) Power supply :
3. User key to which you can assign a function 100 V ( - 15%) to 240 V (+ 10%) AC,
4. Password function provided for avoiding wrong opera- 50/60 Hz
tion and protecting settings 24 V (± 10%) DC. 24 V (± 10%) AC,
5. Front water-proof structure (IP66 in corformity) 50/60 Hz.
3. Advanced control functions to meet various applications (2) Power consumption:
1. Sampling cycle 200 ms 12 VA MAX.
2. Input indication accuracy ± 0.3%FS (3) Insulation resistance:
3. Manual control function 20 MΩ MIN. (at 500 V DC)
4. Control method selectable out of 8 different types: (4) Withstand voltage:
ON/OFF control, PID control, fuzzy PID control, self- Power source ⇔ all terminals
tuning control, PID2 control, motorized valve control 1500 V AC for 1 min
(without PFB input) Relay contact output ⇔ all terminals
5. Heating/cooling control selectable 1500 V AC for 1 min
6. Auto tuning function Between others 500 V AC for 1 min
4. A variety of functions extending the possibility of tem- (5) Approvals and certification:
perature controller UL(UL873), C-UL(CSA C22.2 No.24-93 or
1. Guarantee soak function provided, 16 step ramp/soak equivalent), CE mark(LVD : EN61010-1,
function EMC : EN61326-1)
2. 8 PID setting pallets, 8 SV pallets capable of frequent
change of control 2. Input section
3. Soft start function that limits MV output when start-
ing up 2.1 Process value input
4. Ramp SV function enables graduate change of SV (1) Number of inputs :
5. Loop burnout alarm, heater burnout alarm and various 1 point
event outputs are available in digital output (option) (2) Input setting: Programmable scale
6. Control standby function (3) Input signal: See Table 1 (thermocouple, resistance
7. Loader interface (RS-232C) standard provided bulb, mV, voltage, current (With external
8. RS485 communication (option) 250Ω resistance) universal input)
(4) Standard measurement range and input type:
See Table 1

EDS11-158c
Date Apr. 1, 2011
PXG4

(5) Indication accuracy (at Ta = 23˚C) : (3) Detected current accuracy:


• Thermocouple input: ± 0.3%FS ± 1 digit Setting ± 10%FS
± 1˚C or ± 2˚C, whichever greater (4) Detected current resolution:
*except: 0.1 A
Thermocouple B, 0 to 400˚C (5) ON time necessary for detection:
± 5%FS ± 1 digit ± 1˚C 800 ms MIN.
Thermocouple R, 0 to 500˚C 2.4 Digital input (DI)
±1%FS ± 1 digit ± 1˚C
(1) Number of points:
Thermocouple T, -200 to 0˚C
Up to 2 points (up to 3 points for motor-
±0.5%FS± 1 digit ± 1˚C
ized valve control output)
• Resistance bulb input: ± 0.3%FS ± 1
(2) Specifications: No-voltage contact or transistor input
digit or ± 0.5˚C, whichever greater
(3) Contact capacity:
• mV input, voltage input, current input:
30 V DC, about 3 mA (per point)
± 0.3%FS ± 1 digit
(4) Input judgment:
(6) Indication accuracy by change of temperature:
ON assumed at 1 kΩ or lower (contact) or
± 0.3%FS/10˚C
5 V DC or lower (transistor)
(7) Indication resolution:
OFF assumed at 100 kΩ or higher (con-
See Table 1
tact) or 18 V DC or higher (transistor)
(8) Input sampling cycle:
(5) Sampling pulse width:
200 ms
200 ms MIN.
(9) Input impedance:
(6) Functions: Remote mode selection, SV changeover,
• Thermocouple, mV input: 1 MΩ MIN.
control standby, AT startup, timer startup,
• Current input: 250 Ω
alarm unlatch, Program selection, start /
• Voltage input: About 1 MΩ
stop / reset, PID switching (normal/re-
(10) Variation by signal source resistance:
verse), etc.
• Thermocouple, mV input: ± 0.3%FS ±
1 digit per 100 Ω 3. Output section
• Voltage input: ± 0.3%FS ± 1 digit per
500 Ω 3.1 Control output
(11) Allowable wiring resistance:
(1) Number of points:
• Resistance bulb: 10 Ω MAX. (per wire)
Up to 2 points (2 points: Heating/cooling
(12) Allowable input voltage:
control)
• DC voltage input: Between +35 and
(2) Type: selected out of [1] to [5] below
- 10 V
[1] Relay contact output
• Current input: Within ± 25 mA
• Proportional cycle: 1 to 150 sec
• Thermocouple, resistance bulb, mV in-
• Contact structure: 1 NO (SPST) con-
put: Within ± 5 V
tact
(13) Noise rejection ratio:
• Contact capacity:
• Normal mode: 40 dB (50/60 Hz)
220 V AC/30 V DC, 3 A (resistive
• Common mode: 120 dB (50/60 Hz)
load)
From ground, at 220 V AC, 50/60 Hz
220 V AC/30 V DC, 1 A (inductive
Between input and output, at 220 V AC,
load)
50/60 Hz
• Minimum ON/OFF current: 100 mA
(14) Input correction:
(24 V DC)
(a) User adjustment: Zero point, span
• Mechanical life: 20 million operations
± 50%FS for each
MIN. (100 operations/min)
(b) Process value shift: ± 10%FS
• Electrical life: 100,000 operations
(c) Input filter: 0.0 to 120.0 sec (filter OFF
MIN. (rated load)
if set at 0.0)
[2] SSR/SSC drive output
(15) Overrange, underrange:
• Proportional cycle: 1 to 150 sec
Beyond range of -5 to 105% (accuracy
• ON voltage: 20 V DC (18 to 24 V DC)
not guaranteed between -5 and 0, and be-
• OFF voltage: 0.5 V DC or lower
tween 100 and 105%FS)
• Maximum current: 20 mA DC (for
2.2 Auxiliary analog input (remote SV input) each of outputs 1 and 2)
(1) Number of inputs: • Load resistance: 850 Ω MIN.
Up to 1 point [3] Current output (0 to 20 mA DC/4 to
(2) Input signal: Voltage, 0 to 5 V DC /1 to 5 V DC 20 mA DC)
(3) Input impedance: • Accuracy: ± 5%FS
About 1 MΩ • Linearity: ± 5%FS
(4) Sampling rate: • Load resistance: 600 Ω MAX.
800ms [4] Voltage output (0 to 5 V DC/1 to 5 V
2.3 Heater current detector (CT) input DC/0 to 10 V DC/2 to 10 V DC)
• Accuracy: ± 5%FS
(1) Input type: Single phase CT Up to 1 point
• Linearity: ± 5%FS
For 1 to 30 A: CTL-6-S-H
• Load resistance: 10 kΩ MIN.
For 20 to 50 A: CTL-12-S36-8F
(2) Range of detected current:
1 to 50A

2
[5] Motorized valve control output 4. Indication/setting section
• Contact structure: 2 NO (SPST) con-
tacts 4.1 Display unit
• Contact capacity: 220 V AC/30 V DC, (1) Type: LED
1A (2) Indication contents:
• Minimum ON/OFF current: 100 mA Process value indication: 7 segments, 4
(24 V DC) digits [red]
• Mechanical life: 20 million operations Setpoint indication: 7 segments, 4 digits
MIN. (100 operations/min) [green]
• Electrical life: 100,000 operations Indication status: 6 indicator lamps
MIN. (rated load)
4.2 Setting section
• Output interlock: Unavailable
3.2 Digital output (DO) (1) Type: Sheet type keys (with emboss)
(2) Number of keys: 4 keys.
(1) Number of outputs:
Relay contact output SEL , , plus user function
Up to 3 points (shared common) key
Up to 2 points (independent common)
(2) Output specifications: 5. Control functions
Relay contact output
Contact structure: 1 NO (SPST) con- 5.1 Control types
tact (1) 2-position control (set parameter P to 0%)
Contact capacity: 220 V AC/30 V DC, 1 (2) PID control (fuzzy PID included)
A • PID parameters determination: Auto tuning,
Minimum Open/Close current: 100 mA Selftuning
(24 V DC) (3) PID dual (heating, cooling) function (fuzzy PID included)
Mechanical life: 20 million operations MIN. • PID parameters determination: Auto tuning
(100 operations/min) (4) Motorized valve control (servo) without position feed-
Electrical life: 100,000 operations MIN. back
(rated load) • Full stroke time: 30 sec MIN.
(3) Output functions: 5.2 Control parameters
Alarm output (see "Alarm function")
Main unit control mode output, program • Proportional band (P):
status output, etc. 0.0 to 999.9%. 2-position control when
(4) Output cycle: 200ms P = 0.
• Integral time (I): 0 to 3200 sec. Integral time control in-
3.3 Auxiliary analog output (re-transmission output)
validated when I = 0.
(1) Number of points: Up to 1 point • Differential time (D):
(2) Type: Current/voltage output (0 to 20 mA DC/4 0.0 to 999.9 sec. Differential time con-
to 20 mA DC/0 to 5 V DC/1 to 5 V DC/ trol invalidated when D = 0.
0 to 10 V DC/2 to 10 V DC) • Control cycle: 200 ms
• Guaranteed output range: 0 to 20.6 mA • Anti-reset windup:
DC/0 to 10.3 V DC 0 to 100% of measurement range
• Accuracy: ± 0.2%FS (± 5%FS at 1 mA • Hysteresis band:
or smaller) 50% of measurement range (at 2-posi-
• Linearity: ± 0.2%FS (± 5%FS at 1 mA tion control only)
or smaller) • Number of SV and PID combinations:
• Resolution: 5000 MIN. 8 combinations.
• Load resistance: 600 Ω MAX. (current) Changed by any of parameter setting,
10 kΩ MIN. (voltage) digital input, communication and user
(3) Output cycle: 200 ms function keying
(4) Output contents: 5.3 Control mode
PV, SV, DV, MV
(5) Additional function: (1) Mode type: Auto, Manual, Remote
Scaling function (2) Mode changeover:
(6) Limitation: Not selectable when using control output 2 Auto↔Manual: Balanceless · bumpless
Auto/Manual→Remote: Balance ·
bumpless
Auto/Manual←Remote: Balance ·
bumpless

3
PXG4

6. Alarm function 11. Structure

6.1 Number of alarm setting points (1) Mounting method:


Mounted with panel
• Up to 3 points (depends on number of DO)
(2) External terminals:
6.2 Alarm type Screw terminals, M3
• Process value (upper limit/lower limit, absolute/devia- (3) Case: • Material: ABS, and degeneration PPO
tion, range), main unit error, etc. • Non-combustibility grade: UL94V-0
(non-excitation, delay, latch, timer function option provided) equivalent
• Color: Black
6.3 Heater burnout alarm function (4) Protection structure:
(1) Detectable range: • Panel front side: IP66, NEMA-4X equiva-
1 to 50 A lent (if panel is mounted using our
(2) Detected current resolution: genuine packing. Not water-proof if
0.1 A mounted closely together.)
(3) Setting resolution: • Body: IP20 equivalent (slits on top and
0.1 A bottom)
(4) Hysteresis: 0.0 to 50.0 A • Terminals: IP00 equivalent. Terminal
cover can be mounted optionally.
(5) Dimensions: 48 (W) × 48 (H) × 80 (D) mm
7. Communication function (6) Mass: About 200 g

7.1 RS-485 interface


12. Scope of delivery
(1) Number of points: 1 point
(2) Physical specifications: EIA RS485 • Controller: 1 unit
(3) Protocol: Modbus-RTU • Instruction manual: 1 copy
(4) Communication method: • Panel mounting frame: 1 pc
Half duplex bit serial, Asynchronous com- • Water-proof packing: 1 pc
munication • Shunt resistor: 1 pc
(5) Code type: Data length 8 data bits. Parity ... Odd, • Unit nameplate: 1 pc
even, none.
(6) Communication rate:
9600 bps, 19200 bps 13. User customize function
(7) Connection status:
Up to 32 units connectable including multi- 13.1 Program (ramp/soak) function
drop master function
(1) Number of program steps:
(8) Communication distance:
16 steps × 1 pattern,
Up to 500 m (total connect extension)
8 steps × 2 patterns, or
4 steps × 4 patterns
(1 step = 2 segments)
8. Processing at power failure (2) Control option:
Control by digital input
• Memory protection: Status output by digital output
Protect by non-volatile memory (3) Basic function:
[1] Segment time can be set in "Hour,
9. Self-diagnosis Minutes" or "Minutes, Seconds"
[2] Guarantee soak
• Method: Program error supervision by watchdog [3] Repeat action
timer [4] PV start
[5] Delay start
[6] Power failure restoring function
10. Operation and storage conditions
(4) Memory backup:
(1) Operating ambient temperature: EEPROM
-10 to 50˚C 13.2 User functions
(2) Storage temperature:
• Pressing the user key can perform Auto/Manual change,
-20 to 60˚C
Standby ON/OFF change, remote SV change, ramp/soak
(3) Operating/storage ambient humidity:
change or other function as assigned
90%RH MAX. (no condensing)
(4) Warm-up time: 13.3 Password function
30 min MIN • 3 level password function
(5) Vibration: 10 to 70 Hz, 9.8 m/s2 (1 G) MAX.
(6) Impact: 49 m/s2 (5 G) MAX.

4
CODE SYMBOLS
Standard type
1 2 3 4 5 6 7 8 9 1011 12 13 Digit
P XG 4
Digit Specifications Note
4 <Front panel size W × H>
48 × 48mm 4
5 <Output 1>
Relay contact A
SSR drive C
Current (0 to 20 mA DC/4 to 20 mA DC) Note1 E
Voltage (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC) Note1 P
6 <Output 2>
None Y
Relay contact Note2 Note4 A
SSR drive Note2 Note4 C
Current (0 to 20 mA DC/4 to 20 mA DC) Note2 Note4 E
Voltage (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC) Note2 Note4 P
Re-transmission output, current (0 to 20 mA DC/4 to 20 mA DC) Note2 Note4 R
Re-transmission output, voltage (0 to 5 V DC/1 to 5 V DC/0 to 10 V DC/2 to 10 V DC) Note2 Note4 S
7 <Option 1>
None Y
RS485 M
Digital input (No.1) + Digital input (No.2) T
Digital input (No.1) + RSV1 H
Digital input (No.1) + CT1 Note1 Note3 G
RS485 + Digital input (No.1) V
RS485 + RSV1 K
RS485 + CT1 Note1 Note3 J
RS485 + Digital input (No.1) + RSV1 Note4 F
Digital input (No.1) + RSV1 +Digital input (No.2) Note4 2
8 <Revision symbol>
1
9 <Digital output> (relay contact output)
None Note3 0
digital output 1 point (No.1) 1
digital output 2 points (No.1,2) F
digital output 3 points (No.1,2,3) Note2 M
digital output 2 points [independent common] (No. 1, 2) J
10 <Power source, instruction manual>
100 to 240 V AC, no instruction manual N
100 to 240 V AC, Japanese instruction manual Y
100 to 240 V AC, English instruction manual V
24 V AC/DC, no instruction manual C
24 V AC/DC, Japanese instruction manual A
24 V AC/DC, English instruction manual B
11 <Option 2>
12 None Y 0 0
13

Note 1: If output 1 was for current or voltage output, option cannot be assigned to CT1.
(If 7th digit was assigned to G or J, 5th digit cannot be assigned to E nor P.)

Note 2: If output 2 was for relay contact, SSR drive, current, voltage or retransmission output, 3 digital
outputs cannot be assigned.
(If 6th digit was assigned to A, C, E, P, R or S, 9th digit cannot be assigned to M.)

Note 3: If CT1 was selected in option 1, None in <Digital output> cannot be assigned.
(If 7th digit was assigned to G or J, 9th digit cannot be assigned to 0.)

Note 4: If RSV1 in option 1 and digital input 1 were selected simultaneously, output 2 cannot be assigned.
(If 7th digit was assigned to F or 2, 6th digit cannot be assigned to A, C, E, P, R nor S.)

5
PXG4

CODE SYMBOLS
Motorized valve control type
1 2 3 4 5 6 7 8 9 1011 12 13 Digit
P XG 4
Digit Specifications Note
4 <Front panel size W × H>
48 × 48mm 4
5 <Output 1>
Motorized valve control output (Without PFB) Note1 S
6 <Output 2>
None Y
7 <Option 1>
None Y
Digital input (No.1) + RSV1 H
Digital input (No.1,2,3) D
RS485 + Digital input (No.1) V
RS485 + RSV1 K
8 <Revision symbol>
1
9 <Digital output> (relay contact output)
None 0
digital output 1 point (No.1) 1
digital output 2 points (No.1,2) F
digital output 2 points [independent common] (No. 1, 2) J
10 <Power source, instruction manual>
100 to 240 V AC, no instruction manual N
100 to 240 V AC, Japanese instruction manual Y
100 to 240 V AC, English instruction manual V
24 V AC/DC, no instruction manual C
24 V AC/DC, Japanese instruction manual A
24 V AC/DC, English instruction manual B
11 <Option 2>
12 None Y 0 0
13
Note 1: If front panel size is 48 × 48, position feedback input (PFB input) function is not available.

OPTIONALLY ITEMS
Instruction manual for communication functionRS485 (Modbus) Type:INP—TN514450—E
Current detector for heater burnout alarm (CT) 1 to 30A Type:ZOZ *CCTL—6—S—H
20 to 50A Type:ZOZ *CCTL12—S36—8F
Rear terminal cover Type:ZZPPXR1—A230
Shunt resistor 250Ω ± 0.1% Type:ZZPPXR1—A190
PC loader communication cable Type:ZZP PXH1 *TK4H4563

6
TABLE 1
[1] Unit of temperature: ˚C
Input Measurement range [˚C] Indication/setting resolution [˚C]
Input type
code Max. Min. Max. Min.
Resistance JPt100Ω 0 -150 to 600 0 to 150 1 0.1
bulb Pt100Ω 1 -200 to 850 0 to 150 1 0.1
Thermocouple J 2 0 to 1000 0 to 400 1 0.1
K 3 0 to 1200 0 to 400 1 0.1
R 4 0 to 1600 1
B 5 0 to 1800 1
S 6 0 to 1600 1
T 7 -200 to 400 -200 to 200 0.1/1
E 8 -200 to 800 0 to 800 1 0.1/1
N 12 0 to 1300 1
PL- 13 0 to 1300 1
Unusable 14
DC voltage DC0 to 5V 15
DC1 to 5V 16
DC0 to 10V 17 -1999 to 9999
(Range where scaling is allowed) 1/1000 digit
DC2 to 10V 18
DC0 to 100mV 19
DC current DC0 to 20mA 15
DC4 to 20mA 16

[2] Unit of temperature: ˚F


Input Measurement range [˚F] Indication/setting resolution [˚F]
Input type
code Max. Min. Max. Min.
Resistance bulb Pt100Ω 1 -238 to 1562 32 to 302 1 0.1
Thermocouple J 2 32 to 1832 32 to 752 1 0.1
K 3 32 to 2192 32 to 752 1 0.1
R 4 32 to 3272 1
B 5 32 to 3272 1
S 6 32 to 2912 1
T 7 -328 to 752 -328 to 392 1
E 8 -328 to 1472 32 to 1472 1
N 12 32 to 2372 1
PL- 13 32 to 2372 1
Unusable 14 * Input a DC current to 1 to 5 V
DC voltage DC0 to 5V 15 DC or 0 to 5 V DC range via
DC1 to 5V 16 external resistor of 250 Ω.
* Input type and ranges are
DC0 to 10V 17 -1999 to 9999 standardly factory set as follows.
(Range where scaling is allowed) 1/1000 digit
DC2 to 10V 18 K: 0 to 400˚C
DC0 to 100mV 19 Pt, JPt: 0 to 150˚C
Voltage, current: 0 to 100%
DC current DC0 to 20mA 15
Standard input type is
DC4 to 20mA 16 thermocouple K.

7
PXG4

OUTLINE DIAGRAM (Unit : mm)


Mounting frame
Panel
93.8 (If with terminal cover)
9 78.8
48 1

˚C
C1 C2 D01 D02 D03

PV

44.8
48
48

SV

A/M SEL

PXG-4

t
Water-proof packing Terminal cover (option)

Mounting frame Terminal section


PC loader interface
48
1-6 7-12 13-18

No.7
No.1 No.13
57

6.2

No.6 No.18
No.12
Terminal screw M3

Panel cutout size Side stick mounting (n units)


(water-proof property is lost in this case)

45+0.5
0 n units mounted

(48 × N-3) +0.5


0
45+0.5
0

73MIN.

45+0.5
0

Mass about 0.2 kg


63MIN.

8
OPTIONALLY ARRANGED ARTICLES
Heater current detector (CT)

. Specification : 1 to 30 A . Specification : 20 to 50 A
. Type : CTL-6-S-H . Type : CTL-12-S36-8F

21 30 φ2.36

15 2.8

9
7
φ5.8

25

40
10.5

2.5

φ12
10

30

15
40
φ3.5
M3,depth 4

7.5
30

40

Note 1) Detection is available only for single phase heater.


Note 2) Unusable for heater control by thyristor phase angle control.

9
PXG4

EXTERNAL CONNECTION DIAGRAM


Standard type

OPTION 1 RS485,DI1,DI2,RSV1,CT1

DO Digital output DI1+DI2+RSV1 RS485+DI+RSV1 RS485+RSV1/RS485+CT1/RS485+DI

DO1- DO- DI1


COM
1 COM
1 7 7 7 7 7
RS485 RS485 RS485 RS485
DO1 2 DO1 2 DI-COM 8 8 8 8 8
DO2- DI2 DI1
COM
3 DO2 3 9 9 9 9 DI1 9
DI- RSV1 CT1
DO2 4 DO3 4 10 COM 10 10 10 COM 10

11 11
RSV1 RSV1
12 12

DI1+DI2/DI1+RSV1/DI1+CT1

DI1 7 DI1 7 DI1 7


COM 8 COM 8 COM 8
OUT 1 Output 1
DI2 9 9 9
RSV1 CT1
1 7 13 10 10 10
13 13
2 8 14
14 14
3 9 15

4 10 16 Contact output Voltage output

5 11 17 PV Process value input

6 12 18 (Note 1)
13 13 15 15 15 15 15
14 14 16 16 16 16 16

17 17 17 17 17
SSR Drive output Current output
18 18 18 18 18

T.C. R.T.D. DC Voltage DC Voltage DC Current


(V) (mV) (mA)

PS Power supply OUT 2 Output 2

11 11 11 11 11 11
5 5
12 12 12 12 12 12
6 6

100-240VAC 24VAC/24VDC Contact output SSR Drive output Current output Voltage output Re-Trans Re-Trans
50/60Hz 50/60Hz (Current) (Voltage)

Note 1 : Connect the furnished resistor to 15 and 18

10
Motorized valve control type

DO Digital output OPTION1 RS485,DI1,DI2,DI3,RSV1

DO1- DO-
COM
1 COM
1

DO1 2 DO1 2 RS485,DI1,RSV1

DO2-
COM
3 DO2 3

DO2 4 4 7 7
RS485 RS485
8 8
DI1 9 9
RSV1
DI-COM 10 10

DI1,DI2,DI3,RSV1

DI1 7 DI1 7
DI-COM 8 DI-COM 8
DI2 9 9
RSV1
DI3 10 10
1 7 13

2 8 14

3 9 15

4 10 16

5 11 17
PO Open signal
6 12 18

Open
13
OUT
14
COM

PV Process value input


PS Power supply
PO Close signal (Note 1)
15 15 15 15 15
Close 16 16 16 16 16
5 5 11
OUT
6 6 12 17 17 17 17 17
COM
18 18 18 18 18
100-240VAC 24VAC/24VDC
50/60Hz 50/60Hz T.C. R.T.D. DC Voltage DC Voltage DC Current
(V) (mV) (mA)

Note 1 : Connect the furnished resistor to 15 and 18

11
PXG4

ISOLATED BLOCK DIAGRAM

Power supply Internal Circuit

Process value input

Control output 1 (relay contact)


or
OPEN output Auxiliary analog input (remote SV input)

Heater current detector input

Control output 1 (SSR drive, current, voltage)


Control output 2 (relay contact)
or
CLOSE output

Control output 2
(SSR drive, current, voltage)
or
auxiliary analog output
(re-transmission output)
Digital output 1
(relay contact)

Digital output 1 to 3
Digital input
(relay contact)

Digital output 2
(relay contact) Communication (RS485)

When the 9th digit of the When the 9th digit of the
code symbols = J code symbols = Other than J
(DO1, 2 independent common) (DO1 to 3 shared common)

: Basic insulation (1500 V AC)

: Functional insulation (500 V AC)

: Non-insulation