PDHK 0 A 2021
PDHK 0 A 2021
type TUH/TCHE/TRHE
REFRIGERATION AND
AIR CONDITIONING Technical leaflet
Technical leaflet Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE
Contents Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Standard range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Replacement capacity and mass flow
R134a . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
R22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
R404A/R507 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
R407C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
R410A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Design/Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions and weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
For all types, the bulb only serves as a reservoir temperature variation during operation is limited
for the charge. However, it is recommended (see application drawings).
that the bulb be mounted in a location where
Identification - TUH & TCHE Main valve data is given on the element (fig. 1)
and on the valve body (fig. 2).
Ordering
Supplied with bulb strap Standard range R134a, R22, R404A/R507, R407C, R410A
Nominal replacement Connection
Orifice capacity 1) Pressure Inlet × Outlet
Refrigerant Type
no. equalisation
kW TR in. 2) Code no. mm 3) Code no.
TUH TUH 9 1.8 0.5 int. 3
/8 × /21
068U2953 10 × 12 068U2950
TCHE 3 2.6 0.8 ext. 3
/8 × 1/2 068U4540 10 × 12 068U4530
TCHE 4 3.4 1 ext. 3/8 × 1/2 068U4537 10 × 12 068U4534
R134a TRHE10 10 2.9 0.8 ext. 5
/8 × 5/8 067L1500 16 × 16 ---
TRHE20 20 6.5 1.9 ext. 5
/8 × 5/8 067L1600 16 × 16 ---
TRHE40 40 11.3 3.2 ext. 7/8 × 7/8 067L3500 22 × 22 ---
TRHE80 70 20.8 5.9 ext. 11/8 × 11/8 067L3600 28 × 28 ---
TUH 9 4.5 1.3 int. 3
/8 × 1/2 068U2954 10 × 12 068U2951
TCHE 3 5.9 1.7 ext. 3/8 × 1/2 068U4541 10 × 12 068U4531
TCHE
TCHE 4 7.6 2.2 ext. 3
/8 × 1/2 068U4538 10 × 12 068U4535
R404A/R507 TRHE10 10 5.1 1.5 ext. 5
/8 × 5/8 067L1501 16 × 16 ---
TRHE20 20 11.3 3.2 ext. 5/8 × 5/8 067L1601 16 × 16 ---
TRHE40 40 20.0 5.7 ext. 7
/8 × 7/8 067L3501 22 × 22 ---
TRHE80 70 41.3 11.8 ext. 11/8 × 11/8 067L3601 28 × 28 ---
TUH 9 2.8 0.8 int. 3/8 × 1/2 068U2955 10 × 12 068U2952
TCHE 3 4.1 1.2 ext. 3
/8 × 1/2 068U4542 10 × 12 068U4532
TCHE 4 5.3 1.5 ext. 3
/8 × 1/2 068U4539 10 × 12 068U4536
TRHE R407C TRHE10 10 4.1 1.2 ext. 5
/8 × 5/8 067L1502 16 × 16 ---
TRHE20 20 9.1 2.6 ext. 5/8 × 5/8 067L1602 16 × 16 ---
TRHE40 40 16.6 4.7 ext. 7
/8 × 7/8 067L3502 22 × 22 ---
TRHE80 70 28.8 8.2 ext. 11/8 × 11/8 067L3602 28 × 28 ---
TUH 9 3.0 0.9 int. 3/8 × 1/2 068U2959 10 × 12 068U2957
TCHE 3 4.1 1.2 ext. 3/8 × 1/2 068U4546 10 × 12 068U4544
TCHE 4 5.3 1.5 ext. 3
/8 × 1/2 068U4547 10 × 12 068U4545
R22 TRHE10 10 5.4 1.6 ext. 5/8 × 5/8 067L1503 16 × 16 ---
TRHE20 20 11.9 3.4 ext. 5
/8 × 5/8 067L1603 16 × 16 ---
TRHE40 40 20.8 5.9 ext. 7/8 × 7/8 067L3503 22 × 22 ---
TRHE80 70 37.5 10.7 ext. 11/8 × 11/8 067L3603 28 × 28 ---
TUH 9 7.3 2.1 int. 3
/8 × 1/2 068U2960 10 × 12 068U2958
TCHE 3 10.0 2.9 ext. 3
/8 × 1/2 068U4548 10 × 12 068U4528
TCHE 4 12.9 3.7 ext. 3/8 × 1/2 068U4549 10 × 12 068U4529
R410A TRHE10 10 10.3 3.0 ext. 5/8 × 5/8 067L1504 16 × 16 ---
TRHE20 20 22.6 6.4 ext. 5
/8 × 5/8 067L1604 16 × 16 ---
TRHE40 40 34.9 10.0 ext. 7/8 × 7/8 067L3504 22 × 22 ---
TRHE80 70 70.3 20.1 ext. 11/8 × 11/8 067L3604 28 × 28 ---
1) The nominal replacement capacity is the regulator capacity at
evaporating temperature te = –2°C / 28°F,
condensing temperature tc = +40°C / 104°F,
reduction of suction temperature / suction pressure ∆ts = 4 K / 7°F.
2) Valves with inch connections have 1/4 in. pressure-equalisation.
3) Valves with mm connections have 6 mm pressure-equalisation.
Sizing
R134a
1 TCHE 3
TCHE 4
0 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Example
Refrigerant R134 The corrected replacement capacity thus
Compressor capacity 6 kW at +2/+50°C becomes 3 kW divided by 1.2 = 2.5 kW.
Min. load 50% 3 kW
Replacement capacity 6 – 3 = 3 kW The TCHE 4 gives 2.7 kW at –1.0/+40°C ( )
Min. evaporating temperature te = –1.0°C and gives 2.5 kW at –0.8/+40°C ( )
Condensing temperature tc = +50°C
Correction factor (table) 1.2 Thus the TCHE 4 would be a suitable choice.
Replacement capacity
R134a
TUH & TCHE
6 Conditions used in calculation:
tc = +40°C
Start opening: te = +2°C
5
1 TCHE 3
TCHE 4
0 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
TRHE
35 Conditions used in calculation:
tc = +40°C
30 Start opening: te = +2°C
Replacement capacity [kW]
25
20
15
10
TRHE 10
5 TRHE 20
TRHE 40
0 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
0.020
Mass flow [kg/s]
0.015
0.010
0.005 TCHE 3
TCHE 4
0.000 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
TRHE
0.18 Conditions used in calculation:
tc = +40°C
0.16
Start opening: te = + 2°C
0.14
0.12
Mass flow [kg/s]
0.10
0.08
0.06
0.04 TRHE 10
TRHE 20
0.02 TRHE 40
0.00 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
Replacement capacity
R22
TUH & TCHE
8
Conditions used in calculation:
tc = +40°C
7
Start opening: te = +2°C
6
1 TCHE 3
TCHE 4
0 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
TRHE
70 Conditions used in calculation:
tc = +40°C
60 Start opening: te = +2°C
Replacement capacity [kW]
50
40
30
20
TRHE 10
10 TRHE 20
TRHE 40
0 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
0.02
0.01
TCHE 3
TCHE 4
0.00 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
TRHE
0.30 Conditions used in calculation:
tc = +40°C
Start opening: te = + 2°C
0.25
0.20
Mass flow [kg/s]
0.15
0.10
TRHE 10
0.05 TRHE 20
TRHE 40
TRHE 80
0.00
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
2
TCHE 3
TCHE 4
0 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
TRHE
70 Conditions used in calculation:
tc = +40°C
60 Start opening: te = +2°C
Replacement capacity [kW]
50
40
30
20
TRHE 10
10 TRHE 20
TRHE 40
0 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
0.06
0.05
Mass flow [kg/s]
0.04
0.03
0.02
0.01 TCHE 3
TCHE 4
0.00 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
TRHE
0.4 5 Conditions used in calculation:
tc = +40°C
0.4 0
Start opening: te = + 2°C
0.3 5
0.3 0
Mass flow [kg/s]
0.2 5
0.2 0
0.1 5
TRHE 10
0.1 0 TRHE 20
0.0 5 TRHE 40
TRHE 80
0.0 0
-6 -5 -4 -3 -2 -1 0 1 2 3
Replacement capacity
R407C
TUH & TCHE
8
Conditions used in calculation:
tc = +40°C
7 Start opening: te = +2°C
6
1 TCHE 3
TCHE 4
0 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
TRHE
50 Conditions used in calculation:
45 tc = +40°C
Start opening: te = +2°C
40
Replacement capacity [kW]
35
30
25
20
15
TRHE 10
10
TRHE 20
5 TRHE 40
0 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
0.03
0.02
0.01
TCHE 3
TCHE 4
0.00 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
TRHE
0.30
Conditions used in calculation:
tc = +40°C
0.25 Start opening: te = + 2°C
0.20
Mass flow [kg/s]
0.15
0.10
TRHE 10
0.05 TRHE 20
TRHE 40
0.00 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Replacement capacity
R410A
TUH & TCHE
20 Conditions used in calculation:
18 tc = +40°C
Start opening: te = +2°C
16
TRHE
120 Conditions used in calculation:
tc = +40°C
100 Start opening: te = +2°C
Replacement capacity [kW]
80
60
40
TRHE 10
20 TRHE 20
TRHE 40
0 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
0.06
0.05
0.04
0.03
0.02
TCHE 3
0.01
TCHE 4
0.00 TUH 9
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
TRHE
0.60
Conditions used in calculation:
tc = +40°C
0.50 Start opening: te = + 2°C
0.40
Mass flow [kg/s]
0.30
0.20
TRHE 10
0.10 TRHE 20
TRHE 40
0.00 TRHE 80
-6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [°C]
Design/Function
TCHE
Application
Note:
The bulb serves only as a
reservoir for the charge,
however, it is recommended
to mount it in a position where
the temperature variation
during running conditions is
limited (see a and b in the
application drawings).
1. Evaporator
2. Condenser
3. Receiver
4. Solenoid valve
5. Discharge bypass valve with
adjustable setting System with capillary tube expansion and internal pressure-equalised hot gas bypass valve, type TUH
6. Compressor
System with capillary tube expansion and external pressure-equalised hot gas bypass valve TCHE or TRHE
System with thermostatic expansion valve and external pressure-equalised hot gas bypass valve TCHE or TRHE