0% found this document useful (0 votes)
27 views

Installation Manual For Slim Medium Static Pressure Duct Unit

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views

Installation Manual For Slim Medium Static Pressure Duct Unit

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

INSTALLATION MANUAL

Medium Static Pressure Duct Type

Thank you very much for purchasing our air conditioner,


Before using your air conditioner , please read this manual carefully and keep it for future reference.
When installing the unit in a small room, take measures to
keep refrigerant concentration from exceeding allowable
safety limits in the event of refrigerant leakage. Contact the
place of purchase for more information. Excessive refrigerant in
a closed ambient can lead to oxygen deficiency.

Use the attached accessories parts and specified parts for


installation.
Otherwise, it will cause the set to fall, water leakage, electric
shocks, fire.

Install at a strong and firm location which is able to


withstand the set's weight.
If the strength is not enough or installation is not properly done,
the set will drop to cause injury.

The appliance must be installed 2.5m above floor.

The appliance shall not be installed in the laundry.

Before obtaining access to terminals, all supply circuits


must be disconnected.

The appliance must be positioned so that the plug is


accessible.

1. PRECAUTIONS The enclosure of the appliance shall be marked by word, or


by symbols, with the direction of the fluid flow.

For electrical work, follow the local national wiring


Precautions before reading the Installation manual. standard, regulation and this installation instructions. An
independent circuit and single outlet must be used.
This Installation manual is for the indoor unit. If electrical circuit capacity is not enough or defective in
electrical work, it will cause electrical shock fire.
Refer to the indoor unit Installation manual for indoor parts
installation.
Use the specified cable and connect tightly and clamp the
cable so that no external force will be acted on the
Please read the power source unit Installation manual to install
terminal.
the power source unit.
If connection or fixing is not perfect, it will cause heat-up or fire
Please refer to the refrigerant distributor Installation manual to at the connection.
install the refrigerant distributor.
Wiring routing must be properly arranged so that control
board cover is fixed properly.
The safety precautions listed here are divided into two categories. In If control board cover is not fixed perfectly, it will cause heat-up
either case, important safety information is listed which must be read at connection point of terminal, fire or electric shocks.
carefully.
If the supply cord is damaged, it must be replaced by the
manufacturer or its service agent or similarly qualified
WARNING person in order to avoid a hazard.
Failure to observe a warning may result in death.
An all-poles disconnection switch having a contact
CAUTION separation of at least 3mm in all poles should be
connected in fixed wiring.
Failure to observe a caution may result in injury or damage
to the equipment.
When carrying out piping connection, take care not to let
air substances go into refrigeration cycle.
After completing the installation, make sure that the unit operates Otherwise, it will cause lower capacity, abnormal high pressure
properly during the start-up operation. Please instruct the customer in the refrigeration cycle, explosion and injury.
on how to operate the unit and keep it maintained. Also, inform
customers that they should store this Installation manual along with Do not modify the length of the power supply cord or use
the owner's manual for future reference. extension cord, and do not share the single outlet with
other electrical appliances.
Otherwise, it will cause fire or electri shocks.

WARNING Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Be sure only trained and qualified service personnel to Improper installation work may result in the equipment falling
install, repair or service the equipment. and causing accidents.
Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to the If the refrigerant leaks during installation, ventilate the area
equipment. immediately.
Toxic gas may be produced if the refrigerant comes into the
Install according to this installation instructions strictly. place contacting with fire.
If installation is defective, it will cause water leakage, electrical
shock fire. The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper tube.

Installation manual

1
After completing the installation work, check that the
refrigerant does not leak. 2. INSTALLATION INFORMATION
Toxic gas may be produced if the refrigerant leaks into the room
and comes into contact with a source of fire, such as a fan
heater, stove or cooker.
To install properly, please read this "installation manual" at
first.
The appliance shall be installed in accordance with
national wiring regulations.
The air conditioner must be installed by qualified persons.
An all-pole disconnection device which has at least 3mm
When installing the indoor unit or its tubing, please follow
separation distance in all pole and a residual current
this manual as strictly as possible.
device(RCD)with the rating of above 10mA shall be
incorporated in the fixed wiring according to the national
If the air conditioner is installed on a metal part of the
rule.
building, it must be electrically insulated according to the
relevant standards to electrical appliances.
The power cord type designation is H05RN-R/H07RN-F or
above.
When all the installation work is finished, please turn on
the power only after a thorough check.

CAUTION Regret for no further announcement if there is any change


of this manual caused by product improvement.

Ground the air conditioner.


Do not connect the ground wire to gas or water pipes,
lightning rod or a telephone ground wire.Incomplete INSTALLATION ORDER
grounding may result in electric shocks.
Select the location;
Be sure to install an earth leakage breaker.
Install the indoor unit;
Failure to install an earth leakage breaker may result in
electric shocks.
Install the outdoor unit;
Connect the outdoor unit wires , then connect the indoor
Install the connecting pipe ;
unit wires.
You are not allowed to connect the air conditioner with the
Connect the drain pipe;
power source until wiring and piping the air conditioner is
done.
Wiring;
While following the instructions in this installation
Test operation.
manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent
condensation.
Improper drain piping may result in water leakage and
property damage.

Install the indoor and outdoor units, power supply wiring


and connecting wires at least 1 meter away from
televisions or radios in order to prevent image
interference or noise.
Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise.

The appliance is not intended for use by young children


or infirm persons without supervision.

Don't install the air conditioner in the following locations:

There is petrolatum existing.

There is salty air surrounding (near the coast).

There is caustic gas (the sulfide, for example) existing in


the air (near a hot spring).

The Volt vibrates violently (in the factories).

In buses or cabinets.

In kitchen where it is full of oil gas.

There is strong electromagnetic wave existing.

There are inflammable materials or gas.

There is acid or alkaline liquid evaporating.

Avoid installing it in a narrow sapce which has a high


requirement to noise.

Other special conditions.

Installation manual

2
3. ACCESSORIES 5. INDOOR UNIT INSTALLATION
Table.3-1 Confirm that there is enough room for installation and mainte-
nance.
Name of
Q‘ty Outline Usage
Accessories

500mm or more
Installation manual 1 (This manual) Maintenance roomage
Control the
Remote controller 1 air-conditioner

600mm or more
Pipe insulation material 2 Heat insulation
Maintenance roomage
Water outlet joint 1 For drainage
Chucking the joint which
600mmX600mm
connect the drain hose checking orifice
Clasp 1
and the outlet of indoor Fig.5-1
unit
Use for pipe
Copper nut 1 connection of
engineering installation

Display box 1 Operation and fault display

Confirm the minimum


drain tilt is 1/100 or more
checking orifice
Fig.5-2

Cautions on remote controller installation

● Never throw or beat the controller.


5.1 Installation Φ10 Hanging Screw Bolts (4 Bolts)
● Before installation, operate the remote controller to determine
its location in a reception range.
Please refer to the following figure for the distance
Keep the remote controller at least 1m apart from the nearest measurement between the screw bolts.

TV set or stereo equipment. (It is necessary to prevent image
disturbances or noise interferences.) Please install with Φ10 hanging screw bolts.

Do not install the remote controller in a place exposed to direct The handling to the ceiling varies from the constructions, consult

sunlight or close to a heatingsource, such as a stove. Note that the construction personnels for the specific procedures.
the positive and negative poles are in right positions when
loading batteries. ● The size of the ceiling to be handled ... ... do keep the ceiling
flat. Consolidate the roof beam for possible vibration.

● Cut off the roof beam.


4. INSPECTING AND HANDLING THE UNIT
● Strengthen the place cut off, and consolidate the roof beam.
At delivery, the package should be checked and any damage should
be reported immediately to the service agent. Carry out the pipe and line operation in the ceiling after
finishing the installation of the main body. While choosing where
When handling the unit, take into account the following: to start the operation, determine the direction of the pipes to be
drawn out. Especially in case there is a ceiling, position the
1 Fragile, handle the unit with care. refrigerant pipes, drain pipes, indoor & outdoor lines to the
connection places before hanging up the machine.
2 Choose on before hand the path along which the unit is to be
brought in. The installation of hanging screw bolts.

3 Move this unit as original package as possible.


5.2 Wooden construction
4 When lifting the unit , always use protectors to prevent belt
Put the square timber tra versely ove r the ro of beam, th en
damage and pay attention to the position of the unit’s centre
install the hanging screw bolts. (Refer to Fig.5-3)
of gravity.

Timber over the beam

Ro of beam
Ce iling

Ha nging screw bolts

Fig.5-3

Installation manual

3
5.3 New concrete bricks Canvas tie-in Canvas tie-in
Inlaying or embedding the screw bolts (refer to Fig.5-4)

Isolation booth

Blade shape insertion Slide insertion


Air outlet Air inlet
Fig.5-4 Isolation booth Air dust filter
checking orifice
5.4 For original concrete bricks
Use embedding screw bolt, crock and stick harmless (refer Fig.5-8
to Fig.5-5)

Steel bar NOTE


Embedding screw bolt
1. Do not put the connecting duct weight on the indoor unit.
(Pipe hanging and embedding screw bolt) 2. When connecting duct, use inflammable canvas tie-in to prevent
Fig.5-5 vibrating.
3. When connecting duct, install in place prone to takedown for
maintenance.
5.5 Steel roof beam structure 4. Change the fan motor static pressure corresponding to external
Install and use directly the supporting angle steel. (refer to duct static pressure.
Fig.5-6) 5. If installed in place like meeting room where noise is easy to be
perceived, design isolation booth and internal duct underlayer to
Hanging screw bolt muffle the duct system and weaken the air encounter noise in the
duct.

Supporting
Hanging bolts angle steel

Fig.5-6

5.6 Overhanging the indoor unit


(1) Overhang the indoor unit onto the hanging screw bolts with
block.
(2) Position the indoor unit in a flat level by using the level
indicator, unless it may cause leakage.

Screw nut
Shockproof cushion

Washer Overhang part


Hanging
screw bolt

Fig.5-7

5.7 Installing the dust proof net and canvas air


passage
(1) Install the dust proof net according to the installation manual;
(2) Install the canvas air passage underneath the dust proof net.

5.8 Duct Design


(1) Air inlet and air outlet duct should be apart far enough to
prevent air outlet entering air Inlet.
(2) There is dust filter on the indoor unit.

Recommended duct connection

Installation manual

4
■ The positioning of ceiling hole and indoor unit and hanging screw bolts

routine method of installation: the size of installation for indoor unit following the Fig.5-9

Outline dimension and air outlet opening size Unit: mm


H

92
Φ
G

B
New air inlet

F E C 20
A D

Air return opening size


A

J
B

Air filter
I

Position size of descensional ventilation opening

Air filter
L

Electric control cabinet

Size of mounted lug


M
N

Fig.5-9
Electric control cabinet

Mode(W) A B C D E F G H I J K L M N

1500~3600 700 210 450 500 512 45 145 17 600 196 600 196 740 350

4500~5600 920 210 450 500 732 45 145 17 820 200 820 200 960 350

7100 1140 210 450 500 950 45 145 17 1040 200 1040 200 1180 350

Table.5-1 Unit: mm

Model(W) 1500~4500 5600~7100 Refrigerant

A(Liquid side) Φ6.4 Φ9.5


Size of copper pipe R410A
B(Gas side) Φ12.7 Φ15.9

Installation manual

5
■ How to adjust the air ventilated direction? (From rear ventilated adjust it to descensional.)
1. Take off air filter,ventilation panel and air return flange. 2. Install ventilation panel,air return flange and air filter.

Air return flange Ventilation panel

Ventilation panel
Air filter

Air filter
Air return flange

Fig.5-10

NOTE

All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased
(depend on model).The actual shape shall prevail.

5.9 Fan performances


Static pressure curve
External static pressure (Pa)

Supper High speed(reserved)


External static pressure (Pa)

Supper High speed(reserved)


High speed
High speed
Medium speed
Medium speed
Low speed
Low speed

2.2KW~2.8KW Fig.5-11 4.5KW~5.6KW Fig.5-13


External static pressure (Pa)
External static pressure (Pa)

Supper High speed(reserved)


Supper High speed(reserved)

High speed
High speed

Medium speed Medium speed

Low speed Low speed

3.6KW Fig.5-12 7.1KW Fig.5-14

Installation manual

6
6. INSTALL THE CONNECTING PIPE Use frozen oil

Check whether the height drop between the indoor unit and
outdoor unit, the length of refrigerant pipe, and the number of the
bends meet the following requirements: Fig.6-1

● The max height drop and The length of refrigerant pipe deponding
on the ouotdoor unit.(If the height drop is more than 10m, you
had better put the outdoor unit over above the indoor unit.) Bend the pipe with thumb

● The number bends fewer than 15


Fig.6-2
● Do not let air, dust, or other impurities fall in the pipe system
during the time of installation.

● The connecting pipe should not be installed until the indoor and
Make the ends
outdoor units have been fixed already. straight
● Keep the connecting pipe dry, and do not let moisture in during Fig.6-3
installation.

The Procedure of Connecting Pipes


Locate The Pipe
Measure the necessary length of the connecting pipe, and make
it by the following way.
● Drill a hole in the wall (suitable just for the size of the wall conduit,
● 90mm in general), then set on the fittings such as the wall conduit
Connect the indoor unit at first, then the outdoor unit.
and its cover.
① Bend the tubing in proper way. Dont harm them.
● Bind the connecting pipe and the cables together tightly with
binding tapes. Do not let air in, which will cause water leakage
② Daub the surfaces of the flare pipe and the joint nuts with frozen
by condensation.
oil, and wrench it for 3~4rounds with hands before fasten the
flare nuts. (Refer to Fig.6-1)
● Pass the bound connecting pipe through the wall conduit from
outside. Be careful of the pipe all ocation to do no damage to the
③ Be sure to use two wrenches simultaneously when you connect
tubing.
or disconnect the pipes.
Connect the pipes.
● The stop valve of the outdoor unit should be closed absolutely
(as original state). Every time you connect it, first loosen the nuts
at the part of stop valve, then connect the flare pipe immediately Then, open the stem of stop valves of the outdoor unit to make the re-
(in 5 minutes). If the nuts have been loosened for a long time, frigerant pipe connecting the indoor unit with the outdoor unit
dusts and other impurities may enter the pipe system and may fluently flow.
cause malfunction later. So please expel the air out of the pipe
with refrigerant before connection. Be sure of no leakage by checking it with leak detector or soap
water.
● Expel the air (refer to the “Expel The Air”) after connecting the
refrigerant pipe with the indoor unit and the outdoor unit.Then Cover the joint of the connecting pipe to the indoor unit with the
fasten the nuts at the repair-points. sound proof/insulating sheath (fittings), and bind it well with the
tapes to prevent leakage.
Notices For Benable pipe.

● The bending angle should not exceed 90°C


7. REFRIGERANT PIPE CONNECTION
● Bending position is preferably in the bendable pipe. The larger
the better it is .
7.1 Expel The Air
● Do not bend the pipe more than three times.
Flaring
Bend the connecting pipe of small wall thickness.
● Cut a pipe with a pipe cutter.
● Cut out a desired concave at the bending part of the insulating
pipe. ● Insert a flare nut into a pipe and flare the pipe.

● Then expose the pipe(cover it with tapes after bending).


Lean crude burr
To prevent collapsing of deforming, please bend the pipe at its 90

biggest radius.

● Use bender to get a small radius pipes. Fig.7-1

Use the market brass pipe.


Be sure to use the same insulating materials when you buy the
brass pipe. (More than 9mm thick).

Installation manual

7
90 °± 4 ● Turn on the vacuum pump. At the beginning of pumping, loosen
45 °
±2 the maintenance terminator nut of stop valve B a little to check
A whether the air comes in (the sound of the pump changes, and
the indicator of compound meter turns below zero). Then fasten
R0.4~0.8 the nut.
Fig.7-2
● When the pumping has finished, close the Lo-lever of the
manifold valve completely and turn off the vacuum pump.
Table.7-1 ● When you have pumped for over 15 minutes, please confirm
A(mm) that the indicator of multimeter is on -1.0X105Pa (-76cmHg)
Outside diameter
Max Min ● Loosen and remove the quadrangle cover of stop valves A
and B to open stop valve A and B completely, then fasten
Φ6.4mm 8.7 8.3
them.
Φ9.5mm 12.4 12.0
● Disassemble the charge hose from the repair-mouth of stop
Φ12.7mm 15.8 15.4 valve A, and fasten the nut.
Φ15.9mm 19.0 18.6
Manifold valve

Multi-meter Pressure meter

Fasten the nut


-76 cmHg

Put the connecting tubing at the proper position, wrench the Lo-lever Hi-lever
nuts with hands then fasten it with a wrench. (Refer to Charge hose
Charge hose
Fig.7-3)
Vacuum pump

Too large torque will harm the bellmouthing and too small will
cause leakage. Please determine the torque according to
● Table.7-2.

Lo-lever
Fig.7-4


All the stop valves should be opened before test operation.
Fig.7-3 Each air conditioner has two stop valves of different sizes on
the side of the outdoor unit which operate as Lo-stop value,
respectively. (Refer to Fig.7-5)
Table.7-2

Tubing size Torque Flare nut

Φ6.4mm 14.2~17.2 N.m (144~176 kgf.cm)


Stopper
Φ9.5mm 32.7~39.9 N.m (333~407 kgf.cm)
Cap
Φ12.7mm 49.5~60.3 N.m (504~616 kgf.cm)
Φ15.9mm 61.8~75.4 N.m (630~770 kgf.cm)
Valve body

Valve stem
Fig.7-5
The necessary filling amount of refrigerant
7.2 Check The Leakage
● Refrigerant volume to be added is calculated according to
outdoor unit installation manual .Be sure to add refrigerant Check all the joints with the leak detector or soap water. (See
measuring by a scale. L: The length of the pipe Fig.7-6 as a reference illustration)

● Please record the quantity added and store it carefully for future
Check-point of indoor unit D C
maintenance.

Expel the air with a vacuum pump (Refer to Fig.7-4) (Please


refer to its manual for the way of using manifold valve)

● Loosen and remove the maintenance nuts of stop valves A


and B, and connect the charge hose of the manifold valve with
B A
the maintenance terminator of stop valve A. (Be sure that stop Check-point of outdoor unit
valves A and B are both closed)

● Connect the joint of the charge hose with the vacuum pump.

● Open the Lo-lever of the manifold valve completely.


A......Lo-stop valve B......Hi-stop valve
C,D..Joints of the connecting pipe to the indoor unit.

Fig.7-6

Installation manual

8
7.3 Insulation The drain pipe installation for the unit without pump.

Be sure to with insulating materials cover all the exposed parts


of the flare pipe joints and refrigerant pipe on the liquid-side and 0.8-1.0m
the gas-side. Ensure that there is no gap between them.

Incomplete insulation may cause water condensation.


Lean over 1/100

Fig.8-3
8. CONNECT THE DRAIN PIPE
Drainage test
Check whether the drainpipe is unhindered.
Install the drainpipe of the indoor unit
New built house should have this test done before paving
Please use the accessory drain hose to connect the outlet of the ceiling.
indoor unit with the PVC water pipe, and then use the
accessory clasp for chucking(Refer to Fig.8-1).
The unit with pump.
Connections of other water pipes please use rigid PVC binder,
and confirm there whether have leakage or not. 1 Remove the test cover (Rotate the test cover to opening up),
and stow water of about 2000ml to the water receiver through
the stow tube.

Indoor unit Clasp Water outlet joint PVC water pipe(Φ25)

Outlet Rigid PVC binder


Fig.8-1

To prevent water from flowing backwards into the air


conditioner while the air conditioner stops, please lean the
drainpipe down toward outdoor (outlet-side) at a degree of over
1/ 100. And please avoid any bulge or water deposit.
Do not drag the drainpipe violently when connecting to prevent
the body from being pulled. Meanwhile, one support point
should be set every 0.8~1.0m to prevent the drainpipe from
yielding. Or you can tie the drainpipe with the connecting pipe
to fix it. CLOSED OPEN
CLOSE D
OPE

In the case of prolonged drainpipe, you had better tighten its


N

indoor part with a protection tube to prevent it from loosing.


In case the drainpipe outlet is higher than pumping connective
pipe of the main body, the drainpipe must be arranged upwards
vertically by using connective assembly of the water outlet for Test cap Fig.8-4
vertical bending, and the height of the drainpipe shall set to the
defrosting pan surface no more than 600mm, otherwise, too
much backflow while shutdown would leads to overflow (Refer
to Fig.8-2).(Only available for the unit with pump.)
The end of the drainpipe should be over 50mm higher than the
ground or the bottom of the drainage chute, and do not
immerse it in water. If you discharge the water directly into
sewage, be sure to make a U-form aquaseal by bending the
drainpipe.

The drain pipe installation for the unit with pump.

0.8-1.0m Lean over 1/100


<200mm
Max. 600mm

Stow tube

Fig.8-2 Fig.8-5

Installation manual

9
2 Turn on the power, and operate the air conditioner under the Pump maintaince:
"COOLING" mode. Listen to the sound of the drain pump.
Check whether the water is discharger well (a lag of 1min is 1. Screw off four screws from drain pump.
allowed before discharging, according to the length of the drain 2. Plug off pump power supply and water level switch cable.
pipe), and check whether water leaks from the joints.
3. Take off pump.
3 Stop the air conditioner, turn off the power, and reset the test
cover to its original position.

The unit without pump.

Pump

Fig.9-2

Fig.8-6 10. WIRING


Remove the test cover, and stow water of about 2000ml to the Attaching wiring
water receiver through the stow tube,check whether the
drainpipe is unhindered. ● The air conditioner should use separate power supply with
rated voltage.

● The external power supply to the air conditioner should have


ground wiring, which is linked to the ground wiring of the indoor
and outdoor unit.
9. MOTOR AND DRAIN PUMP MAINTENANCE ● The wiring work should be done by qualified persons according
(Take rear ventilated as example) to circuit drawing.

● A leakage protector should be installed according to the National


Motor maintaince: Standard concerning electrical appliance.
1. Remove off the ventilated panel.
● Be sure to locate the power wiring and the signal wring well to
2. Remove off a half of motor housing. avoid cross-disturbance and their contact with connecting pipe
3. Take off the motor. or stop value body.

● Generally, do not twist two wiring together unless the joint is


soldered well and covered with insulator tape.

● Do not turn on the power until you have checked carefully after
wiring.

Motor

Blower housing

Ventilated panel

Fig.9-1

Installation manual

10
The Specification of Power
NOTE
Table.10-1 The air-conditioners can connect with Central Control Monitor
(CCM). Before operation, please wiring correctly and set
Model(kW) 1.5 ~7.1 system address and network address of indoor units.
Phase 1-Phase
Power
Frequency and volt 208/230V-1ph-60Hz

Power Capacity 16A


switch
Safety fuse 16A L N
Indoor unit power wiring (mm2) 3×2.5

Indoor/outdoor connectingwiring
3-core shielded wire 3×0.75
(mm2) (Electric signal)
To indoor power
Fig.10-2

CAUTION
Please use 3-core shielded wire,and connect the shielded layer to .
A disconnection device having an air gap contact separation in
all active conductors should be incorporated in the fixed wiring
according to the National Wiring Regulation.

X Y E P Q
Wiring chart

Power

SWICH
To Central Control Indoor/outdoor
FUSE Monitor (CCM) connection wire

L N
Fig.10-3
OUTDOOR UNIT

INDOOR UNIT INDOOR UNIT INDOOR UNIT


L N L N L N

SWICH FUSE
11. CONTROL OPERATION
Power

JUNCTION BOX
Design specialized power for the indoor unit and outdoor unit respectively 11.1 Horsepower set
Horsepower code
Central controller
OUTDOOR UNIT monitor(CCM)
P Q E XY E XYE
PO WER_S
F0 1
E
23
B CD

Vacant
4 56

789 A
Use shielded cable
and well earthing
ENC1
INDOOR UNIT INDOOR UNIT INDOOR UNIT
X Y E PQ X Y EP Q XYEPQ

Base on different purposes to setting the switch cords on PC panel


of indoor electrical control box. Once finish the setting, please cut
Matching resistor off the main power, and then input power again, otherwise, setting
Wire Remote (the last unit only)
controller controller function could not work.
The remote controller and CCM are selected accessories
please purchase from the local distributor when necessary.

Fig.10-1

CAUTION

The reserved function is indicated in broken line table,users can


select it when necessary.

Terminal board diagram


Please refer to the indoor unit wiring diagram for the wiring.

Installation manual

11
Table.11-1
CAUTION
ENC1 Toggle switch For set horsepower

Code Capacity(Horsepower) The system together have 64units(0-63),everyone has only


system addresscode,If two addresses are the same in one
F 1500W(0.6HP) system , the abnormal operation will occur.
Note: The horsepower
0 2200W(0.8HP)
has been set before Please switch off the power before setting,otherwise the
leaving the factory , 1 2800W(1.0HP) unexpected error will occur.
anyone can’t
2 3600W(1.2HP)
modify it except the
maintenance person. 3 4500W(1.7HP)
11.2 Network address set
4 5600W(2.0HP)
5 7100W(2.5HP) 1) Network address is set by communication of indoor and
outdoor unit; the address is the same as indoor address, there
is no need to set separately.
2) The central control of indoor units can be done on outdoor
unit, there is no need to control indoor unit separately, for
details please refer to V4+ outdoor unit manual.
3) For previous control of indoor units, the network can be set
by connecting (X,Y,E) terminals, there is no need to set
network address. The network can also be set by outer
network module and main board (CN20).

11.2 Main board Code designation

SW1 definition
SW1 ● 1 means factory test mode SW1
ON ON ● 01 means DC fan static pressure is 1
● 0 means add. auto searching mode
(reserved)
(default setting)
1234 1234
SW1 SW1
ON ● 1 means DC fan Is chosen ON ● 10 means DC fan static pressure is 2
● 0 means AC fan Is chosen
(reserved)
1234 1234
SW1 SW1
ON ● 00 means DC fan static pressure is 0
ON ● 11 means DC fan static pressure is 3
(reserved) (reserved)
1234 1234

SW2 definition
S W2 SW2
ON ● 00 means shutting down the unit to ON ● 00 means the time of stopping
"stop cold air" at 15℃ TERMAL fan is 4 minutes
12 34 1234
S W2 ● 01 means shutting down the unit to SW2
ON ON ● 01 means the time of stopping
"stop cold air" at 20℃ TERMAL fan is 8 minutes
12 34 1234
S W2 ● 10 means shutting down the unit to SW2
ON ON ● 10 means the time of stopping
"stop cold air" at 24℃
TERMAL fan is 12 minutes
12 34 1234
S W2 ● 11 means shutting down the unit to SW2
ON "stop cold air" at 26℃ ON ● 11 means the time of stopping
TERMAL fan is 16 minutes
12 34 1234

SW5 definition
SW 5 SW5
ON ● 00 means temperature compensation is ON ● 10 means temperature compensation
6 degrees under heating mode is 4 degrees under heating mode
1 2 1 2
SW 5 SW5
ON ● 01 means temperature compensation is ON ● 11 means temperature compensation
2 degrees under heating mode is 8 degrees under heating mode
1 2 1 2

Installation manual

12
SW6 definition 13. TEST OPERATION
SW6
ON ● 1 means old display panel 1 The test operation must be carried out after the entire
● 0 means new display panel installation has been completed.
1 2 3
SW6 2 Please confirm the following points before the test operation:
ON ● 1 means auto wind under auto mode
● 0 means auto wind under non auto mode
The indoor unit and outdoor unit are installed properly.
1 2 3 Tubing and wiring are correctly completed.
SW6 The refrigerant pipe system is leakage-checked.
ON reserved The drainage is unimpeded.

1 2 3 The heating insulation works well.


The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of
the refrigerant have been recorded.
J1,J2 definition The power voltage fits the rated voltage of the air
conditioner.
J1 There is no obstacle at the outlet and inlet of the outdoor
without jumper "J1" for auto
restart function and indoor units.
The gas-side and liquid-side stop valves are both opened.
J1 The air conditioner is pre-heated by turning on the power.
with jumper "J1" for non-auto
restart function 3 According to the user's requirement, install the remote
controller frame where the remote controller's signal can
reach the indoor unit smoothly.
J2
reserved 4 Test operation

Set the air conditioner under the mode of "COOLING" with the
remote controller, and check the following points. If there is
any malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
SW7 definition 0/1 definition
1) The indoor unit
a. Whether the switch on the remote controller works well.
SW7 b. Whether the buttons on the remote controller works
ON Standard configure ON
Means 0 well.
c. Whether the air flow louver moves normally.
1 2 d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
SW7 ON f. Whether the temporary buttons works well.
ON Last one in the network Means 1
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during
1 2 operation.
I. Whether the air conditioner heats well in the case of
the HEATING/COOLING type.
2) The outdoor unit
a. Whether there is vibration or abnormal noise during
operation.
b. Whether the generated wind, noise, or condensed of by
12. ERR0R CODE & INDICATION the air conditioner have influenced your neighborhood.
c. Whether any of the refrigerant is leaked.
No
 address when first time Timer LED and run LED flash togather
power on or show "FE"
CAUTION
M_Home
 non-matching 4 LED flash togather or show "H0"
A protection feature prevents the air conditioner from being
activated for approximately 3 minutes when it is restarted
mode
 conflict Defrost LED flash or show "E0"
immediately after shut off.
communication
 error between
Timer LED flash or show "E1"
indoor and outdoor unit
temp.sensor
 (T1) error Run LED flash or show "E2"

temp.sensor(T2)
 error Run LED flash or show "E3"

temp.sensor(T2B)
 error Run LED flash or show "E4"

EEPROM
 error Defrost LED flash slowly or show "E7"

outdoor
 unit error Alarm LED flash slowly or show "Ed"

water
 level alarm Alarm LED flash or show "EE"

Installation manual

13
202000192558

You might also like