Installation Manual For Slim Medium Static Pressure Duct Unit
Installation Manual For Slim Medium Static Pressure Duct Unit
WARNING Carry out the specified installation work after taking into
account strong winds, typhoons or earthquakes.
Be sure only trained and qualified service personnel to Improper installation work may result in the equipment falling
install, repair or service the equipment. and causing accidents.
Improper installation, repair, and maintenance may result in
electric shocks, short-circuit, leaks, fire or other damage to the If the refrigerant leaks during installation, ventilate the area
equipment. immediately.
Toxic gas may be produced if the refrigerant comes into the
Install according to this installation instructions strictly. place contacting with fire.
If installation is defective, it will cause water leakage, electrical
shock fire. The temperature of refrigerant circuit will be high, please
keep the interconnection cable away from the copper tube.
Installation manual
1
After completing the installation work, check that the
refrigerant does not leak. 2. INSTALLATION INFORMATION
Toxic gas may be produced if the refrigerant leaks into the room
and comes into contact with a source of fire, such as a fan
heater, stove or cooker.
To install properly, please read this "installation manual" at
first.
The appliance shall be installed in accordance with
national wiring regulations.
The air conditioner must be installed by qualified persons.
An all-pole disconnection device which has at least 3mm
When installing the indoor unit or its tubing, please follow
separation distance in all pole and a residual current
this manual as strictly as possible.
device(RCD)with the rating of above 10mA shall be
incorporated in the fixed wiring according to the national
If the air conditioner is installed on a metal part of the
rule.
building, it must be electrically insulated according to the
relevant standards to electrical appliances.
The power cord type designation is H05RN-R/H07RN-F or
above.
When all the installation work is finished, please turn on
the power only after a thorough check.
In buses or cabinets.
Installation manual
2
3. ACCESSORIES 5. INDOOR UNIT INSTALLATION
Table.3-1 Confirm that there is enough room for installation and mainte-
nance.
Name of
Q‘ty Outline Usage
Accessories
500mm or more
Installation manual 1 (This manual) Maintenance roomage
Control the
Remote controller 1 air-conditioner
600mm or more
Pipe insulation material 2 Heat insulation
Maintenance roomage
Water outlet joint 1 For drainage
Chucking the joint which
600mmX600mm
connect the drain hose checking orifice
Clasp 1
and the outlet of indoor Fig.5-1
unit
Use for pipe
Copper nut 1 connection of
engineering installation
Do not install the remote controller in a place exposed to direct The handling to the ceiling varies from the constructions, consult
●
sunlight or close to a heatingsource, such as a stove. Note that the construction personnels for the specific procedures.
the positive and negative poles are in right positions when
loading batteries. ● The size of the ceiling to be handled ... ... do keep the ceiling
flat. Consolidate the roof beam for possible vibration.
Ro of beam
Ce iling
Fig.5-3
Installation manual
3
5.3 New concrete bricks Canvas tie-in Canvas tie-in
Inlaying or embedding the screw bolts (refer to Fig.5-4)
Isolation booth
Supporting
Hanging bolts angle steel
Fig.5-6
Screw nut
Shockproof cushion
Fig.5-7
Installation manual
4
■ The positioning of ceiling hole and indoor unit and hanging screw bolts
routine method of installation: the size of installation for indoor unit following the Fig.5-9
92
Φ
G
B
New air inlet
F E C 20
A D
J
B
Air filter
I
Air filter
L
Fig.5-9
Electric control cabinet
Mode(W) A B C D E F G H I J K L M N
1500~3600 700 210 450 500 512 45 145 17 600 196 600 196 740 350
4500~5600 920 210 450 500 732 45 145 17 820 200 820 200 960 350
7100 1140 210 450 500 950 45 145 17 1040 200 1040 200 1180 350
Table.5-1 Unit: mm
Installation manual
5
■ How to adjust the air ventilated direction? (From rear ventilated adjust it to descensional.)
1. Take off air filter,ventilation panel and air return flange. 2. Install ventilation panel,air return flange and air filter.
Ventilation panel
Air filter
Air filter
Air return flange
Fig.5-10
NOTE
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air conditioner you purchased
(depend on model).The actual shape shall prevail.
High speed
High speed
Installation manual
6
6. INSTALL THE CONNECTING PIPE Use frozen oil
Check whether the height drop between the indoor unit and
outdoor unit, the length of refrigerant pipe, and the number of the
bends meet the following requirements: Fig.6-1
● The max height drop and The length of refrigerant pipe deponding
on the ouotdoor unit.(If the height drop is more than 10m, you
had better put the outdoor unit over above the indoor unit.) Bend the pipe with thumb
● The connecting pipe should not be installed until the indoor and
Make the ends
outdoor units have been fixed already. straight
● Keep the connecting pipe dry, and do not let moisture in during Fig.6-3
installation.
Installation manual
7
90 °± 4 ● Turn on the vacuum pump. At the beginning of pumping, loosen
45 °
±2 the maintenance terminator nut of stop valve B a little to check
A whether the air comes in (the sound of the pump changes, and
the indicator of compound meter turns below zero). Then fasten
R0.4~0.8 the nut.
Fig.7-2
● When the pumping has finished, close the Lo-lever of the
manifold valve completely and turn off the vacuum pump.
Table.7-1 ● When you have pumped for over 15 minutes, please confirm
A(mm) that the indicator of multimeter is on -1.0X105Pa (-76cmHg)
Outside diameter
Max Min ● Loosen and remove the quadrangle cover of stop valves A
and B to open stop valve A and B completely, then fasten
Φ6.4mm 8.7 8.3
them.
Φ9.5mm 12.4 12.0
● Disassemble the charge hose from the repair-mouth of stop
Φ12.7mm 15.8 15.4 valve A, and fasten the nut.
Φ15.9mm 19.0 18.6
Manifold valve
Put the connecting tubing at the proper position, wrench the Lo-lever Hi-lever
nuts with hands then fasten it with a wrench. (Refer to Charge hose
Charge hose
Fig.7-3)
Vacuum pump
Too large torque will harm the bellmouthing and too small will
cause leakage. Please determine the torque according to
● Table.7-2.
Lo-lever
Fig.7-4
●
All the stop valves should be opened before test operation.
Fig.7-3 Each air conditioner has two stop valves of different sizes on
the side of the outdoor unit which operate as Lo-stop value,
respectively. (Refer to Fig.7-5)
Table.7-2
Valve stem
Fig.7-5
The necessary filling amount of refrigerant
7.2 Check The Leakage
● Refrigerant volume to be added is calculated according to
outdoor unit installation manual .Be sure to add refrigerant Check all the joints with the leak detector or soap water. (See
measuring by a scale. L: The length of the pipe Fig.7-6 as a reference illustration)
● Please record the quantity added and store it carefully for future
Check-point of indoor unit D C
maintenance.
● Connect the joint of the charge hose with the vacuum pump.
Fig.7-6
Installation manual
8
7.3 Insulation The drain pipe installation for the unit without pump.
Fig.8-3
8. CONNECT THE DRAIN PIPE
Drainage test
Check whether the drainpipe is unhindered.
Install the drainpipe of the indoor unit
New built house should have this test done before paving
Please use the accessory drain hose to connect the outlet of the ceiling.
indoor unit with the PVC water pipe, and then use the
accessory clasp for chucking(Refer to Fig.8-1).
The unit with pump.
Connections of other water pipes please use rigid PVC binder,
and confirm there whether have leakage or not. 1 Remove the test cover (Rotate the test cover to opening up),
and stow water of about 2000ml to the water receiver through
the stow tube.
Stow tube
Fig.8-2 Fig.8-5
Installation manual
9
2 Turn on the power, and operate the air conditioner under the Pump maintaince:
"COOLING" mode. Listen to the sound of the drain pump.
Check whether the water is discharger well (a lag of 1min is 1. Screw off four screws from drain pump.
allowed before discharging, according to the length of the drain 2. Plug off pump power supply and water level switch cable.
pipe), and check whether water leaks from the joints.
3. Take off pump.
3 Stop the air conditioner, turn off the power, and reset the test
cover to its original position.
Pump
Fig.9-2
● Do not turn on the power until you have checked carefully after
wiring.
Motor
Blower housing
Ventilated panel
Fig.9-1
Installation manual
10
The Specification of Power
NOTE
Table.10-1 The air-conditioners can connect with Central Control Monitor
(CCM). Before operation, please wiring correctly and set
Model(kW) 1.5 ~7.1 system address and network address of indoor units.
Phase 1-Phase
Power
Frequency and volt 208/230V-1ph-60Hz
Indoor/outdoor connectingwiring
3-core shielded wire 3×0.75
(mm2) (Electric signal)
To indoor power
Fig.10-2
CAUTION
Please use 3-core shielded wire,and connect the shielded layer to .
A disconnection device having an air gap contact separation in
all active conductors should be incorporated in the fixed wiring
according to the National Wiring Regulation.
X Y E P Q
Wiring chart
Power
SWICH
To Central Control Indoor/outdoor
FUSE Monitor (CCM) connection wire
L N
Fig.10-3
OUTDOOR UNIT
SWICH FUSE
11. CONTROL OPERATION
Power
JUNCTION BOX
Design specialized power for the indoor unit and outdoor unit respectively 11.1 Horsepower set
Horsepower code
Central controller
OUTDOOR UNIT monitor(CCM)
P Q E XY E XYE
PO WER_S
F0 1
E
23
B CD
Vacant
4 56
789 A
Use shielded cable
and well earthing
ENC1
INDOOR UNIT INDOOR UNIT INDOOR UNIT
X Y E PQ X Y EP Q XYEPQ
Fig.10-1
CAUTION
Installation manual
11
Table.11-1
CAUTION
ENC1 Toggle switch For set horsepower
SW1 definition
SW1 ● 1 means factory test mode SW1
ON ON ● 01 means DC fan static pressure is 1
● 0 means add. auto searching mode
(reserved)
(default setting)
1234 1234
SW1 SW1
ON ● 1 means DC fan Is chosen ON ● 10 means DC fan static pressure is 2
● 0 means AC fan Is chosen
(reserved)
1234 1234
SW1 SW1
ON ● 00 means DC fan static pressure is 0
ON ● 11 means DC fan static pressure is 3
(reserved) (reserved)
1234 1234
SW2 definition
S W2 SW2
ON ● 00 means shutting down the unit to ON ● 00 means the time of stopping
"stop cold air" at 15℃ TERMAL fan is 4 minutes
12 34 1234
S W2 ● 01 means shutting down the unit to SW2
ON ON ● 01 means the time of stopping
"stop cold air" at 20℃ TERMAL fan is 8 minutes
12 34 1234
S W2 ● 10 means shutting down the unit to SW2
ON ON ● 10 means the time of stopping
"stop cold air" at 24℃
TERMAL fan is 12 minutes
12 34 1234
S W2 ● 11 means shutting down the unit to SW2
ON "stop cold air" at 26℃ ON ● 11 means the time of stopping
TERMAL fan is 16 minutes
12 34 1234
SW5 definition
SW 5 SW5
ON ● 00 means temperature compensation is ON ● 10 means temperature compensation
6 degrees under heating mode is 4 degrees under heating mode
1 2 1 2
SW 5 SW5
ON ● 01 means temperature compensation is ON ● 11 means temperature compensation
2 degrees under heating mode is 8 degrees under heating mode
1 2 1 2
Installation manual
12
SW6 definition 13. TEST OPERATION
SW6
ON ● 1 means old display panel 1 The test operation must be carried out after the entire
● 0 means new display panel installation has been completed.
1 2 3
SW6 2 Please confirm the following points before the test operation:
ON ● 1 means auto wind under auto mode
● 0 means auto wind under non auto mode
The indoor unit and outdoor unit are installed properly.
1 2 3 Tubing and wiring are correctly completed.
SW6 The refrigerant pipe system is leakage-checked.
ON reserved The drainage is unimpeded.
Set the air conditioner under the mode of "COOLING" with the
remote controller, and check the following points. If there is
any malfunction, please resolve it according to the chapter
"Troubleshooting" in the "Owner's Manual".
SW7 definition 0/1 definition
1) The indoor unit
a. Whether the switch on the remote controller works well.
SW7 b. Whether the buttons on the remote controller works
ON Standard configure ON
Means 0 well.
c. Whether the air flow louver moves normally.
1 2 d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
SW7 ON f. Whether the temporary buttons works well.
ON Last one in the network Means 1
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during
1 2 operation.
I. Whether the air conditioner heats well in the case of
the HEATING/COOLING type.
2) The outdoor unit
a. Whether there is vibration or abnormal noise during
operation.
b. Whether the generated wind, noise, or condensed of by
12. ERR0R CODE & INDICATION the air conditioner have influenced your neighborhood.
c. Whether any of the refrigerant is leaked.
No
address when first time Timer LED and run LED flash togather
power on or show "FE"
CAUTION
M_Home
non-matching 4 LED flash togather or show "H0"
A protection feature prevents the air conditioner from being
activated for approximately 3 minutes when it is restarted
mode
conflict Defrost LED flash or show "E0"
immediately after shut off.
communication
error between
Timer LED flash or show "E1"
indoor and outdoor unit
temp.sensor
(T1) error Run LED flash or show "E2"
temp.sensor(T2)
error Run LED flash or show "E3"
temp.sensor(T2B)
error Run LED flash or show "E4"
EEPROM
error Defrost LED flash slowly or show "E7"
outdoor
unit error Alarm LED flash slowly or show "Ed"
water
level alarm Alarm LED flash or show "EE"
Installation manual
13
202000192558