Datasheet of Eaton 9E-In 10000 VA (Long Back UP) 1x1 UPS System
Datasheet of Eaton 9E-In 10000 VA (Long Back UP) 1x1 UPS System
Eaton 9E-IN
10kVA/10kW 1x1 (XL-Model) UPS
Manufacturer’s declaration in accordance with IEC 62040-3
Value Proposition:
High Performance
● kVA=kW
● True Input PF 0.99
● True output Unity PF 1
● Input THDi 3%
● Output THDv 1%
● Higher Power Density
● Higher Efficiency upto 95%
● Support Critical Virtualization
2
Eaton 9E-IN
Overload Capability
100%<Load≤105%: Constant
105%<Load≤125%: 10 minutes
-Line mode
125%<Load≤150%: 30s
>150% :500ms
100%<Load≤105%: Constant
105%<Load≤125%: 1 minutes
-Battery mode
125%<Load≤150%: 30s
>150% :500ms
105%<Load≤125%: Constant
-Bypass Mode 125%<Load≤150%: 30s
Load>150%: 500ms
BATTERY
-Inner Battery Rating/Type NO
-External battery connection Connector
-Back-up Time (50% load) /
-Back-up Time (70% load) /
-Back-up Time (full load) /
-DC Voltage 192VDC (192V~240V adjustable)
11.4V/pc
10.5V/pc
-Leakage current <300uA
-Battery fuse current 100A
Charger
-Charger current default 4A (0~12A adjustable)
-Floating Voltage Phase 13.65V/pc
-Charging time /
Features
-ECO Mode YES
-Battery Capacity Calculation YES
-Fan Speed Control YES
-Frequency Converter Mode(CVCF) YES, 60% load
-Maintenance Bypass Switch factory optional
-Parallel up to 3 units
INDICATOR & ALARM
-Display Multi-language LCD + status LED
-Battery mode Beeps every four second
-Battery low Sounding every second
-Overload Sounding twice every second
-Fault Continuous beeping
INTERFACE
-RS232 YES
-USB YES
-EPO Function YES
-Comm slot box YES
-Comm card Optional(NMC/Moudbus/Dry Contact)
-Dry Contact (Dry in/Dry out) YES
-Input connection TB
-Outlet socket TB
MECHANICAL
-WxHxD(mm) 225*348*452
-Net weight(Kg) 15.2
-Wheels NO
3
Eaton 9E-IN
ENVIRONMENTAL
Operating Temperature Range 0°C ~ 40 °C (40~50°C 50% load)
Relative Humidity 0 ~ 95% (No condensing)
Audible Noise(>75% load, charger current >2A) ≤60dB
Audible Noise(>75% load, charger current <2A or 50%~75% load, charger current > 2A) ≤55dB
Audible Noise(50~75% load, charger current <2A or 25%~50% load, charger current >
≤50dB
2A)
Audible Noise(25~50% load, charger current <2A or 0%~25% load) ≤45dB
REGULATIONS
-ESD IEC 61000-4-2 Level 3
-RS IEC 61000-4-3 Level 3
-EFT IEC 61000-4-4 Level 4
-Surge IEC 61000-4-5 Level 4
-Conduction IEC 62040-2 Category C3
-Radiation IEC 62040-2 Category C3
-Safety CE Marked
-Transportation ISTA 1H
-Protection IP 20
-Performance classification VFI-SS-111