r1 Cooling Load Calcualtions
r1 Cooling Load Calcualtions
By
Managing Partner,
Chandana Dalugoda Consultants
Colombo, Sri Lanka
Rules of Thumb or check figures should not be used to determine the cooling load, since
cooling load poses many variables, that varies building to building. Check figures are
used to verify the accuracy of final cooling load.
Calculations are usually carried out using computer based software programs; ASHRAE
Radiant Time Series (RTS) method, Transfer Function Method. Manual method is
ASHRAE Cooling Load Temperature Deference method (CLTD/SCL/CLF). Advantage is
all calculations are apparent unlike computer programs.
This lecture will be based on ASHRAE CLTD/SCL/CLF method. CLTD is cooling load
temperature difference, SCL is solar cooling load & CLF is cooling load factor
Copyright 2020 © Eng. Chandana Dalugoda. 2
Sun will be directly overhead Tropic of Cancer on June 21st and Tropic of Capricorn on December 21st.
So countries situated between Tropic of Cancer & Capricorn are known as Tropical climates or Tropics.
During December South Pole has 24 hr daylight and during June North Pole has 24 hr daylight.
Copyright 2020 © Eng. Chandana Dalugoda. 10
RH % 66 46 36 52
Copyright 2020 © Eng. Chandana Dalugoda. 11
Tropical
weather
03/03/2012
U-Factor
The U factor is the rate of steady-state heat flow.
In SI units, it is the amount of heat in Watts that
flows through a one square meter area with
one degree Celsius temperature difference.
R-Value
R-value is the thermal resistance to hate flow.
U = 1/R (w/m K)
2
R = R1 + R2 + R3+….Rn
Thermal properties of common building materials are given in Table-1, Building and R=x/k
x = thickness (m)
Insulating Materials: Design Values, 2013 ASHRAE Handbook-Fundamentals (SI).
k = conductivity W/mK
This table is arranged into 8 basic families of materials, starting with insulating materials.
Copyright 2020 © Eng. Chandana Dalugoda. 19
Three terms that will be used throughout this course are the thermal capacitance,
sensible energy transfer and latent energy transfer.
Basic equation used to calculate thermal capacitance is;
Q = m Cp ΔT
Where;
Q = Heat transfer, W
m = mass of the material kg
Cp = specific heat, KJ/Kg.ºK
ΔT = temperature change in the material as a result of the heat transfer, ºK
But sizing cooling system for hottest temperature ever recorded will result in an oversized air
conditioner that will more expensive than necessary to buy and often less efficient to operate.
Extensive record of climatic condones for various countries can be found in 1997 ASHAR
Handbook-Fundamentals. 2009 & 2013 ASHRAE Handbook Fundamentals CD Rom has
additional details for most of the cities which has WMO weather station number.
q = U A (CLTD)
q = U A (CLTD)
A = Area of wall (m )
2
q = U A (CLTD)
q = A . SC . SHGF . CLF
Actual Cooling Load, Solar Heat Gain, Light, Medium and Heavy Construction
Copyright 2020 © Eng. Chandana Dalugoda. 33
q = U . A . TD
TD = ta - tr
ta = temp. of adjacent space, °C
tr = room design temp., °C
People
People
Latent q latent = N F d q lhg
Appliances
Appliances
ACH method
For residential & small commercial buildings ACH method is used.
Usually 0.5 ACH is used, assuming good construction practices
are used. Area x hight x ACH gives infiltration rate in m3/h.
Construction ACH
Tight 0.3
Medium 0.6
Loose 0.9
Copyright 2020 © Eng. Chandana Dalugoda. 44
Infiltration Load
Infiltration of air
Sensible q s= 1.23 (ύ) (to-tr)
DB °C WB °C w Kg/Kg
OUTDOOR 32 27 0.0206
INDOOR 24 17 0.0093
DIFFE 8 10 0.0113
Infiltration Load
Latent q l= 3.0 (ύ) (wo-wr)
Ventilation Load
Ventilation air
Sensible q s= 1.23 (ύ) (to-tr)
Ventilation Load
DB °C WB °C w Kg/Kg
ύ = volume flow rate of ventilation air, L/s
OUTDOOR 32 27 0.0206 wo = moisture content for outdoor air, kg/kg
INDOOR 24 17 0.0093
DIFFE 8 10 0.0113
wr = moisture content for room air, kg/kg
Copyright 2020 © Eng. Chandana Dalugoda. 48
The design outdoor airflow required in the breathing zone of the occupiable space or spaces in
a zone, i.e., the breathing zone outdoor airflow (Vbz), shall be determined in accordance with
following Equation
Where:
Az = zone floor area: the net occupiable floor area of the zone m2, (ft2).
Pz = zone population: the largest number of people expected to occupy the zone during typical
usage. default occupant density listed in Table 6-1.
Rp = outdoor airflow rate required per person as determined from Table 6-1. Note: These
values are based on adapted occupants.
Ra = outdoor airflow rate required per unit area as determined from Table 6-1.
Copyright 2020 © Eng. Chandana Dalugoda. 49
q = U As (ta-td)
NOTE: The heat gains of duct system must be considered when the ducts are not in the
conditioned space. Total heat gain from ducts would be 1 to 2 % of the room sensible
heat gain, when the ducts are not in the conditioned space and insulate.
Copyright 2020 © Eng. Chandana Dalugoda. 51
ZONES
Separating a building into zones enables the temperatures in each zone to be controlled more
accurately, particularly when there are varying heat gains between zones.
Each zone will have its own system or part of the system that cools the area. As an example,
AHU’s serving each zone, or VAV system with VAV terminals for every room or a group of fan
coil for the purpose of cooling only that zone.
By adding the loads for the east & west zone at each hour, the
building load at each hour can be identified.
From these totals, the peak simultaneous load can be found and as
above it is 145 kW
Copyright 2020 © Eng. Chandana Dalugoda. 58