Fuel Cell Formulary
Fuel Cell Formulary
Contents
1 Fundamentals 4
1.1 Thermodynamic of H2 /O2 electrochemical device . . . . 4
1.2 Nernst equation . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Reactant consumption and feed . . . . . . . . . . . . . . 8
1.4 Hydrogen energy and power . . . . . . . . . . . . . . . 10
1.5 PolCurve (Current voltage dependency) . . . . . . . . . 12
1.5.1 Kinetic of the H2 /O2 electrochemical device . . . 12
1.5.2 Butler-Volmer equation . . . . . . . . . . . . . . 12
1.5.3 Example PolCurve . . . . . . . . . . . . . . . . . 15
1.6 Fuel cell stack power . . . . . . . . . . . . . . . . . . . . 16
1.7 Fuel cell efficiencies . . . . . . . . . . . . . . . . . . . . 18
1.7.1 Different efficiencies . . . . . . . . . . . . . . . . 18
1.7.2 Electric efficiency calculation . . . . . . . . . . . 23
3 Example calculations 36
3.1 Stack operating parameters . . . . . . . . . . . . . . . . 39
4 Appendix 1: Fundamentals 41
4.1 Thermodynamic fundamentals . . . . . . . . . . . . . . 41
4.2 Energy and relevant energy units . . . . . . . . . . . . . 43
4.3 Temperature dependency of thermodynamic values . . 44
4.4 Standard temperature and pressure . . . . . . . . . . . 44
4.5 HHV and LHV . . . . . . . . . . . . . . . . . . . . . . . . 47
4.6 PolCurve parameter variation . . . . . . . . . . . . . . . 47
6 Appendix 3: Air 52
6.1 Moist air . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.1.1 Water vapor saturation pressure . . . . . . . . . 52
6.1.2 Other formulas to express humidity of air . . . . 55
6.2 Energy and power of air . . . . . . . . . . . . . . . . . . 66
6.3 Air compression . . . . . . . . . . . . . . . . . . . . . . 67
6.3.1 Definitions . . . . . . . . . . . . . . . . . . . . . . 67
6.3.2 Thermodynamics . . . . . . . . . . . . . . . . . . 68
6.3.3 Ideal and real compressor . . . . . . . . . . . . . 73
6.3.4 Examples . . . . . . . . . . . . . . . . . . . . . . 74
6.3.5 Comment . . . . . . . . . . . . . . . . . . . . . . 75
1 Fundamentals
This is a collection of relevant formulas, calculations and equations
for designing a fuel cell system (FCS).
1
H2 + O2 → H2 O(g) ∆r H < 0
2
1 kJ
H2 + O2 → H2 O(g) − ∆f HH2 O(g) = LHV = 241.82
2 mol
1 kJ
H2 + O2 → H2 O(l) − ∆f HH2 O(l) = HHV = 285.83
2 mol
Please note that LHV and HHV have positive signs whereas ∆H is
negative. All thermodynamic potentials are dependent on tempera-
ture and pressure, but are defined at thermodynamic standard condi-
tions (25◦ C and 100 kPa, standard ambient temperature and pressure
SATP, see also section 4.4).
The difference between LHV and HHV of 44.01 kJ/mol is equal to the
molar latent heat of water vaporization at 25◦ C.
The (thermodynamic) electromotive force (EMF) or reversible open
cell voltage (OCV) E 0 of any electrochemical device is defined as:
∆G
E0 =
n·F
260 DG H2O(l)
DG H2O(g)
250
240
230
220
210
200
0 20 40 60 80 100 120 140 160 180 200
T [°C]
hydrogen (i.e. its heating value) were converted into electric energy
(which is obviously not possible!), the following voltage equivalents
would result:
0 LHV 0 HHV
ELHV = = 1.253 V EHHV = = 1.481 V (1.2)
2F 2F
Those two values are the voltage equivalent to the enthalpy ∆H, also
called thermal cell voltage (see [1], page 27) or thermoneutral volt-
age.
The thermodynamic potentials ∆H and ∆G are dependent on tem-
perature; therefore also the corresponding voltage equivalents are
functions of temperature. The temperature dependency (of absolute
values) is shown in figure 1.1, values are calculated with HSC Chem-
istry 6.21.
αβ 1/2
!
RT
0 RT
E=E + ln + ln pSys (1.4)
2F γ 4F
RT p2
∆E = ln (1.5)
4F p1
Assuming a cell runs at 80◦ C, then doubling the system pressure re-
sults in a potential increase of ∆E = 7.6 mV ln 2 = 5.27 mV . It is
important to mention that due to other effects an increase in system
pressure results in much higher cell voltage increas than just given by
Nernst equation!
The reactants H2 and O2 are consumed inside the fuel cell stack by
the electrochemical reaction. Based on the Faraday’s laws the molar
flows ṅ for reactant consumptions are defined as follows:
I ·N mol
ṅH2 = [ṅH2 ] = (1.6)
2F sec
I ·N 1 mol
ṅO2 = = · ṅH2 [ṅO2 ] =
4F 2 sec
I is the stack load (electric current, [I] = A), and N is the amount of
single cells (cell count, [N ] = −). 2 is again the amount of exchanged
electrons per mole H2 for the hydrogen oxidation; respectively 4 e-
per mole O2 for the oxygen reduction. F is the Faraday constant.
The stoichiometry λ defines the ratio between reactant feed (into the
fuel cell) and reactant consumption (inside the fuel cell). Due to fuel
cell design and water management issues etc. the stoichiometry must
always be more than one:
ṅfeed
λ= >1 [λ] = −
ṅconsumed
The reactant feed for H2 and air into the fuel cell stack are now defined
by an anode and cathode stoichiometry λ:
I ·N
ṅH2 , feed = ṅH2 · λanode = · λanode (1.7)
2F
ṅO2 I ·N
ṅair, feed = · λcathode = · λcathode
xO2 4F · xO2
I ·N
ṅH2 , out = ṅH2 , feed − ṅH2 = · (λanode − 1)
2F
!
I ·N λcathode
ṅair, out = ṅair, feed − ṅO2 = · −1
4F xO2
g
ṁ = ṅ · M [ṁ] =
sec
The mass flow for stack anode and cathode inlet are therefore:
IN
ṁH2 , feed = · λanode · MH2 (1.8)
2F
IN
ṁair, feed = · λcathode · Mair (1.9)
4F xO2
The dry mass gas flow at stack cathode outlet contains less oxygen
than air and is calculated as:
!
IN λcathode
ṁcathode, out = ṁair, feed − ṁO2 , consumed = · · Mair − MO2
4F xO 2
(1.10)
The volume flow V̇ is calculated by the gas density ρ or the molar gas
volume V0, mol :
ṁ l
V̇ = = V0, mol · ṅ [V̇ ] =
ρ min
Both the gas density ρ and the molar gas volume V0, mol are tempera-
ture and pressure dependent! Therefor the referring temperature and
pressure need to be defined. N or n indicates that the volume flow
is normalized to a specific reference temperature and pressure (e.g.
[V̇ ] = Nl/min or ln /min). Physical standard temperature and pressure
(STP) is defined as 0◦ C and 101.325 kPa (for more information see
Nl
section 4.4). The molar gas volume at STP is V0, mol = 22.414 mol .
The amount of product water is equal to hydrogen consumption (equa-
tion 1.6) and given by:
I ·N mol
ṅH2 O, prod = ṅH2 = [ṅH2 O ] =
2F sec
I ·N g
ṁH2 O, prod = · MH2 0 [ṁH2 O ] = (1.11)
2F sec
kJ
HHV 285.83 mol kJ kWh
WH2 , HHV = = g = 141.79 ≡ 39.39
M 2.02 mol g kg
kJ
241.82 mol kJ kWh
WH2 , LHV = g = 119.96 ≡ 33.32
2.02 mol g kg
kJ
HHV 285.83 mol J kWh
WH2 , HHV = = ln = 12.75 = 3.54 3
V0, mol 22.414 mol mln mn
kJ
241.82 mol J kWh
WH2 , LHV = ln = 10.79 = 3.00 3
22.414 mol mln mn
J
PH2 , HHV = HHV · ṅH2 [PH2 , HHV ] = =W (1.12)
sec
Now the (chemical) power of H2 consumed in a stack (with N cells at
the stack load I) using equations 1.2 and 1.6 can easily be expressed
as:
8 0.5
6 0.4
ensity j [mA/cm²] / j / j0
0.3
4
0.2
2
0.1
j / j0
0 0.0
-100 -50 0 50 100 -10 -5 0 5 10
-2 -0.1
current de
-0.2
-4
-0.3
-6
-0.4
-8 -0.5
overpotential [mV] overpotential [mV]
" !#
αnF (1 − α)nF
j(ϕ) = j0 exp ϕ − exp ϕ
RT RT
This is the sum of an anodic and cathodic current j(ϕ) = ja (ϕ) + jc (ϕ)
with:
!
αnF (1 − α)nF
ja (ϕ) = j0 exp ϕ jc (ϕ) = −j0 exp ϕ
RT RT
j(ϕ) 1 nF
= 2 sinh ϕ
j0 2 RT
Figure 1.2a shows the anodic current (green line), the cathodic cur-
rent (blue) and the Butler-Volmer equation itself (red). In case of low
ln ( j / j0) 1
0
0 50 100 150 200 250 300
-1
-2
-3
-4
overpotential [mV]
j(ϕ) nF
= ϕ
j0 RT
Figure 1.2b shows this linear relation between current density j and
overpotential ϕ, with the slope m = nF/RT . In case of high overpo-
tentials (|ϕ| > 100mV , α = 1/2) the Butler-Volmer equation simplifies
to:
j(ϕ) 1 nF
ln = ϕ
j0 2 RT
1.0
cell voltage thermal power (HHV) thermal power (LHV)
0.9
800mV
0.8
U [V] / P [W/cm²] / efficiency [%]
0.3
0.2
0.1
0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
current density [A/cm²]
The PolCurve plots the cell voltage versus current density of a single
cell or stack. Figure 1.4 shows an theoretical PolCurve, including the
electric and thermal power based on LHV or HHV (equation 1.17),
and the electric efficiency based on LHV (1.18).
For simulation and modeling it is helpful to have a mathematical ex-
pression for the PolCurves. The following empirical equation with
physical background describes the voltage current dependency quite
well (see [2], [3]):
Electric stack power Pel is the product of stack voltage and stack
load, also called gross power:
1.481 V
Ptherm, HHV = (1.481 V − AveCell) · N · I = Pel −1 (1.17)
AveCell
Recovered heat The recovered heat is that part of the thermal stack
power that is actually converted into usable heat. This is e.g. the heat
transferred into the (liquid) coolant and can be calculated as follows:
Precovered heat = V̇ · cp · ∆T · ρ
∆G
ηel, max =
∆H
For the hydrogen fuel cell it is:
The Handbook of Fuel Cells [1] calls this simply ”ideal efficiency”.
The Fuel Cell Handbook [4] calls this efficiency the ”thermal efficiency
of an ideal fuel cell operating reversibly on pure hydrogen and oxygen
at standard conditions”.
Fuel Cell Systems Explained [5] calls this efficiency “the maximum ef-
ficiency possible” or “maximum efficiency limit” which explains it also
very well.
Pel
ηel =
Pfuel, consumed
Pel is the stack electric (gross) power and Pfuel, consumed is the con-
sumed fuel power (see equations 1.16 and 1.13).
The electric efficiency can easily expressed as (more details see sec-
tion 1.7.2):
AveCell AveCell
ηel, LHV = or ηel, HHV = (1.18)
1.253 V 1.481 V
How this efficiency is named in literature and codes & standards:
1. “Load efficiency” in the Handbook of Fuel Cells [1], refers to both
LHV and HHV.
2. The Fuel Cell Handbook [4] refers to HHV and says “this effi-
ciency is also referred to as the voltage efficiency”.
3. “Cell efficiency” in Fuel Cell Systems Explained [5], and refers
to LHV.
Pel is the stack electric gross power and Pfuel, feed is the fuel feed power
(see equations 1.16 and 1.14).
According to equation 1.18 it is:
AveCell AveCell
ηfuel, el, LHV = or ηfuel, el, HHV =
1.253 V · λanode 1.481 V · λanode
Obviously, the relation between ηfuel, el and ηel is the anode stoic:
ηel
ηfuel, el =
λanode
AveCell
ηvoltage =
E0
AveCell AveCell
ηvoltage = 0
=
El 1.229 V
AveCell
ηvoltage = ηel, HHV · ηel, TD, HHV = · 83.1%
1.481 V
Ptherm
ηtherm =
Pfuel, consumed
1.481 V − AveCell
ηtherm, HHV =
1.481 V
Recovered heat efficiency Due to the fact that not all thermal power
Ptherm is transferred into the coolant the recovery heat efficiency can
be calculated:
Precovered heat
ηrecovered heat =
Ptherm
Precovered heat V̇ · cp · ∆T · ρ
ηrecovered heat, HHV = =
Ptherm, HHV (1.481 V − AveCell) · N · I
Pel + Ptherm
ηoverall = =1
Pfuel, consumed
Therefore it is also:
Obviously ηtotal < 1, because Precovered heat < Ptherm and Pfuel, feed >
Pfuel, consumed !
Pel
ηel, LHV = Pfuel, consumed
AveCell·N ·I
= ṅH2 ·LHV
= AveCell·2F
LHV
AveCell AveCell
= 0
ELHV
= 1.253 V
Hydrogen is feed into the fuel cell system from a tank system. The
consumed hydrogen inside the fuel cell stack is based on the Faraday
equation (equation 1.6) and dependent on the stack load. Actually
Drawings
always more for the document
hydrogen „Fuel cells
is feed intoformulary“
the FCS than is consumed inside
Created: Alexander Kabza; May 28, 2008
the stack.Last modification: Alexander Kabza; July 14, 2015
The anode flow shall on one hand beFuel high enough to remove product
cell system
water, but shall on the other hand be low to increase efficiency. This
H 2
flow (e.g. λgross > 2) through the stack and allows a nearly complete
utilization of hydrogen (λnet 1.1). This stack anode off gas is finally
purged either into the cathode exhaust or directly out of the FCS. This
purged hydrogen is obviously lost for the electrochemical conversion,
therefore the amout of anode purge losses shall be minimized.
The relation between hydrogen feed versus consumed hydrogen is
called FCS fuel stoichiometry:
ηfuel,FCS = 1/λfuel,FCS
The anode recirculation loop and its anode purge controls needs to be
optimized regarding high fuel efficiency or low fuel losses. By doing
this the fuel stoichiometry can be close to 1. One controls concept
is the Amperehour counter. The anode purge is triggered when the
integral of stack load reaches an Ah-threshold of e.g. 50 Ah. If the
stack runs at 300 A constant load there is one purge every 10 min,
calculated as following:
300 A 300 A
= = 0.00166 s−1 = 0.1 min−1
50 Ah 180, 000 As
λ Mwater
x
· Yin + 2 · Mair
Yout = λ MO2 (2.1)
x
− Mair
[‐] 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5
Y.So.C [kg/kg] 0.224 0.206 0.191 0.178 0.167 0.157 0.148 0.140 0.133 0.126 0.120 0.115
T.So.C [°C] 66.6 65.2 63.9 62.7 61.6 60.6 59.5 58.6 57.8 56.8 56.0 55.2
Table 2.1: Specific humidity and temp. at stack outlet versus cathode
stoichiometry
5
x 10
4
In: 70°C, 150kPa, RH 50%, CStoic 2.0
CStoic 1.8
3.5 RHin 80%
2.5
pout [Pa]
1.5
0.5
70 75 80 85 90 95 100
Tout [°C]
q
p2 − p0 (αA ρ0 )2 · (p0 + p2 )2 + 2 ṁ2 p0 ρ0
∆p = + − p2 ∆p ∝ ṁx
2 2 αA ρ0
(2.3)
Here p2 is the gauge pressure at the stack exhaust, and p0 and ρ0 are
absolute pressure and air density at STP.
κ−1
p2
wcomp = cp, m T1 · Π κ −1 Π=
p1
kJ W
[wcomp ] = =
kg g/sec
For dry air at room temperature (25◦ C) this compression work wcomp
as a function of pressure ratio Π looks as follows:
Finally the required power for compression is:
Pcomp = ṁ · wcomp
W
Pcomp = ṁ · wcomp = 92 g/sec · 88 = 8.1 kW
g/sec
160
143
140
Power per mass flow [W / g/sec]
127
120
Isentropic work [kJ/kg]
109
100 88
80
65
60
36
40
19
20
0
0
1.0 1.5 2.0 2.5 3.0 3.5 4.0
Pressure ratio [‐]
Precovered heat
V̇ = [V̇ ] = l/min
cp · ∆T · ρ
The overall FCS efficiency considers the fuel, electric and thermal
input and electric and thermal output (see [8], 5.1.9.1):
When the thermal output is used in the vehicle and the electric and
thermal inputs are negligible, this equation simplifies to:
Pnet output
ηFCS, el =
Pfuel input
“Fuel power input” Pfuel input is the fuel (chemical) energy content fed
into the FCS (see equation 1.12). It can be expressed based on LHV
or HHV; both [1] and [8] refer to LHV.
The electric net power output Pnet output is the stack gross power minus
the total electric power consumption of all auxiliary FCS components
(e.g. compressor or blower, pumps, valves, etc.):
X
Pnet = Pgross − Paux Paux = Pcomponent i
i
with
AveCell 1 Pnet
ηstack = , ηfuel = and ηperipheral =
1.253 V λfuel Pgross
I ·N
ṁ = ṁair (I) = · λcathode (I) · Mair
4F · xO2
κ−1
1
Pcompressor = ṁ · cp, m T1 · Π(I) κ −1 ·
ηcompressor (Π, ṁ)
Under the assumption that the power consumption of all other auxil-
iary components is constant, the total aux power consumption can be
estimated.
3 Example calculations
Hydrogen flow power: A hydrogen flow transports (chemical) power.
According to equation 1.12 the hydrogen flow of e.g. 1 g/sec is equiv-
alent to:
g ln m3
1 ≡ 667.1 ≡ 40.0 n ≡ 120.0 kWLHV ≡ 141.8 kWHHV
sec min h
AveCell 0.6 V
ηel, LHV = 0
= = 47.9%
ELHV 1.253 V
ln
150 min mol
ṅH2 feed = ln sec = 0.1115
22.414 mol · 60 min sec
kJ
Pel 10 sec
ηfuel, el, LHV = = = 37.1%
ṅH2 feed · LHV 0.1115 mol
sec
· 241.82 kJ
mol
100
90
80 gross
net
70 aux
Electric power [kW]
60
50
40
30
20
10
0
0 50 100 150 200 250 300 350 400 450
Stack load [A]
and 1.8 above 0.15 A/cm2 . The cathode inlet pressure is linear be-
tween 130 kP a at low and 200 kP a at high load. The compressor effi-
ciency is linear between 70% at low and 80% at high air mass flow.
Based on the polarization curve shown in chapter 1.5, and using the
above parameter to calculate Paux , we get the electric power showed
in figure 3.1:
With an assumed net anode stoichiometry of 1.3 at low and 1.05 at
higher loads above 0.15 A/cm2 , the FCS efficiencies can be calcu-
lated as shown in figur 3.2.
The FCS peak efficiency is 55% for this example. The zero power
level is called idle point; here the FCS net power is zero, but the FCS
is still operating and consumes fuel.
50%
Efficiency [%]
40%
30%
20%
10%
0%
0 10 20 30 40 50 60 70 80 90
FCS net power [kW]
Example H2 /air fuel cell stack with 200 cells and 300 cm2 active area:
Stack electric
Current density * A/cm2 0.05 0.10 0.20 0.40 0.60 1.00
Ave cell voltage * mV 839 797 756 703 661 588
Current (gross) A 15 30 60 120 180 300
Voltage V 168 159 151 141 132 118
Power (gross) kW el 3 5 9 17 24 35
Stack anode
Stoichiometry * - 3.0 2.0 1.3 1.3 1.3 1.3
Hydrogen flow Nl/min 62.7 83.6 108.7 217.4 326.2 543.6
Hydrogen flow g/sec 0.09 0.13 0.16 0.33 0.49 0.81
Stack cathode in
Stoichiometry * - 2.2 2.0 1.8 1.8 1.8 1.8
Air flow Nl/min 109.5 199.1 358.4 716.8 1075.2 1792.1
Air flow g/sec 2.4 4.3 7.7 15.4 23.2 38.6
Air flow kg/h 8.5 15.4 27.8 55.6 83.4 138.9
Stack thermal
P therm LHV kW 1.2 2.7 6.0 13.2 21.3 39.9
P therm HHV kW 1.9 4.1 8.7 18.7 29.5 53.6
delta HHV - LHV kW 0.7 1.4 2.7 5.5 8.2 13.7
Coolant inlet temp * °C 60 60 60 60 60 60
Coolant outlet temp * °C 61 63 66 67 68 70
Coolant delta T K 1 3 6 7 8 10
Coolant flow LHV 2 l/min 17.9 13.1 14.3 27.1 38.3 57.4
Coolant flow HHV 2 l/min 27.7 19.7 20.8 38.3 53.1 77.0
* given values
1
20°C and 50% compressor efficiency
2
WEG 50vol% at 60°C
4 Appendix 1: Fundamentals
−S U V
H A
−p G T
dU = −pdV + T dS dH = V dp + T dS
[E]= J = kg m2 /s2 = Nm = Ws
35
30
25
20
0 50 100 150 200
T [°C]
By the way The well known molar volume of an ideal gas is given
at this temperature and pressure:
T0
V0, mol = R · = 22.414 ln /mol
p0
The higher heating value (HHV) of any fuel can be measured within
a calorimeter. The result of this measurement is the energy of the
chemical (oxidation) reaction starting at 25◦ C and ending at 25◦ C;
therefore product water is condensed completely. Due to that the
HHV includes the latent heat of water vaporization; but the specific
amount of product water produced by the fuel oxidation reaction needs
to be considered.
The lower heating value (LHV) itself can not be measured directly;
therefore the LHV needs to be calculated from HHV minus latent heat
of water vaporization.
Charts 4.2 show parameter variations for the empirical PolCurve equa-
tion 1.15. The baseline parameters are: E0 = 1.0 V, b = 0.08 V/dec,
R = 0.1 Ω cm2 , m = 0.0003 V, and n = 3.30 cm2 /A.
Variation E0: 1.05 − 1.0 − 0.95 V Variation b: 0.06 − 0.08 − 0.1 V/dec
1 1
0.8 0.8
Cell voltage [V]
0.6 0.6
0.4 0.4
0.2 0.2
0 0
0 0.5 1 1.5 2 0 0.5 1 1.5 2
Variation R: 0.07 − 0.01 − 0.13 Ω cm2 Variation m: 1e−4 − 3e−4 − 5e−4 cm2/A
1 1
0.8 0.8
Cell voltage [V]
0.6 0.6
0.4 0.4
0.2 0.2
0 0
0 0.5 1 1.5 2 0 0.5 1 1.5 2
2
Current density [A/cm ] Current density [A/cm2]
5 Appendix 2: Constant
values and abbreviations
Constant values
Faraday’s constant F = 96 485.3399 Amol
sec
[11]
J
Molar gas constant R = 8.314472 K mol [11]
Magnus equation const C1 = 610.780 Pa
C2 = 17.08085
C3 = 234.175 ◦ C
Thermodynamics
Standard temp. and pressure T0 = 273.15 K [12]
(STP, see section 4.4) p0 = 101.325 kPa [12]
Molar volume of ideal gases
(at STP) V0, mol = RT0 /p0 = 22.414 ln /mol
Standard ambient T and p Tc = 298.15 K [13]
(SATP) pc = 100.000 kPa [13]
kJ
LHV of H2 (at SATP) −∆HH2 O(g) = 241.82 mol [13], [14]
=119.96
ˆ kJ/g [15]
kJ
HHV of H2 (at SATP) −∆HH2 O(l) = 285.83 mol [13], [14]
=141.79
ˆ kJ/g [15]
kJ
Gibbs free enthalpy of H2 O(g) −∆GH2 O(g) = 228.57 mol [13]
kJ
and H2 O(l) (at SATP) −∆GH2 O(l) = 237.13 mol [13]
Molar weights
Molar weight water Mwater = 18.0153 g/mol
hydrogen MH2 = 2.01588 g/mol [11]
oxygen MO2 = 31.9988 g/mol [11]
nitrogen MN2 = 28.01348 g/mol [11]
CO2 MCO2 = 44.0095 g/mol [11]
air Mair = 28.9646431 g/mol [11]
Molar fraction of O2 in air xO2 = 0.21
Other relevant constants
Individual gas constant of air Rair = R/Mair = 287.06 kgJK
Individual gas const. water vapor Rw = R/Mw = 461.52 kgJK
Density of air (at STP) ρair = 1.293 kg/m3n
Density of H2 (at STP) ρH2 = 0.0899 kg/m3n
Specific heat capacity of water (20◦ C) cp, m, water = 4182 kgJK
Density of water (20◦ C) ρwater = 998.2 kg/m3
Specific heat cap. air (p = const) cp, m, air = 1005.45 kgJK
Specific heat cap. air (V = const) cV, m, air = cp, m, air − Rair
= 718.39 kgJK
Ratio of specific heats for air κ = cp /cV = 1.40
(κ − 1)/κ = 0.285
Specific heat capacity of water vapor cp, water = 1858.94 kgJK
Enthalpy of water vaporization (0◦ C) hwe = 2500.827 gJ
6 Appendix 3: Air
Magnus equation:
C2 · t
pws (t) = C1 · exp [pws (t)] = Pa, [t] = ◦ C (6.1)
C3 + t
100
101.32
Water vapor saturation pressure [kPa]
80
70.04
60
47.29
40
31.12
19.90
20
12.33
7.38
4.25
0.61 1.23 2.34
0
0 10 20 30 40 50 60 70 80 90 100
Temperature t [°C]
1600
1596
1400
Water vapor saturation pressure [kPa]
1284
1200
1023
1000
805
800
627
600
481
400 364
272
200 199
143
101
0
100 110 120 130 140 150 160 170 180 190 200
Temperature t [°C]
3
Ci T i
X
Θ=T−
i=0
3
bi Θi + b4 ln Θ
X
ln pws (T ) =
i=−1
Antoine equation:
B
log10 pws (t) = A −
t+C
ϕ pws (t)
Y (p, t, ϕ) = 0.622 · (6.4)
pair − ϕ pws (t)
2.0
0.8
RH is 100% (saturation)
0.6
0.4
0.2
0.0
0 20 40 60 80 100
Temperature t [°C]
pw (t) aw (t) mw
ϕ= = = ϕ = 0.0 − 1.0
pws (t) aws (t) mws
2.0
1.8
absolute pressure is 101.325 kPa 100% RH
1.6
75% RH
midity Y [kg/kg]
1.4
50% RH
1.2 25% RH
1.0
Specific hum
0.8
0.6
0.4
0.2
0.0
0 20 40 60 80 100
Temperature t [°C]
Y (t) p Y (t) p
ϕ= Mw · = · (6.5)
Mair
+ Y (t) ps (t) 0.622 + Y (t) ps (t)
Mw pw (t) 1 pw g K pw (t)
a(t) = · = · = 2.167 ·
R T0 + t Rw (t) T0 + t J T0 + t
600
300
200
100
0
0 20 40 60 80 100
Temperature [°C]
pw (t)
y(t) = y = 0.0 − 1.0
pa
1.0
1E-2
0.9
0.8 1E-4
0.7 1E-6
0.6
Mol fraction y
1E-8
0.5 -100 -80 -60 -40 -20 0
0.4
0.3
101.325 kPa
0.2 120 kPa
150 kPa
0.1 200 kPa
0.0
0 20 40 60 80 100 120
Dew point temperature Tdp [°C]
C2 ·t
C3 · ln ϕ + C3 +t
Tdp = ·t
C2 − ln ϕ − CC32+t
C ·T
pw (t) exp C32+Tdpdp
ϕ= = ·t
pws (t) exp CC32+t
100
80 100% RH
80% RH
60% RH
mperature [°C]
60 40% RH
20% RH
40
Dew point tem
20
-20
0 20 40 60 80 100
Temperature t [°C]
100%
90%
80%
70%
midity RH [%]
60%
50%
relative hum
40%
30% DPT = t - 2K
20% DPT = t - 5K
DPT = t - 10K
10% DPT = t - 20K
0%
0 20 40 60 80 100
Temperature t [°C]
with
where Y is the specific humidity of moist air, cp, air is the specific heat
capacity of dry air, cp, water is the specific heat capacity of water vapor
and hwe is the specific enthalpy of water vaporization. In case of dry
air (Y = 0), the enthalpy is a linear function of temperature (with slope
cp, air ). Heat capacities are dependent on temperature (see chapter
4.3), but between 0 and 100◦ C this may be neglected.
Because the enthalpy is not an absolute value; only the enthalpy dif-
ference to a reference temperature can be calculated. Depending on
the unit of temperature, the reference temperature is 0◦ C if [t] = ◦ C;
or 0 K if [t] = K. If the temperature is given in ◦ C, the enthalpy is 0 kg
kJ
500
450
400
Specific entthalpy h [kJ/kg]
350
300
100% RH
250 75% RH
200 50% RH
25% RH
150 dry (0%)
100
50
absolute pressure is 101.325 kPa
0
0 10 20 30 40 50 60 70 80 90 100
Temperature t [°C]
2000
1800
101.325 kPa
1600 120 kPa
halpy h [kJ/kg]
1000
Specific enth
600
400
200
0
0 10 20 30 40 50 60 70 80 90 100
Temperature t [°C]
The following table lists the water vapor saturation pressure over liq-
uid water (between 0 and 200 ◦ C) according to [16].
Energy and power of dry and wet air are important to calculate e.g.
the power demand for air humidification in a fuel cell system or to
calculate efficiencies. See also ASME PTC 50-2002 Fuel Cell Power
Systems Performance [18] and DIN IEC 62282-3-2 Fuel cell technolo-
gies - Part 3-2: Stationary fuel cell power systems [10].
The energy of air contains the air enthalpy and the pressure:
T0 and p0 are the reference temperature and pressure, see section 4.4.
1
P = ∆h · ṁair = 40.218 kJ/kg · 30 kg/hr · hr/sec = 335 W
3600
1
P = ∆h · ṁair = 326.61 kJ/kg · 30 kg/hr · hr/sec = 2722 W
3600
6.3.1 Definitions
6.3.2 Thermodynamics
Wel
ature T1 to pressure p2 and temperature
T2 . p2 > p1 in case of compression and
Gas in Compressor Gas out
p2 < p1 in case of expansion. The pres-
sure ratio Π is defined as:
Wloss
p2
Π=
p1 Figure 6.11: Gas compres-
sion
For compression Π > 1 and for expan-
sion Π < 1.
A compression process consumes energy or work, an expansion pro-
cess produces energy or work.
To calculate the efficiency of a compression process the theoretical
energy demand needs to be calculated based on an isentropic pro-
cess. In a real compression process there is always heat transferred
to the surrounding (or cooling), and also gas mass flow losses can
occur inside the compressor.
Thermodynamic of gases
dU = dq + dw
dH = dU + pdV + V dp
CV = (∂U/∂T )V Cp = (∂H/∂T )p
dU = CV dT and dH = Cp dT (6.7)
For ideal gases the specific heat capacities cp and cV with [c] =
J/mol K are independent of temperature! For ideal one atomic gases
it ist:
Cp 5 CV 3 5
cp = = R cV = = R κ = = 1.67
n 2 n 2 3
The specific heat capacities cp, m and cV, m are given as:
cp, m = cp /M and cV, m = cV /M
[cp, m ] = [cV, m ] = J/kg K
dw = dU = −p dV = CV dT
CV dT /T = −nR dV /V
The integral over start (1) and end state (2) is:
Z 2 Z 2
CV dT /T = −nR dV /V
1 1
cp
n=κ= >1
cV
CV cV 1
With cp − cV = R, cV = CV /n and therefore nR
= cp −cV
= κ−1
it is:
κ−1
T1 V2
=
T2 V1
κ−1 ! κ−1
κ κ
T1 V2 T1 p1 p1 V2
= = =
T2 V1 T2 p2 p2 V1
The volume (change) work wV,12 is the work that is done on a piston
to reduce the start volume V1 to the end volume V2 . It is equivalent in
the change of inner energy. The volume work for an adiabatic process
(dq = 0) is defined as:
Z V2 Z 2 Z T2
wV, 12 = − p dV = dU = CV dT = CV ∆T
V1 1 T1
The technical work wt,12 is the work that is transferred from or mass
flow via a technical system (for instance a mechanical axle). The
technical work is equal to the enthalpy of the kinetic and potential
energy of a stationary mass flow. The technical work wt,12 for com-
pression is the work given to the drive shaft of the compressor; it
contains the displacement work, but not the friction [19]!
The technical work for an adiabatic process (dq = 0) is defined as:
Z p2 Z 2
wt, 12 = + V dp = dH = Cp ∆T
p1 1
Therefore:
wt, 12 = wV, 12 + p2 V2 − p1 V1
The technical work is always more than the volume work, because
κ > 1.
κ−1
T2, s = T1 · Π κ
κ−1
ws, 12 = cp, m · (T2, s − T1 ) = cp, m T1 · Π κ −1
6.3.4 Examples
J kJ
wact = cp, m · (T2, act − T1 ) = 1005 · 120 K = 120.6
kg · K kg
Isentropic temperature:
!0.285
κ−1 3 bara
T2, s = T1 · Π κ = 303.15 K · = 414.6 K
1 bara
ws = cp, m · (T2, s − T1 )
J kJ
= 1005 kg·K · (414.6 K − 303.15 K) = 112.4 kg
Isentropic efficiency:
ws 112.4 kJ/kg
ηs = = = 0.932 or 93.2%
wact 120.6 kJ/kg
kJ
Ps = ṁ · ws = 87.6 · 27 kg/h = 2365.2 kJ/h = 657.0 W
kg
Ps 657.0 W
ηel = = = 0.50 or 50%
Pel 1305 W
6.3.5 Comment
κ cp /cV cp
·R= · (cp − cV ) = · (cp − cV ) = cp
κ−1 cp /cV − 1 cp − cV
1 1 cV
·R= · (cp − cV ) = · (cp − cV ) = cV
κ−1 cp /cV − 1 cp − cV
7.1 Assumptions
7.2 Derivation
NI λ
ṁair in = · Mair · see equation 1.9
4F x
Stack outlet: Water inet and product water exit the cathode
!
IN λcathode
ṁcathode, out = · · Mair − MO2 see equation 1.10
4F xO 2
λ Mwater
mwater, out ṁwater, in + ṁwater, prod x
· Yin + 2 · Mair
Yout = = = MO2
ṁcathode, out IN
· λcathode
· Mair − MO2
λ
−
4F xO2 x Mair
The reactant pressure drops through the fuel cell stack anode and
cathode are important stack parameters for system design consid-
erations. Especially the pressure drop on the cathode side needs
to be considered, because air needs to be compressed accordingly.
For simplification the stack can be seen as an orifice with a specific
pneumatic resistance, see figure 8.1
p1 (p.Si.C) and p2 (p.So.C) are gauge pressures before (upstream)
and behind (downstream) the stack or orifice. For gases the mass
flow ṁ is given by the following orifice equation:
q
ṁ = αA · 2 ρ1 ∆p (8.1)
p p
Si.C So.C
pD
T S.C T
Si.C So.C
F
F.Air.C (MFC) V1 Stack = orifice V2 p.PC.C
ρ1 = ρ0 p1p+p
0
0
is the gas density at pressure p1 (temperature is not con-
sidered here!), and ∆p = p1 −p2 is the pressure drop at the orifice. αA
is an orifice specific parameter containing the orifice flow coefficient α
and the orifice cross-sectional area A, [αA] = m2 . This coefficient is
hardly accessible by theory, but it can easily be measured if all other
parameters of equation 8.1 are known.
Example: The air flow through a single cell is V̇ = 10 Nl/min (ṁ =
0.216 g/sec). Pressures are measured to be p1 = 15 kPa and ∆p =
10 kPa (and therefore p2 = 5 kPa), then αA = 1.251 · 10−6 m2 .
This orifice equation 8.1 can be solved to ∆p with the following result:
q
p2 − p0 (αA ρ0 )2 · (p0 + p2 )2 + 2 ṁ2 p0 ρ0
∆p = + − p2 ∆p ∝ ṁx
2 2 αA ρ0
(8.2)
Figure 8.2 shows the pressure drop ∆p as a function of air mass flow
ṁ with three three different values of αA. According to equation 8.1
αA = 2.9 · 10−4 m2 for a given pressure drop of 25 kPa at the air mass
flow of 115 g/sec and cathode exhaust pressure of 130 kPaabs.
25
2.60e-04
2.80e-04
20 3.00e-04
10
0
20 40 60 80 100
Air flow [g/sec]
But during air mass flow transients the volume V between the air feed
and the fuel cell stack needs to be considered, as described here
[20]. The reason therefore is that each individual air flow corresponds
to a specific pressure drop (see equation 8.2), and therefore also the
pressure p1 before the stack is a function of air flow. An increasing air
flow ṁin also increases the pressure in the volume V , and therefore
ṁC > 0:
∆p(ṁ)
τ = RStack CVol and RStack = (non-linear)
ṁStack
p p
Si.C So.C
RStack
m in m out
m C m Stack
CVol
V V ∆p
CVol = and therefore τ ∝
Rair T ṁ
t
∆p(t) = ∆pstatic · exp (− ) (8.3)
τ
On fuel cell teststands often the air flow ṁ is lower and the volume
V is higher than in the final FCS application. Especially there the
dynamic response needs to be considered! During electric load tran-
sients it needs to be considered that the reactant flows through the
stack may be significantly delayed by several seconds (depending on
τ )! Anode and cathode starvation issues may occure.
Bibliography
[1] Arnold Lamm Wolf Vielstich and Hubert A. Gasteiger. Handbook
of Fuel Cells Vol. 1. John Wiley & Sons Ltd, 1 edition, 2003.
[2] S. Srinivasan et al. Advances in solid polymer electrolyte fuel
cell technology with low platinum loading electrodes. J. of Power
Sources, 22:359 – 375, 1988.
[3] J. Kim et al. Modeling of pemfc performance with an empirical
equation. J. Electrochem. Soc., 142(8):2670 – 2674, 1995.
[4] U.S. Department of Energy. Fuel Cell Handbook. National Tech-
nical Information Service, U.S. Department of Commerce, 7 edi-
tion, 2004.
[5] James Larminie and Andrew Dicks. Fuel Cell Systems Ex-
plained. John Wiley & Sons Ltd, 2 edition, 2004.
[6] Performance Working Group within the SAE Fuel Cell Stan-
dards Committee. SAE J2617: Recommended Practice for test-
ing Performance of PEM Fuel Cell Stack Sub-system for Auto-
motive Applications. SAE International, Nov2007.
[7] Fuel Cell Technologies BSI Technical Committee GEL/105. DD
IEC TS 62282-1:2005 Fuel cell technologies - Part 1: Terminol-
ogy. BSI British Standards, 18 April 2005.
[8] Performance Working Group within the SAE Fuel Cell Stan-
dards Committee. SAE J2615: Testing Performance of Fuel