E10 CO2 Room Sensor, BAPI-Stat “Quantum Prime”

Air Quality Sensors Rev. 04/28/21

Features & Options


● Automatic Barometric Pressure Compensation for Accurate Readings
Regardless of Weather or Altitude
● Optional Temperature, Setpoint, Override and Humidity
● Models for Periodically or Continuously Occupied Areas
● Models that Meet California AB 841 When Connected to a Building
Automation System (choose option N when ordering)

The BAPI CO2 Sensor is an accurate and reliable way of incorporating


demand controlled ventilation into a building’s HVAC strategy. It
measures the CO2 in a range of 0 to 2,000 ppm with a field selectable
output of 0 to 5 or 0 to 10 VDC.
The Single Channel unit has been optimized for periodically unoccupied
areas and features automatic background calibration over a long time
period to reduce drift. The Dual Channel “24/7” unit has been optimized
for continuously occupied areas and features a 3-point calibration
process for enhanced accuracy and stability.
Barometric pressure changes can affect CO2 sensors, even putting
them outside of their specified accuracy. The BAPI unit has a built-in
Barometric pressure sensor that continuously compensates the output
BAPI-Stat “Quantum
for accurate readings despite the weather or altitude.
Prime” CO2 Sensors
The CO2 level is indicated by three LEDs on the front of the unit. A 60mm (bottom unit shown with
mounting base is available to fit European style junction boxes. optional 60mm mounting base)

Specifications
Power for 0 to 5 VDC Outputs:
0 to 5V Outputs: 9 to 35 VDC @ 240 mA (9 to 24 VDC recomm.)
0 to 10V Outputs: 15 to 35 VDC @ 240 mA (15 to 24 VDC recomm.)
CO2 Sensor: Single or Dual Channel Non-Dispersive Infrared (NDIR)
Humidity Sensor: Capacitive Polymer ±2% RH Accuracy
Temperature Sensor: Thermistor or RTD
Operating Environment:
32 to 122°F (0 to 50°C) • 0 to 95%RH non-condensing
Material: ABS Plastic, Material Rated UL94V-O
CO2 Detection Range: 0 to 2,000 ppm
Start-Up Time: <2 Minutes
Response Time: <2 Minutes for 90% step change typical (after start-up)
Unit Dimensions
CO2 Accuracy (Single Channel Units): (bottom unit shown with 60mm
400 to 1,250 ppm: ±30ppm or 3% of reading, whichever is greater mounting base)
1,250 to 2,000 ppm: ±5% of reading + 30ppm
CO2 Accuracy (Dual Channel “24/7” Units):
400 to 1,000 ppm: ±75 ppm • >1,000 ppm: ±10% of reading
CO2 Drift Stability (Dual Channel “24/7” Units):
<5% of full scale over life of product.
Mounting: Standard 2”x4” junction box, European junction box or
drywall mount (screws provided)
LED CO2 Level Indicator:
Good, Green < 1,000 PPM (1,100 PPM when option “N” chosen)
Fair, Yellow = 1,000 to 1,500 PPM (1,100 to 1,500 PPM when “N” chosen)
Poor, Red > 1,500 PPM
Agency: RoHS, California Title 24 and AB 841

Building Automation Products, Inc. • 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel: +1-608-735-4800 • Fax: +1-608-735-4804 • Email: [email protected] • Web: www.bapihvac.com
CO2 Room Sensor, BAPI-Stat “Quantum Prime” E11
Air Quality Sensors
Submittal sheets without List Prices are available on our website at www.bapihvac.com

Use the Option Selection Guide below to create your custom part number. Replace the number and
parenthesis with the designator for each selection. Skip the designator and dashes for optional selections
that are not required in your configuration.

BAPI-Stat “Quantum Prime” CO2 Sensor Option Selection Guide:


Unit w/ Standard Mounting Base
BA/AQP( #1 ) - ( #2 ) - ( #3 ) - ( #4 ) - ( #5 ) - ( #6 )( #7 ) - ( #8 ) - ( #9 )
Unit w/ Standard Mounting Base
BA/AQP60( #1 ) - ( #2 ) - ( #3 ) - ( #4 ) - ( #5 ) - ( #6 )( #7 ) - ( #8 ) - ( #9 )

#1: Display Style (required) #6: Setpoint Display Range (required)


F .......Unit with Display and °F indication ...... $35 A .......-3 to +3

.
B .......-5 to +5
.
.
C .......Unit with Display and °C indication...... $35

.
C .......50 to 90 °F or 10 to 32 °C
.
.
X .......Unit without Display

.


D ......55 to 85 °F or 13 to 30 °C
.
#2: CO2 Output (required)

.


E .......60 to 80 °F or 15 to 27 °C
A .......Single Channel, 0 to 5V Output ......... $475

.


F .......65 to 80 °F or 18 to 27 °C
.
.
B .......Single Channel, 0 to 10V Output ....... $475 P.......-2 to +2
.


.
.
C .......Dual Channel, 0 to 5V Output ........... $505 X .......No Setpoint Adjustment
.
#7: Setpoint Output Range (required)
.
.
D .......Dual Channel, 0 to 10V Output ......... $505
00......0 to 5 V
.
.
#3: Temperature Sensor (required)
10......0 to 10 V
A .......1K Platinum RTD (385 curve).............. $25
40......0 to 1 K
.
B .......10K-2 Thermistor ................................. $18
60......0 to 10 KΩ
.
.
C .......10K-3 Thermistor ................................. $18
80......0 to 20 KΩ
.
.
D .......10K-3[11K] Thermistor......................... $18
81......4.75 K to 24.75 KΩ
.
.
E .......20K Thermistor .................................... $18
82......6.19 K to 26.19 KΩ
.
.
F .......1.8K Thermistor ................................... $18
84......10 K to 30 KΩ
.
.
G .......1K Ω Nickel RTD ................................. $35
X .......No Setpoint Adjustment
.
.
H .......3K Thermistor ...................................... $18
.
#8: Occupant Override (required)
.
.
X .......No Temperature Sensor
J ........Override as a Separate Output ............. $5
.
#4: Humidity Output (required)
.
.
N .......Override in Parallel (//) with Sensor ....... $5
A .......±2% Accuracy, Output of 0 to 5V ......... $80
.
.
P .......Override in Parallel (//) with Setpoint ..... $5
.
.
B .......±2% Accuracy, Output of 0 to 10V ....... $80
.
.
X .......No Override
.
.
X .......No Humidity Output
.
#9: Optional Selections* (optional)
.
#5: Setpoint Adjustment (required) A .......Differential Ground
1........Slider Setpoint Adjustment .................... $6
.
B .......Comm Jack C35 .................................. $10
.
X .......No Setpoint Adjustment
.
.
F .......Test and Balance Switch .................. $7.50
.
.
.
N .......LED Alert Level for California AB 841 ....... $6
Additional options are available for these
.
.
units but not shown in this Selection Guide. *When more than one is selected, put in alphabetical
Contact your BAPI representative for the order. Additional options can be found on pg. I4
complete list of options.

Example Number: BA/AQP ( F ) - ( A ) - ( B ) - ( A )- ( 1 ) - ( F )( 80 ) - ( N )


Actual Number (with brackets removed): BA/AQPF-A-B-A-1-F80-N
Description: BAPI-Stat “Quantum Prime” CO2 Sensor, °F Display, 0 to 5V Single Channel CO2
Output, 10K-2 Thermistor Temperature Sensor, 0 to 5V Humidity Output, Sider Setpoint Adjustment,
65 to 80 Temp Setpoint Display Range, 0 to 20K Temp Setpoint Output Range, Override in Parallel
with the temp sensor, No Additional Options
List Price: $35 (°F Display) + $475 (CO2 Unit) + $18 (Thermistor) + $80 (Humidity) + $6 (Setpoint)
+ $5 (Override) = $619 List

Your Number: BA/



Building Automation Products, Inc. • 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel: +1-608-735-4800 • Fax: +1-608-735-4804 • Email: [email protected] • Web: www.bapihvac.com