We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36
POWER QUALITY
Power System Harmonics
Power System Harmonics Harmonic currents and voltages are integer multiples of the system's fundamental frequency. For example, with a fundamental frequency of 60Hz, the 3rd harmonic frequency is 180Hz (3 x 60Hz). What causes harmonic currents? Nonlinear loads are the source of harmonic currents. That is, the load's current waveform is non-sinusoidal. As a result, the distorted current waveform is rich in sinusoidal harmonic current waveforms.
Nonlinear loads include electronic devices such as
rectifiers, current controllers, AC and DC drives, cyclo- converters and devices with switch-mode power supplies such as computers monitors, telephone systems, printers, scanners, and electronic lighting ballasts. What causes harmonic voltages? The electrical distribution system's harmonic impedances cause the load-generated harmonic currents to produce harmonic voltages (EH = IH x ZH).
Transformers, and feeder and branch circuit
impedances will cause maximum voltage distortion at the nonlinear loads. Examples Non-linear load Adjustable Speed Drives (ASD) Definitions RMS The rms value of a periodic current (or voltage) waveform is defined as: Total Harmonic Distortion (THD) The most commonly-used measure for harmonics is total harmonic distortion (THD), also known as distortion factor. It is applied to both voltage and current. THD is defined as the rms value of the harmonics above fundamental, divided by the rms values of the fundamental. THD & RMS
Because line losses are proportional to the
square of rms current (and sometimes increase more rapidly due to the resistive skin effect), then line losses always increase when harmonics are present.
Current distortion in loads varies from a few
percent to more than 100%, voltage distortion is generally less than 5%. Voltage THDs below 0.05 Average Power Harmonic powers (including the fundamental) add and subtract independently to produce total average power. Average power is defined as: True Power Factor
Power factor in the presence of harmonics is given
by: Phase sequence Harmonic Effects Harmonics-related problems on electric utility distribution systems are usually created by primary- metered customers. Typically, these problems are due to 500kVA (and larger) ASDs or induction heaters. In weaker systems, or near the end of long feeders, 100 – 200kVA nonlinear loads may be sufficiently large to create problems. The significant harmonics are almost always 5th, 7th, 11th, or 13th, with the 5th harmonic being the problem in most instances. Resonance Tripping of Sensitive Loads Some computer-controlled loads are sensitive to voltage distortion. Although it is difficult to find reliable data on this subject, one case documented showed that a THDV of 5.5% regularly shut down computerized lathes at a large pipe company heat treatment operation in Houston. While voltage distortions of 5% are not usually a problem, voltage distortions above 10% will cause significant nuisance tripping. Blown Capacitor Fuses, Failure of Capacitor Cells A common harmonics-related complaint comes from capacitor crew foremen or other distribution feeder maintenance personnel who complain that “a capacitor bank has to be rebuilt often, ”fuses on a capacitor bank blow regularly,” “a capacitor bank hums,” or “the capacitance of a bank is diminishing.” Harmonic voltages produce exaggerated harmonic currents in capacitors because of the inverse relationship between capacitor impedance and frequency. Capacitor Current Transformer Overheating There are two reasons for overheating. Losses in a conductor increase when harmonics are present because losses are in proportion to the square (at least) of rms current, and rms current increases with current distortion according to:
Because of the resistive skin effect, one ampere of
harmonic current produces more losses than does one ampere of fundamental current. Telephone Interference Telephone interference has been a harmonics-related concern for many decades, but the gradual phasing out of open-wire telephone circuits has reduced the number of interference problems. While the frequency response of the combined telephone circuit and human ear is largely Immune to 60 Hz interference, higher harmonics fall into the low- audio range. When harmonic currents on power lines inductively couple into nearby phone lines, they can cause significant interference. Motor Heating Harmonic voltages can create additional rotor winding currents and increase the I 2R winding losses in three-phase motors by several percent. High efficiency single-phase induction motors are more sensitive to voltage harmonics than are three-phase motors. The series auxiliary winding inductance and run capacitor create a series resonant path in the 4th – 11th harmonic range. Overloaded Neutral Conductors In a three-phase, four-wire system, the sum of the three phase currents returns through the neutral conductor. Positive and negative sequence components add to zero at the neutral point, but zero sequence components are additive at the neutral. Power system engineers are accustomed to the traditional rule that “balanced three-phase systems have no neutral currents.” However, this rule is not true when zero sequence harmonics (i.e., primarily the 3rd harmonic) are present. In commercial buildings with large numbers of PC loads, the rms neutral current can actually exceed rms phase currents. Neutral Current Harmonic Analysis
There are two major methods for
harmonic analysis: 1. Time domain method. 2. Frequency domain method. Fourier Transform
Fourier Series States:
Any physically realizable periodic waveform can be decomposed into a Fourier series of DC, fundamental frequency, and harmonic terms. In sine form, the Fourier series is:
The formulas for computing Idc , Ik , θk are well known.
Fourier Series Example Time domain method The system is represented by differential equations. The i-v characteristics of the nonlinear load is integrated with the system model. Time domain solution is obtained over a long period of time (4-6 cycles). Fourier Transform is applied to the obtained voltage and current waveforms to obtain the harmonic spectrum. RMS, THD and Power loss can be calculated using the obtained harmonic spectrum. Example consider the case shown in where a perfect 120Vac (rms) power system with 1Ω internal resistance supplies a triac controlled 1000W incandescent lamp. Let the firing angle is 90°, so the lamp is operating at half- power. Solution Power Calculations If a wattmeter is placed immediately to the left of the triac, the metered voltage is Frequency Domain analysis The nonlinear load is modeled as a current source at each harmonic frequency. The system is represented by a linear equivalent circuit. The circuit model is solved at each harmonic frequency with only the harmonic component of the same frequency exists. Superposition method is applied to obtain the overall harmonic content of the system. Performance measures The following functions can be evaluated using the obtained results: THDV RMSI PLoss The size of the required filters. Harmonic Reduction Techniques The most effective harmonic reduction techniques are as follows: Passive LC filters. Active filters. 3 – 5 % inductive reactance. Increase X/R ratio of the cable. Change transformer connection. Parallel connection of harmonic producing devices.