6.0004.0301-30 Suntrio Plus (12-60K) User Manual -2021-2-2-V3.3-20210703021400345-١
6.0004.0301-30 Suntrio Plus (12-60K) User Manual -2021-2-2-V3.3-20210703021400345-١
User Manual
SAJ Solar Inverter
Suntrio Plus Series
www.saj-electric.com
- 0 -
Suntrio Plus Series
Preface
- 1 -
Suntrio Plus Series
Content
Preface ......................................................................................... - 1 -
Content ........................................................................................ - 2 -
Chapter 1 Safety Precautions ................................................... - 4 -
1.1 Scope of Application .................................................................... - 4 -
1.2 Safety Instructions ....................................................................... - 4 -
1.3 Target Group ................................................................................ - 5 -
- 2 -
Suntrio Plus Series
- 3 -
Suntrio Plus Series
DANGER
· DANGER indicates a hazardous situation, which, if not avoided, will result in death
or serious injury.
WARNING
· WARNING indicates a hazardous situation, which, if not avoided, can result in
death or serious injury or moderate injury.
CAUTION
· CAUTION indicates a hazardous condition, which, if not avoided, can result in
minor or moderate injury.
NOTICE
· NOTICE indicates a situation that can result in potential damage, if not avoided.
- 4 -
Suntrio Plus Series
- 5 -
Suntrio Plus Series
Chapter 2 Preparation
DANGER
· Dangerous due to electrical shock and high voltage.
· Do not touch the operating component of the inverter, or it might result in burning
or death.
· To prevent risk of electric shock during installation and maintenance, please make
sure that all AC and DC terminals are plugged out.
· Do not touch the surface of the inverter while the housing is wet, or it might lead to
electrical shock.
· Do not stay close to the inverter while there are severe weather conditions
including storm, lighting, etc.
· Before opening the housing, the SAJ inverter must be disconnected from the grid
and PV generator; you must wait for at least five minutes to let the energy storage
capacitors fully be discharged after disconnecting from power source.
WARNING
·The installation, service, recycling and disposal of the inverters must be performed
by qualified personnel only in compliance with national and local standards and
regulations.
·Any unauthorized actions including modification of product functionality of any form
may cause lethal hazard to the operator, third parties, the units or their property.
SAJ is not responsible for the loss and these warranty claims.
·The SAJ inverter must only be operated with PV generator. Do not connect any
other source of energy to the SAJ inverter.
·Be sure that the PV generator and inverter are well grounded in order to protect
safety of people’s life and property.
CAUTION
·The PV inverter will become hot during operation. Please do not touch the heat
sink or peripheral surface during or shortly after operation.
- 6 -
Suntrio Plus Series
NOTICE
·Public utility only
·The PV inverter is designed to feed AC power directly to the public utility power
grid; do not connect AC output of the inverter to any private AC equipment.
- 7 -
Suntrio Plus Series
NOTICE, danger!
This is directly connected with electricity generators and public grid.
Without Transformer
This inverter does not use transformer for the isolation function.
CE Mark
Equipment with the CE mark fulfills the basic requirements of the
Guideline Governing Low-Voltage and Electro-magnetic Compatibility.
CQC Mark
The inverter complies with the safety instructions from China's Quality Center.
- 8 -
Suntrio Plus Series
- 9 -
Suntrio Plus Series
- 10 -
Suntrio Plus Series
- 11 -
Suntrio Plus Series
3.4 Datasheet
Suntrio Plus 12K/15K/17K/20K/25K
Suntrio Suntrio Suntrio Suntrio Suntrio
Type
Plus 12K Plus 15K Plus 17K Plus 20K Plus 25K
Input (DC)
Max. PV ArrayPower [Wp]@STC
1
18000 22500 25500 26000 37500
25000/2750
Max. AC Power [VA] 13200 16500 18700 22000
0
- 12 -
Suntrio Plus Series
- 13 -
Suntrio Plus Series
- 14 -
Suntrio Plus Series
1.1000W/m2 25℃
4.If you need more information about our product certifications, please contact our
sales.
- 15 -
Suntrio Plus Series
DANGER
· Dangerous to life due to potential fire or electricity shock.
· Do not install the inverter near any inflammable or explosive items.
· This inverter will be directly connected with HIGH VOLTAGE power generation
device; the installation must be performed by qualified personnel only in compliance
with national and local standards and regulations.
NOTICE
· This equipment is suitable for the pollution degree II.
· Inappropriate or unharmonized installation environment may jeopardize the life
span of the inverter.
· Installation directly exposed under intensive sunlight is not recommended.
· The installation site must have good ventilation condition.
- 16 -
Suntrio Plus Series
- 17 -
Suntrio Plus Series
if necessary.
To make sure the installation spot is suitably ventilated, if multiple SAJ
on-grid solar inverters are installed together, the following safety clearance
in Figure 4.2 shall be followed for proper ventilation conditions.
30CM
30CM
- 18 -
Suntrio Plus Series
120
348
508.5
400
- 19 -
Suntrio Plus Series
538
279.6
200.4
120
388
498
400
35
558
388
120 ∅8
324
261
- 20 -
Suntrio Plus Series
- 21 -
Suntrio Plus Series
- 22 -
Suntrio Plus Series
- 23 -
Suntrio Plus Series
DANGER
· Dangerous to life due to potential fire or electricity shock.
· When power-on, the equipment should be in conformity with national rules and
regulations.
· The direct connection between the converter and high voltage power systems
must be operated by qualified technicians in accordance with local and national
power grid standards and regulations.
- 24 -
Suntrio Plus Series
WARNING
·When the photovoltaic array is exposed to light, it supplies a d.c voltage to the
inverter.
NOTICE
- 25 -
Suntrio Plus Series
G DC Switch
Table 5.1 Specifications for Suntrio Plus-12/ 15/ 17/ 20K interface
- 26 -
Suntrio Plus Series
- 27 -
Suntrio Plus Series
- 28 -
Suntrio Plus Series
- 29 -
Suntrio Plus Series
NOTICE
·Please place the connector separately after unpacking in order to avoid confusion for
connection of cables.
·Please connect the positive connector to the positive side of the solar panels, and
connect the negative connector to the negative side of the solar side. Be sure to connect
them in right position.
Connecting Procedures:
1. Tighten the lock screws on positive and negative connector.
2. Use specified strip tool to strip off the insulated enclosure of the positive
and negative cables with appropriate length.
- 30 -
Suntrio Plus Series
3. Feed the positive and negative cables into corresponding lock screws.
4. Insert the positive and negative connectors into positive cable and
negative cable whose insulated enclosure has been stripped off, and crimp
them tightly with a wire crimper. Make sure that the withdrawal force of the
pressed cable is bigger than 400N.
5. Plug in the pressed positive and negative cables into relevant insulated
enclosure, a “click” sound should be heard when the contact cable assembly
is seated correctly.
6. Fasten the lock screws on positive and negative connectors into
respective insulated enclosure and make them tight.
7. Connect the positive and negative connectors into positive and negative
DC input terminals of the inverter, a “click” sound should be heard when the
contact cable assembly is seated correctly.
- 31 -
Suntrio Plus Series
1. Connection Port
NOTICE
·Before inserting the connector into the DC input terminal of the inverter, please
make sure that the DC switch of the inverter is OFF.
- 32 -
Suntrio Plus Series
1 N.C /
2 GND_W Ground
3 N.C /
4 N.C /
5 N.C /
6 N.C /
7 RS485-A
Transmit RS485 signal
8 RS485-B
- 33 -
Suntrio Plus Series
Object Description
Communication Yellow light blinking Sending data
A
status Blue light blinking Receiving data
The inverter has
Solid red
detected fault
The inverter is on-grid
Solid green
B Inverter status and running
The inverter is in
Off initializing state or count
downing for grid-tie
The power system of
C Power status Solid yellow inverter is operating
normally
D◀ Moves the cursor to the left
- 34 -
Suntrio Plus Series
Power
Please Set Time & Date 0 W
E-Today
Date: 09/23/2015
0.00 kWh
Time: 13:23:56
E-Total
0.00 kWh
T-Today
0.0 h
Ok Return
T-Total
0.0 h
Users can press Up, Down, Left, Right and ENT buttons to set local time and
confirm the selection. Then the inverter will display the interface for country
selection as shown in Figure 6.3:
Graph Setting Run-Info About
Country 1 Power
Australia Please set 0 W
Australia grid country
Belgium E-Today
Barzil
Demmark
0.00 kWh
Finland
France E-Total
Luxembourg 0.00 kWh
Netherland
T-Today
0.0 h
T-Total
0.0 h
Please press the "ENT" button, LCD will show the countries for option.
Users can press " " or" " to select the correct country and press "ENT"
- 35 -
Suntrio Plus Series
- 36 -
Suntrio Plus Series
Main Menu
Factory Reset
Change Password
PV Mode Setting
Exit
25.9
Exit 11.33 kWh
22.2
18.5 E-Total
LCD displays daily, monthly,
14.8 14.35 kWh
yearly and gross generating
11.1
T-Today
7.4 1.7 h capacity.
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
- 37 -
Suntrio Plus Series
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
RS232 address: 1
0 W Press ▼and▲to set the
RS232 Baud Rate: 115200 bit/s
E-Today communication address of
0.00 kWh
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
T-Today
0.0 h
Ok Return
T-Total
0.0 h
- 38 -
Suntrio Plus Series
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
T-Today
1.7 h
Ok Cancel
T-Total
4.6 h
Germany 0 W
Australia
Australia Then click OK to save the
Belgium E-Today
Barzil
Demmark
0.00 kWh changes.
Finland
France E-Total
Luxembourg 0.00 kWh
Netherland
T-Today
0.0 h
Return
T-Total
0.0 h
E-Today
25.9 Clear Energy 11.33 kWh
22.2 LCD Setting
18.5
Factory Reset E-Total
Change Password 14.35 kWh
14.8
PV Mode Setting
11.1 Exit T-Today
7.4 1.7 h
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
- 39 -
Suntrio Plus Series
Power
ENT to enter into “Clear Fault
1230W
Records”, click OK or return
Attention : If you click the button “Ok”, all E-Today
the Error records saved in the inverter will be 11.33 kWh back.
deleted permanently!
E-Total
14.35 kWh
T-Today
1.7 h
Ok Cancel
T-Total
4.6 h
T-Today
1.7 h
Ok Cancel
T-Total
4.6 h
- 40 -
Suntrio Plus Series
Power
ENT to enter into “Display
1230W
Settings”, and then press
LCD Backlight Time-out :
E-Today
11.33 kWh ▲and▼to change the sleep
30 Seconds E-Total time of LCD, click OK or return
14.35 kWh
back.
T-Today
1.7 h
Ok Cancel
T-Total
4.6 h
About
1. In the main LCD interface,
Graph Setting Run-Info
Communicate Set
Power
press “ENT” button, then
kW Language & Time
33.3 Grid Compliance
1230W
press ▶ to enter into “Setting”.
Factory Reset
T-Today
if you need password.
1.7 h
Ok Cancel
T-Total
Factory Reset
4.6 h
Power
changes.
1230W
Attention :If you click the button “Ok”,
all generated energy data and error records saved in E-Today
inverter will be deleted permanently! The password 11.33 kWh
and grid compliance etc. will be reset to factory
setting.
E-Total
14.35 kWh
T-Today
1.7 h
Ok Cancel
T-Total
4.6 h
- 41 -
Suntrio Plus Series
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
T-Today
if you need password.
1.7 h
Ok Cancel
T-Total
4.6 h
1230W
E-Total
0 0 0 0 0 0
14.35 kWh
T-Today
1.7 h
Ok Cancel
T-Total
4.6 h
1230W
33.3
29.6
Grid Compliance
Clear Error
press ▶ to enter into
E-Today
Clear Energy
25.9
22.2 LCD Setting
11.33 kWh “Setting”.
18.5
Factory Reset E-Total
Change Password 14.35 kWh
14.8
PV Mode Setting
11.1 Exit T-Today
7.4 1.7 h
3.7
0 T-Total
3 5 7 9 11 13 15 17 19 21h 4.6 h
- 42 -
Suntrio Plus Series
Power
to enter into “PV Mode
1230W
Setting”. Press▲and ▼to
PV Mode Setting E-Today
11.33 kWh choose PV mode.then choose
1
E-Total
14.35 kWh
to confirm.
PV Independent
- 43 -
Suntrio Plus Series
Ufp2(81<.S2)test
Return T-Total appears when the grid
ALL test 4.6 h
is under normal
grid-connected state.
- 44 -
Suntrio Plus Series
Power
press “ENT” button to enter
<Ovp(59.S2)test>
1230W into setting.
E-Today
11.33 kWh
Start Test E-Total
14.35 kWh
View Results
T-Today
Return 1.7 h
T-Total
4.6 h
Power
1230W
<Ovp(59.S2)test>
E-Today
11.33 kWh
Testting,please wait. . .
E-Total
14.35 kWh
T-Today
Return 1.7 h
T-Total
4.6 h
- 45 -
Suntrio Plus Series
Ovp(59.S2)test Power
“Ovp10(59.S1)test” and
of average voltage
1230W
Ovp10(59.S1)test press “ENT” button to enter
Uvp(27.S1)test E-Today
Uvp2(27.S2)test
11.33 kWh into setting.
Ofp(81>.S1)test E-Total Note: Follow the operation
14.35 kWh
Ofp2(81>.S2)test steps in item 1 to start test
T-Today
Ufp(81<.S1)test 1.7 h and view results.
Ufp2(81<.S2)test
Return T-Total
ALL test 4.6 h
Uvp(27.S1)test E-Today
Uvp2(27.S2)test
11.33 kWh into setting.
Ofp(81>.S1)test E-Total Note: Follow the operation
14.35 kWh
Ofp2(81>.S2)test steps in item 1 to start test
T-Today
Ufp(81<.S1)test 1.7 h and view results.
Ufp2(81<.S2)test
Return T-Total
ALL test 4.6 h
Ovp(59.S2)test Power
“Ufp(81>.S1)test” and
1230W
Ovp10(59.S1)test press “ENT” button to enter
Uvp(27.S1)test E-Today
Uvp2(27.S2)test
11.33 kWh into setting.
test
- 46 -
Suntrio Plus Series
“Ufp2(81>.S2)test” and
Ovp(59.S2)test Power
Ovp10(59.S1)test 1230W press “ENT” button to enter
protection test
Uvp(27.S1)test E-Today
11.33 kWh
into setting.
Uvp2(27.S2)test
E-Total
Note: Follow the operation
Ofp(81>.S1)test
Ofp2(81>.S2)test
14.35 kWh
steps in item 1 to start test
T-Today
Ufp(81<.S1)test 1.7 h and view results.
Ufp2(81<.S2)test
Return T-Total
ALL test 4.6 h
Ovp(59.S2)test Power
“Ufp(81<.S1)test” and
Under-frequency
1230W
Ovp10(59.S1)test press “ENT” button to enter
protection test
Uvp(27.S1)test E-Today
11.33 kWh into setting.
Uvp2(27.S2)test
Ofp(81>.S1)test E-Total Note: Follow the operation
14.35 kWh
Ofp2(81>.S2)test steps in item 1 to start test
T-Today
Ufp(81<.S1)test 1.7 h and view results.
Ufp2(81<.S2)test
Return T-Total
ALL test 4.6 h
Uvp2(27.S2)test
Ofp(81>.S1)test E-Total
14.35 kWh
Note: Follow the operation
Ofp2(81>.S2)test steps in item 1 to start test
T-Today
Ufp(81<.S1)test
Ufp2(81<.S2)test
1.7 h
and view results.
Return T-Total
ALL test 4.6 h
autotest.
3. When test is completed,
results will be viewed from
item 1.
Attention:
1. If any item is not tested, results will be as below:
Power
1230W
<Ovp(59.S2)test>
E-Today
11.33 kWh
No Result!
E-Total
14.35 kWh
T-Today
1.7 h
Next Return
T-Total
4.6 h
Power
1230W
<Ovp(59.S2)test>
E-Today
11.33 kWh
Test failed!
E-Total
14.35 kWh
T-Today
1.7 h
Next Return
T-Total
4.6 h
- 48 -
Suntrio Plus Series
- 49 -
Suntrio Plus Series
- 50 -
Suntrio Plus Series
- 51 -
Suntrio Plus Series
- 52 -
Suntrio Plus Series
- 53 -
Suntrio Plus Series
- 54 -
Suntrio Plus Series
Postcode: 510663
International Sales
E-mail: [email protected]
Domestic Sales
Tel: 020-66600058/66608588
Fax: 020-66608589
- 55 -
Suntrio Plus Series
Extension of Warranty
The purchaser of SAJ inverters (Sununo-TL Series inverters & Suntrio-TL
Series inverters and Sununo Plus Series inverters & Suntrio Plus Series
inverters) should extend the warranty period in 18 months from the date of
settlement or 30 months from the date of shipment from SAJ by providing the
serial number of the unit and purchased receipt (whichever is shorter). You
can purchase the warranty extension for 10 years, 15 years, 20 years or 25
years but do not apply the extension beyond the specified date, or else your
application will be unacceptable. Please refer to the Warranty Extension
Order Form for more details.
Once the purchase of the warranty extension goes into effect, SAJ will send
the warranty extension certificate to the customer for confirming the
extended warranty period.
Warranty Conditions
If your inverter gets fault and requires troubleshooting, please contact your
distributor or dealer directly. Alternatively, feedback briefly to SAJ service
hotline for logging and send your warranty card to our service department by
- 56 -
Suntrio Plus Series
(e.g.22030G1825EN00001)
After receiving above information, SAJ will decide how to proceed the
service
- 57 -
Suntrio Plus Series
the closest SAJ Service Center by packing in its original package if possible.
■ On-site attendance fee: Cost of travel and time for the technician in
attending on-site.
■ Parts: Cost of replacement parts (including any shipping/admin fee that
may apply).
■ Labor: Labor time fee charged for the technician, who is repairing,
maintaining, installing (hardware or software) and debugging the faulty
product.
■ Logistic fee: Cost of delivery, tariff and other derived expense when
defective products are sent from user to SAJ or/and repaired products are
sent from SAJ to user.
Exclusion of Liability
- 58 -
Suntrio Plus Series
Any defect caused by the following circumstances will not be covered by the
manufacturer’s warranty (the Dealers or Distributors are responsible and
authorized by SAJ for the following investigation):
- 59 -
Suntrio Plus Series
- 60 -
Suntrio Plus Series
Warranty Card
The installer should fill in the second form while installing the inverter. For
warranty claim, please complete the below forms and send this page to SAJ
attached with the Customer’s invoice.
Name:
Information on Device
Device type: Serial No.(S/N):
Fault time:
Signature: Date:
- 61 -
Suntrio Plus Series
Company:
Signature: Date:
- 62 -
Suntrio Plus Series