Air cooled screw chillers


ALS 081.2÷142.2 (Energyplus)
Standard Efficiency – Cooling capacity from 300 to 525 kW
High Efficiency – Cooling capacity from 323 to 546 kW
High Ambient – Cooling capacity from 318 to 540 kW
50Hz – Refrigerant: HFC 134a
New air cooled screw chillers McQuay ALS
McQuay International introduces their newest air cooled screw chillers equipped with new single screw
compressors, the first in cooling capacity range 300 kW – 550 kW.
McQuay air cooled ALS are a new range of chillers using the last generation of McQuay Frame 3200 single screw
compressors. They are manufactured by McQuay to satisfy the requirements of the consultants and the end user.
McQuay ALS units are designed to minimise energy costs while maximising the refrigeration capacities. Once
again McQuay has developed a line of chillers unsurpassed in performance and quality that will meet the most
stringent requirements of comfort cooling, ice storage and process applications.
McQuay’s chiller design experience, combined with outstanding features makes the ALS chiller unmatched in the
industry.

Lower noise – higher flexibility


The McQuay original compressor design with a single screw and twin rotors allows a constant gas flow. This
compression process completely eliminates gas pulsations.
The twin gas compressor discharge chambers are designed to act as attenuators, based on the harmonic wave
principle with destructive interference, thus always resulting almost equal to zero. The extremely low noise
compressor performance allows the use of ALS chiller for all applications.
The reduced level of vibrations produced from the ALS chillers offers a surprisingly quiet operation eliminating the
noise transmission through the structure and the chilled water piping system.

Code requirements
All ALS units are designed and manufactured in accordance with applicable selections of the following which are
equivalent to American Air-conditioning industry applicable codes:
Rating of chillers: EN 12055.
Construction of pressure vessel: TUV Standards (on request).
Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety Codes
Safety Codes: CEI-EN 60204–1 Codes.
Manufacturing Quality Stds: ISO 9001.

Infinitely variable capacity control


Cooling capacity control is infinitely variable by means of a capacity slide controlled by microprocessor system.
Each unit has infinitely variable capacity control from 100% to 12.5%. This modulation allows the compressor
capacity to exactly match the building cooling load. The result is a decrease in chiller energy costs, particularly at
the part-load conditions at which the chiller operates most of the time.
Additionally, in some case there should be the possibility to avoid inertial tank in the water circuit.

11 different lines
ALS 3200 line is available with two different efficiencies in order to satisfy every kind of requirements.
Acoustic flexibility up to 65 dBA thanks to different noise level versions:
• SE Standard Efficiency
- ST Standard noise – 79,0 ÷ 80,0 dBA
- CN Sound proof cabinet on compressors – 77,0 ÷ 78,0 dBA
- LN Low noise – 75,0 ÷ 76,0 dBA
- XN Extra low noise – 71,0 ÷ 72,0 dBA
- XXN Super quiet – 65,0 dBA

• XE High Efficiency with high COP


- ST Standard noise – 79,0 ÷ 80,0 dBA
- CN Sound proof cabinet on compressors – 77,0 ÷ 78,0 dBA
- LN Low noise – 75,0 ÷ 76,0 dBA
- XN Extra low noise – 71,0 ÷ 72,0 dBA

507 B – 03/05 E – pag. 2/32


HA High Ambient Applications (suitable for all high ambient application)
- ST Standard noise – 79,0 ÷ 80,0 dBA
- CN Sound proof cabinet on compressors – 77,0 ÷ 78,0 dBA

Noise version description


CN - The compressors are fitted inside a cabinet which is sound insulated with highly absorbent acoustic material.
LN – Condenser fans rotating at 700 rpm. No sound proof cabinet. Discharge flexible pipes.
XN – Version including sound proof cabinet, fans having 700 rpm and discharge flexible pipes.
XXN – Version including sound proof cabinet, fans having 500 rpm and discharge flexible pipes. Some sizes are
equipped with oversized condensing section.

Unmatched serviceability
Field serviceability has not been sacrificed. Inspection covers allows visual inspection of the main screw and
gaterotors.

Outstanding reliability features


Full factory testing of all the units ensures a trouble free start-up. Extensive test makes certain that each safety
and operating control is properly adjusted, and operates correctly.

General characteristics
Cabinet and structure
The cabinet of ALS units is made of galvanized steel sheet and painted to provide a high resistance to corrosion. The
unit base frame has holes to lift the unit with ropes for an easy installation. The weight is uniformly distribuited along the
profiles of the base and this facilitates the arrangement of the unit.

Screw compressors with integrated oil separator


The newest StargateTM single-screw compressor (Frame 3200) has a well balanced compression mechanism
which cancels the screw rotor load in both the radial and axial directions. Inherent to the basic single-screw
compressor design is the virtually load-free operation, that gives main bearing design life of 3-4 times greater than
twin-screws, and eliminates expensive and complicated thrust balancing schemes. The two exactly opposed
gaterotors create two exactly opposed compression cycles. Compression is made at the lower and upper parts of
the screw rotor at the same time, thus cancelling the radial loads. Also, both ends of the screw rotor are subjected
to suction pressure only, which cancels the axial loads and eliminates the huge thrust loads inherent in twin-screw
compressors.
Compressors are provided with an integrated high efficiency oil separator to maximise oil separation. Compressors
have an infinitely variable capacity control down to 25% of its total capacity. This control is made by means of
capacity slides controlled by microprocessors.
Standard start is star-delta type; Soft start type is available (as option) in order to have lower inrush current.

Ecological HFC 134a refrigerant


As the HCFC phase out will occur more quickly than currently legislated, the designers, owners and operators
should only evaluate equipment using chlorine free refrigerants. McQuay has designed and optimized new
StargateTM compressors to operate with HFC 134a, ecological refrigerant with zero ODP (Ozone Depletion
Potential) and very low GWP (Global Warming Potential) that means low TEWI (Total Equivalent Warming
Impact).

Evaporator
The units is supplied with new optimised counter-flow evaporator single refrigerant pass. It is direct expansion
with refrigerant inside the tubes and water outside (shell side) with carbon steel tube sheets, with straight copper
tubes that are spirally wound internally for higher efficiencies, expanded on the tube plates. The external shell, is
linked with an electrical heater to prevent freezing down to -28 °C ambient temperature, commanded by a
thermostat and is covered with a closed cell insulation material. Each evaporator have 2 refrigerant circuits one for
each compressor. Each evaporator is manufactured in accordance to PED approval.

507 B – 03/05 E– pag. 3/32


Condenser coils
The new ALS units are constructed with internally enhanced seamless copper tubes arranged in a staggered row
pattern and mechanically expanded into McQuay lanced and rippled aluminium condenser fins with full fin collars.
An integral subcooler circuit provides sub-cooling to effectively eliminate liquid flashing and increases in cooling
capacity without increasing the power input.

Condenser coil fans


The condenser fans are helical type with wing-profile blades to achieve a better performance. The direct coupling
with the electrical motor eliminates any problems with regard to the application of transmission devices reducing
vibrations caused by the functioning. The three-phase type motors are supplied as standard with IP54 protection
(Insulation class F); they are protected against overloading and short circuits by circuit breakers located inside the
electrical control panel.

Electronic expansion valve


ALS air cooled chiller is equipped with the most advanced electronic expansion valve to achieve precise control of
refrigerant mass flow. As today’s system requires improved energy efficiency, tighter temperature control, wider
range of operating conditions and incorporate new features like remote monitoring and diagnostics, the application
of electronic expansion valves becomes mandatory. ALS’s electronic expansion valve proposes features that
makes it unique: short opening and closing time, high resolution, positive shut-off function to eliminate use of
additional solenoid valve, highly linear flow capacity, continous modulation of mass flow without stress in the
refrigerant circuit and corrosion resistance stainless steel body.

Electrical control panel


Power and control are located into two sections of the main panel that is manufactured to insure protection for all
weather conditions.
The power panel is fitted with an interlocked door main isolator to prevent access while power supply is on.
Electrical panel is IP54.
Power section includes - The power section includes contactors, all compressors fuses, fans circuit breaker
(magneto-thermal), and control circuit transformer. Additional space is provided for an easy installation of the
various optional accessories provided to enhance the ALS units capabilities.

Intelligent Compressor Start Mode


Control software includes an intelligent compressor start mode that is unloading the first compressor to 75% during
the start of compressor n° 2, in order to reduce inrush current.

Certifications
All the ALS units are CE marked (89/392). McQuay Italia obtained ISO 9001 certification in 1997.

Water content in cooling circuits


The cooled water distribution circuits should have a minimum water content to avoid excessive compressors start
and stop.
In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressor sump and
simultaneously there is a rise in the temperature of the compressor motor’s stator due to the inrush current during
the start-up. To prevent damage to the compressors, McQuay has envisaged the application of a device to limit
frequent stops and restarts.
During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore
ensure that the overall water content allows a more constant functioning of the unit and consequently greater
environmental comfort. The minimum installation water content envisaged should be calculated with a certain
approximation using this simplified formula:

P (kW) 1
(1) Q = 35,83 X X
∆T(°C) N

where:
Q = Minimum content of the plant expressed in litres
P = Cooling capacity of the plant expressed in kW

507 B – 03/05 E – pag. 4/32


∆T = Entering/leaving water temperature difference of the evaporator expressed in °C
N = Number of compressors.

For a more accurate determination of the quantity of water, it is advisable to contact the designer of the plant.

MicroTech II C Plus controller


MicroTech II C Plus controller is installed as standard on all the units; it can be used to modify unit set points and
check control parameters. A display illustrates the machine's operating status, programable values and setpoints
e.g. temperatures, and pressures of fluids (water, refrigerant and air). Device controls maximise the McQuay
chillers energy efficiency and reliability characteristics. It uses sophisticated software with predictive logic to select
the most energy efficient combination of compressor, EEXV and condenser fan to keep stable operating conditions
and maximise energy efficiency. The compressors are automatically rotated to ensure equal operating hours.
MicroTech II protects critical components in response to external signals from its system sensors measuring:
motor temperatures, refrigerant gas and oil pressures, correct phase sequence and evaporator.

Control section - main features:


• Management of the compressor capacity slide and fans modulation according to the distributed
multiprocessor logic system
• Chillers enabled to work in partial failure condition thanks to the distributed multiprocessor logic system
• Full routine operation at condition of:
- High ambient temperature value
- High thermal load
- High evaporator entering water temperature (start-up)
• Display of evaporator entering/leaving water temperature
• Display of condensing-evaporating temperature and pressure, suction and discharge superheat for each
circuit
• Leaving water cooled temperature regulation. Temperature tolerance=0,1°C
• Compressors and evaporator/condenser pumps hours counter
• Display of Status Safety Devices
• Start up numbers and compressors working hours equalization
• Excellent management of compressors load
• Fans management according to condensing pressure
• Automatic re-start in case of power supply interruption (adjustable)
• Soft Load
• Return Reset
• AOT Reset
• Setpoint Reset
• Demand limit or Current limit (optional)
• Speedtrol control (optional)

Safety for each refrigerant circuit


High pressure (pressure switch)
Low pressure (pressure switch)
Oil differential pressure switch
Compressor thermal (optional)
Condensation fan Magneto-thermal
High Discharge Temperature on the compressor
Phase Monitor
Star / Delta Transition Failed
Low Delta Pressure between Suction and Discharge

507 B – 03/05 E– pag. 5/32


Low pressure ratio
High oil pressure drop
Low oil pressure

System security
Phase monitor
Freeze protection

Regulation type
Proportional + integral + derivative regulation on the leaving water evaporator output probe.

Condensation
The condensation can be carried out according to temperature or pressure. The fans can be managed according
to ON/OFF mode or with a 0/10 V modulating signal or both (SPEEDTROL).

MicroTech II C Plus terminal


The MicroTech II C Plus terminal has following features:
• 4-lines by 20-character liquid crystal display back lighting
• Removable and remote key-pad
• Key-pad consisting of 15 keys “ clear language display ”
• Memory to protect the data
• General faults alarm relays
• 4-level password access to modify the setting
• Service report displaying all running hours and general conditions
• Alarm history memory to allow an easy fault analysis

MicroPlantTM:
Solution for: tele-maintenance and supervisory systems

MicroTech II can be monitored locally or via modem by MicroPlantTM supervision program, that runs on PC
systems under Windows ’95 – ’98.

MicroPlantTM is the best solution:


• To centralise all the information in just one local and/or remote PC
• To check all the parameters for each unit connected
• Data logging of temperature - pressure
• Printouts of alarms, parameters and graphs
• To control several plants located in different geographical areas from a
central station
• To manage the Service centers

MicroPlantTM allows:

• Visualization of all working conditions for each controller


• Visualization of their graphics
• Display, print-out of the actual alarms
• Connection between local and remote computer via telephone line
(Modem)
• unit ON/OFF
• Set-Point change

507 B – 03/05 E – pag. 6/32


MicroTech II C Plus remote control

Compatibility with supervisory systems is becoming


increasingly important in HVAC. MicroTech II C Plus
allows easy interfacing with BMS (Building
Management Systems), the external world that
can be:

• Full compatible Siemens, Johnson;


• Every MODBUS compatible system;
( Satchwell, Honeywell )
• BacNet point to point, ECHELON FTT10.
( available on request )

Standard Accessories (furnished on basic unit)


Star Delta Compressors starter – For low inrush current and reduced starting torque.
Phase monitor – The phase monitor controls that phases sequence is correct and controls phase loss
Evaporator electric heater – Electric heater controlled by a thermostat to protect the evaporator from freezing
down to -28°C ambient temperature.
Evaporator connection water side Victaulic – Hydraulic joint with gasket for an easy and quick water
connection.
General fault relay – Contactor for the alarm warning.
Brine double set point version (CB) - Dual leaving glycol mixture temperature setpoints. The lower setpoint can
go down to -8°C.
Discharge line shut off valves – Installed on the discharge port of the compressor.
External high static pressure fans – For all the applications where a higher fans lift is required (not available for
XXN version – see table 8 and 9, pag.11). This feature is valid only when fans run at full speed.
Alarm from external device – Microprocessor is able to receive an alarm signal from an external device (pump
etc…). User can decide if this alarm signal will stop or not the unit.

Options (on request)


100% total heat recovery R – Realized with shell and tube heat exchangers to produce hot water up to 55°C. The
heat exchangers are mounted on the refrigerant circuits parallel to the condenser coils to remove all the
condensation heat. With this option the length of units equipped with 4,6 and 8 fans must be increased of
1250mm. For units equipped with 10 fans the length remains unchanged.
25% partial heat recovery D – Produced with plate to plate heat exchangers installed between the compressor
discharge and the condenser coil. These allow hot water to be produced up to a maximum temperature of 55°C.
Compressor thermal overload relays - Safety devices against compressor motor overloading in addition to the
normal protection envisaged by the electrical windings.
Ammeter and voltmeter - Digital meters of unit drawn amperes and voltage values, installed on the electrical
control panel.
Condenser power factor correction - Installed on the electrical control panel to ensure it conforms to the plant
rules. (McQuay advices maximum 0,9).
Absorbed Current Limit / Display – This options allows to monitor the chiller absorbed current with possibility to
set a limit value. This option excludes the Demand Limit.
250 Pa lift fans – For all the applications where a higher fans lift is required (not available for LN, XN and
XXN version).(Fan speed controller not available with this option)

507 B – 03/05 E– pag. 7/32


Fan speed control device - This device allows the continuous variation of the fan speed, modifying the air flow
according to the external temperature conditions. It allows the unit working with air temperature down to –18°C.
Speedtrol – Continous fan speed modulation on the first fan of each circuit. It allows the unit working with air
temperature down to -20 °C.
Fan Silent Mode - The microprocessor clock switches the fan at low speed according to the client setting (i.e.
Night & Day), providing that the ambient temperature/condensing pressure is allowing the speed change. It allows
a perfect condensing control down to –18°C
Condenser coil guards - Metal protection guards fixed on all the external surface of the condenser coils.
Evaporator area guards – Metal protection guards around evaporator area.
Cu-Cu condensing coils - To give better protection against corrosion by aggressive environments.
Cu-Cu-Sn condensing coils - To give better protection against corrosion in aggressive environments and by salty
air.
Alucoat condensing coils - Fins are protected by a special acrylic paint with a high resistance to corrosion.
Flow switch - Supplied separately to be wired and installed on the evaporator water piping (by the customer).
Suction line shut off valve – Suction shut-off valve installed on the suction port of the compressor to facilitate
maintenance operation.
Spreader bars - Facilitate the lifting of the units keeping the ropes away from the unit's casing.
Under/Over Voltage – This device control the voltage value and stop the chiller when this exceeds limits set by
customer.
Rubber type antivibration mounts - Supplied separately, these are positioned under the base of the unit during
installation. Ideal to reduce the vibrations when the unit is floor mounted.
Spring type antivibration mounts - Supplied separately, these are positioned under the base of the unit during
installation. Ideal for dampening vibrations for installation on roofs and metallic structures.
Soft start – Electronic starting device to reduce inrush current and to start compressors gradually, with very low
mechanical stress. An overload protection is included (no need of compressors thermal relays).
Witness tests - Every unit is always tested at the test bench prior to the shipment. On request, a second test can
be carried out, at customer’s presence, in accordance with the procedures indicated on the test form. (Not
available for units with Glycol mixtures).
Water circulation pump – The pump is unit mounted for chillers with 6,8 and 10 fans. Hydronic kit consists of:
one centrifugal pump direct driven, expansion tank, water feed circuit with pressure gauge, safety valve. The pump
motor is protected by a circuit breaker installed in control panel. The kit is assembled and wired to the control
panel. About units with 4 fans (ALS 081.2 SE ST / CN – ALS 081.2 SE LN / XN) pump is mounted on a metal base
frame (1000 x 1000 mm) placed on unit shorter side (that without panel control). See pag. 28 for more information.
Two water circulation pumps – Pumps units are unit mounted for chillers with 6,8 and 10 fans. Hydronic kit
consists of: two centrifugal pumps direct driven, expansion tank, water feed circuit with pressure gauge, safety
valve, check valves, shut-off valves. The pumps motors are protected by circuit breakers installed in control panel.
The kit is assembled and wired to the control panel. About units with 4 fans (ALS 081.2 SE ST / CN – ALS 081.2
SE LN / XN) pumps are mounted on a metal base frame (1000 x 1000 mm) placed on unit shorter side (that
without panel control). See pag. 28 for more information.

Installation notes
Handling
Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from
anything other than the base, and block the pushing vehicle away from the unit to prevent damage to the cabinet.
Never allow the unit fall during unloading or moving as this may result in serious damage. To lift the unit, holes are
provided in the base of the unit. Spreader bar and cables should be arranged to prevent damage to the condenser
coil or unit cabinet.

Location
The ALS units are produced for outside installation on roofs, floors or below ground level on condition that the area
is free from obstacles for the passage of the condenser air. The unit should be positioned on solid foundations and

507 B – 03/05 E – pag. 8/32


perfectly level; in the case of installation on roofs or floors, it may be advisable to arrange the use of suitable
weight distribution beams. When the units are installed on the ground, a concrete base at least 250 mm wider and
longer than the unit’s footprint should be laid. Furthermore, this base should withstand the unit weight mentioned in
the technical data table. When the units are positioned in areas which are easily accessible by persons or animals,
it is advisable to fit guards to protect the condenser coil guards and, when necessary, also guards to protect the
evaporator area.

Space requirements
The ALS units are air-cooled, hence it is important to observe the minimum distances which guarantee the best
ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in
cooling capacity and an increase in electricity consumption.
To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the
condenser heat transfer surface. Two conditions must be avoided to achieve the best performance: warm air
recirculation and coil starvation.
Both these conditions cause an increase of condensing pressures that results in reductions in unit efficiency and
capacity. The ALS chiller performance is less affected in poor air flow situations because of its special condensing
coil geometry.
Moreover McQuay’s unique microprocessor has the ability to calculate the operating environment of the chiller and
the capacity to optimize its performance staying on-line during abnormal conditions.
Each side of the unit must be accessible after installation for periodic service. Fig.1 shows you minimum
recommended clearance requirements.
Vertical condenser air discharge must be unobstructed because the unit would have its capacity and efficiency
significantly reduced.
If the units are positioned in places surrounded by walls or obstacles of the same height as the units, the units
should be at least 2500 mm from obstacles (fig.2). In the event the obstacles are higher than the units, the units
should be at least 3000 mm from the obstacle (fig.4). Units installed closer than the minimun recommended
distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation,
thus causing reduction in unit capacity and efficienty reductions. Once again, the microprocessor will allow the
chiller to stay on line, producing the maximum available capacity, even at less than recommended lateral
clearances.
When two or more units are positioned side by side it is recommended that the condenser coils are at least 3600
mm distance from one another (fig.3); stong wind could be the cause of air warm recirculation.
For other installation solutions, consult McQuay technicians.

507 B – 03/05 E– pag. 9/32


Acoustic protection
The low noise levels of the ALS units means that they meet the most restrictive regulations, thanks to the
availability of four versions with different sound levels. When the noise level must meet special requirements it will
be necessary to pay the maximum attention to ensure the perfect insulation of the unit from the support base by
applying appropriate vibration-dampening devices, applying vibration-dampening mounts on the water pipes and
on the electrical connections.

Table 1 – Operating limits – ALS SE


Unit version ST/CN LN XN XXN
Max ambient temperature °C + 45 + 40 + 40 + 40
Min ambient temperature (1) °C + 10 +5 + 5 +5
Max entering evaporator water temperature °C + 20 + 20 + 20 + 20
Min leaving evap. water temp.(without glycol) °C +4 +4 +4 +4
Min leaving evap. water temp.(with glycol) °C -8 -8 -8 -8
Max evaporator ∆T °C 8 8 8 8
Min evaporator ∆T °C 4 4 4 4
Note: (1) When air temperature is lower then +10°C (ST – CN) or +5°C (LN – XN – XXN) you need the fan speed control
device. It allows the unit working with air temperature down to –18°C.

Table 2 – Operating limits – ALS XE


Unit version ST/CN LN XN
Max ambient temperature °C + 50 + 45 + 45
Min ambient temperature (1) °C + 10 +5 +5
Max entering evaporator water temperature °C + 20 + 20 + 20
Min leaving evap. water temp.(without glycol) °C +4 +4 +4
Min leaving evap. water temp.(with glycol) °C -8 -8 -8
Max evaporator ∆T °C 8 8 8
Min evaporator ∆T °C 4 4 4
Note: (1) When air temperature is lower then +10°C (ST – CN) or +5°C (LN – XN) you need the fan speed control device. It
allows the unit working with air temperature down to –18°C.

Table 3 – Operating limits – ALS HA


Unit version ST/CN
Max ambient temperature °C + 50
Min ambient temperature °C + 10
Max entering evaporator water temperature °C + 20
Min leaving evap. water temp.(without glycol) °C +4
Min leaving evap. water temp.(with glycol) °C -8
Max evaporator ∆T °C 8
Min evaporator ∆T °C 4

Table 4 – Evaporator fouling factors


Fouling factors Cooling capacity Power input COP
m2°C / kW correction factor corretion factor correction factor
0,0176 1,000 1,000 1,000
0,0440 0,978 0,986 0,992
0,0880 0,957 0,974 0,983
0,1320 0,938 0,962 0,975

507 B – 03/05 E – pag. 10/32


Table 5 – Altitude correction factors
Elvation above sea level (m) 0 300 600 900 1200 1500 1800
Barometric pressure (mbar) 1013 977 942 908 875 843 812
Cooling cap.correction factor 1,000 0,993 0,986 0,979 0,973 0,967 0,960
Power input correction factor 1,000 1,005 1,009 1,015 1,021 1,026 1,031

Table 6 – Ethylene glycol and low ambient temperature correction factors


Air ambient temperature °C -3 -8 -15 -23 -35
% of ethylene glycol by weight 10 20 30 40 50
Cooling capacity correction factor 0,991 0,982 0,972 0,961 0,946
Power input correction factor 0,996 0,992 0,986 0,976 0,966
Flow rate correction factor 1,013 1,040 1,074 1,121 1,178
Water pressure drops correction factor 1,070 1,129 1,181 1,263 1,308

Table 7 – Low temperature operation performance factors


Ethylene glycol/water leaving temperature °C 2 0 -2 -4 -6 -8
Max air ambient temperature °C (SE-ST) 40 39 38 37 36 35
Max air ambient temperature °C (XE-ST) 44 43 42 41 40 39
Cooling capacity correction factor 0,842 0,785 0,725 0,670 0,613 0,562
Power input compressors correction factor 0,95 0,94 0,92 0,89 0,87 0,84
Min. % of ethylene glycol 10 20 20 30 30 30
Low temperature operation performance factors must be applied to the nominal performance data to have the adjusted value
(12/7°C, design ambient temperature).

507 B – 03/05 E– pag. 11/32


Performance Correction Factor for External High Static
Pressure Application

Table 8 – Correction Factor for ALS Unit ST / CN version (SE & XE & HA) with fan
80CC/6/7 900 RPM
External static
10 20 30 40 50 60 70 80 90 100 120 Pa
pressure

Cooling capacity 0.997 0.993 0.990 0.985 0.981 0.976 0.972 0.966 0.961 0.953 0.935

Power input 1,004 1.007 1,012 1,016 1,020 1,025 1,031 1,036 1,042 1,050 1,068

MAX allowed
Ambient 44,7 44,5 44,1 43,8 43,4 43,0 42,6 42,2 41,7 41,1 39,6 °C
Temperature (SE)
MAX allowed
Ambient 49,7 49,5 49,1 48,8 48,4 48,0 47,6 47,2 46,7 46,1 44,6 °C
Temperature (XE)

Table 9 – Correction Factor for ALS Unit LN / XN version (SE & XE) with fan
80CC/6/7 700 RPM
External static
10 20 30 40 50 60 Pa
pressure

Cooling capacity 0.992 0.982 0,972 0,961 0,948 0,935

Power input 1,008 1,017 1,026 1,036 1,047 1,059

MAX allowed
Ambient 40,4 39,7 38,9 38,0 37,0 35,8 °C
Temperature (SE)
MAX allowed
Ambient 45,4 44,7 43,9 43,0 42,0 40,8 °C
Temperature (XE)

507 B – 03/05 E – pag. 12/32


Nomenclature

ALS XE 101 . 2 LN 134


ALS Air cooled screw chiller

SE Standard Efficiency
XE High Efficiency
HA High Ambient

081÷142 Unit size

2 N° of compressors

ST Standard version
CN Sound proof cabinet around compressors
LN Low noise version
XN Extra low noise version
XXN Super quiet

134 Refrigerant HFC 134a

507 B – 03/05 E– pag. 13/32


Physical data ALS SE ST / CN HFC 134a
ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Cooling capacity (1) kW 301,1 347,0 370,7 408,0 452,0 524,8
Power input (1) kW 114,6 117,5 131,1 147,2 164,4 173,4
COP 2,63 2,95 2,83 2,77 2,75 3,02
McQuay Screw compressors No. 2 2 2 2 2 2
Refrigerant circuits No. 2 2 2 2 2 2
Refrigerant charge HFC 134a kg 70 70 80 80 100 100
Oil charge l 20 20 20 20 20 20
Min % of capacity reduction % 12,5% 12,5% 12,5% 12,5% 12,5% 12,5%
Condenser fans
No. of fans / nominal power fan kW 4 / 1,6 6 / 1,6 6 / 1,6 6 / 1,6 6 / 1,6 8 / 1,6
Fan speed rpm 900 900 900 900 900 900
Diameter mm 800 800 800 800 800 800
Total air flow m3/s 21,7 33,8 33,8 33,2 32,6 45,0
Evaporator
Evaporators / water volume No./l 1 / 198 1 / 181 1 / 181 1 / 181 1 / 227 1 / 273
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 139,7 139,7 139,7 139,7 139,7 139,7
Condenser coil
Coil type Lanced fins – Internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 3250 3515 3515 3515 3565 3895
Standard unit shipping weight ( CN ) kg 3510 3775 3775 3775 3825 4195
Standard unit operating weight kg 3448 3696 3696 3696 3792 4168
Standard unit operating weight ( CN ) kg 3708 3956 3956 3956 4052 4468
Unit length mm 2790 3460 3460 3460 3460 4355
Unit width mm 2225 2225 2225 2225 2225 2225
Unit height mm 2500 2500 2500 2500 2500 2500

Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.

Electrical data ALS SE ST / CN HFC 134a


ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 201 205 223 247 270 285
Max compressor current (3) A 241 247 273 304 335 369
Fans current A 16 24 24 24 24 32
Max unit current (3) A 257 271 297 328 359 401
Max unit inrush current (4) A 402 405 419 419 436 450
Max unit current for wires sizing (5) A 282 318 338 368 398 414

Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 45°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.

507 B – 03/05 E – pag. 14/32


Physical data ALS SE LN / XN HFC 134a
ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Cooling capacity (1) kW 287,4 337,3 359,4 402,7 433,2 512,6
Power input (1) kW 123,0 123,7 138,6 158,8 176,5 186,1
COP 2,34 2,73 2,59 2,54 2,45 2,75
McQuay Screw compressors No. 2 2 2 2 2 2
Refrigerant circuits No. 2 2 2 2 2 2
Refrigerant charge HFC 134a kg 70 70 80 80 100 100
Oil charge l 20 20 20 20 20 20
Min % of capacity reduction % 12.5% 12.5% 12.5% 12.5% 12.5% 12,5%
Condenser fans
No. of fans / nominal power fan kW 4/1 6/1 6/1 6/1 6/1 8/1
Fan speed rpm 700 700 700 700 700 700
Diameter mm 800 800 800 800 800 800
Total air flow m3/s 17,3 27 27 26,5 25,9 36,0
Evaporator
Evaporators / water volume No./l 1 / 198 1 / 181 1 / 181 1 / 181 1 / 227 1 / 273
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 139,7 139,7 139,7 139,7 139,7 139,7
Condenser coil
Coil type Lanced fins – Internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 3250 3515 3515 3515 3565 3895
Standard unit shipping weight ( XN ) kg 3510 3775 3775 3775 3825 4195
Standard unit operating weight kg 3448 3696 3696 3696 3792 4168
Standard unit operating weight ( XN ) kg 3708 3956 3956 3956 4052 4468
Unit length mm 2790 3460 3460 3460 3460 4355
Unit width mm 2225 2225 2225 2225 2225 2225
Unit height mm 2500 2500 2500 2500 2500 2500
Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.

Electrical data ALS SE LN / XN HFC 134a


ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 212 213 234 262 288 304
Max compressor current (3) A 237 239 264 297 328 354
Fans current A 9 14 14 14 14 18
Max unit current (3) A 246 252 277 311 342 372
Max unit inrush current (4) A 400 397 413 413 433 443
Max unit current for wires sizing (5) A 275 308 328 358 388 400

Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.

507 B – 03/05 E– pag. 15/32


Physical data ALS SE XXN HFC 134a
ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Cooling capacity (1) kW 294,1 330,7 363,3 409,5 447,8 516,9
Power input (1) kW 118,6 127,7 136,0 149,4 161,5 189,0
COP 2,48 2,59 2,67 2,74 2,77 2,74
McQuay Screw compressors No. 2 2 2 2 2 2
Refrigerant circuits No. 2 2 2 2 2 2
Refrigerant charge HFC 134a kg 70 70 80 80 100 100
Oil charge l 20 20 20 20 20 20
Min % of capacity reduction % 12.5% 12.5% 12.5% 12.5% 12.5% 12,5%
Condenser fans
No. of fans / nominal power fan kW 6 / 0,74 7 / 0,74 8 / 0,74 9 / 0,74 10 / 0,74 10 / 0,74
Fan speed rpm 500 500 500 500 500 500
Diameter mm 800 800 800 800 800 800
Total air flow m3/s 19,3 22,5 25,7 26,3 26,9 32,1
Evaporator
Evaporators / water volume No./l 1 / 192 1 / 192 1 / 190 1 / 225 1 / 221 1 / 265
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 139,7 139,7 139,7 139,7 139,7 139,7
Condenser coil
Coil type Lanced fins – Internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 3720 4000 4110 4335 4435 4535
Standard unit operating weight kg 3912 4192 4300 4560 4656 4800
Unit length mm 3460 4355 4355 5255 5255 5255
Unit width mm 2225 2225 2225 2225 2225 2225
Unit height mm 2500 2500 2500 2500 2500 2500
Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.

Electrical data ALS SE XXN HFC 134a


ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 207 220 232 255 274 309
Max compressor current (3) A 231 247 261 288 310 361
Fans current A 9 11 12 14 15 15
Max unit current (3) A 240 257 273 301 325 376
Max unit inrush current (4) A 398 400 410 413 429 442
Max unit current for wires sizing (5) A 271 295 318 352 385 385

Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.

507 B – 03/05 E – pag. 16/32


Physical data ALS XE ST / CN HFC 134a
ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Cooling capacity (1) kW 323,2 366,0 392,6 456,4 491,6 546,2
Power input (1) kW 103,8 115,4 128,8 135,1 150,5 158,7
COP 3,11 3,17 3,05 3,38 3,27 3,44
McQuay Screw compressors No. 2 2 2 2 2 2
Refrigerant circuits No. 2 2 2 2 2 2
Refrigerant charge HFC 134a kg 70 70 80 80 100 100
Oil charge l 20 20 20 20 20 20
Min % of capacity reduction % 12,5% 12,5% 12,5% 12,5% 12,5% 12,5%
Condenser fans
No. of fans / nominal power fan kW 6 / 1,6 6 / 1,6 6 / 1,6 8 / 1,6 8 / 1,6 10 / 1,6
Fan speed rpm 900 900 900 900 900 900
Diameter mm 800 800 800 800 800 800
Total air flow m3/s 33,8 32,6 32,6 46,7 46,7 56,3
Evaporator
Evaporators / water volume No./l 1 / 181 1 / 227 1 / 227 1 / 205 1 / 205 1 / 265
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 139,7 139,7 139,7 139,7 139,7 139,7
Condenser coil
Coil type Lanced fins – Internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 3515 3565 3565 3855 3855 4235
Standard unit shipping weight ( CN ) kg 3775 3825 3825 4155 4155 4535
Standard unit operating weight kg 3696 3792 3792 4060 4060 4500
Standard unit operating weight ( CN ) kg 3956 4052 4052 4360 4360 4800
Unit length mm 3460 3460 3460 4355 4355 5255
Unit width mm 2225 2225 2225 2225 2225 2225
Unit height mm 2500 2500 2500 2500 2500 2500

Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.

Electrical data ALS XE ST / CN HFC 134a


ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 186 202 219 235 259 262
Max compressor current (3) A 239 262 290 313 348 378
Fans current A 24 24 24 32 32 40
Max unit current (3) A 263 286 314 345 380 418
Max unit inrush current (4) A 405 404 417 422 440 449
Max unit current for wires sizing (5) A 298 318 338 384 414 430

Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 50°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.

507 B – 03/05 E– pag. 17/32


Physical data ALS XE LN / XN HFC 134a
ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Cooling capacity (1) kW 315,1 354,8 379,5 444,9 478,2 537,1
Power input (1) kW 108,7 122,0 136,6 141,5 158,3 168,1
COP 2,90 2,91 2,78 3,14 3,02 3,19
McQuay Screw compressors No. 2 2 2 2 2 2
Refrigerant circuits No. 2 2 2 2 2 2
Refrigerant charge HFC 134a kg 70 70 80 80 100 100
Oil charge l 20 20 20 20 20 20
Min % of capacity reduction % 12,5% 12,5% 12,5% 12,5% 12,5% 12,5%
Condenser fans
No. of fans / nominal power fan kW 6/1 6/1 6/1 8/1 8/1 10 / 1
Fan speed rpm 700 700 700 700 700 700
Diameter mm 800 800 800 800 800 800
Total air flow m3/s 33,8 32,6 32,6 46,7 46,7 45,1
Evaporator
Evaporators / water volume No./l 1 / 181 1 / 227 1 / 227 1 / 205 1 / 205 1 / 265
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 139,7 139,7 139,7 139,7 139,7 139,7
Condenser coil
Coil type Lanced fins – Internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 3515 3565 3565 3855 3855 4235
Standard unit shipping weight ( XN ) kg 3775 3825 3825 4155 4155 4535
Standard unit operating weight kg 3696 3792 3792 4060 4060 4500
Standard unit operating weight ( XN ) kg 3956 4052 4052 4360 4360 4800
Unit length mm 3460 3460 3460 4355 4355 5255
Unit width mm 2225 2225 2225 2225 2225 2225
Unit height mm 2500 2500 2500 2500 2500 2500

Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.

Electrical data ALS XE LN / XN HFC 134a


ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 193 211 230 245 271 277
Max compressor current (3) A 230 254 282 300 335 357
Fans current A 14 14 14 18 18 23
Max unit current (3) A 244 268 296 319 354 380
Max unit inrush current (4) A 397 396 411 412 431 438
Max unit current for wires sizing (5) A 288 308 328 370 400 413

Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 45°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.

507 B – 03/05 E – pag. 18/32


Physical data ALS HA HFC 134a
ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Cooling capacity (1) kW 318,3 353,1 378,0 444,2 477,5 539,6
Power input (1) kW 103,0 113,6 126,6 133,5 148,6 158,0
COP 3,09 3,11 2,99 3,33 3,21 3,42
McQuay Screw compressors No. 2 2 2 2 2 2
Refrigerant circuits No. 2 2 2 2 2 2
Refrigerant charge HFC 134a kg 70 70 80 80 100 100
Oil charge l 20 20 20 20 20 20
Min % of capacity reduction % 12,5% 12,5% 12,5% 12,5% 12,5% 12,5%
Condenser fans
No. of fans / nominal power fan kW 6 / 1,6 6 / 1,6 6 / 1,6 8 / 1,6 8 / 1,6 10 / 1,6
Fan speed rpm 900 900 900 900 900 900
Diameter mm 800 800 800 800 800 800
Total air flow m3/s 33,8 32,6 32,6 46,7 46,7 56,3
Evaporator
Evaporators / water volume No./l 1 / 181 1 / 227 1 / 227 1 / 205 1 / 205 1 / 265
Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5
Water connection diameter mm 139,7 139,7 139,7 139,7 139,7 139,7
Condenser coil
Coil type Lanced fins – Internally spiral wound tubes
Weight and dimensions
Standard unit shipping weight kg 3515 3565 3565 3855 3855 4235
Standard unit operating weight kg 3696 3792 3792 4060 4060 4500
Unit length mm 3460 3460 3460 4355 4355 5255
Unit width mm 2225 2225 2225 2225 2225 2225
Unit height mm 2500 2500 2500 2500 2500 2500

Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.

Electrical data ALS HA HFC 134a


ALS Unit Size 081.2 094.2 101.2 114.2 125.2 142.2
Standard voltage (1) 400 V – 3ph – 50 Hz
Nominal unit current (2) A 186 200 217 232 255 261
Max compressor current (3) A 238 261 288 310 344 376
Fans current A 24 24 24 32 32 40
Max unit current (3) A 262 285 312 342 376 416
Max unit inrush current (4) A 405 404 416 422 439 449
Max unit current for wires sizing (5) A 298 318 338 384 414 430

Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 50°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.

507 B – 03/05 E– pag. 19/32


Sound pressure level ALS SE, XE, HA ST
ALS Sound pressure level at 1 m from the unit in free field (rif. 2 x 10-5 Pa)
Unit size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
081.2 64,8 73,6 71,7 78,6 71,5 73,0 60,2 52,0 79,0
094.2 65,0 73,8 71,8 78,5 71,6 73,1 60,5 51,8 79,0
101.2 64,9 73,7 71,9 78,8 71,3 72,9 60,6 52,5 79,0
114.2 65,2 74,0 72,0 79,3 71,7 73,3 60,9 53,0 79,5
125.2 66,0 74,5 72,8 79,8 71,9 73,9 61,8 54,0 80,0
142.2 65,8 74,4 73,0 79,7 72,0 74,0 61,9 54,5 80,0

Sound pressure level ALS SE, XE, HA CN


ALS Sound pressure level at 1 m from the unit in free field (rif. 2 x 10-5 Pa)
Unit size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
081.2 62,8 71,6 71,1 76,8 68,8 70,9 58,2 50,0 77,0
094.2 62,5 71,7 71,3 76,7 68,9 71,0 58,0 50,8 77,0
101.2 62,9 71,9 70,5 77,0 68,5 70,8 58,5 50,4 77,0
114.2 63,0 72,1 71,6 77,1 69,8 71,5 58,6 51,5 77,5
125.2 63,4 72,3 72,2 77,9 70,2 71,5 58,9 51,0 78,0
142.2 63,5 72,5 72,5 77,5 70,6 71,8 59,2 52,1 78,0

Sound pressure level ALS SE, XE, LN


ALS Sound pressure level at 1 m from the unit in free field (rif. 2 x 10-5 Pa)
Unit size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
081.2 55,8 66,2 67,0 74,8 66,4 69,4 54,7 46,3 75,0
094.2 56,0 66,7 67,5 75,1 66,8 70,1 55,0 46,7 75,5
101.2 56,2 66,9 67,4 75,0 66,9 70,2 55,1 47,0 75,5
114.2 56,3 66,5 67,5 75,2 66,5 70,3 55,0 47,1 75,5
125.2 56,5 66,9 67,9 75,7 67,0 70,6 55,5 47,5 76,0
142.2 56,8 70,0 67,7 75,5 67,3 70,7 55,7 48,0 76,0

Sound pressure level ALS SE, XE, XN


ALS Sound pressure level at 1 m from the unit in free field (rif. 2 x 10-5 Pa)
Unit size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
081.2 56,4 69,6 69,5 70,5 65,6 61,4 54,1 43,8 71,0
094.2 56,4 69,6 69,0 71,0 65,2 61,2 53,8 43,8 71,0
101.2 56,8 70,0 69,5 71,5 65,6 61,5 54,0 44,0 71,5
114.2 56,5 70,5 69,5 71,5 65,6 61,7 54,5 45,0 71,5
125.2 56,5 70,0 69,1 71,8 65,4 61,3 54,6 45,5 71,5
142.2 57,0 71,0 69,6 72,2 65,9 61,5 55,0 45,6 72,0

Sound pressure level ALS SE XXN


ALS Sound pressure level at 1 m from the unit in free field (rif. 2 x 10-5 Pa)
Unit size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
081.2 62,0 60,1 63,5 62,8 59,9 58,1 46,9 36,5 65,0
094.2 62,5 59,5 64,0 62,5 59,2 58,7 49,0 39,0 65,0
101.2 62,5 59,5 63,5 62,3 60,4 58,5 46,4 36,0 65,0
114.2 62,0 60,1 63,5 62,8 59,9 58,1 46,9 36,5 65,0
125.2 63,0 59,0 63,0 62,0 60,0 59,0 46,0 36,5 65,0
142.2 61,0 58,0 63,0 64,0 58,5 58,0 49,5 38,6 65,0
Note: Average sound pressure level rated in accordance to ISO 3744, free field semispheric conditions.
Note: Sound pressure levels are referred to ALS Units furnished without water pump.

507 B – 03/05 E – pag. 20/32


Sound pressure level correction factor for different distances ALS SE ST, CN, LN, XN
ALS Distance (m)
Unit size 1 5 10 15 20 25
081.2 0 8,0 12,9 16,0 18,3 20,1
094.2 0 7,8 12,6 15,7 18,0 19,8
101.2 0 7,8 12,6 15,7 18,0 19,8
114.2 0 7,8 12,6 15,7 18,0 19,8
125.2 0 7,8 12,6 15,7 18,0 19,8
142.2 0 7,6 12,3 15,3 17,6 19,4

Sound pressure level correction factor for different distances ALS XE ST, CN, LN, XN;
ALS HA ST, CN
ALS Distance (m)
Unit size 1 5 10 15 20 25
081.2 0 7,8 12,6 15,7 18,0 19,8
094.2 0 7,6 12,3 15,3 17,6 19,4
101.2 0 7,6 12,3 15,3 17,6 19,4
114.2 0 7,3 12,0 15,0 17,2 19,0
125.2 0 7,3 12,0 15,0 17,2 19,0
142.2 0 7,3 12,0 15,0 17,2 19,0

Sound pressure level correction factor for different distances ALS SE XXN
ALS Distance (m)
Unit size 1 5 10 15 20 25
081.2 0 7,8 12,6 15,7 18,0 19,8
094.2 0 7,8 12,6 15,7 18,0 19,8
101.2 0 7,8 12,6 15,7 18,0 19,8
114.2 0 7,6 12,3 15,3 17,6 19,4
125.2 0 7,6 12,3 15,3 17,6 19,4
142.2 0 7,3 12,0 15,0 17,2 19,0
Note: The values reported in tables must be substracted to those declaread at 1 meter in free field semispheric conditions.

507 B – 03/05 E– pag. 21/32


Standard ratings ALS SE 081.2 ÷ 142.2 ST, CN
AIR AMBIENT TEMPERATURE - °C

leaving water
Evaporator

temp. (°C)
ALS
25 30 35 40 45
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capacity input capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 304,6 90,4 290,2 99,7 275,1 109,9 259,1 121,2 242,1 133,7
5 313,4 91,8 298,7 101,2 283,3 111,4 267,0 122,7 249,6 135,2
6 322,5 93,3 307,4 102,7 291,7 113,0 275,0 124,3 257,3 136,7
081.2 7 331,6 94,8 316,3 104,3 301,1 114,6 283,1 125,9 265,0 138,4
8 340,8 96,4 325,2 105,9 308,7 116,2 291,3 127,6 272,8 140,1
9 350,3 98,0 334,2 107,5 317,4 117,9 299,6 129,3 280,8 141,8
10 359,7 99,6 343,4 109,2 326,1 119,7 308,1 131,1 288,9 143,6
4 349,3 92,7 333,7 102,4 317,3 112,9 300,2 124,6 282,1 137,5
5 359,7 94,1 343,8 103,8 327,1 114,4 309,5 126,1 291,2 139,0
6 370,3 95,5 354,1 105,3 336,9 115,9 319,1 127,6 300,3 140,5
094.2 7 381,2 97,0 364,5 106,8 347,0 117,5 328,8 129,2 309,5 142,1
8 392,0 98,5 375,0 108,3 357,2 119,0 338,5 130,8 318,9 143,7
9 403,1 100,0 385,7 109,9 367,5 120,7 348,5 132,5 328,4 145,4
10 414,3 101,5 396,5 111,5 378,0 122,3 358,6 134,2 338,1 147,1
4 374,3 103,4 357,3 114,2 339,6 126,0 321,0 139,1 301,4 153,6
5 385,2 105,0 367,9 115,8 349,9 127,7 330,9 140,8 310,9 155,3
6 396,5 106,6 378,7 117,5 360,3 129,4 340,8 142,5 320,5 157,0
101.2 7 407,7 108,3 389,7 119,2 370,7 131,2 351,0 144,3 330,2 158,8
8 419,3 110,0 400,8 121,0 381,5 133,0 361,3 146,1 340,1 160,6
9 430,8 111,7 411,9 122,7 392,3 134,8 371,7 148,0 350,1 162,5
10 442,6 113,5 423,4 124,6 403,2 136,7 382,2 149,9 360,2 164,4
4 412,9 116,0 393,9 128,0 374,0 141,3 353,1 156,1 331,2 172,5
5 424,8 117,8 405,5 129,9 385,1 143,2 363,9 158,0 341,6 174,3
6 437,0 119,6 417,3 131,8 396,6 145,1 374,9 159,9 352,0 176,3
114.2 7 449,4 121,5 429,1 133,7 408,0 147,1 385,9 161,9 362,6 178,3
8 461,9 123,4 441,3 135,7 419,7 149,2 397,1 164,0 373,4 180,3
9 474,6 125,4 453,5 137,7 431,6 151,3 408,5 166,1 384,2 182,5
10 487,4 127,4 465,9 139,8 443,4 153,4 419,9 168,3 395,2 184,6
4 458,3 129,7 436,8 143,0 414,2 157,7 390,5 174,0 365,6 192,2
5 471,8 131,7 449,7 145,1 426,6 159,9 402,5 176,2 377,1 194,4
6 485,3 133,9 462,7 147,3 439,2 162,1 414,5 178,4 388,6 196,6
125.2 7 499,0 136,1 476,0 149,5 452,0 164,4 426,8 180,8 400,3 198,9
8 512,9 138,3 489,4 151,9 464,9 166,7 439,2 183,1 412,1 201,2
9 526,9 140,6 503,0 154,2 478,0 169,2 451,7 185,6 424,2 203,7
10 541,2 143,0 516,7 156,6 491,2 171,6 464,4 188,1 436,3 206,2
4 519,3 129,5 499,8 148,1 481,6 167,5 462,3 188,4 439,2 210,9
5 533,5 131,9 514,2 150,1 496,0 169,4 476,3 190,4 452,4 213,4
6 547,8 134,2 528,8 152,1 510,4 171,4 490,2 192,6 465,9 216,0
142.2 7 562,3 136,6 543,4 154,1 524,8 173,4 504,4 194,8 479,3 218,7
8 576,9 138,9 558,3 156,2 539,8 175,4 518,9 197,1 493,1 221,6
9 591,8 141,3 573,4 158,3 554,8 177,6 533,6 199,6 507,2 224,6
10 607,0 143,7 588,9 160,6 570,3 179,9 548,6 202,2 521,5 227,9
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.

507 B – 03/05 E – pag. 22/32


Standard ratings ALS SE 081.2 ÷ 142.2 LN, XN
AIR AMBIENT TEMPERATURE - °C

leaving water
Evaporator

temp. (°C)
ALS 25 30 35 40
Unit
size Cooling Power Cooling Power Cooling Power Cooling Power
capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 294,3 97,0 279,5 106,8 264,0 117,7 247,4 129,7
5 302,7 98,6 287,6 108,5 271,6 119,4 254,7 131,5
6 311,2 100,3 295,8 110,3 279,5 121,2 262,2 133,3
081.2 7 319,8 102,1 304,0 112,1 287,4 123,0 269,6 135,1
8 328,4 103,8 312,4 113,9 295,4 124,9 277,3 137,0
9 337,3 105,7 320,8 115,8 303,5 126,9 285,0 139,0
10 346,2 107,6 329,3 117,8 311,5 128,9 292,7 141,0
4 341,4 97,6 325,5 107,6 308,8 118,7 291,4 130,9
5 351,4 99,1 335,2 109,2 318,2 120,3 300,3 132,5
6 361,6 100,7 345,0 110,8 327,6 122,0 309,4 134,2
094.2 7 371,9 102,3 355,0 112,5 337,3 123,7 318,6 135,9
8 382,4 104,0 365,1 114,2 346,9 125,4 327,9 137,7
9 393,0 105,7 375,3 116,0 356,8 127,2 337,4 139,6
10 403,7 107,4 385,7 117,8 366,8 129,1 346,9 141,4
4 365,0 109,2 347,8 120,5 329,6 132,9 310,6 146,7
5 375,6 111,0 357,9 122,3 339,5 134,8 320,0 148,5
6 386,3 112,8 368,2 124,2 349,3 136,7 329,6 150,4
101.2 7 397,1 114,7 378,6 126,1 359,4 138,6 339,3 152,4
8 408,0 116,6 389,2 128,0 369,6 140,6 348,9 154,4
9 419,2 118,5 399,9 130,0 379,9 142,7 358,8 156,5
10 430,4 120,5 410,8 132,1 390,3 144,8 368,8 158,7
4 410,8 125,2 390,5 137,9 369,3 151,9 347,0 167,5
5 422,7 127,4 401,9 140,1 380,3 154,2 357,5 169,7
6 434,8 129,6 413,6 142,4 391,4 156,4 368,1 172,0
114.2 7 447,0 131,8 425,4 144,7 402,7 158,8 378,9 174,4
8 459,4 134,1 437,2 147,0 414,1 161,2 389,9 176,8
9 471,8 136,5 449,2 149,5 425,6 163,7 400,9 179,3
10 484,5 138,9 461,4 151,9 437,2 166,2 412,0 181,9
4 443,1 139,0 421,1 153,2 397,8 168,9 373,5 186,3
5 455,7 141,4 433,2 155,6 409,5 171,3 384,7 188,8
6 468,5 143,8 445,5 158,1 421,4 173,9 396,0 191,3
125.2 7 481,4 146,3 457,9 160,6 433,2 176,5 407,4 193,9
8 494,6 148,9 470,5 163,3 445,3 179,1 418,8 196,6
9 507,7 151,5 483,2 166,0 457,5 181,9 430,5 199,4
10 521,1 154,2 496,0 168,7 469,8 184,7 442,3 202,3
4 508,0 139,9 489,5 158,9 471,0 179,2 449,8 201,0
5 522,1 142,3 503,7 161,1 484,9 181,4 463,1 203,6
6 536,2 144,7 518,0 163,3 498,8 183,7 476,4 206,3
142.2 7 550,6 147,0 532,2 165,6 512,6 186,1 489,8 209,1
8 565,1 149,4 546,8 167,9 527,1 188,7 503,5 212,1
9 580,0 151,9 561,8 170,3 541,7 191,3 517,3 215,3
10 595,1 154,4 577,0 172,9 556,6 194,2 531,6 218,7
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.

507 B – 03/05 E– pag. 23/32


Standard ratings ALS SE 081.2 ÷ 142.2 XXN
AIR AMBIENT TEMPERATURE - °C

leaving water
Evaporator

temp. (°C)
ALS 25 30 35 40
Unit
size Cooling Power Cooling Power Cooling Power Cooling Power
capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 299,7 93,5 285,2 103,0 269,9 113,5 253,6 125,2
5 308,4 95,0 293,5 104,6 277,8 115,2 261,2 126,8
6 317,1 96,6 301,9 106,2 285,9 116,8 268,9 128,5
081.2 7 326,0 98,2 310,5 107,9 294,1 118,5 276,8 130,2
8 335,1 99,9 319,1 109,6 302,4 120,3 284,7 132,0
9 344,1 101,6 327,9 111,4 310,8 122,1 292,7 133,8
10 353,3 103,4 336,7 113,2 319,3 124,0 300,8 135,7
4 336,1 100,7 320,0 111,0 303,1 122,4 285,4 134,9
5 345,9 102,4 329,5 112,7 312,3 124,1 294,1 136,7
6 355,8 104,1 339,0 114,5 321,4 125,9 302,9 138,5
094.2 7 365,8 105,8 348,7 116,3 330,7 127,7 311,7 140,3
8 376,0 107,6 358,5 118,1 340,1 129,6 320,8 142,2
9 386,3 109,4 368,4 120,0 349,7 131,5 329,9 144,2
10 396,7 111,2 378,4 121,9 359,3 133,5 339,2 146,2
4 368,2 107,2 351,0 118,3 333,1 130,5 314,2 144,0
5 378,9 108,9 361,4 120,1 343,0 132,3 323,7 145,8
6 389,8 110,7 371,8 121,9 353,1 134,2 333,5 147,7
101.2 7 400,8 112,5 382,4 123,7 363,3 136,0 343,2 149,6
8 411,9 114,3 393,2 125,6 373,7 138,0 353,2 151,6
9 423,2 116,1 404,0 127,5 384,1 139,9 363,2 153,6
10 434,5 118,0 415,1 129,5 394,7 142,0 373,4 155,6
4 414,8 118,0 395,2 130,0 374,8 143,3 353,5 158,0
5 427,0 119,9 407,1 132,0 386,2 145,3 364,4 160,0
6 439,4 121,8 419,1 134,0 397,8 147,3 375,5 162,0
114.2 7 452,0 123,8 431,2 136,0 409,5 149,4 386,7 164,1
8 464,8 125,9 443,5 138,2 421,3 151,6 398,1 166,3
9 477,7 128,0 456,0 140,3 433,3 153,8 409,6 168,6
10 490,8 130,1 468,6 142,5 445,4 156,1 421,2 170,9
4 453,3 127,4 432,2 140,5 410,2 155,0 387,1 171,1
5 466,6 129,5 445,1 142,6 422,6 157,1 399,0 173,2
6 480,0 131,5 458,1 144,7 435,1 159,3 411,1 175,4
125.2 7 493,7 133,6 471,3 146,9 447,8 161,5 423,3 177,6
8 507,5 135,8 484,6 149,1 460,7 163,8 435,6 179,9
9 521,5 138,0 498,1 151,4 473,7 166,1 448,2 182,3
10 535,7 140,3 511,8 153,8 486,9 168,5 460,8 184,7
4 512,2 142,3 493,6 161,3 474,5 181,6 452,6 203,7
5 526,5 144,7 507,9 163,6 488,6 184,0 465,9 206,4
6 540,9 147,1 522,4 165,8 502,6 186,4 479,2 209,3
142.2 7 555,5 149,6 537,0 168,2 516,9 189,0 492,9 212,3
8 570,4 152,0 551,8 170,6 531,4 191,7 506,6 215,5
9 585,5 154,6 567,0 173,2 546,2 194,5 520,7 218,9
10 601,1 157,3 582,5 175,9 561,3 197,6 535,2 222,6
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.

507 B – 03/05 E – pag. 24/32


Standard ratings ALS XE 081.2 ÷ 142.2 ST, CN
AIR AMBIENT TEMPERATURE - °C

leaving water
Evaporator

temp. (°C)
ALS
25 30 35 40 45 50
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capac. input capac. input capac. input capac. input capac. input capac. input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 324,3 82,0 310,1 90,5 295,1 99,8 279,4 110,1 262,8 121,5 245,3 134,0
5 334,2 83,2 319,6 91,8 304,3 101,1 288,3 111,4 271,4 122,7 253,5 135,2
6 344,2 84,4 329,3 93,0 313,7 102,4 297,4 112,7 280,0 124,0 261,7 136,5
081.2 7 354,5 85,7 339,2 94,3 323,2 103,7 306,5 114,1 288,9 125,4 270,2 137,9
8 364,8 86,9 349,2 95,7 332,9 105,1 315,8 115,5 297,8 126,8 278,7 139,3
9 375,3 88,3 359,3 97,0 342,7 106,5 325,3 116,9 306,8 128,3 287,4 140,7
10 386,0 89,6 369,7 98,4 352,7 108,0 334,8 118,4 316,1 129,8 296,2 142,2
4 367,6 91,3 350,9 100,7 333,7 110,9 315,6 122,2 296,7 134,6 276,9 148,4
5 378,9 92,7 361,9 102,1 344,3 112,4 325,8 123,7 306,5 136,1 286,2 149,8
6 390,5 94,1 373,2 103,6 355,1 113,9 336,2 125,2 316,5 137,6 295,7 151,3
094.2 7 402,3 95,6 384,5 105,1 366,0 115,4 346,7 126,8 326,6 139,2 305,3 152,8
8 414,2 97,1 396,1 106,6 377,2 117,0 357,4 128,4 336,8 140,8 315,1 154,4
9 426,3 98,6 407,7 108,2 388,4 118,7 368,3 130,0 347,2 142,5 325,1 156,1
10 438,6 100,1 419,7 109,8 399,9 120,3 379,4 131,7 357,7 144,2 335,2 157,8
4 395,3 101,8 377,3 112,2 358,5 123,6 338,8 136,2 318,3 150,1 296,7 165,5
5 407,3 103,4 388,8 113,9 369,6 125,3 349,5 137,9 328,7 151,8 306,6 167,1
6 419,6 105,0 400,7 115,5 381,0 127,0 360,6 139,6 339,2 153,5 316,7 168,8
101.2 7 432,0 106,7 412,7 117,2 392,6 128,8 371,6 141,4 349,8 155,3 326,9 170,6
8 444,6 108,4 424,8 119,0 404,3 130,6 382,9 143,2 360,6 157,1 337,2 172,4
9 457,3 110,1 437,1 120,8 416,2 132,4 394,3 145,1 371,5 159,0 347,6 174,2
10 470,3 111,8 449,6 122,6 428,2 134,3 405,9 147,0 382,6 160,9 358,2 176,2
4 457,3 106,9 436,9 117,9 415,8 129,9 393,8 143,2 370,8 157,9 346,6 174,1
5 471,6 108,5 450,8 119,5 429,1 131,6 406,6 144,9 383,0 159,5 358,5 175,7
6 486,0 110,1 464,7 121,2 442,7 133,3 419,6 146,6 395,5 161,2 370,4 177,4
114.2 7 500,7 111,8 479,0 122,9 456,4 135,1 432,9 148,4 408,3 163,0 382,6 179,1
8 515,8 113,4 493,5 124,7 470,4 136,9 446,4 150,2 421,3 164,8 395,0 181,0
9 530,9 115,2 508,2 126,5 484,6 138,7 460,0 152,1 434,4 166,7 407,6 182,8
10 546,3 116,9 523,1 128,3 499,0 140,6 473,9 154,0 447,7 168,7 420,3 184,8
4 493,7 119,1 471,7 131,3 448,7 144,7 424,6 159,6 399,4 176,0 373,0 194,3
5 508,8 120,9 486,3 133,2 462,7 146,6 438,2 161,5 412,4 177,9 385,6 196,1
6 524,2 122,8 501,2 135,1 477,1 148,6 452,0 163,4 425,8 179,8 398,3 198,0
125.2 7 539,8 124,7 516,2 137,0 491,6 150,5 466,0 165,4 439,2 181,8 411,1 199,9
8 555,7 126,6 531,5 139,0 506,4 152,6 480,3 167,5 452,9 183,9 424,2 202,0
9 571,6 128,6 547,1 141,1 521,4 154,7 494,7 169,6 466,7 186,0 437,5 204,1
10 588,0 130,6 562,8 143,2 536,7 156,8 509,4 171,8 480,8 188,2 451,0 206,2
4 542,1 117,3 519,9 135,2 500,7 153,7 482,3 173,4 461,8 194,7 436,8 217,9
5 556,6 119,7 534,8 137,1 515,8 155,4 497,1 175,0 476,2 196,5 450,6 220,1
6 571,2 122,2 549,8 139,0 530,9 157,0 512,1 176,6 490,8 198,3 464,5 222,5
142.2 7 586,0 124,7 564,9 141,0 546,2 158,7 527,2 178,3 505,6 200,2 478,6 224,9
8 600,9 127,1 580,3 143,0 561,8 160,5 542,7 180,1 520,7 202,3 493,1 227,5
9 616,2 129,6 596,1 145,0 577,7 162,3 558,5 182,0 536,1 204,5 507,9 230,3
10 631,9 132,2 612,2 147,2 594,0 164,2 574,8 184,0 552,0 206,8 523,2 233,2
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.

507 B – 03/05 E– pag. 25/32


Standard ratings ALS XE 081.2 ÷ 142.2 LN, XN
AIR AMBIENT TEMPERATURE - °C

leaving water
Evaporator

temp. (°C)
ALS
25 30 35 40 45
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capacity input capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 317,7 85,9 303,2 94,7 288,0 104,4 272,1 115,1 255,2 126,9
5 327,3 87,2 312,4 96,1 296,9 105,8 280,6 116,5 263,3 128,3
6 336,9 88,6 321,8 97,5 306,0 107,2 289,3 118,0 271,6 129,7
081.2 7 346,8 90,0 331,3 98,9 315,1 108,7 298,0 119,5 280,0 131,2
8 356,8 91,4 340,9 100,4 324,3 110,2 306,9 121,0 288,5 132,8
9 366,9 92,8 350,7 101,9 333,8 111,8 315,9 122,6 297,2 134,4
10 377,2 94,3 360,6 103,5 343,4 113,4 325,2 124,2 306,0 136,0
4 358,4 96,5 341,6 106,2 324,0 116,9 305,7 128,7 286,3 141,7
5 369,3 98,0 352,1 107,8 334,1 118,6 315,3 130,4 295,6 143,4
6 380,3 99,6 362,7 109,5 344,4 120,2 325,2 132,1 305,0 145,1
094.2 7 391,5 101,3 373,6 111,2 354,8 122,0 335,2 133,8 314,6 146,8
8 403,0 102,9 384,5 112,9 365,4 123,8 345,3 135,6 324,2 148,6
9 414,5 104,6 395,7 114,7 376,1 125,6 355,6 137,5 334,1 150,5
10 426,3 106,4 407,0 116,5 386,9 127,5 366,0 139,4 344,1 152,4
4 384,5 108,0 366,1 118,9 347,0 130,8 327,1 144,1 306,1 158,7
5 396,0 109,8 377,3 120,7 357,7 132,7 337,3 146,0 315,8 160,6
6 407,6 111,6 388,5 122,6 368,6 134,6 347,7 147,9 325,8 162,5
101.2 7 419,5 113,4 399,8 124,5 379,5 136,6 358,2 149,9 335,8 164,5
8 431,4 115,4 411,4 126,5 390,5 138,6 368,8 151,9 346,0 166,6
9 443,6 117,3 423,0 128,5 401,7 140,7 379,5 154,1 356,2 168,7
10 455,9 119,3 434,9 130,6 413,1 142,8 390,4 156,2 366,6 170,8
4 447,8 112,0 427,2 123,3 405,8 135,8 383,6 149,6 360,2 164,9
5 461,6 113,7 440,6 125,2 418,6 137,7 395,9 151,5 372,0 166,7
6 475,5 115,5 454,0 127,0 431,7 139,6 408,3 153,4 384,0 168,6
114.2 7 489,7 117,4 467,8 128,9 444,9 141,5 421,1 155,3 396,2 170,6
8 504,2 119,2 481,6 130,9 458,3 143,5 434,0 157,4 408,5 172,6
9 518,8 121,2 495,8 132,8 471,9 145,6 447,0 159,4 421,1 174,7
10 533,6 123,1 510,1 134,9 485,7 147,7 460,2 161,6 433,8 176,8
4 482,6 125,2 460,2 137,9 436,9 151,9 412,4 167,4 386,9 184,6
5 497,2 127,2 474,3 139,9 450,5 153,9 425,5 169,5 399,3 186,6
6 512,0 129,2 488,6 142,0 464,2 156,1 438,7 171,6 412,0 188,8
125.2 7 526,9 131,3 503,1 144,2 478,2 158,3 452,1 173,8 424,8 191,0
8 542,1 133,5 517,7 146,4 492,2 160,6 465,7 176,1 437,9 193,2
9 557,6 135,7 532,6 148,7 506,6 162,9 479,4 178,5 451,1 195,6
10 573,1 137,9 547,7 151,0 521,1 165,3 493,4 180,9 464,4 198,0
4 531,4 125,4 510,9 143,5 492,3 162,6 473,2 182,9 451,1 205,0
5 545,9 127,8 525,6 145,5 507,2 164,4 487,7 184,8 464,8 207,3
6 560,5 130,2 540,5 147,5 522,0 166,2 502,3 186,8 478,9 209,6
142.2 7 575,2 132,6 555,6 149,5 537,1 168,1 517,0 188,8 493,1 212,1
8 590,1 135,0 570,9 151,5 552,4 170,0 532,1 190,9 507,6 214,6
9 605,4 137,4 586,5 153,7 568,1 172,1 547,5 193,2 522,4 217,4
10 621,1 139,9 602,5 155,9 584,1 174,3 563,3 195,7 537,6 220,4
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.

507 B – 03/05 E – pag. 26/32


Standard ratings ALS HA 081.2 ÷ 142.2
AIR AMBIENT TEMPERATURE - °C

leaving water
Evaporator

temp. (°C)
ALS
25 30 35 40 45 50
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capac. input capac. input capac. input capac. input capac. input capac. input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 319,2 81,4 305,3 89,9 290,9 99,3 275,5 109,6 259,5 121,0 242,2 133,5
5 328,9 82,6 314,6 91,1 299,8 100,5 284,2 110,8 267,8 122,2 250,2 134,7
6 338,6 83,7 324,1 92,3 308,9 101,7 293,1 112,1 276,2 123,5 258,3 136,0
081.2 7 348,5 84,9 333,7 93,6 318,3 103,0 302,0 113,4 284,8 124,8 266,5 137,3
8 358,6 86,2 343,5 94,9 327,6 104,4 311,0 114,8 293,5 126,1 274,9 138,6
9 368,8 87,4 353,3 96,2 337,2 105,7 320,3 116,1 302,4 127,5 283,4 140,0
10 379,2 88,7 363,4 97,6 346,9 107,1 329,6 117,6 311,3 129,0 292,0 141,5
4 354,4 89,7 338,8 99,1 322,7 109,4 305,8 120,7 287,9 133,3 269,1 147,2
5 365,1 91,0 349,2 100,4 332,6 110,8 315,4 122,1 297,3 134,7 278,0 148,5
6 375,9 92,3 359,7 101,8 342,8 112,2 325,2 123,5 306,6 136,1 287,0 149,9
094.2 7 386,9 93,7 370,3 103,2 353,1 113,6 335,2 125,0 316,2 137,5 296,2 151,4
8 398,1 95,0 381,3 104,6 363,6 115,1 345,2 126,5 325,8 139,1 305,4 152,8
9 409,5 96,4 392,2 106,1 374,2 116,6 355,4 128,1 335,7 140,6 314,9 154,4
10 420,9 97,9 403,4 107,6 385,0 118,1 365,8 129,6 345,7 142,2 324,5 156,0
4 380,2 99,9 363,4 110,3 345,8 121,8 327,5 134,5 308,2 148,5 287,9 164,0
5 391,4 101,3 374,3 111,8 356,4 123,3 337,7 136,0 317,9 150,1 297,3 165,6
6 402,9 102,8 385,4 113,4 367,1 124,9 348,0 137,6 327,9 151,7 306,7 167,1
101.2 7 414,5 104,3 396,6 115,0 378,0 126,6 358,5 139,3 337,9 153,3 316,4 168,8
8 426,3 105,9 408,0 116,6 388,9 128,2 369,1 141,0 348,2 155,0 326,1 170,4
9 438,3 107,5 419,6 118,2 400,2 129,9 379,8 142,7 358,5 156,8 336,0 172,2
10 450,3 109,1 431,2 119,9 411,4 131,7 390,7 144,5 369,0 158,6 346,1 174,0
4 444,8 105,5 425,5 116,5 405,3 128,6 384,3 142,0 362,3 156,7 339,3 173,1
5 458,3 107,0 438,6 118,1 418,0 130,2 396,6 143,5 374,1 158,3 350,6 174,6
6 472,1 108,6 451,9 119,7 430,9 131,8 409,1 145,2 386,1 159,9 362,0 176,2
114.2 7 486,2 110,1 465,6 121,3 444,2 133,5 421,8 146,9 398,4 161,6 373,8 177,9
8 500,4 111,7 479,3 123,0 457,5 135,2 434,6 148,6 410,8 163,3 385,7 179,6
9 514,8 113,3 493,4 124,7 471,0 137,0 447,6 150,4 423,3 165,1 397,7 181,3
10 529,5 115,0 507,6 126,4 484,7 138,7 461,0 152,2 436,1 167,0 410,0 183,2
4 479,3 117,4 458,3 129,7 436,5 143,1 413,6 158,1 389,7 174,7 364,4 193,1
5 493,7 119,1 472,3 131,4 450,0 144,9 426,6 159,9 402,2 176,4 376,4 194,8
6 508,2 120,9 486,5 133,2 463,7 146,8 439,8 161,7 414,9 178,2 388,6 196,6
125.2 7 523,1 122,6 500,7 135,0 477,5 148,6 453,3 163,6 427,8 180,1 401,0 198,4
8 538,1 124,5 515,3 136,9 491,6 150,6 466,8 165,5 440,8 182,1 413,5 200,3
9 553,4 126,3 530,1 138,8 505,9 152,5 480,6 167,5 454,1 184,1 426,3 202,3
10 568,8 128,2 545,1 140,8 520,4 154,5 494,6 169,6 467,6 186,1 439,2 204,3
4 535,9 116,2 513,9 134,4 495,0 153,1 476,8 172,8 456,8 194,0 432,4 217,1
5 550,2 118,7 528,6 136,3 509,8 154,7 491,4 174,4 470,9 195,8 445,8 219,3
6 564,6 121,1 543,3 138,2 524,6 156,3 506,1 176,0 485,3 197,6 459,6 221,6
142.2 7 579,1 123,5 558,1 140,1 539,6 158,0 521,0 177,6 499,8 199,5 473,4 224,0
8 593,7 125,9 573,2 142,1 554,8 159,7 536,1 179,3 514,5 201,4 487,5 226,5
9 608,6 128,4 588,5 144,1 570,4 161,4 551,6 181,1 529,6 203,5 502,0 229,2
10 623,8 130,9 604,3 146,1 586,2 163,3 567,3 183,0 545,1 205,8 516,9 232,0
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.

507 B – 03/05 E– pag. 27/32


Total heat recovery ratings ALS 081.2 ÷ 142.2
TEMPERATURA ACQUA USCENTE DAL RECUPERATORE °C

evaporatore °C
acqua uscita
Temperatura
Taglia 55
40 45 50
unità
ALS Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot.
Frigor. Assor. Recup Frigor. Assor. Recup Frigor. Assor. Recup Frigor. Assor. Recup
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 304,6 90,4 383,2 290,2 99,7 378,2 275,1 109,9 373,5 259,1 121,2 368,9
5 313,4 91,8 393,0 298,7 101,2 387,9 283,3 111,4 382,9 267,0 122,7 378,0
6 322,5 93,3 403,3 307,4 102,7 397,8 291,7 113 392,6 275,0 124,3 387,3
081.2 7 331,6 94,8 413,6 316,3 104,3 408,0 301,1 114,6 403,2 283,1 125,9 396,7
8 340,8 96,4 424,1 325,2 105,9 418,2 308,7 116,2 412,2 291,3 127,6 406,3
9 350,3 98 434,9 334,2 107,5 428,4 317,4 117,9 422,2 299,6 129,3 416,0
10 359,7 99,6 445,5 343,4 109,2 439,0 326,1 119,7 432,4 308,1 131,1 426,0
4 349,3 92,7 428,7 333,7 102,4 423,0 317,3 112,9 417,3 300,2 124,6 412,1
5 359,7 94,1 440,2 343,8 103,8 434,2 327,1 114,4 428,3 309,5 126,1 422,5
6 370,3 95,5 451,8 354,1 105,3 445,6 336,9 115,9 439,2 319,1 127,6 433,3
094.2 7 381,2 97 463,9 364,5 106,8 457,2 347,0 117,5 450,6 328,8 129,2 444,3
8 392,0 98,5 475,8 375,0 108,3 468,8 357,2 119 461,9 338,5 130,8 455,2
9 403,1 100 488,0 385,7 109,9 480,7 367,5 120,7 473,6 348,5 132,5 466,6
10 414,3 101,5 500,3 396,5 111,5 492,8 378,0 122,3 485,3 358,6 134,2 478,0
4 374,3 103,4 463,4 357,3 114,2 457,4 339,6 126 451,6 321,0 139,1 446,3
5 385,2 105 475,5 367,9 115,8 469,2 349,9 127,7 463,3 330,9 140,8 457,5
6 396,5 106,6 488,0 378,7 117,5 481,3 360,3 129,4 475,0 340,8 142,5 468,8
101.2 7 407,7 108,3 500,5 389,7 119,2 493,6 370,7 131,2 486,8 351,0 144,3 480,4
8 419,3 110 513,4 400,8 121 506,1 381,5 133 499,1 361,3 146,1 492,2
9 430,8 111,7 526,2 411,9 122,7 518,6 392,3 134,8 511,3 371,7 148 504,1
10 442,6 113,5 539,4 423,4 124,6 531,6 403,2 136,7 523,7 382,2 149,9 516,1
4 412,9 116 513,0 393,9 128 506,2 374,0 141,3 499,8 353,1 156,1 493,9
5 424,8 117,8 526,3 405,5 129,9 519,3 385,1 143,2 512,5 363,9 158 506,2
6 437,0 119,6 539,9 417,3 131,8 532,6 396,6 145,1 525,4 374,9 159,9 518,8
114.2 7 449,4 121,5 553,8 429,1 133,7 545,9 408,0 147,1 538,4 385,9 161,9 531,4
8 461,9 123,4 567,7 441,3 135,7 559,7 419,7 149,2 551,8 397,1 164 544,3
9 474,6 125,4 582,0 453,5 137,7 573,5 431,6 151,3 565,4 408,5 166,1 557,4
10 487,4 127,4 596,4 465,9 139,8 587,5 443,4 153,4 578,9 419,9 168,3 570,6
4 458,3 129,7 570,4 436,8 143 562,4 414,2 157,7 554,7 390,5 174 547,6
5 471,8 131,7 585,4 449,7 145,1 577,0 426,6 159,9 568,9 402,5 176,2 561,3
6 485,3 133,9 600,6 462,7 147,3 591,7 439,2 162,1 583,3 414,5 178,4 575,1
125.2 7 499,0 136,1 616,0 476,0 149,5 606,7 452,0 164,4 597,9 426,8 180,8 589,4
8 512,9 138,3 631,7 489,4 151,9 622,1 464,9 166,7 612,7 439,2 183,1 603,6
9 526,9 140,6 647,5 503,0 154,2 637,5 478,0 169,2 627,8 451,7 185,6 618,2
10 541,2 143 663,7 516,7 156,6 653,1 491,2 171,6 642,9 464,4 188,1 632,9
4 519,3 129,5 629,3 499,8 148,1 628,5 481,6 167,5 629,6 462,3 188,4 631,2
5 533,5 131,9 645,4 514,2 150,1 644,4 496,0 169,4 645,4 476,3 190,4 646,7
6 547,8 134,2 661,5 528,8 152,1 660,5 510,4 171,4 661,3 490,2 192,6 662,3
142.2 7 562,3 136,6 677,9 543,4 154,1 676,6 524,8 173,4 677,3 504,4 194,8 678,2
8 576,9 138,9 694,3 558,3 156,2 693,1 539,8 175,4 693,7 518,9 197,1 694,5
9 591,8 141,3 711,1 573,4 158,3 709,7 554,8 177,6 710,4 533,6 199,6 711,2
10 607,0 143,7 728,2 588,9 160,6 727,0 570,3 179,9 727,7 548,6 202,2 728,3

507 B – 03/05 E – pag. 28/32


Partial heat recovery ratings ALS 081.2 ÷ 142.2
LEAVING DESUPERHEATERS WATER TEMPERATURE – °C
ALS
Unit 40 45 50 55
Size
Heating capacity (kW) Heating capacity (kW) Heating capacity (kW) Heating capacity (kW)

081.2 55,4 50,5 45,7 40,9


Leaving chilled water temperature 7°C
∆T 5°C – Air temperature 35°C

094.2 62,2 56,6 51,1 45,8


101.2 67,1 61,1 55,2 49,5
114.2 74,2 67,5 61,1 54,8
125.2 82,6 75,1 67,8 60,8
142.2 90,9 83,7 76,8 69,9

Water pump diagram


Total hydraulic pressure lift (kPa)

270

240

210

180 A

150 B
120
10 15 20 25 30 35

Water flow (l/s)

Type Unit Motor Electric


AMPS Voltage
pump models power protection
kW A V / Hz
A 081.2 - 101.2 SE
081.2 - 125.2 XE 7,5 16,0 IP54 400/3/50
B 114.2 - 142.2 SE
142.2 XE 7,5 16,0 IP54 400/3/50

Note: to have the useful hydraulic lift is necessary to subtract the evaporator pressure drop to the total hydraulic lift.

507 B – 03/05 E– pag. 29/32


Evaporator pressure drop – ALS SE ST, CN, LN, XN, XXN; ALS XE
ST, CN, LN, XN; ALS HA

SE ST/LN/XN 142.2
XE ST/LN/XN 142.2
XE SE/LN/XN 114.2 – 125.2
SE XXN 142.2
SE XXN 114.2 – 125.2

HA 114.2 – 125.2

SE ST/LN/XN 094.2 – 101.2


XE ST/LN/XN 081.2 HA 142.2
HA 094.2 – 101.2
SE ST/LN/XN 114.2 – 125.2
SE XXN 094.2 – 101.2

XE ST/LN/XN 094.2 – 101.2

SE ST/LN/XN 081.2
HA 081.2

507 B – 03/05 E – pag. 30/32


Dimensions ALS SE, XE, HA 081.2 ÷ 142.2 ST, CN, LN, XN, XXN

A B

Length – A Width – B Height


ALS SE Units
(mm) (mm) (mm)
ST-CN-LN-XN
ALS SE 081.2 2790 2225 2500
ALS SE 094.2 – 101.2 – 114.2 – 125.2 3460 2225 2500
ALS SE 142.2 4355 2225 2500
XXN
ALS SE 081.2 3460 2225 2500
ALS SE 094.2 – 101.2 4355 2225 2500
ALS SE 114.2 – 125.2 – 142.2 5255 2225 2500

Length – A Width – B Height


ALS XE Units
(mm) (mm) (mm)
ST-CN-LN-XN
ALS XE 081.2 – 101.2 3460 2225 2500
ALS XE 114.2 – 125.2 4355 2225 2500
ALS XE 142.2 5255 2225 2500

Length – A Width – B Height


ALS HA Units
(mm) (mm) (mm)
ST-CN
ALS SE 081.2 – 094.2 – 101.2 3460 2225 2500
ALS SE 114.2 – 125.2 4355 2225 2500
ALS SE 142.2 5255 2225 2500

507 B – 03/05 E– pag. 31/32


We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.