Air Cooled Screw Chillers: ALS 081.2÷142.2 (Energyplus)
Air Cooled Screw Chillers: ALS 081.2÷142.2 (Energyplus)
Code requirements
All ALS units are designed and manufactured in accordance with applicable selections of the following which are
equivalent to American Air-conditioning industry applicable codes:
Rating of chillers: EN 12055.
Construction of pressure vessel: TUV Standards (on request).
Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety Codes
Safety Codes: CEI-EN 60204–1 Codes.
Manufacturing Quality Stds: ISO 9001.
11 different lines
ALS 3200 line is available with two different efficiencies in order to satisfy every kind of requirements.
Acoustic flexibility up to 65 dBA thanks to different noise level versions:
• SE Standard Efficiency
- ST Standard noise – 79,0 ÷ 80,0 dBA
- CN Sound proof cabinet on compressors – 77,0 ÷ 78,0 dBA
- LN Low noise – 75,0 ÷ 76,0 dBA
- XN Extra low noise – 71,0 ÷ 72,0 dBA
- XXN Super quiet – 65,0 dBA
Unmatched serviceability
Field serviceability has not been sacrificed. Inspection covers allows visual inspection of the main screw and
gaterotors.
General characteristics
Cabinet and structure
The cabinet of ALS units is made of galvanized steel sheet and painted to provide a high resistance to corrosion. The
unit base frame has holes to lift the unit with ropes for an easy installation. The weight is uniformly distribuited along the
profiles of the base and this facilitates the arrangement of the unit.
Evaporator
The units is supplied with new optimised counter-flow evaporator single refrigerant pass. It is direct expansion
with refrigerant inside the tubes and water outside (shell side) with carbon steel tube sheets, with straight copper
tubes that are spirally wound internally for higher efficiencies, expanded on the tube plates. The external shell, is
linked with an electrical heater to prevent freezing down to -28 °C ambient temperature, commanded by a
thermostat and is covered with a closed cell insulation material. Each evaporator have 2 refrigerant circuits one for
each compressor. Each evaporator is manufactured in accordance to PED approval.
Certifications
All the ALS units are CE marked (89/392). McQuay Italia obtained ISO 9001 certification in 1997.
P (kW) 1
(1) Q = 35,83 X X
∆T(°C) N
where:
Q = Minimum content of the plant expressed in litres
P = Cooling capacity of the plant expressed in kW
For a more accurate determination of the quantity of water, it is advisable to contact the designer of the plant.
System security
Phase monitor
Freeze protection
Regulation type
Proportional + integral + derivative regulation on the leaving water evaporator output probe.
Condensation
The condensation can be carried out according to temperature or pressure. The fans can be managed according
to ON/OFF mode or with a 0/10 V modulating signal or both (SPEEDTROL).
MicroPlantTM:
Solution for: tele-maintenance and supervisory systems
MicroTech II can be monitored locally or via modem by MicroPlantTM supervision program, that runs on PC
systems under Windows ’95 – ’98.
MicroPlantTM allows:
Installation notes
Handling
Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from
anything other than the base, and block the pushing vehicle away from the unit to prevent damage to the cabinet.
Never allow the unit fall during unloading or moving as this may result in serious damage. To lift the unit, holes are
provided in the base of the unit. Spreader bar and cables should be arranged to prevent damage to the condenser
coil or unit cabinet.
Location
The ALS units are produced for outside installation on roofs, floors or below ground level on condition that the area
is free from obstacles for the passage of the condenser air. The unit should be positioned on solid foundations and
Space requirements
The ALS units are air-cooled, hence it is important to observe the minimum distances which guarantee the best
ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in
cooling capacity and an increase in electricity consumption.
To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the
condenser heat transfer surface. Two conditions must be avoided to achieve the best performance: warm air
recirculation and coil starvation.
Both these conditions cause an increase of condensing pressures that results in reductions in unit efficiency and
capacity. The ALS chiller performance is less affected in poor air flow situations because of its special condensing
coil geometry.
Moreover McQuay’s unique microprocessor has the ability to calculate the operating environment of the chiller and
the capacity to optimize its performance staying on-line during abnormal conditions.
Each side of the unit must be accessible after installation for periodic service. Fig.1 shows you minimum
recommended clearance requirements.
Vertical condenser air discharge must be unobstructed because the unit would have its capacity and efficiency
significantly reduced.
If the units are positioned in places surrounded by walls or obstacles of the same height as the units, the units
should be at least 2500 mm from obstacles (fig.2). In the event the obstacles are higher than the units, the units
should be at least 3000 mm from the obstacle (fig.4). Units installed closer than the minimun recommended
distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation,
thus causing reduction in unit capacity and efficienty reductions. Once again, the microprocessor will allow the
chiller to stay on line, producing the maximum available capacity, even at less than recommended lateral
clearances.
When two or more units are positioned side by side it is recommended that the condenser coils are at least 3600
mm distance from one another (fig.3); stong wind could be the cause of air warm recirculation.
For other installation solutions, consult McQuay technicians.
Table 8 – Correction Factor for ALS Unit ST / CN version (SE & XE & HA) with fan
80CC/6/7 900 RPM
External static
10 20 30 40 50 60 70 80 90 100 120 Pa
pressure
Cooling capacity 0.997 0.993 0.990 0.985 0.981 0.976 0.972 0.966 0.961 0.953 0.935
Power input 1,004 1.007 1,012 1,016 1,020 1,025 1,031 1,036 1,042 1,050 1,068
MAX allowed
Ambient 44,7 44,5 44,1 43,8 43,4 43,0 42,6 42,2 41,7 41,1 39,6 °C
Temperature (SE)
MAX allowed
Ambient 49,7 49,5 49,1 48,8 48,4 48,0 47,6 47,2 46,7 46,1 44,6 °C
Temperature (XE)
Table 9 – Correction Factor for ALS Unit LN / XN version (SE & XE) with fan
80CC/6/7 700 RPM
External static
10 20 30 40 50 60 Pa
pressure
MAX allowed
Ambient 40,4 39,7 38,9 38,0 37,0 35,8 °C
Temperature (SE)
MAX allowed
Ambient 45,4 44,7 43,9 43,0 42,0 40,8 °C
Temperature (XE)
SE Standard Efficiency
XE High Efficiency
HA High Ambient
2 N° of compressors
ST Standard version
CN Sound proof cabinet around compressors
LN Low noise version
XN Extra low noise version
XXN Super quiet
Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 45°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 40°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.
Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 50°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.
Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 45°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.
Note: (1) Nominal cooling capacity and power input are based on: 12/7 °C entering/leaving evaporator water temperature;
35°C ambient temperature. The power input is for compressor only.
Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.
(3) Maximum current are based on: 15/10 °C entering/leaving evaporator water temperature and 50°C ambient temp.
(4) Inrush current of biggest compressor + 75% of nominal absorbed current of the other compressor (see pag. 4 “Intelligent
Start Compressor Mode” ) + fans current.
(5) Compressor FLA + fans current.
Sound pressure level correction factor for different distances ALS XE ST, CN, LN, XN;
ALS HA ST, CN
ALS Distance (m)
Unit size 1 5 10 15 20 25
081.2 0 7,8 12,6 15,7 18,0 19,8
094.2 0 7,6 12,3 15,3 17,6 19,4
101.2 0 7,6 12,3 15,3 17,6 19,4
114.2 0 7,3 12,0 15,0 17,2 19,0
125.2 0 7,3 12,0 15,0 17,2 19,0
142.2 0 7,3 12,0 15,0 17,2 19,0
Sound pressure level correction factor for different distances ALS SE XXN
ALS Distance (m)
Unit size 1 5 10 15 20 25
081.2 0 7,8 12,6 15,7 18,0 19,8
094.2 0 7,8 12,6 15,7 18,0 19,8
101.2 0 7,8 12,6 15,7 18,0 19,8
114.2 0 7,6 12,3 15,3 17,6 19,4
125.2 0 7,6 12,3 15,3 17,6 19,4
142.2 0 7,3 12,0 15,0 17,2 19,0
Note: The values reported in tables must be substracted to those declaread at 1 meter in free field semispheric conditions.
leaving water
Evaporator
temp. (°C)
ALS
25 30 35 40 45
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capacity input capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 304,6 90,4 290,2 99,7 275,1 109,9 259,1 121,2 242,1 133,7
5 313,4 91,8 298,7 101,2 283,3 111,4 267,0 122,7 249,6 135,2
6 322,5 93,3 307,4 102,7 291,7 113,0 275,0 124,3 257,3 136,7
081.2 7 331,6 94,8 316,3 104,3 301,1 114,6 283,1 125,9 265,0 138,4
8 340,8 96,4 325,2 105,9 308,7 116,2 291,3 127,6 272,8 140,1
9 350,3 98,0 334,2 107,5 317,4 117,9 299,6 129,3 280,8 141,8
10 359,7 99,6 343,4 109,2 326,1 119,7 308,1 131,1 288,9 143,6
4 349,3 92,7 333,7 102,4 317,3 112,9 300,2 124,6 282,1 137,5
5 359,7 94,1 343,8 103,8 327,1 114,4 309,5 126,1 291,2 139,0
6 370,3 95,5 354,1 105,3 336,9 115,9 319,1 127,6 300,3 140,5
094.2 7 381,2 97,0 364,5 106,8 347,0 117,5 328,8 129,2 309,5 142,1
8 392,0 98,5 375,0 108,3 357,2 119,0 338,5 130,8 318,9 143,7
9 403,1 100,0 385,7 109,9 367,5 120,7 348,5 132,5 328,4 145,4
10 414,3 101,5 396,5 111,5 378,0 122,3 358,6 134,2 338,1 147,1
4 374,3 103,4 357,3 114,2 339,6 126,0 321,0 139,1 301,4 153,6
5 385,2 105,0 367,9 115,8 349,9 127,7 330,9 140,8 310,9 155,3
6 396,5 106,6 378,7 117,5 360,3 129,4 340,8 142,5 320,5 157,0
101.2 7 407,7 108,3 389,7 119,2 370,7 131,2 351,0 144,3 330,2 158,8
8 419,3 110,0 400,8 121,0 381,5 133,0 361,3 146,1 340,1 160,6
9 430,8 111,7 411,9 122,7 392,3 134,8 371,7 148,0 350,1 162,5
10 442,6 113,5 423,4 124,6 403,2 136,7 382,2 149,9 360,2 164,4
4 412,9 116,0 393,9 128,0 374,0 141,3 353,1 156,1 331,2 172,5
5 424,8 117,8 405,5 129,9 385,1 143,2 363,9 158,0 341,6 174,3
6 437,0 119,6 417,3 131,8 396,6 145,1 374,9 159,9 352,0 176,3
114.2 7 449,4 121,5 429,1 133,7 408,0 147,1 385,9 161,9 362,6 178,3
8 461,9 123,4 441,3 135,7 419,7 149,2 397,1 164,0 373,4 180,3
9 474,6 125,4 453,5 137,7 431,6 151,3 408,5 166,1 384,2 182,5
10 487,4 127,4 465,9 139,8 443,4 153,4 419,9 168,3 395,2 184,6
4 458,3 129,7 436,8 143,0 414,2 157,7 390,5 174,0 365,6 192,2
5 471,8 131,7 449,7 145,1 426,6 159,9 402,5 176,2 377,1 194,4
6 485,3 133,9 462,7 147,3 439,2 162,1 414,5 178,4 388,6 196,6
125.2 7 499,0 136,1 476,0 149,5 452,0 164,4 426,8 180,8 400,3 198,9
8 512,9 138,3 489,4 151,9 464,9 166,7 439,2 183,1 412,1 201,2
9 526,9 140,6 503,0 154,2 478,0 169,2 451,7 185,6 424,2 203,7
10 541,2 143,0 516,7 156,6 491,2 171,6 464,4 188,1 436,3 206,2
4 519,3 129,5 499,8 148,1 481,6 167,5 462,3 188,4 439,2 210,9
5 533,5 131,9 514,2 150,1 496,0 169,4 476,3 190,4 452,4 213,4
6 547,8 134,2 528,8 152,1 510,4 171,4 490,2 192,6 465,9 216,0
142.2 7 562,3 136,6 543,4 154,1 524,8 173,4 504,4 194,8 479,3 218,7
8 576,9 138,9 558,3 156,2 539,8 175,4 518,9 197,1 493,1 221,6
9 591,8 141,3 573,4 158,3 554,8 177,6 533,6 199,6 507,2 224,6
10 607,0 143,7 588,9 160,6 570,3 179,9 548,6 202,2 521,5 227,9
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.
leaving water
Evaporator
temp. (°C)
ALS 25 30 35 40
Unit
size Cooling Power Cooling Power Cooling Power Cooling Power
capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 294,3 97,0 279,5 106,8 264,0 117,7 247,4 129,7
5 302,7 98,6 287,6 108,5 271,6 119,4 254,7 131,5
6 311,2 100,3 295,8 110,3 279,5 121,2 262,2 133,3
081.2 7 319,8 102,1 304,0 112,1 287,4 123,0 269,6 135,1
8 328,4 103,8 312,4 113,9 295,4 124,9 277,3 137,0
9 337,3 105,7 320,8 115,8 303,5 126,9 285,0 139,0
10 346,2 107,6 329,3 117,8 311,5 128,9 292,7 141,0
4 341,4 97,6 325,5 107,6 308,8 118,7 291,4 130,9
5 351,4 99,1 335,2 109,2 318,2 120,3 300,3 132,5
6 361,6 100,7 345,0 110,8 327,6 122,0 309,4 134,2
094.2 7 371,9 102,3 355,0 112,5 337,3 123,7 318,6 135,9
8 382,4 104,0 365,1 114,2 346,9 125,4 327,9 137,7
9 393,0 105,7 375,3 116,0 356,8 127,2 337,4 139,6
10 403,7 107,4 385,7 117,8 366,8 129,1 346,9 141,4
4 365,0 109,2 347,8 120,5 329,6 132,9 310,6 146,7
5 375,6 111,0 357,9 122,3 339,5 134,8 320,0 148,5
6 386,3 112,8 368,2 124,2 349,3 136,7 329,6 150,4
101.2 7 397,1 114,7 378,6 126,1 359,4 138,6 339,3 152,4
8 408,0 116,6 389,2 128,0 369,6 140,6 348,9 154,4
9 419,2 118,5 399,9 130,0 379,9 142,7 358,8 156,5
10 430,4 120,5 410,8 132,1 390,3 144,8 368,8 158,7
4 410,8 125,2 390,5 137,9 369,3 151,9 347,0 167,5
5 422,7 127,4 401,9 140,1 380,3 154,2 357,5 169,7
6 434,8 129,6 413,6 142,4 391,4 156,4 368,1 172,0
114.2 7 447,0 131,8 425,4 144,7 402,7 158,8 378,9 174,4
8 459,4 134,1 437,2 147,0 414,1 161,2 389,9 176,8
9 471,8 136,5 449,2 149,5 425,6 163,7 400,9 179,3
10 484,5 138,9 461,4 151,9 437,2 166,2 412,0 181,9
4 443,1 139,0 421,1 153,2 397,8 168,9 373,5 186,3
5 455,7 141,4 433,2 155,6 409,5 171,3 384,7 188,8
6 468,5 143,8 445,5 158,1 421,4 173,9 396,0 191,3
125.2 7 481,4 146,3 457,9 160,6 433,2 176,5 407,4 193,9
8 494,6 148,9 470,5 163,3 445,3 179,1 418,8 196,6
9 507,7 151,5 483,2 166,0 457,5 181,9 430,5 199,4
10 521,1 154,2 496,0 168,7 469,8 184,7 442,3 202,3
4 508,0 139,9 489,5 158,9 471,0 179,2 449,8 201,0
5 522,1 142,3 503,7 161,1 484,9 181,4 463,1 203,6
6 536,2 144,7 518,0 163,3 498,8 183,7 476,4 206,3
142.2 7 550,6 147,0 532,2 165,6 512,6 186,1 489,8 209,1
8 565,1 149,4 546,8 167,9 527,1 188,7 503,5 212,1
9 580,0 151,9 561,8 170,3 541,7 191,3 517,3 215,3
10 595,1 154,4 577,0 172,9 556,6 194,2 531,6 218,7
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.
leaving water
Evaporator
temp. (°C)
ALS 25 30 35 40
Unit
size Cooling Power Cooling Power Cooling Power Cooling Power
capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 299,7 93,5 285,2 103,0 269,9 113,5 253,6 125,2
5 308,4 95,0 293,5 104,6 277,8 115,2 261,2 126,8
6 317,1 96,6 301,9 106,2 285,9 116,8 268,9 128,5
081.2 7 326,0 98,2 310,5 107,9 294,1 118,5 276,8 130,2
8 335,1 99,9 319,1 109,6 302,4 120,3 284,7 132,0
9 344,1 101,6 327,9 111,4 310,8 122,1 292,7 133,8
10 353,3 103,4 336,7 113,2 319,3 124,0 300,8 135,7
4 336,1 100,7 320,0 111,0 303,1 122,4 285,4 134,9
5 345,9 102,4 329,5 112,7 312,3 124,1 294,1 136,7
6 355,8 104,1 339,0 114,5 321,4 125,9 302,9 138,5
094.2 7 365,8 105,8 348,7 116,3 330,7 127,7 311,7 140,3
8 376,0 107,6 358,5 118,1 340,1 129,6 320,8 142,2
9 386,3 109,4 368,4 120,0 349,7 131,5 329,9 144,2
10 396,7 111,2 378,4 121,9 359,3 133,5 339,2 146,2
4 368,2 107,2 351,0 118,3 333,1 130,5 314,2 144,0
5 378,9 108,9 361,4 120,1 343,0 132,3 323,7 145,8
6 389,8 110,7 371,8 121,9 353,1 134,2 333,5 147,7
101.2 7 400,8 112,5 382,4 123,7 363,3 136,0 343,2 149,6
8 411,9 114,3 393,2 125,6 373,7 138,0 353,2 151,6
9 423,2 116,1 404,0 127,5 384,1 139,9 363,2 153,6
10 434,5 118,0 415,1 129,5 394,7 142,0 373,4 155,6
4 414,8 118,0 395,2 130,0 374,8 143,3 353,5 158,0
5 427,0 119,9 407,1 132,0 386,2 145,3 364,4 160,0
6 439,4 121,8 419,1 134,0 397,8 147,3 375,5 162,0
114.2 7 452,0 123,8 431,2 136,0 409,5 149,4 386,7 164,1
8 464,8 125,9 443,5 138,2 421,3 151,6 398,1 166,3
9 477,7 128,0 456,0 140,3 433,3 153,8 409,6 168,6
10 490,8 130,1 468,6 142,5 445,4 156,1 421,2 170,9
4 453,3 127,4 432,2 140,5 410,2 155,0 387,1 171,1
5 466,6 129,5 445,1 142,6 422,6 157,1 399,0 173,2
6 480,0 131,5 458,1 144,7 435,1 159,3 411,1 175,4
125.2 7 493,7 133,6 471,3 146,9 447,8 161,5 423,3 177,6
8 507,5 135,8 484,6 149,1 460,7 163,8 435,6 179,9
9 521,5 138,0 498,1 151,4 473,7 166,1 448,2 182,3
10 535,7 140,3 511,8 153,8 486,9 168,5 460,8 184,7
4 512,2 142,3 493,6 161,3 474,5 181,6 452,6 203,7
5 526,5 144,7 507,9 163,6 488,6 184,0 465,9 206,4
6 540,9 147,1 522,4 165,8 502,6 186,4 479,2 209,3
142.2 7 555,5 149,6 537,0 168,2 516,9 189,0 492,9 212,3
8 570,4 152,0 551,8 170,6 531,4 191,7 506,6 215,5
9 585,5 154,6 567,0 173,2 546,2 194,5 520,7 218,9
10 601,1 157,3 582,5 175,9 561,3 197,6 535,2 222,6
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.
leaving water
Evaporator
temp. (°C)
ALS
25 30 35 40 45 50
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capac. input capac. input capac. input capac. input capac. input capac. input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 324,3 82,0 310,1 90,5 295,1 99,8 279,4 110,1 262,8 121,5 245,3 134,0
5 334,2 83,2 319,6 91,8 304,3 101,1 288,3 111,4 271,4 122,7 253,5 135,2
6 344,2 84,4 329,3 93,0 313,7 102,4 297,4 112,7 280,0 124,0 261,7 136,5
081.2 7 354,5 85,7 339,2 94,3 323,2 103,7 306,5 114,1 288,9 125,4 270,2 137,9
8 364,8 86,9 349,2 95,7 332,9 105,1 315,8 115,5 297,8 126,8 278,7 139,3
9 375,3 88,3 359,3 97,0 342,7 106,5 325,3 116,9 306,8 128,3 287,4 140,7
10 386,0 89,6 369,7 98,4 352,7 108,0 334,8 118,4 316,1 129,8 296,2 142,2
4 367,6 91,3 350,9 100,7 333,7 110,9 315,6 122,2 296,7 134,6 276,9 148,4
5 378,9 92,7 361,9 102,1 344,3 112,4 325,8 123,7 306,5 136,1 286,2 149,8
6 390,5 94,1 373,2 103,6 355,1 113,9 336,2 125,2 316,5 137,6 295,7 151,3
094.2 7 402,3 95,6 384,5 105,1 366,0 115,4 346,7 126,8 326,6 139,2 305,3 152,8
8 414,2 97,1 396,1 106,6 377,2 117,0 357,4 128,4 336,8 140,8 315,1 154,4
9 426,3 98,6 407,7 108,2 388,4 118,7 368,3 130,0 347,2 142,5 325,1 156,1
10 438,6 100,1 419,7 109,8 399,9 120,3 379,4 131,7 357,7 144,2 335,2 157,8
4 395,3 101,8 377,3 112,2 358,5 123,6 338,8 136,2 318,3 150,1 296,7 165,5
5 407,3 103,4 388,8 113,9 369,6 125,3 349,5 137,9 328,7 151,8 306,6 167,1
6 419,6 105,0 400,7 115,5 381,0 127,0 360,6 139,6 339,2 153,5 316,7 168,8
101.2 7 432,0 106,7 412,7 117,2 392,6 128,8 371,6 141,4 349,8 155,3 326,9 170,6
8 444,6 108,4 424,8 119,0 404,3 130,6 382,9 143,2 360,6 157,1 337,2 172,4
9 457,3 110,1 437,1 120,8 416,2 132,4 394,3 145,1 371,5 159,0 347,6 174,2
10 470,3 111,8 449,6 122,6 428,2 134,3 405,9 147,0 382,6 160,9 358,2 176,2
4 457,3 106,9 436,9 117,9 415,8 129,9 393,8 143,2 370,8 157,9 346,6 174,1
5 471,6 108,5 450,8 119,5 429,1 131,6 406,6 144,9 383,0 159,5 358,5 175,7
6 486,0 110,1 464,7 121,2 442,7 133,3 419,6 146,6 395,5 161,2 370,4 177,4
114.2 7 500,7 111,8 479,0 122,9 456,4 135,1 432,9 148,4 408,3 163,0 382,6 179,1
8 515,8 113,4 493,5 124,7 470,4 136,9 446,4 150,2 421,3 164,8 395,0 181,0
9 530,9 115,2 508,2 126,5 484,6 138,7 460,0 152,1 434,4 166,7 407,6 182,8
10 546,3 116,9 523,1 128,3 499,0 140,6 473,9 154,0 447,7 168,7 420,3 184,8
4 493,7 119,1 471,7 131,3 448,7 144,7 424,6 159,6 399,4 176,0 373,0 194,3
5 508,8 120,9 486,3 133,2 462,7 146,6 438,2 161,5 412,4 177,9 385,6 196,1
6 524,2 122,8 501,2 135,1 477,1 148,6 452,0 163,4 425,8 179,8 398,3 198,0
125.2 7 539,8 124,7 516,2 137,0 491,6 150,5 466,0 165,4 439,2 181,8 411,1 199,9
8 555,7 126,6 531,5 139,0 506,4 152,6 480,3 167,5 452,9 183,9 424,2 202,0
9 571,6 128,6 547,1 141,1 521,4 154,7 494,7 169,6 466,7 186,0 437,5 204,1
10 588,0 130,6 562,8 143,2 536,7 156,8 509,4 171,8 480,8 188,2 451,0 206,2
4 542,1 117,3 519,9 135,2 500,7 153,7 482,3 173,4 461,8 194,7 436,8 217,9
5 556,6 119,7 534,8 137,1 515,8 155,4 497,1 175,0 476,2 196,5 450,6 220,1
6 571,2 122,2 549,8 139,0 530,9 157,0 512,1 176,6 490,8 198,3 464,5 222,5
142.2 7 586,0 124,7 564,9 141,0 546,2 158,7 527,2 178,3 505,6 200,2 478,6 224,9
8 600,9 127,1 580,3 143,0 561,8 160,5 542,7 180,1 520,7 202,3 493,1 227,5
9 616,2 129,6 596,1 145,0 577,7 162,3 558,5 182,0 536,1 204,5 507,9 230,3
10 631,9 132,2 612,2 147,2 594,0 164,2 574,8 184,0 552,0 206,8 523,2 233,2
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.
leaving water
Evaporator
temp. (°C)
ALS
25 30 35 40 45
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capacity input capacity input capacity input capacity input capacity input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 317,7 85,9 303,2 94,7 288,0 104,4 272,1 115,1 255,2 126,9
5 327,3 87,2 312,4 96,1 296,9 105,8 280,6 116,5 263,3 128,3
6 336,9 88,6 321,8 97,5 306,0 107,2 289,3 118,0 271,6 129,7
081.2 7 346,8 90,0 331,3 98,9 315,1 108,7 298,0 119,5 280,0 131,2
8 356,8 91,4 340,9 100,4 324,3 110,2 306,9 121,0 288,5 132,8
9 366,9 92,8 350,7 101,9 333,8 111,8 315,9 122,6 297,2 134,4
10 377,2 94,3 360,6 103,5 343,4 113,4 325,2 124,2 306,0 136,0
4 358,4 96,5 341,6 106,2 324,0 116,9 305,7 128,7 286,3 141,7
5 369,3 98,0 352,1 107,8 334,1 118,6 315,3 130,4 295,6 143,4
6 380,3 99,6 362,7 109,5 344,4 120,2 325,2 132,1 305,0 145,1
094.2 7 391,5 101,3 373,6 111,2 354,8 122,0 335,2 133,8 314,6 146,8
8 403,0 102,9 384,5 112,9 365,4 123,8 345,3 135,6 324,2 148,6
9 414,5 104,6 395,7 114,7 376,1 125,6 355,6 137,5 334,1 150,5
10 426,3 106,4 407,0 116,5 386,9 127,5 366,0 139,4 344,1 152,4
4 384,5 108,0 366,1 118,9 347,0 130,8 327,1 144,1 306,1 158,7
5 396,0 109,8 377,3 120,7 357,7 132,7 337,3 146,0 315,8 160,6
6 407,6 111,6 388,5 122,6 368,6 134,6 347,7 147,9 325,8 162,5
101.2 7 419,5 113,4 399,8 124,5 379,5 136,6 358,2 149,9 335,8 164,5
8 431,4 115,4 411,4 126,5 390,5 138,6 368,8 151,9 346,0 166,6
9 443,6 117,3 423,0 128,5 401,7 140,7 379,5 154,1 356,2 168,7
10 455,9 119,3 434,9 130,6 413,1 142,8 390,4 156,2 366,6 170,8
4 447,8 112,0 427,2 123,3 405,8 135,8 383,6 149,6 360,2 164,9
5 461,6 113,7 440,6 125,2 418,6 137,7 395,9 151,5 372,0 166,7
6 475,5 115,5 454,0 127,0 431,7 139,6 408,3 153,4 384,0 168,6
114.2 7 489,7 117,4 467,8 128,9 444,9 141,5 421,1 155,3 396,2 170,6
8 504,2 119,2 481,6 130,9 458,3 143,5 434,0 157,4 408,5 172,6
9 518,8 121,2 495,8 132,8 471,9 145,6 447,0 159,4 421,1 174,7
10 533,6 123,1 510,1 134,9 485,7 147,7 460,2 161,6 433,8 176,8
4 482,6 125,2 460,2 137,9 436,9 151,9 412,4 167,4 386,9 184,6
5 497,2 127,2 474,3 139,9 450,5 153,9 425,5 169,5 399,3 186,6
6 512,0 129,2 488,6 142,0 464,2 156,1 438,7 171,6 412,0 188,8
125.2 7 526,9 131,3 503,1 144,2 478,2 158,3 452,1 173,8 424,8 191,0
8 542,1 133,5 517,7 146,4 492,2 160,6 465,7 176,1 437,9 193,2
9 557,6 135,7 532,6 148,7 506,6 162,9 479,4 178,5 451,1 195,6
10 573,1 137,9 547,7 151,0 521,1 165,3 493,4 180,9 464,4 198,0
4 531,4 125,4 510,9 143,5 492,3 162,6 473,2 182,9 451,1 205,0
5 545,9 127,8 525,6 145,5 507,2 164,4 487,7 184,8 464,8 207,3
6 560,5 130,2 540,5 147,5 522,0 166,2 502,3 186,8 478,9 209,6
142.2 7 575,2 132,6 555,6 149,5 537,1 168,1 517,0 188,8 493,1 212,1
8 590,1 135,0 570,9 151,5 552,4 170,0 532,1 190,9 507,6 214,6
9 605,4 137,4 586,5 153,7 568,1 172,1 547,5 193,2 522,4 217,4
10 621,1 139,9 602,5 155,9 584,1 174,3 563,3 195,7 537,6 220,4
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.
leaving water
Evaporator
temp. (°C)
ALS
25 30 35 40 45 50
Unit
Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
size
capac. input capac. input capac. input capac. input capac. input capac. input
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 319,2 81,4 305,3 89,9 290,9 99,3 275,5 109,6 259,5 121,0 242,2 133,5
5 328,9 82,6 314,6 91,1 299,8 100,5 284,2 110,8 267,8 122,2 250,2 134,7
6 338,6 83,7 324,1 92,3 308,9 101,7 293,1 112,1 276,2 123,5 258,3 136,0
081.2 7 348,5 84,9 333,7 93,6 318,3 103,0 302,0 113,4 284,8 124,8 266,5 137,3
8 358,6 86,2 343,5 94,9 327,6 104,4 311,0 114,8 293,5 126,1 274,9 138,6
9 368,8 87,4 353,3 96,2 337,2 105,7 320,3 116,1 302,4 127,5 283,4 140,0
10 379,2 88,7 363,4 97,6 346,9 107,1 329,6 117,6 311,3 129,0 292,0 141,5
4 354,4 89,7 338,8 99,1 322,7 109,4 305,8 120,7 287,9 133,3 269,1 147,2
5 365,1 91,0 349,2 100,4 332,6 110,8 315,4 122,1 297,3 134,7 278,0 148,5
6 375,9 92,3 359,7 101,8 342,8 112,2 325,2 123,5 306,6 136,1 287,0 149,9
094.2 7 386,9 93,7 370,3 103,2 353,1 113,6 335,2 125,0 316,2 137,5 296,2 151,4
8 398,1 95,0 381,3 104,6 363,6 115,1 345,2 126,5 325,8 139,1 305,4 152,8
9 409,5 96,4 392,2 106,1 374,2 116,6 355,4 128,1 335,7 140,6 314,9 154,4
10 420,9 97,9 403,4 107,6 385,0 118,1 365,8 129,6 345,7 142,2 324,5 156,0
4 380,2 99,9 363,4 110,3 345,8 121,8 327,5 134,5 308,2 148,5 287,9 164,0
5 391,4 101,3 374,3 111,8 356,4 123,3 337,7 136,0 317,9 150,1 297,3 165,6
6 402,9 102,8 385,4 113,4 367,1 124,9 348,0 137,6 327,9 151,7 306,7 167,1
101.2 7 414,5 104,3 396,6 115,0 378,0 126,6 358,5 139,3 337,9 153,3 316,4 168,8
8 426,3 105,9 408,0 116,6 388,9 128,2 369,1 141,0 348,2 155,0 326,1 170,4
9 438,3 107,5 419,6 118,2 400,2 129,9 379,8 142,7 358,5 156,8 336,0 172,2
10 450,3 109,1 431,2 119,9 411,4 131,7 390,7 144,5 369,0 158,6 346,1 174,0
4 444,8 105,5 425,5 116,5 405,3 128,6 384,3 142,0 362,3 156,7 339,3 173,1
5 458,3 107,0 438,6 118,1 418,0 130,2 396,6 143,5 374,1 158,3 350,6 174,6
6 472,1 108,6 451,9 119,7 430,9 131,8 409,1 145,2 386,1 159,9 362,0 176,2
114.2 7 486,2 110,1 465,6 121,3 444,2 133,5 421,8 146,9 398,4 161,6 373,8 177,9
8 500,4 111,7 479,3 123,0 457,5 135,2 434,6 148,6 410,8 163,3 385,7 179,6
9 514,8 113,3 493,4 124,7 471,0 137,0 447,6 150,4 423,3 165,1 397,7 181,3
10 529,5 115,0 507,6 126,4 484,7 138,7 461,0 152,2 436,1 167,0 410,0 183,2
4 479,3 117,4 458,3 129,7 436,5 143,1 413,6 158,1 389,7 174,7 364,4 193,1
5 493,7 119,1 472,3 131,4 450,0 144,9 426,6 159,9 402,2 176,4 376,4 194,8
6 508,2 120,9 486,5 133,2 463,7 146,8 439,8 161,7 414,9 178,2 388,6 196,6
125.2 7 523,1 122,6 500,7 135,0 477,5 148,6 453,3 163,6 427,8 180,1 401,0 198,4
8 538,1 124,5 515,3 136,9 491,6 150,6 466,8 165,5 440,8 182,1 413,5 200,3
9 553,4 126,3 530,1 138,8 505,9 152,5 480,6 167,5 454,1 184,1 426,3 202,3
10 568,8 128,2 545,1 140,8 520,4 154,5 494,6 169,6 467,6 186,1 439,2 204,3
4 535,9 116,2 513,9 134,4 495,0 153,1 476,8 172,8 456,8 194,0 432,4 217,1
5 550,2 118,7 528,6 136,3 509,8 154,7 491,4 174,4 470,9 195,8 445,8 219,3
6 564,6 121,1 543,3 138,2 524,6 156,3 506,1 176,0 485,3 197,6 459,6 221,6
142.2 7 579,1 123,5 558,1 140,1 539,6 158,0 521,0 177,6 499,8 199,5 473,4 224,0
8 593,7 125,9 573,2 142,1 554,8 159,7 536,1 179,3 514,5 201,4 487,5 226,5
9 608,6 128,4 588,5 144,1 570,4 161,4 551,6 181,1 529,6 203,5 502,0 229,2
10 623,8 130,9 604,3 146,1 586,2 163,3 567,3 183,0 545,1 205,8 516,9 232,0
Note: The power input is for compressor only; cooling cap. and power input referred to evap. fouling factor=0,0176m2 °C/kW.
evaporatore °C
acqua uscita
Temperatura
Taglia 55
40 45 50
unità
ALS Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot. Pot.
Frigor. Assor. Recup Frigor. Assor. Recup Frigor. Assor. Recup Frigor. Assor. Recup
(kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)
4 304,6 90,4 383,2 290,2 99,7 378,2 275,1 109,9 373,5 259,1 121,2 368,9
5 313,4 91,8 393,0 298,7 101,2 387,9 283,3 111,4 382,9 267,0 122,7 378,0
6 322,5 93,3 403,3 307,4 102,7 397,8 291,7 113 392,6 275,0 124,3 387,3
081.2 7 331,6 94,8 413,6 316,3 104,3 408,0 301,1 114,6 403,2 283,1 125,9 396,7
8 340,8 96,4 424,1 325,2 105,9 418,2 308,7 116,2 412,2 291,3 127,6 406,3
9 350,3 98 434,9 334,2 107,5 428,4 317,4 117,9 422,2 299,6 129,3 416,0
10 359,7 99,6 445,5 343,4 109,2 439,0 326,1 119,7 432,4 308,1 131,1 426,0
4 349,3 92,7 428,7 333,7 102,4 423,0 317,3 112,9 417,3 300,2 124,6 412,1
5 359,7 94,1 440,2 343,8 103,8 434,2 327,1 114,4 428,3 309,5 126,1 422,5
6 370,3 95,5 451,8 354,1 105,3 445,6 336,9 115,9 439,2 319,1 127,6 433,3
094.2 7 381,2 97 463,9 364,5 106,8 457,2 347,0 117,5 450,6 328,8 129,2 444,3
8 392,0 98,5 475,8 375,0 108,3 468,8 357,2 119 461,9 338,5 130,8 455,2
9 403,1 100 488,0 385,7 109,9 480,7 367,5 120,7 473,6 348,5 132,5 466,6
10 414,3 101,5 500,3 396,5 111,5 492,8 378,0 122,3 485,3 358,6 134,2 478,0
4 374,3 103,4 463,4 357,3 114,2 457,4 339,6 126 451,6 321,0 139,1 446,3
5 385,2 105 475,5 367,9 115,8 469,2 349,9 127,7 463,3 330,9 140,8 457,5
6 396,5 106,6 488,0 378,7 117,5 481,3 360,3 129,4 475,0 340,8 142,5 468,8
101.2 7 407,7 108,3 500,5 389,7 119,2 493,6 370,7 131,2 486,8 351,0 144,3 480,4
8 419,3 110 513,4 400,8 121 506,1 381,5 133 499,1 361,3 146,1 492,2
9 430,8 111,7 526,2 411,9 122,7 518,6 392,3 134,8 511,3 371,7 148 504,1
10 442,6 113,5 539,4 423,4 124,6 531,6 403,2 136,7 523,7 382,2 149,9 516,1
4 412,9 116 513,0 393,9 128 506,2 374,0 141,3 499,8 353,1 156,1 493,9
5 424,8 117,8 526,3 405,5 129,9 519,3 385,1 143,2 512,5 363,9 158 506,2
6 437,0 119,6 539,9 417,3 131,8 532,6 396,6 145,1 525,4 374,9 159,9 518,8
114.2 7 449,4 121,5 553,8 429,1 133,7 545,9 408,0 147,1 538,4 385,9 161,9 531,4
8 461,9 123,4 567,7 441,3 135,7 559,7 419,7 149,2 551,8 397,1 164 544,3
9 474,6 125,4 582,0 453,5 137,7 573,5 431,6 151,3 565,4 408,5 166,1 557,4
10 487,4 127,4 596,4 465,9 139,8 587,5 443,4 153,4 578,9 419,9 168,3 570,6
4 458,3 129,7 570,4 436,8 143 562,4 414,2 157,7 554,7 390,5 174 547,6
5 471,8 131,7 585,4 449,7 145,1 577,0 426,6 159,9 568,9 402,5 176,2 561,3
6 485,3 133,9 600,6 462,7 147,3 591,7 439,2 162,1 583,3 414,5 178,4 575,1
125.2 7 499,0 136,1 616,0 476,0 149,5 606,7 452,0 164,4 597,9 426,8 180,8 589,4
8 512,9 138,3 631,7 489,4 151,9 622,1 464,9 166,7 612,7 439,2 183,1 603,6
9 526,9 140,6 647,5 503,0 154,2 637,5 478,0 169,2 627,8 451,7 185,6 618,2
10 541,2 143 663,7 516,7 156,6 653,1 491,2 171,6 642,9 464,4 188,1 632,9
4 519,3 129,5 629,3 499,8 148,1 628,5 481,6 167,5 629,6 462,3 188,4 631,2
5 533,5 131,9 645,4 514,2 150,1 644,4 496,0 169,4 645,4 476,3 190,4 646,7
6 547,8 134,2 661,5 528,8 152,1 660,5 510,4 171,4 661,3 490,2 192,6 662,3
142.2 7 562,3 136,6 677,9 543,4 154,1 676,6 524,8 173,4 677,3 504,4 194,8 678,2
8 576,9 138,9 694,3 558,3 156,2 693,1 539,8 175,4 693,7 518,9 197,1 694,5
9 591,8 141,3 711,1 573,4 158,3 709,7 554,8 177,6 710,4 533,6 199,6 711,2
10 607,0 143,7 728,2 588,9 160,6 727,0 570,3 179,9 727,7 548,6 202,2 728,3
270
240
210
180 A
150 B
120
10 15 20 25 30 35
Note: to have the useful hydraulic lift is necessary to subtract the evaporator pressure drop to the total hydraulic lift.
SE ST/LN/XN 142.2
XE ST/LN/XN 142.2
XE SE/LN/XN 114.2 – 125.2
SE XXN 142.2
SE XXN 114.2 – 125.2
HA 114.2 – 125.2
SE ST/LN/XN 081.2
HA 081.2
A B