VC1008F-D Spec - Mar13
VC1008F-D Spec - Mar13
PRODUCT DESCRIPTION
The Venticator, VC1008FD is a simple, low
cost, state-of-the-art, maintenance-free infrared
carbon dioxide transmitter for installation in the
climate zone or in the ventilation duct.
The VC1008FD measures the carbon dioxide
concentration in the ambient air up to 2,000
ppm and transforms the data into 0-10 V or 4-
20mA output signals and display the
VC1008FD
measurement on a LC Display.
IP20 wall housing
VC1008FD helps you save money by with LC display
decreasing your energy consumption while
maintaining a healthier indoor climate!
FEATURES APPLICATIONS
Using patented state-of-the-art infrared (NDIR) VC1008FD is an extremely cost-effective
wave-guide technology and offers reliable sensor/transmitter for building climate control
measurements and other processes where measurement of
measurement range: 0 - 2 000 ppm CO2 carbon dioxide concentration is required.
or 0 - 5 000 ppm CO2 By controlling the ventilation based on actual
analogue outputs (jumper select): demand, it helps to reduce energy consumption
while maintaining a healthy indoor climate!
OUT: 0 - 10 V (= 0 - 2 000 ppm CO2)
or 4 – 20mA (= 0 - 2 000 ppm CO ) The two different housing options and output
2 configurations (current and voltage signal)
Voltage-free contact pre-set at 800, 1,000 or makes the VC1008FD most suitable for general
8,000ppm (jumper select) applications.
maintenance-free in normal applications
non-frill design; cost-optimized for connection
to DDCs
Two different housing options
1) IP45 wall housing
2) IP65 duct housing
CONNECTIONS
Screw terminals
1 G+ 24 V AC/DC (+)
2 G0 System ground (-)
3 Out Linear output (+) 0-10 V = 0 – 2 000 ppm CO2
4 NO Normally opened contact of relay output
5 COM Common contact of relay output
6 NC Normally closed contact of relay output
General Performance
Compliance with .............................................. EMC directive 89/336/EEC
Operating Temperature Range ....................... 0 - 50 °C
Storage Temperature Range ........................... -40 to +70 °C (display model -D: -20 to +70 °C )
Operating Humidity Range .............................. 0 to 95% RH (non-condensing)
Operating Environment ................................... residential, commercial and industrial spaces 1
Warm-up Time ................................................ 1 min. (@ full specs 15 minutes)
Sensor Life Expectancy ................................... > 15 years
Maintenance Interval ....................................... no maintenance required 2
Electrical
Power Input ..................................................... 24 VAC/VDC ±20%, 50 Hz (half-wave rectifier input)
Power Consumption ........................................ < 1 Watt average
Connection screw terminal ............................. 6 x 1,5 mm2 for power input (G+, G0), output (Out), and relay contacts (NC,
........................................................................ NO & COM).
CO2 Measurement
Sensing method .............................................. Infrared (NDIR) wave-guide technology with Automatic Background
Calibration (ABC) and passive gas diffusion (no moving parts)
Response Time (T1/e) ....................................... < 10 sec. @ 30 cc/min. flow rate
< 3 min. diffusion time
Repeatability .................................................... ± 20 ppm ± 1 % of reading
Accuracy 2 ....................................................... ± 70 ppm ± 3 % of reading
Annual Zero Drift 2 ........................................... < ± 10 ppm
Pressure Dependence .................................... + 1.6 % reading per hPa
Installation support ......................................... Background level calibration adjustment with jumper trigger (bCAL).
Outputs
Voltage signal terminal CO2 3
Output measuring range .................................. 0 ~ 2,000ppm or 0 ~ 5,000ppm (jumper selection)
Output linear conversion range ....................... 0 -10 VDC for 0 - 2 000 ppmvol. or 4 – 20mA for 0 - 2 000 ppmvol.
D/A resolution .................................................. 10 bits, 10 mV or 0.016mA
D/A conversion accuracy.................................. ± 2 % of reading ± 50 mV
Electrical characteristics ................................... Voltage output - ROUT < 100 Ohm, RLOAD > 5 kOhm
........................................................................ Current output – RLOAD < 500 Ohm
Relay output
Relay contact setting ................................... 800, 1,000 or 8,000ppm (jumper selection)
Relay contact rating .................................... isolated N.O. & N.C., 1mA/5V up to 1A, 24V ac/dc
Housing options
WALL HOUSING (standard) DUCT HOUSING (model –KS)
Dim.: 100 x 80 x 27 mm (H x W x D) Dim.: 142 x 84 x 46 mm (H x W x D)
Protection class: IP20 Duct probe length: 245 mm
60 mm hole separation for European (adjustable according to duct dimension)
standard J-boxes. Protection class: IP65
VC1008FD VC1008FD-KS
Note 1: The SO2 enriched environments are excluded.
Note 2: In normal IAQ applications (@ NTP). Accuracy is defined after minimum 3 weeks of continuous operation.
The tolerance of the span calibration gas (2 % unless otherwise requested) and test gas adds to the total incertainty.
Note 3: The specifications are valid for the output load connected to ground G0. Other outputs and measurement ranges are available per request.