AVR CONVERSION INSTRUCTIONS

FITTING KIT 45-0053


FOR USE WITH MX341 AVR Part No. E000-23410
PERMANENT MAGNET GENERATORS ONLY
Fitting kit 45-0053 comprises the following:- The MX341 AVR is fully interchangeable with the following:-

1 - Adjustment & Identity Label E00-13418 Series 3 4 Pole 450-11700


1 - MX341 Instruction Sheet NP7-006:5513 Series 3 3 Phase Sensing 450-11800**
Series 3 VAr, AVR E000-23010
Series 3 VAr, AVR (3 Phase Sensing) E000-23015**
Series 3 Special Slope AVR E000-23000
Series 3 LA32 E000-23020
Series 3 LA33 E000-23030
** For 3 phase sensing unit see final section on 3 phase sensing unit.

Figure 1: Old Serie 3 AVR

Figure 2: MX341 AVR-E000-2412


INSTRUCTIONS
Refer to figure 1 and 2 (above) the following instructions refer to items 1-5 respectively on above diagrams.
Refer to figure 3 and 4 (overleaf) for instruction 6 and AVR and auxiliary terminal position.

1. Connect AVR wires to terminals with identical markings. Cut off and insulate lead P1 if fitted.
2. Select correct frequency tapping 50Hz or 60Hz, 4 and 6 pole machines.
3. Select correct link on C, B, A, for size of generator.
4. Links will be connected as shown on AVR, DO NOT MOVE THESE LINKS unless your old AVR (figure 1) is type 450-11800
with separate 3 phase sensing unit. See section overleaf on 3 phase sensing unit.
5. DO NOT REMOVE LINK MARKED K1-K2 on AVR terminals unless a protection trip was fitted across K1-K2 on previous
AVR.
Refer to figure 3, 4, 5 and 6 overleaf.
6. Remove generator terminal box lid, link together auxiliary terminals marked 1 and 2 or short wires 1 and 2 together on the
same terminal.
WARNING do not link 1&2 on generators with the designation C504/C506 pre October 1975 or C604/C606 pre April
1976 – If in doubt contact Stamford’s Service Department on 44(0) 1780484732, FAX 44 (0) 01780 484104

NOTE. The MX341 has two pins marked ‘2’, they are connected internally, either one can be used.
Generators Types - AVR and Auxiliary Terminal Position

AVR Position Auxiliary Terminals


6

Figure 4: SC and HC Range Generator with AVR Mounted


Figure 3: C Range Generator with AVR Mounted on Frame on the Terminal Box

AUXILIARY TERMINALS SETTING UP INSTRUCTIONS

If a remote voltage trimmer is not required, short circuit Refer to MX341 instruction sheet (Publication No.
auxiliary terminal 1 and 2, as shown in figures 5 and 6. TD_MX341 GB_11.06_03, for adjustment of voltage and
stability controls.
MACHINES MANUFACTURED AFTER FEB 87
If the generator is NOT required for parallel operation or for
For machines manufactured after February 1987 a new Push- use with VAr/PF controller, adjust AVR controls marked
on auxiliary terminal arrangement is within the terminal box "DROOP" AND "TRIM" fully ANTICLOCKWISE.
(See figure 5 below). Pull-off wire marked 1 and push-on to
auxiliary terminal marked 2. For parallel operation the MX341 AVR is fully compatible with
existing droop equipment in the generator.
Remove cable marked 1
to terminal marked 2
REMOTE HAND TRIMMER : 1K Ω Part No. 071-01649

If a remote hand trimmer is required, it is connected to the


auxiliary terminal block at terminals 1 and 2 in the generator
terminal box. If a 4.7K Ω trimmer (Part No. 071-01037) is
already fitted, then the effective control will be "all at one end".
If this is unsatisfactory for fine voltage adjustment then the
Figure 5: Auxiliary Terminals after February 1987
new 1K Ω hand trimmer should be fitted.

3 PHASE SENSING UNIT


MACHINES MANUFACTURED BEFORE FEB 87
The MX341 will operate in conjunction with the existing 3
For machines manufactured before February 1987 a Stud phase sensing unit (Part No. 450-11000). The correct
arrangement is within the terminal box (See figure 6 below). connection links must be made on the AVR for 3 phase
Unscrew stud holding wire marked 1 remove all washers and sensing. Refer to the MX341 instruction sheet (Publication
place onto auxiliary terminal marked 2. No. TD_MX341 GB_11.06_03
Remove cable marked 1
to terminal marked 2
Should the 3 phase sensing unit be faulty, a direct
replacement is available from our Parts Department.

IMPORTANT ! SEE ITEM 4 OVERLEAF.

DO NOT CONNECT AVR IN THE 3 PHASE SENSING


MODE UNLESS A SEPERATE 3 PHASE SENSING UNIT IS
ALREADY FITTED OR HAS BEEN PURCHASED FOR
Figure 6: Auxiliary Terminals before February 1987 FITTING WITH THE MX341 AVR