Plsed310089en Web
PB124315
PM1125H
PM1225H
PM1000H Series EasyLogic™ PM1120H/PM1125H/PM1225H meters are ideal replacements for multiple analog
meters for stand-alone metering in custom panels, switch boards, switch-gear, genset panels, motor
control centres, power factor improvement panels and OEM panel board.
PB124318
• Application
– Cost management applications
– Measurement of basic electrical parameters in control panels, motor control
panels, power distribution boards, OEM’s, Building management systems, panel
instrumentation
– Aggregation of energy consumption and cost allocation per area, per usage,
per shift and per time within the same facility
– Network management applications
– Power quality analysis (THD %)
– Demand measurement
– Measurement of Power Factor
– Phase angle between the voltage and current
– % unbalance among voltage and current
– Modbus RTU protocol RS-485 communication port for integration with energy
EasyLogic™ PM1125H front view LED display management systemMain characteristics
• Main characteristics
– Easy to install: Mounts using two retainer clips, no tools required. Compact meter with
49 mm meter depth behind the panel, connectable up to 480 V +10% AC volts L-L
without voltage transformers for installation complaint with measurement category III,
and double insulated.
– Easy to operate: Intuitive navigation with self-guided menus and Heart beat LED
PB124317
PM1000H Series
Technical specifications
General
Use on LV & MV systems with Potential transformer (PT or VT)/ Current transformer (CT) ratio programmable at site
Digital panel meters for measurement of basic electrical parameters
Instantaneous rms values
Current Average line current of 3-phase, per-phase, and calculated neutral current
Voltage Average voltage of L-L, L-N parameters, per-phase
Frequency Any available line
Real (active), reactive, and apparent power Total and per-phase
True power factor Average and per-phase signed
% Unbalance Maximum % unbalance among phases for Volts & Amps
Revolution per minute (RPM) RPM of alternator or generator when number of poles set for 2, 4, 6, 8, 12, 14 or 16 (any one pole)
Energy values stored in non-volatile memory
Delivered & Received or Forward & Reverse or Import & Export energy (4 quadrant) - Accumulated or Integrated active (Real - Wh), reactive (VARh), apparent
(VAh). 2 quadrant energy measurment in PM1120H.
Independent energy (Wh) counter with non-resettable feature.
Energy values can be set for overflow units (e.g., in kilo or mega scale) (for PM1225H)
Quadrant based registers for Reactive energy
Time counters such as meter ON Hrs, load RUN Hrs and power outage counters
Old registers facilitate retrieval of last cleared energy values and load Run Hrs. Set up counters for tracking number of edits carried out since from installation
Display
LED display: Bright red colour, 8 segment alphanumeric LED, ~ 14.2 mm (0.55 in) height, 3 rows with 4 digits per row, auto range, auto scroll
LCD display: Elegant single row, bright back lit graphical LCD display 132 (Horizontal) * 32 (Vertical) pixels. Fast in-line view, three parameters name and value
at one glance
Communication
RS-485 serial channel connection Industry standard Modbus RTU protocol
Native Plug and Play support for Schneider Electric energy management system software - EcoStruxure™ Power Monitoring Expert, EcoStruxure™ Power
Operation along with ION Setup programming support
Diagnostics
Diagnostic page indicates the healthiness of communication system, device serial number, device model number OS & RS version, communication status,
All LED segment check in LED display. In LCD display meter - alternate pixels ON/ OFF test. LCD contrast level, set back-lit time out in the range of 1 to 99
seconds
Page lock
Page lock and unlock features. Once the commonly referred page is enabled for lock feature, then the display returns to locked page in 4 minutes of inactive
time
Favourite page
Number and type of parameters can be chosen and arranged in Favourite page according to the user’s requirement
Electrical characteristics
Type of measurement True RMS, 4 quadrant power and energy, 32 samples/cycle
Measurement accuracy
Current, per-phase & average ± 0.5 % of reading
Voltage, L-N, L-L, per-phase & average ± 0.5 % of reading
Frequency ± 0.05 % for F-nominal 50/ 60 Hz ± 2 Hz
± 0.2 % for Frequency range from 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz
Power (active and apparent) ± 1.0 % for Class 1.0, ± 0.5 % for Class 0.5
Power (reactive) ± 2.0 % for Class 1.0
Power factor, per-phase & average ± 0.01 of reading
Active or real energy Class 1.0 (± 1.0 %), Class 0.5 (± 0.5 %)
Apparent energy ± 1.0 % for Class 1.0, ± 0.5 % for Class 0.5
Reactive energy Class 2.0 (± 2.0 %)
THD % ± 5 % of reading
Input-voltage
VT (PT) connection Selectable from No VT (direct), 1 VT, 2 VT to 3 VT
VT (PT) primary 100 V L-L to 999 kV L-L max
U (V) nominal (secondary) Up to 277 V L-N/ 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Operating voltage range with accuracy 80-480 V L-L ± 10 % Category III
Measured Voltage with full range 35 to 600 V L-L
Permanent overload (withstand) 750 V L-L, continuous
Impedance ≥5 MΩ
Frequency range 50/ 60 Hz ± 2
VA burden ≤0.2 VA at 240 V L-N at 50 Hz
Frequency – measurement
Nominal operating range 50/60 Hz ± 2 Hz (± 0.05 % accuracy)
Extended operating range 30 to 48 Hz, 52 to 58 Hz and 62 to 70 Hz (± 0.2 % accuracy)
Voltage input 80 to 480 V L-L ± 10 %
PM1000H Series
Technical specifications (continued)
Input-current
CT connect Solo or multi-phase current measurement by installing CT (s) in either of A1, A2, A3, A12, A23, A13, A123
phase(s)
CT primary 1 A to 32767 Amps, programmable
CT secondary 1 A or 5 Amps I-nominal (field settable)
Operating current range with accuracy 10 mA to 6 A (+1)
Measured Amps with full range 5 mA to 10 A
Suppression current 5 to 99 mA (to disregard negligible load)
Permanent overload (withstand) Continuous 10 A, 10 s/hr 50 A, 1s/hr 500 A
Impedance 0.3 mΩ
Frequency range 50/60 Hz ± 2 Hz
VA burden ≤0.1 VA at 5 A, 50 Hz
AC - control power
Operating range 48 to 277 V AC ± 10 %
Burden ≤4 VA at 240 V L-N, 50 Hz
Frequency 50/60 Hz nominal (45 to 65 Hz operating range)
Ride-through time 100 ms at 240 V L-N, 50 Hz
DC - control power
Operating range 48 to 277 V DC ± 10 % or Low Voltage DC option of 10 to 32 V DC ± 10 % for PM1125H and PM1225H
Burden ≤2 W at 240 V DC, <2 W at 24 V DC
Ride-through time 50 ms at 125 V DC
Display update
Instantaneous/ RMS parameters 1s
Demand parameters 5s
THD % (voltage and current) 5s
Power system
Phase labelling Configurable to 123, ABC, rst, pqr or ryb
Wiring configuration 13 wiring schemes (5 on front screen)
1ph, 2 w, L-N
1ph, 2 w, L-L
1ph, 3 w, L-L with N (2phase)
3ph, 3 w, Delta, Ungrounded
3ph, 3 w, Delta, Corner Grounded (+2)
3ph, 3 w, Wye, Ungrounded (+2)
3ph, 3 w, Wye Grounded (+2)
3ph, 3 w, Wye, Resistance Grounded (+2)
3ph, 4 w, Open Delta, Center-Tapped (+2)
3ph, 4 w, Delta, Center-Tapped (+2)
3ph, 4 w, Wye, Ungrounded (+2)
3ph, 4 w, Wye Grounded
3ph, 4 w, Wye, Resistance Grounded (+2)
Mechanical characteristics
Weight ~ 300 g (10.6 oz)
IP degree of protection IP 51 front side, IP 30-meter body, tested as per IEC 60529
(IP 54 with optional gasket METSEIP54GK96X96FF or upgrade to IP65 front side with Optional accessory kit
METSEIP65OP96X96FF)
Material Polycarbonate meets UL 94V-0 flammability rating
96 x 96 x 49 mm (3.78 x 3.78 x 1.93 in) (D = depth of the meter from housing mounting flange)
Dimensions W x H x D
13 mm (0.51 in) protrusion of meter from housing flange
Mounting position Vertical
Panel thickness 5 mm (0.196 in) maximum
Environmental characteristics
Operating temperature - 10 to +60º C (14 to140º F)
Storage temperature - 20 to +70º C (-4 to 158º F)
Humidity rating 5 % to 95 % RH non-condensing
Pollution degree 2
Attitude ≤2000 metres (6562 ft), Category III
Product life >7 years
Insulation category Double insulation for user accessible parts
(+1)
Additional error of ± 2 % between 10 mA to 50 mA, ± 1% between 50 mA to 100 mA
(+2)
Set up through communication
PM1000H Series
Technical specifications (continued)
Electromagnetic compatibility (tested as per IEC 61326-1)
Electrostatic discharge IEC 61000-4-2
Immunity to radiated field IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to impulse waves IEC 61000-4-5
Conducted immunity IEC 61000-4-6
Immunity to magnetic fields IEC 61000-4-8
Immunity to voltage dips IEC 61000-4-11
Emissions Emissions FCC Part 15 Class A/CE
Safety
Europe CE, as per IEC 61010-1 edition-3
US and Canada cULus as per UL61010-1 and CAN/CSA-C22.2 IEC 61010-1 edition-3, for 480 V AC L-L
Measurement Category (Voltage inputs) Category III up to 480 V L-L
Overvoltage Category (Control power) Category III up to 300 V L-N
Dielectric As per IEC/UL 61010-1 edition-3
Protective Class Category II, Double insulated for user accessible parts
Green premium EOL, REACH, PEP, RoHS complied
Communication
RS-485 port Modbus RTU: 2-Wires, 4800, 9600, 19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity is Odd or
Even, 2 stop bits if none.
DLF3000: Firmware update through communication port
In PM1120H, measurement and display of any one power parameter at a time - configurable through set-up/ communication Energy measurement
(+3)
depends on type of power parameter selected during set up (W/Wh or VA/VAh or VAR/VARh).
(+4)
Quadrant based VARh: Measurement of total or net VARh on display and quadrant based VARh through communication.
90.5
(3.56)
96 90.5
(3.78) (3.56)
96 48.8 13.9
(3.78) (1.92) (0.54)
92.0+0.8 K
AC
(3.62)+0.03 CL
K
AC
CL
(3.99)
L1 120
G
110
100
90.5
90 (3.56)
(3.56)
90.5
(3.78)
80
96
70
%A FS
G
60
50
40
30
G
20
10
48.8 (1.92)
96 13.9
(3.78) (0.54)
92.0 +0.8
<6.4
(3.62)+0.03
(<0.25)
mm
(in)
K
AC
92.0 +0.8 CL
(3.62)+0.03
ACK
CL
>
Up key: To navigate up
<
D
Right/OK key: To navigate right/
<
Enter key C
C B LED indicators
Red: Pulse
Green: Heartbeat
B B
C Alphanumeric LED/LCD display
A
D Analog load bar A
PM1125H display
E Current inputs PM1225H display
J I F Alternate source (e.g. Genset)
G RS-485
H Retainer clip
I Control power
J Voltage inputs
K Voltage line indicators
H
E F
August 2022
EasyLogic™ PM1000H Series As standards, specifications and designs develop from time to time, please