3 Check air terminals and copper tapes are securely anchored and clamped at proper
intervals /
4 Check tightness of bonding between the roof & down conductors and test link
/
5 Check all exposed equipments and metal /steel works in the roof are securely
bonded to the air termination network /
Check installation of earth temination network which composed of but not limited
to the following: Test Link, Earth Rod, Earth Pit, Main Earth Loop, etc. is carried-
6 out as per the approved shop drawing and methodology /
Check test link location is in accessible position for isolation/ disconnection of the
air termination network and enable testing of the earth termination network
7 /
Check èarth rods are driven in the approved location and are provided with earth
8 pit to allow access for bonding of main earth loop and LPS earth lead to the earth /
rod
9 Check tightness of bonding between the earth rod, main earth loop, LPS earth
lead and test link /
10 Check earth pit is provided with appropriate label, engraved "LPS Earth Below"
/
11 Lightning Protection System installation is complete as per project requirements
and is ready for testing and commissioning /
Name: Name:
Date: Date:
Designation: SUPERVISOR ELECTRICAL Designation:
Company: ISRINA RESOURCES SDN BHD Company: KLCC URUSHARTA SDN BHD