Floor standing unit

Technical data book


FXLQ-P

FXLQ20P5VEB
FXLQ25P5VEB
FXLQ32P5VEB
FXLQ40P5VEB
FXLQ50P5VEB
FXLQ63P5VEB

EEDEN20
Table of contents

FXLQ-P
1 Features 4
FXLQ-P 4

2 Specifications 5

3 Electrical data 7

4 Safety device settings 8

5 Options 9

6 Capacity tables 10
Cooling Capacity Tables 10
Heating Capacity Tables 11

7 Dimensional drawings 12

8 Centre of gravity 14

9 Piping diagrams 15

10 Wiring diagrams 16
Wiring Diagrams - Single Phase 16

11 Sound data 17
Sound Pressure Spectrum 17

3
Floor standing unit • FXLQ-P

1 Features
1-1 FXLQ-P
For perimeter zone air conditioning

1 ›› Unit can be installed as free standing model by use of optional ›› Requires very little installation space
back plate ›› Wall mounted installation facilitates cleaning beneath the unit
›› Its low height enables the unit to fit perfectly beneath a window where dust tends to accumulate
›› Stylish modern casing finished in pure white (RAL9010) and iron ›› Wired remote control can easily be integrated in the unit
grey (RAL7012) blends easily with any interior

Inverter Home leave Fan only Auto cooling- Fan speed Dry Air filter Weekly timer Infrared
operation heating steps programme remote control
changeover

Wired remote Centralised Auto-restart Self diagnosis Multi tenant


control control

4 F XLQ-P
Floor standing unit • FXLQ-P

2 Specifications
1-1 FXLQ-P
Technical Specification FXLQ20P FXLQ25P FXLQ32P FXLQ40P FXLQ50P FXLQ63P
Cooling capacity Sensible Nom. kW 1.70 2.10 2.50 3.10 3.90 4.90
capacity
Latent
capacity
Nom. kW 0.500 0.700 1.10 1.40 1.70 2.20
2
Total Nom. kW 2.2 (2) 2.8 (2) 3.6 (2) 4.5 (2) 5.6 (2) 7.1 (2)
capacity
Heating capacity Total Nom. kW 2.5 (1) 3.2 (1) 4.0 (1) 5.0 (1) 6.3 (1) 8.0 (1)
capacity
Power input - 50Hz Cooling Nom. kW 0.05 (2) 0.09 (2) 0.11 (2)
Heating Nom. kW 0.05 (1) 0.09 (1) 0.11 (1)
Power input - 60Hz Cooling Nom. kW 0.05 (2) 0.08 (2) 0.11 (2)
Heating Nom. kW 0.05 (1) 0.08 (1) 0.11 (1)
Dimensions Unit Height mm 600
Width mm 1,000 1,140 1,420
Depth mm 232
Packed Height mm 720
unit Width mm 1,128 1,268 1,548
Depth mm 346
Weight Unit kg 27 32 38
Packed unit kg 32 37 43
Casing Colour Fresh white (RAL9010) / Dark grey (RAL7012)
Heat exchanger Rows Quantity 3
Fin pitch mm 1.50
Face area m² 0.159 0.200 0.282
Stages Quantity 14
Fin Type Cross fin coil
Fan Type Sirocco fan
Air flow Cooling High m³/min 7 8 11 14 16
rate - Low m³/min 6.0 8.5 11.0 12.0
50Hz
Fan motor Drive Direct drive
Refrigerant Type R-410A
GWP 2,087.5
Control Electronic expansion valve
Sound power level Cooling High dBA 54 57 58 59
Sound pressure Cooling High dBA 35 38 39 40
level Low dBA 32 33 34 35
Heating High dBA 35 38 39 40
Low dBA 32 33 34 35
Piping connections Liquid Type Flare connection
OD mm 6,35
Gas Type Flare connection
OD mm 12.7 15.9
Drain O.D. 21 (Vinyl chloride)
Heat insulation Glass Fiber/Urethane Foam
Sound absorbing insulation Glass fiber / Urethane foam
Air filter Type Resin net
Safety devices Item 01 Fuse
02 Fan motor thermal protection
Control systems Infrared remote control BRC4C65
Wired remote control BRC1E53A / BRC1E53B / BRC1E53C / BRC1D52
Simplified wired remote control for hotel BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
applications

Electrical Specification FXLQ20P FXLQ25P FXLQ32P FXLQ40P FXLQ50P FXLQ63P


Power supply Name VE
Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220
Current - 50Hz Minimum circuit amps (MCA) A 0.3 0.6
Maximum fuse amps (MFA) A 15
Full load amps (FLA) Total A 0.2 0.5
Current - 60Hz Minimum circuit amps (MCA) A 0.3 0.5 0.6
Maximum fuse amps (MFA) A 15
Full load amps (FLA) Total A 0.2 0.4 0.5
(1)Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) |
(2)Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) |
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. |
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. |
Maximum allowable voltage range variation between phases is 2%. |
MCA/MFA: MCA = 1.25 x FLA |
MFA ≤ 4 x FLA |
Next lower standard fuse rating minimum 15A |
Select wire size based on the value of MCA |
Instead of a fuse, use a circuit breaker |

Floor standing unit • FXLQ-P 5


Floor standing unit • FXLQ-P

2 Specifications
1-1 FXLQ-P
Contains fluorinated greenhouse gases

6 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

3 Electrical data
3-1 Electrical Data
FXLQ-P

3
UNITS POWER SUPPLY IFM INPUT (W)
MODEL Hz V VOLTAGE RANGE MCA MFA kW FLA COOLING HEATING
FXLQ20P5VEB 0,3 15 0,015 0,2 49 49

FXLQ25P5VEB 0,3 15 0,015 0,2 49 49

FXLQ32P5VEB 0,6 15 0,025 0,5 90 90


MAX. 264
50 220-240
MIN. 198
FXLQ40P5VEB 0,6 15 0,025 0,5 90 90

FXLQ50P5VEB 0,6 15 0,035 0,5 110 110

FXLQ63P5VEB 0,6 15 0,035 0,5 110 110

SYMBOLS:
MCA: MIN. CIRCUIT AMPS (A)
MFA: MAX. FUSE AMPS (SEE NOTE 5)
kW : FAN MOTOR RATED OUTPUT (kW)
FLA: FULL LOAD AMPS (A)
IFM: INDOOR FAN MOTOR

NOTES :
1) VOLTAGE RANGE:
UNITS ARE SUITABLE FOR USE ON ELECTRICAL SYSTEMS WHERE VOLTAGE SUPPLIED
TO UNIT TERMINALS IS NOT BELOW OR ABOWE LISTED RANGE LIMITS.
2) MAXIMUM ALLOWABLE VOLTAGE UNBALANCE BETWEEN PHASES IS 2%.
3) MCA/MFA
MCA = 1.25 x FLA
MFA ≤ 4 x FLA
(NEXT LOWER STANDARD FUSE RATING. MIN. 15A)
4) SELECT WIRE SIZE BASED ON THE MCA.
5) INSTEAD OF FUSE, USE CIRCUIT BREAKER.
3D128572

Floor standing unit • FXLQ-P 7


Floor standing unit • FXLQ-P

4 Safety device settings


4-1 Safety Device Settings

8 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

5 Options
5-1 Options
FXLQ-P

5
Availability
FXLQ20P2VEB FXLQ32P2VEB FXLQ50P2VEB
Product name FXLQ25P2VEB FXLQ40P2VEB FXLQ63P2VEB
Option kit FXLQ20P5VEB FXLQ32P5VEB FXLQ50P5VEB
FXLQ25P5VEB FXLQ40P5VEB FXLQ63P5VEB
BRC1D52/BRC1E53A7⑤
Wired remote control ✓ ✓ ✓
BRC1E53B7⑥/BRC1E53C7⑦⑧
Wireless remote control ·HP· BRC4C65 ✓ ✓ ✓
Wireless remote control ·CO· BRC4C66 ✓ ✓ ✓
Simplified remote control (with operation mode selector button) BRC2E52C②⑧ ✓ ✓ ✓
Simplified remote control (without operation mode selector button) BRC3E52C②⑧ ✓ ✓ ✓
Remote control for hotel use BRC3A61 ✓ ✓ ✓
Adaptor for wiring KRP1B61 ✓ ✓ ✓
Wiring adaptor for electrical appendices ·1· KRP2A51 ✓ ✓ ✓
Wiring adaptor for electrical appendices ·2· KRP4A51 ✓ ✓ ✓
Remote sensor KRCS01-1 ✓ ✓ ✓
Central remote control DCS302B51 ✓ ✓ ✓
Electrical box with earth terminal (·2· blocks) KJB212A ✓ ✓ ✓
Electrical box with earth terminal (·3· blocks) KJB311A ✓ ✓ ✓
Unified ON/OFF controller DCS301BA51 ✓ ✓ ✓
Noise filter (for electromagnetic interface only) KEK26-1 ✓ ✓ ✓
Schedule timer DST301BA51 ✓ ✓ ✓
External adaptor for outdoor unit (installation on indoor unit) DTA104A61 ✓ ✓ ✓
Long-life replacement filter KAF361L28 ✓ ✕ ✕
Long-life replacement filter KAF361L45 ✕ ✓ ✕
Long-life replacement filter KAF361L71 ✕ ✕ ✓
Rear decoration panel EKRDP25A5 ✓ ✕ ✕
Rear decoration panel EKRDP40A5 ✕ ✓ ✕
Rear decoration panel EKRDP63A5 ✕ ✕ ✓
Multi-tenant EKMTAC ✓ ✓ ✓
Digital input adaptor BRP7A51③④ ✓ ✓ ✓

①: This kit contains parts to connect with ·10· multi-tenant indoor units.
②: Included languages are:
Language pack ·1·: English, German, French, Dutch, Spanish, Italian, and Portuguese.
With PC cable ·EKPCCAB3· in combination with the Updater PC software, you can additionally change the language to:
Language pack ·2·: English, Bulgarian, Croatian, Czech, Hungarian, Romanian, and Slovenian.
Language pack ·3·: English, Greek, Polish, Russian, Serbian, Slovak, and Turkish.
③: Only possible in combination with remote control ·BRC2/3E52C, BRC1E53A/B/C7·.
④: Requires installation box for adaptor PCB
⑤: Included languages are: English, German, French, Italian, Spanish, Portuguese, and Dutch.
⑥: Included languages are: English, Czech, Croatian, Hungarian, Slovenian, Romanian, and Bulgarian.
⑦: Included languages are: English, Russian, Greek, Turkish, Polish, Albanian, and Slovak.
⑧: Language pack ·3· of controller ·BRC1E53C7· is different from that of controller ·BRC2/3E52C7·.

3D102604C

Floor standing unit • FXLQ-P 9


Floor standing unit • FXLQ-P

6 Capacity tables
6-1 Cooling Capacity Tables
FXLQ-P
TC: Total capacity; kW
6 SHC: Sensible heat capacity; kW

Indoor air temp.


14.0 °CWB 16.0 °CWB 18.0 °CWB 19.0 °CWB 20.0 °CWB 22.0 °CWB 24.0 °CWB
Unit size
20.0 °CDB 23.0 °CDB 26.0 °CDB 27.0 °CDB 28.0 °CDB 30.0 °CDB 32.0 °CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
20 1.5 1.3 1.8 1.5 2.1 1.7 2.2 1.7 2.3 1.7 2.4 1.6 2.4 1.5
25 1.9 1.6 2.3 1.8 2.6 2.0 2.8 2.1 3.0 2.1 3.0 2.0 3.1 1.9
32 2.4 2.1 2.9 2.2 3.4 2.5 3.6 2.5 3.8 2.5 3.9 2.4 4.0 2.3
40 3.0 2.5 3.6 2.7 4.2 3.1 4.5 3.1 4.7 3.2 4.9 3.1 5.0 2.9
50 3.8 3.0 4.5 3.4 5.2 3.8 5.6 3.9 5.9 4.0 6.0 3.8 6.2 3.6
63 4.8 3.7 5.7 4.2 6.6 4.8 7.1 4.9 7.5 4.9 7.7 4.7 7.8 4.3

CA03A095

10 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

6 Capacity tables
6-2 Heating Capacity Tables
FXLQ-P
Indoor air temp. °CDB
Unit size 16.0 18.0 20.0 21.0 22.0 24.0 6
kW kW kW kW kW kW
20 2.6 2.6 2.5 2.4 2.3 2.2
25 3.4 3.4 3.2 3.1 3.0 2.8
32 4.2 4.2 4.0 3.9 3.7 3.5
40 5.2 5.2 5.0 4.8 4.7 4.4
50 6.6 6.6 6.3 6.1 5.9 5.5
63 8.4 8.4 8.0 7.7 7.5 7.0

CA03A095

Floor standing unit • FXLQ-P 11


Floor standing unit • FXLQ-P

7 Dimensional drawings
7-1 Dimensional Drawings
FXLQ20-25P 20 or more

100 or more 100 or more 1750 or more


Discharge

7
Front of face Suction
1000 or more Base

Required installation space

Piping hole (rear)

4-12x30 Oblong hole


Hole for fear mounting

Level adjusting screw in standard accessory


4xM6
Item Name Description
2-12x18 Oblong hole 1 Liquid pipe connection Ø6.4 Flare connection
Hole for f xing to the f oor
2 Gas pipe connection Ø12.7 Flare connection
3 Drain pipe connection O.D.Ø21
4 Switch box
5 Air f lter
Wiring hole (bottom) Piping hole (bottom)

3TW32294-1

);/43
RUPRUH

RUPRUH
RUPRUH RUPRUH
'LVFKDUJH

6XFWLRQ
)URQWRIIDFH
RUPRUH %DVH

5HTXLUHGLQVWDOODWLRQVSDFH

3LSLQJKROH UHDU

[2EORQJKROH
+ROHIRUIHDUPRXQWLQJ

/HYHODGMXVWLQJVFUHZLQVWDQGDUGDFFHVVRU\
[0

[2EORQJKROH
+ROHIRUI[LQJWRWKHIRRU ,WHP 1DPH 'HVFULSWLRQ
 /LTXLGSLSHFRQQHFWLRQ ‘)ODUHFRQQHFWLRQ
 *DVSLSHFRQQHFWLRQ ‘)ODUHFRQQHFWLRQ
 'UDLQSLSHFRQQHFWLRQ 2'‘
 6ZLWFKER[
:LULQJKROH ERWWRP 3LSLQJKROH ERWWRP
 $LUIOWHU

7:

12 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

7 Dimensional drawings
7-1 Dimensional Drawings
);/43
RUPRUH

RUPRUH
RUPRUH RUPRUH
'LVFKDUJH 7
6XFWLRQ
)URQWRIIDFH
RUPRUH %DVH

5HTXLUHGLQVWDOODWLRQVSDFH

3LSLQJKROH UHDU

[2EORQJKROH
+ROHIRUIHDUPRXQWLQJ
0RGHO $ %
/HYHODGMXVWLQJVFUHZLQVWDQGDUGDFFHVVRU\ );/ ‘ ‘
[0
);/ ‘ ‘
[2EORQJKROH
+ROHIRUI[LQJWRWKHIRRU
,WHP 1DPH 'HVFULSWLRQ
 /LTXLGSLSHFRQQHFWLRQ ‘$)ODUHFRQQHFWLRQ
 *DVSLSHFRQQHFWLRQ ‘%)ODUHFRQQHFWLRQ
 'UDLQSLSHFRQQHFWLRQ 2'‘
:LULQJKROH ERWWRP 3LSLQJKROH ERWWRP  6ZLWFKER[
 $LUIOWHU

7:

Floor standing unit • FXLQ-P 13


Floor standing unit • FXLQ-P

8 Centre of gravity
8-1 Centre of Gravity
FXLQ-P

Model A B
FXLQ 20, 25 P 500 81
FXLQ 32, 40 P 588 89
FXLQ 50, 63 P 728 99

4TW32299-2

14 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

9 Piping diagrams
9-1 Piping Diagrams
FXLQ-P

Gas pipe connection port


Heat exchanger

Fan

Liquid pipe connection port

Filter Filter

Electronic expansion valve

Applicable model
FXC, FXM, FXL, FXN
FXH, FXK, FXS, FJSP
CBXLS, FXSP, FXCP
FZSP, FXNP, FJNP
FHQ, FXA, FXMQ, FBQ
FXAQ, FXSP ~ BA, FAQ, FCQ
FZSP ~ BA (N), FSSP ~ BA
FQSP ~ BAN, FXUQ, FZCP, FZAP
FXSQ ~ PV2S, FXSQ ~ T, FXSP ~ CA (N)
FZSP ~ CA (N), FQSP ~ CAN
FSSP ~ CA, FXSP ~ AA, FSSFP ~ AA

4D034245R

Floor standing unit • FXLQ-P 15


Floor standing unit • FXLQ-P

10 Wiring diagrams
10 - 1 Wiring Diagrams - Single Phase
FXLQ-P
1N~ 220-240V 50Hz
1N~ 220V 60Hz

10

Input from outside


Note 2

Transmission wiring central remote control


Note 1

Wire remote control


(optional accessory) Control box

Indoor unit Colors


A1P Printed circuit board BLK : Black
C1 Capacitor (M1F) BLU : Blue
F1U Fuse ( B , 5A, 250V) BRN : Brown
F2U Field Fuse ORG : Orange
HAP Light emitting diode (service monitor green) PNK : Pink
K1R-K3R Magnetic relay (M1F) RED : Red
M1F Motor (indoor fan) WHT : White
Q1M Thermo switch (M1F embedded) YLW : Yellow
Q1DI Earth Leak Detector
R1T Thermistor (air)
R2T-R3T Thermistor (coil)
T1R Transformer (220-240V/22V)
X1M Terminal block (power supply)
X2M Terminal block (control)
Y1E Electronic expansion valve
Wired remote control
R1T Thermistor (air)
SS1 Select switch (main/sub)
Connector optional accessory
X18A Connector (wiring adapter for electrical appendices)
2D077874

NOTES

1. When using the central remote control see manual for connection to the unit.
2. When connecting the input wires from outside, forced “OFF” or “ON/OFF” operation can be selected by the remote control. See installation manual for more details.
3. Use copper conductors only.
: Terminal block : Connector

: Field wiring : Terminal


L : Live : Protective earth (screw)
N : Neutral

: Connector

16 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

11 Sound data
11 - 1 Sound Pressure Spectrum
FXLQ20,25P 4D034528A

11
Octave band sound pressure level dB (0 dB=0.0002µ bar)

Approximate
threshold hearing for
continuous noise

Octave band center frequency (Hz)

NOTES

1 Over all (dB): Scale 220V 240V


(B, G, N is already rectified) H L H L
A 35 32 37 34
C 40 36.5 42 38.5
2 Measuring place: Anechoic chamber
3 Operating conditons:
• Power source: 220•240V/220V 50/60Hz
• JIS standard 220V
240V
4 Location of microphone Microphone

1.5m

1.5m

5 Operating noise differs with operation and ambient conditions.

FXLQ32P 4D034564A
Octave band sound pressure level dB (0 dB=0.0002µ bar)

Approximate
threshold hearing for
continuous noise

Octave band center frequency (Hz)

NOTES

1 Over all (dB): Scale 220V 240V


(B, G, N is already rectified) H L H L
A 35 32 37 34
C 39 37 41 39
2 Measuring place: Anechoic chamber
3 Operating conditons:
• Power source: 220•240V/220V 50/60Hz
• JIS standard 220V
240V
4 Location of microphone Microphone

1.5m

1.5m

5 Operating noise differs with operation and ambient conditions.

Floor standing unit • FXLQ-P 17


Floor standing unit • FXLQ-P

11 Sound data
11 - 1 Sound Pressure Spectrum
FXLQ40P 4D034565A

11
Octave band sound pressure level dB (0 dB=0.0002µ bar)

Approximate
threshold hearing for
continuous noise

Octave band center frequency (Hz)

NOTES

1 Over all (dB): Scale 220V 240V


(B, G, N is already rectified) H L H L
A 38 33 40 35
C 42 38 44 40
2 Measuring place: Anechoic chamber
3 Operating conditons:
• Power source: 220•240V/220V 50/60Hz
• JIS standard 220V
240V
4 Location of microphone Microphone

1.5m

1.5m

5 Operating noise differs with operation and ambient conditions.

FXLQ50P 4D034566A
Octave band sound pressure level dB (0 dB=0.0002µ bar)

Approximate
threshold hearing for
continuous noise

Octave band center frequency (Hz)

NOTES

1 Over all (dB): Scale 220V 240V


(B, G, N is already rectified) H L H L
A 39 34 41 36
C 44 38.5 46 40.5
2 Measuring place: Anechoic chamber
3 Operating conditons:
• Power source: 220•240V/220V 50/60Hz
• JIS standard 220V
240V
4 Location of microphone Microphone

1.5m

1.5m

5 Operating noise differs with operation and ambient conditions.

18 Floor standing unit • FXLQ-P


Floor standing unit • FXLQ-P

11 Sound data
11 - 1 Sound Pressure Spectrum
FXLQ63P 4D034567A

11
Octave band sound pressure level dB (0 dB=0.0002µ bar)

Approximate
threshold hearing for
continuous noise

Octave band center frequency (Hz)

NOTES

1 Over all (dB): Scale 220V 240V


(B, G, N is already rectified) H L H L
A 40 35 42 37
C 45 39.5 47 41.5
2 Measuring place: Anechoic chamber
3 Operating conditons:
• Power source: 220•240V/220V 50/60Hz
• JIS standard 220V
240V
4 Location of microphone Microphone

1.5m

1.5m

5 Operating noise differs with operation and ambient conditions.

Floor standing unit • FXLQ-P 19


Daikin Europe N.V. Naamloze Vennootschap · Zandvoordestraat 300 · 8400 Oostende · Belgium · www.daikin.eu · BE 0412 120 336 · RPR Oostende (Responsible Editor)

The present leaflet is drawn up by way of information only and does not constitute an
offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of
this leaflet to the best of its knowledge. No express or implied warranty is given for the
completeness, accuracy, reliability or fitness for particular purpose of its content and the
products and services presented therein. Specifications are subject to change without prior
notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in
EEDEN20A 07/2020
the broadest sense, arising from or related to the use and/or interpretation of this leaflet.
All content is copyrighted by Daikin Europe N.V.

You might also like