Trninic - Unutrasnja Jedinica Klime
Trninic - Unutrasnja Jedinica Klime
ITALIANO
ESPAÑOL
INSTALLATION MANUAL
FRANÇAIS
AIR
CONDITIONER
DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
NEDERLANDS
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards by
authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
Ceilling Concealed Duct
POLSKI
Original instruction
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared
Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands
LIMBA ROMÂNĂ
MFL67939918 www.lg.com
Rev.00_112118 Copyright © 2015 - 2018 LG Electronics Inc. All Rights Reserved.
TABLE OF CONTENTS
3 SAFETY PRECAUTIONS
8 MODEL DESIGNATION
8 Product information
9 Airborne Noise Emission
9 Limiting concentration
10 EXTERNAL APPEARANCE
11 INSTALLATION PLACES
11 Selection of the best location
27 OPTIONAL OPERATION
27 Installer Setting -Test Run Mode
28 Installer Setting - Setting Address of Central Control
29 Installer Setting -Thermistor
30 Installer Setting-Group Setting
31 Installer Setting-Dry Contact Mode Setting
32 Installer Setting-Celsius / Fahrenheit Switching
33 Installer Setting -Optional Function Setting
34 Installer Setting – Remote controller Mode Lock
42 SELF-DIAGNOSIS FUNCTION
42 DIP SWITCH SETTING
2
Safety Precautions
ENGLISH
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions
must be followed.
n Be sure to read before installing the air conditioner.
n Be sure to observe the cautions specified here as they include important items related to safety.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
n The meanings of the symbols used in this manual are as shown below.
! WARNING
Installation
• Do not use a defective or underrated circuit breaker. Use this
appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or
an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or
electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
Installation Manual 3
Safety Precautions
ENGLISH
- There is risk of fire or failure of product.
• Do not use the product in a tightly closed space for a long time.
- Oxygen deficiency could occur.
• When flammable gas leaks, turn off the gas and open a window for
ventilation before turn the product on.
- Do not use the telephone or turn switches on or off. There is risk of
explosion or fire.
• If strange sounds, or small or smoke comes from product. Turn the
breaker off or disconnect the power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane. If possible,
remove the product from the window before the hurricane arrives.
- There is risk of property damage, failure of product, or electric shock.
• Do not open the inlet grill of the product during operation. (Do not
touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
• When the product is soaked (flooded or submerged), contact an
Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Ventilate the product from time to time when operating it together with
a stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the product.
- There is risk of electric shock.
• When the product is not be used for a long time, disconnect the power
supply plug or turn off the breaker.
- There is risk of product damage or failure, or unintended operation.
• Take care to ensure that nobody could step on or fall onto the outdoor
unit.
- This could result in personal injury and product damage.
Installation Manual 5
Safety Precautions
! CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of
product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor
unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt
spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the
condenser and evaporator fins, could cause product malfunction or
inefficient operation.
Operation
• Do not expose the skin directly to cool air for long periods of time.
(Don't sit in the draft.)
- This could harm to your health.
• Do not use the product for special purposes, such as preserving foods,
works of art, etc. It is a consumer air conditioner, not a precision
refrigeration system.
- There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow.
- It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic parts of
the product.
6
Safety Precautions
• Do not touch the metal parts of the product when removing the air
ENGLISH
filter. They are very sharp!
- There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units)
- There is risk of personal injury and failure of product.
• Always insert the filter securely. Clean the filter every two weeks or
more often if necessary.
- A dirty filter reduces the efficiency of the air conditioner and could
cause product malfunction or damage.
• Do not insert hands or other objects through the air inlet or outlet while
the product is operated.
- There are sharp and moving parts that could cause personal injury.
• Do not drink the water drained from the product.
- It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning or maintaining the product.
- Be careful and avoid personal injury.
• Replace the all batteries in the remote control with new ones of the
same type. Do not mix old and new batteries or different types of
batteries.
- There is risk of fire or explosion.
• Do not recharge or disassemble the batteries.
Do not dispose of batteries in a fire.
- They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it
well with clean water. Do not use the remote if the batteries have
leaked.
- The chemicals in batteries could cause burns or other health
hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor.
Do not use the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health
hazards.
Installation Manual 7
Model Designation
Model Designation
Product information
- Product Name : Air conditioner
- Model Name :
M S 15 SQ N B 0
Serial number
Chassis name
Indoor Unit / Outdoor Units
N : Indoor Unit U : Outdoor Unit
Detailed product type only for M- series models
AQ : Wall mounted Libero-R SQ : Wall mounted Libero-E
AH* : ARTCOOL AW* : ART COOL Mirror
AH : Ceiling Cassette
AHL : Ceiling Concealed Duct (Low Static)
Detailed product type for U- / C- series models
L : Low Static H : High COP C : Econo
Nominal Capacity
Ex) 7 000 Btu/h Class → '07', 18 000 Btu/h Class → '18'
Product type
S : Wall mounted / ARTCOOL mirror J : Wall mounted
A : ARTCOOL T : Ceiling Cassette
B, M : Ceiling Concealed Duct V : Ceiling Suspended & floor
Q : Console P : Floor Standing
Connectable Outdoor unit type
M : Indoor units only for Multi systems
U : Indoor units only for Single A systems
C : Common Indoor Unit for Multi and Single CAC
8
Model Designation
ENGLISH
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels.
Whilst there is a correlation between the emission and exposure levels, this cannot be
used reliably to determine whether or not further precautions are required.
Factor that influence the actual level of exposure of the workforce include the
characteristics of the work room and the other sources of noise, i.e. the number of
equipment and other adjacent processes and the length of time for which an operator
exposed to the noise. Also, the permissible exposure level can vary from country to
country.
This information, however, will enable the user of the equipment to make a better
evaluation of the hazard and risk.
Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures
can be taken without hurting human body when refrigerant leaks in the air. The limiting
concentration shall be described in the unit of kg/m3 (Freon gas weight per unit air volume)
for facilitating calculation
Installation Manual 9
External Appearance
External Appearance
• Ceiling Concealed Duct – Low static pressure
L1/L2/L3 Chassis
10
Installation Places
ENGLISH
Installation Places
Selection of the best location
Install the air conditioner in the location that satisfies the following conditions.
• The place shall easily bear a load exceeding four times the indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
(Suitable dimension “H” is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
Ceiling Concealed Duct – Low Static Ceiling Concealed Duct – Mid Static
Inspection hole (600 x 600) Inspection hole
Top view Control box (600 x 600)
(unit: mm) Top view
(unit: mm) Control box
Front
Side view
(unit: mm) Air outlet Front view
H=20 or more
H
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Front
Front view
Installation Manual 11
Installation Places
Inspection hole
Top view (600 x 600)
Inspection hole (600X600)
(unit: mm) Control box Top view Control box
(unit: mm)
600 600
1 000
Front
Front
Front view
Front view
H H
! CAUTION
In case that the unit is installed near the sea, the installation parts may be corroded
by salt, The installation parts (and the unit) should be taken appropriate anti
corrosion measures.
12
The indoor unit installation
ENGLISH
The indoor unit installation
Installation of Unit
Install the unit above the ceiling correctly.
CASE 1
POSITION OF SUSPENSION BOLT
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
F
I
D C
H
J Drainage hole
A
B
(Unit: mm)
Canvas Indoor Unit
Ceiling
Dimension Duct
Capacity A B C D E F G H I J
Discharge
(kBtu/h) Intake Flexible Duct
Duct
9 733 772 628 700 36 190 20 660 155 700
12/18 933 972 628 700 36 190 20 860 155 900 Air Discharge
Air Intake Ceiling Port
Board Ceiling Board
24 1 133 1 172 628 700 36 190 20 1 060 155 1 100 Port
Inspection
Port
H
C
E
body
Drainage hole
D
Discharge
Intake Flexible Duct
(Unit:mm) Duct
Dimension
A B C D E F (G) H I J Air Intake Ceiling
Air Discharge
Port
Capacity Port Board Ceiling Board
Inspection
18/24 K 932 882 355 46 450 30 87 750 163 260 Port
Installation Manual 13
The indoor unit installation
E
G
F
I
C
D
J
A Drainage hole
B
(Unit:mm)
Canvas Indoor Unit
Duct
Ceiling Dimension
Capacity A B C D E F G H I J
Discharge (kBtu/h)
Intake Flexible Duct
Duct 18 / 24 / 30 933.4 971.6 619.2 700 30 270 15.2 858 201.4 900
36 / 42 1 283.4 1 321.6 619.2 689.6 30 270 15.2 1 208 201.4 1 250
Air Discharge
Air Intake Ceiling Port 48 / 60 1 283.4 1 321.6 619.2 689.6 30 360 15.2 1 208 291.4 1 250
Port Board Ceiling Board
Inspection
Port
body
H
D
Drainage hole
Joint canvas (G)
F
Main duct
Canvas
Duct
Indoor Unit
Ceiling (Unit:mm)
Dimension
Discharge
Intake Flexible Duct
Capacity A B C D E F (G) H I J
Duct (kBtu/h)
Air Discharge
36 / 42 / 46 1 290 1 230 447 56 590 30 120 1 006 294 380
Air Intake Ceiling Port
Port Board Ceiling Board
Inspection
Port
14
The indoor unit installation
ENGLISH
H
K
G J
I
C
D
FE L
B
A
Discharge
Dimension
Intake Flexible Duct
Capacity A B C D E F G H I J K L
Duct
(kBtu/h)
70
Air Discharge 1 594 1 044 286 460 580 713 1 368 1 622 392 458 1 563 791
Air Intake Ceiling Port 85
Port Board Ceiling Board
Inspection
Port
CASE 2
• Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
M10 Nut X4
POSITION OF CONSOLE BOLT M10 SP. washer X 4 (Local
supply)
M10 washer X4
• A place where the unit will be leveled
and that can support the weight of the
unit.
• A place where the unit can withstand its
vibration. M10 washer X4
• A place where service can be easily (Local
M10 SP. washer X 4 supply)
performed.
M10 Nut X4
Installation Manual 15
Installation Places
Tighten the nut and bolt top revent unit falling. • Local supply
① Set anchor
② Plate washer - M10
③ Spring washer - M10
④ Nut - W3/8 or M10
⑤ Suspension bolt - W3/8 or M10
16
The indoor unit installation
! CAUTION
ENGLISH
1. Install declination of the indoor unit is very important for the drain of the duct type air
conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 10mm.
FRONT OF VIEW
• The unit must be horizontal or declined to the drain hose connected when finished
installation.
Ceiling
Drainage hole
Drain Pump use
Ceiling Concealed Duct – Low static
• The unit must be declined to the drain hose connected when finished installation.
Ceiling
5~10 mm
Drainage hole Drainage hole
CORRECT INCORRECT
Ceiling Concealed Duct – Mid static
Ceiling
H-INV : 5~10 mm
Compact : 1/100~1/50
Ceiling
15 mm~25 mm
Installation Manual 17
The indoor unit installation
CORRECT INCORRECT
Applied U-Trap Dimension
A ≥ 70 mm
• Install the P-Trap (or U-Trap) to prevent B ≥ 2C
C ≥ 2 x SP
a water leakage caused by the blocking SP = External Pressure B
of intake air filter. (mmAq) C
Ex) External Pressure
= 10 mmAq U-Trap
A ≥ 70 mm A
B ≥ 40 mm
C ≥ 20 mm
18
The indoor unit installation
ENGLISH
• Drain piping must have down-slope : be sure
not to provide up-and-down slope to prevent Pipe clamp
Upward
routing
reversal flow. not allowed
• During drain piping connection, be careful not Indoor unit
to exert extra force on the drain port on the
indoor unit.
• The outside diameter of the drain connection Maintenance
drain port
on the indoor unit is 32 mm.
(Ceiling Concealed Duct – High static: 65 mm)
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
• Be sure to execute heat insulation on the drain
piping.
• Install the drain raising pipes at a right
angle to the indoor unit and no more than
300 mm from the unit.
Heat insulation material: Polyethylene foam with thickness more than 10 mm.
Drain test
• Connect the main drain pipe to the exterior and leave
Feed water Flexible drain hose it provisionally until the test comes to an end.
(accessory)
Main • Feed water to the flexible drain hose and check the
drain pipe
piping for leakage.
! CAUTION Hanger
Max 300 mm distance Hanger Bracket
The supplied flexible drain hose should not be 1~15 m 1/50~1/100 slope
curved, neither screwed. The curved or screwed Metal
Max 700 mm
clamp
hose may cause a leakage of water.
Flexible drain hose
Insulation
Installation Manual 19
The indoor unit installation
20
The indoor unit installation
Heat Insulation
ENGLISH
Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas pipe separately
with enough thickness heat-resistant polyethylene, so that no gap is observed in the joint between
indoor unit and insulating material, and insulating materials themselves. When insulation work is
insufficient, there is a possibility of condensation drip, etc. Pay special attention to insulation work to
ceiling plenum.
Ⓑ Pipe
Note :
Ⓒ Outer covering(Wind the connection part
When using polyethylene cover as
and cutting part of heat insulation material
covering material, asphalt roofing shall not
with a finishing tape.)
be required.
• Do not insulate gas or low pressure pipe and liquid or high • Be sure to fully insulate connecting portion.
pressurepipe together.
Liquid pipe
Bad Gas pipe
Power cables
example Finishing tape
Insulating material
Communication cables These parts are not insulated.
Good
example Separ
Liquid pipe -ation
Gas pipe Insulating material
Power cables Communication cables
! CAUTION
Cutting line of insulation must look upper direction. Thickness of insulation is 15 mm(Gas pipe) and
19 mm(Liquid pipe) or over.
Note :
Recommended Insulation material
Material : EPDM
Thickness : 15 mm(Gas pipe) and 19 mm(Liquid pipe) or over.
Density : less than 0.032 ±0.005(g/cm2)
Thermal conductivity : less than 0.03(kcal/m.hr.°C)
Installation Manual 21
The indoor unit installation
Wiring Connection
• Open the control box cover and connect the Remote controller cord and Indoor power wires.
• Remove the control box cover for electrical connection between the indoor and outdoor
unit. (Remove screws ①.)
• Use the cord clamper to fix the cord.
Remote
controler cord
! CAUTION
The connecting cable connected to the indoor and outdoor unit should be complied with the following
NORMAL
specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
CROSS-SECTIONAL
GN AREA 0.75 mm2
/YL
20
mm
If the supply cord is damaged, it must be replaced by a special cord or assembly available from the manufacturer of its service agent. When the
connection line between the indoor unit and outdooor unit and outdoor unit is over 40 m, connect the telecommunication line and power line separately.
22
The indoor unit installation
ENGLISH
u Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Power wire
Round pressure terminal
• For wiring, use the designated power wire and connect firmly, then secure to prevent
outside pressure being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a
small head will strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)
Installation Manual 23
Remote Controller Installation
3. Please fix remote controller upper part into the setup <Connecting order>
board attached to the surface of the wall, as the picture
below, and then, connect with setup board by pressing
lower part.
- Please connect not to make a gap at the remote controller Wall Wall
and setup board’s upper and lower, right and left part. Side Side
- Before assembly with the installation board, arrange the
Cable not to interfere with circuit parts.
24
Remote Controller Installation
4. Please connect indoor unit and remote controller using connection cable.
ENGLISH
12 V Red
Please check if connector is normally connected.
Signal Yellow
5. Please use extension cable if the distance between wired remote controller and indoor unit is more
than 10 m.
! CAUTION
When installing the wired remote controller, do not bury it in the wall. (It can cause damage in the
temperature sensor.)
Do not install the cable to be 50m or above. (It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the remote
controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
Direct
Sun ray contact area
yes
no
5 feet
no
(1.5 meters)
no
Installation Manual 25
Remote Controller Installation
j Some functions may not be operated and displayed depending on the product type.
NOTE
h Display temperature can be different from actual room temperature if the remote controller is
installed at the place where sun-rays are falling directly or the place nearby heat source.
h The actual product can be different from above contents depending upon model type.
h When using simultaneous operation system, whenever press remote controller button, system will
approximately operate after 1~2 minutes.
26
Optional Operation
ENGLISH
Optional Operation
Installer Setting -Test Run Mode
After installing the product, you must run a Test Run mode.
For details related to this operation, refer to the product manual.
1 Ifit enters
pressing button long for 3 seconds,
into remote controller setter
setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press more
than 3 seconds for sure.
- Please cancel the right and left of wind
direction for RAC product.
Installation Manual 27
Optional Operation
1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
Indoor No.
Group No
Function Code
28
Optional Operation
ENGLISH
This is the function to select the temperature sensor to judge the room temperature.
1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
<Thermistor Table>
Temperature sensor selection Function
01 Remote controller Operation in remote controller temperature sensor
02 Indoor unit Operation in indoor unit temperature sensor
Operation of higher temperature by comparing indoor unit's and wired
Cooling remote controller’s temperature.
03 2TH (There are products that operate at a lower temperature.)
Operation of lower temperature by comparing indoor unit's and wired
Heating
remote controller's temperature.
j The function of 2TH has different operation characteristics according to the product.
Installation Manual 29
Optional Operation
1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
3 Select
button.
Master/ Slave by pressing
30
Optional Operation
ENGLISH
Dry contact function is the function that is possible to use only when dry contact equipment is
separately purchased/setup.
1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
2 Ifremote
pressing button repeatedly, it moves to
controller dry contact mode setup
menu as picture below.
Installation Manual 31
Optional Operation
1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it
enters into user setup mode.
Please press more than 3 seconds for
sure.
2 Repeat pressing
Function code 12.
button to select
32
Optional Operation
ENGLISH
Setting feature for indoor unit when air cleaning / heater / humidifier / Up/down grill / Ventilation KIT
/ Auxiliary Heater is newly installed, or installed unit is removed.
1 Ifseconds,
pressing button long for 3
it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
Installation Manual 33
Optional Operation
3 Select thebutton.
remote control master/slave using
code Description
42:00 Doesn’t limit operation mode setting.
42:01 User can setting to cooling mode only.
42:02 User can setting to heating mode only.
h It can limit only wired remote controller button. other controllers can change operation mode.
(for example wireless remote controller and central controller)
34
How to Set E.S.P?
ENGLISH
How to Set E.S.P?
Installer Setting -E.S.P.
This is the function that decides the strength of the wind for each wind level and because this function
is to make the installation easier.
ESP value
Function code,
ESP code
4 Movebutton.
to ESP value setting by pressing
1 Ifseconds,
pressing button long for 3
it enters into remote 5 Press button to setup ESP value.
• When setting ESP value on the product without very weak wind or power wind function, it may not work.
• Please be careful not to change the ESP value for each fan step.
• It does not work to setup ESP value for very low/power step for some products.
• ESP value is available for specific range belongs to the product.
Installation Manual 35
How to Set E.S.P?
- Static Pressure (Code 06) setting will not be used if Static Pressure Step (Code 32)
setting is being used.
- For the static pressure value for each step, refer to the next page Table. 1
36
How to Set E.S.P?
ENGLISH
Table 1
Static Pressure [mmAq (Pa)]
0(0) 1(10) 2(20) 3(29) 4(39) 5(49)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06
LOW 5.5 69 76 83 91 101 111
CB09L.N12 MID 7 81 87 94 101 109 117
HIGH 9 97 103 108 117 124 131
Note :
1. The above table shows the correlation between the air rates and E.S.P.
2. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
3. Table 1 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
Installation Manual 37
How to Set E.S.P?
Static Pressure[mmAq(Pa)]
2.5(25) 4(39) 5(49) 6(59)
7(69) 8(78) 9(88) 10(98) 11(108) 13(127) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 18 96 102 107 110 114 118 122 125 127 132 134
UM30.N14 MID 20 102 110 114 118 121 125 127 130 133 135 137
HIGH 22 110 117 121 124 127 130 133 136 137 138 140
Static Pressure[mmAq(Pa)]
4(39) 5(49) 6(59) 7(69)
8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 24 88 91 95 100 101 108 113 115 118 121 128
UM36.N24 MID 28 93 97 101 105 108 115 118 120 124 127 134
HIGH 32 101 105 109 112 115 119 123 126 128 133 137
Static Pressure[mmAq(Pa)]
5(49) 6(59) 7(69) 8(78)
9(88) 10(98) 11(108) 12(118) 13(127) 14(137) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 28 100 103 106 110 114 118 121 125 128 133 136
UM42.N24 MID 33 108 111 114 118 122 125 128 131 134 138 141
HIGH 38 117 120 124 127 130 133 135 138 141 144 147
Static Pressure[mmAq(Pa)]
4(39) 5(49) 6(59) 7(69)
8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 28 74 76 79 82 89 92 94 96 99 102 107
UM48.N34 MID 34 78 82 84 89 94 96 98 101 104 106 112
HIGH 40 83 89 92 94 98 100 102 105 108 110 116
Static Pressure[mmAq(Pa)]
4(39) 5(49) 6(59) 7(69)
8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 40 82 89 92 94 98 100 102 105 108 110 113
UM60.N34 MID 45 90 92 96 98 102 104 106 109 112 114 117
HIGH 50 94 97 100 104 107 109 112 115 117 119 121
38
How to Set E.S.P?
NOTE
ENGLISH
1. Be sure to set the value refering table 2. Unexpected set value will cause mal-function.
2. Table 2 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
Model Factory set (E.S.P.) mmAq(Pa)
CM18.N14
CM24.N14
UM30.N14
UM36.N24 6(59)
UM42.N24
UM48.N34
UM60.N34
Installation Manual 39
How to Set E.S.P?
NOTE
Be sure to set the value referring table 3. Unexpected set value will cause mal-function.
As far as possible do not set ESP 82,83
Table 3 is based at 230 V. According to the fluctuation of voltage, air flow rate varies.
40
How to Set E.S.P?
ENGLISH
Table 4
Static Pressure[mmAq(Pa)]
6(59) 7(69) 8(78)
9(88) 10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 60 70 72 74 76 78 81 82 85 86 88 91
UB70.N94 MID 65 74 76 78 80 82 85 86 89 90 92 95
HIGH 70 78 80 82 84 86 90 91 93 94 96 99
Static Pressure[mmAq(Pa)]
6(59) 7(69) 8(78)
9(88) 10(98) 12(118) 13(127) 14(137) 15(147) 16(157) 18(176)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
LOW 64 74 75 76 78 79 82 84 86 89 91 95
UB85.N94 MID 72 78 79 80 82 83 87 89 91 94 96 100
HIGH 80 82 84 86 88 90 93 95 97 100 101 105
NOTE
1. Be sure to set the value refering table 4. Unexpected set value will cause mal-function.
2. Table 4 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
3. Factory Set(External Static Pressure) each Model
Model Factory set (E.S.P.) mmAq(Pa)
UB85.N94
13 (127)
UB70.N94
UB85.N94
105
UB70.N94
Installation Manual 41
Self-diagnosis Function
Self-diagnosis Function
Indoor Unit Error
Ex) Error 03 (Remote controller error)
LED02G
(GREEN)
2s 2s
Indoor PCB
Wired/Wireless remote
Selection of Dry Contact controller
SW4 Dry Contact Mode Auto Off
Mode Selection of Manual or Auto
operation Mode
Continuous operation
SW5 Installation Fan continuous operation Working Off
Removal
42