PowerScale - Isilon - HD400-Installation and Setup Guide
PowerScale - Isilon - HD400-Installation and Setup Guide
Topic
HD400
Selections
HD400 - Select CTO Node Activity: Installation and Setup Guide
Installation and Setup Guide: Install the rails in a rack
Installation and Setup Guide: Install the node in a rack
Installation and Setup Guide: Connect network and power cables
Installation and Setup Guide: Power up the node
Installation and Setup Guide: Configure the node
Installation and Setup Guide: Update the Install Base
Installation and Setup Guide: Front panel LCD menu
Installation and Setup Guide: Additional options for getting help
Serial Number(s) or Service Tag(s): ajaakak
SR Number(s): 124357
Company Location: stscs
REPORT PROBLEMS
If you find any errors in this procedure or have comments regarding this application, send email to
[email protected]
Copyright © 2024 Dell Inc. or its subsidiaries. All Rights Reserved. Dell Technologies, Dell, EMC, Dell
EMC and other trademarks are trademarks of Dell Inc. or its subsidiaries. Other trademarks may be
trademarks of their respective owners.
The information in this publication is provided “as is.” Dell Inc. makes no representations or warranties of
any kind with respect to the information in this publication, and specifically disclaims implied warranties of
merchantability or fitness for a particular purpose.
Use, copying, and distribution of any software described in this publication requires an applicable
software license.
This document may contain certain words that are not consistent with Dell's current language guidelines.
Dell plans to update the document over subsequent future releases to revise these words accordingly.
Page 1 of 38
This document may contain language from third party content that is not under Dell's control and is not
consistent with Dell's current guidelines for Dell's own content. When such third party content is updated
by the relevant third parties, this document will be revised accordingly.
Page 2 of 38
Contents
Preliminary Activity Tasks .......................................................................................................5
Read, understand, and perform these tasks.................................................................................................5
Page 3 of 38
Status menu..........................................................................................................................34
Update menu.........................................................................................................................36
Service menu ........................................................................................................................36
Shutdown menu ....................................................................................................................36
Update the Install Base.........................................................................................................37
Additional options for getting help.........................................................................................37
Page 4 of 38
Preliminary Activity Tasks
This section may contain tasks that you must complete before performing this procedure.
Table 1 List of cautions, warnings, notes, and/or KB solutions related to this activity
Page 5 of 38
General Information for Removing and Installing FRUs
This section describes precautions you must take and general procedures you must follow when
removing, installing, or storing field-replaceable units (FRUs). The procedures in this section apply to FRU
handling during hardware upgrades as well as during general replacement.
FRUs are designed to be powered up at all times. This means you can accomplish FRU replacements
and most hardware upgrades while the cabinet is powered up. To maintain proper airflow for cooling and
to ensure EMI compliance, make sure all front bezels, filler panels, and filler modules are reinstalled after
the FRU replacement or hardware upgrade is completed.
IMPORTANT: These procedures are not a substitute for the use of an ESD kit. You should follow them
only in the event of an emergency.
• Before touching any FRU, touch a bare (unpainted) metal surface of the enclosure.
• Before removing any FRU from its antistatic bag, place one hand firmly on a bare metal surface of the
enclosure, and at the same time, pick up the FRU while it is still sealed in the antistatic bag. Once you
have done this, do not move around the room or contact other furnishings, personnel, or surfaces
until you have installed the FRU.
Page 6 of 38
• When you remove a FRU from the antistatic bag, avoid touching any electronic components and
circuits on it.
• If you must move around the room or touch other surfaces before installing a FRU, first place the
FRU back in the antistatic bag. When you are ready again to install the FRU, repeat these
procedures.
NOTE: If you are installing nodes in the Titan 40U-D rack, you must leave the bottom 1U empty.
Begin installing nodes or cable management trays in the second unit from the bottom of the rack.
Page 7 of 38
NOTE:
Take every precaution to ensure that your rack remains stable under the significant weight of an
HD400 node. If you are installing the HD400 in a third party rack you must:
• follow the instructions provided for installing rails in a third party rack.
• install a stabilizer bracket or otherwise secure the rack to the sub�floor.
Installing rails
About this task
Install the rails from the front of the cabinet into which you are installing the . The 4U includes "inner
rails" that slide into the cabinet rail assembly.
CAUTION: Exercise care when installing the short rails. Exposed metal edges may be sharp and
could damage cabling or cause injury to personnel.
Steps
Rail Pins from kit Part Number and Description Suggested Use
036-028-018 - Custom screw, M4 x Used for any non- rack. Can be used in
10MM (Quantity: 4 per kit) racks with threaded holes.
036-028-016 - 3.8MM Alignment Pin Used in racks that have M5, #10, or #12
(Quantity: 8 per kit) threaded holes.
Page 8 of 38
036-028-017 - 4.8MM Alignment Pin Used in racks that have M6 threaded
(Quantity: 8 per kit) holes.
4. Install the right rail to the rack rear channel. Later sections will detail how to adjust rails, if
necessary.
1. Align the right rail with the lower U of the allotted 4U space.
Page 9 of 38
NOTE: Each of the rail alignment pins must be located in the middle holes of the bottom two U
spaces of the 4U space.
2. With the release latch on the outer (rear) part of the rear channel, place the catch
mechanism over the channel.
3. Push the rail back to secure the rail adaptors in the cabinet channel. An audible click
indicates that the rail is secure in the channel.
4. Make sure the rear post/catch mechanism is secure and attached.
Page 10 of 38
Figure 3. Installing the right rail to the front channel
Page 11 of 38
About this task
The rails have four adjustment ranges, 18-22", 22-26", 26-30", 30-34" . The default length (out of the
shipping crate) is the 22-26" setting. The length adjustments provided in this procedure use the default
length as a baseline.
Tool Size/Type
Steps
1. To change the length of the rail to 18-22" (shortest setting) do the following:
1. Orient one of the rails to identify the front of the rail so that the inside of the rail is visible
with the spacing markings visible.
2. Locate the two screws and nuts which hold the length adjustment bracket in place.
3. Using a screwdriver and a nut driver (pliers or vise-grips will work as well), remove both
screws and nuts. The length adjustment bracket will be free of the rail.
4. Move to the front of the rail and align the mounting slots with the mounting holes near
the front of the rail.
Page 12 of 38
Figure 2. 18"-22" marking
5. . Slide the inner rail mechanism to the front of the rail until the 18"-22" mark is visible. If
the inner mechanism is locked, depress the leaf spring and press the rail locking
mechanism to free it.
6. Adjust the hardware to make sure the mounting holes are aligned with the mounting
slots.
7. Secure the length adjustment bracket in place using both screws and nuts that were
removed earlier.
8. Repeat for the other rail.
2. To change the length of the rail to 26-30", do the following:
1. Orient one of the rails to identify the front of the rail so that the inside of the rail is visible
with the spacing markings visible.
2. Locate the most forward (closest to the front of the rail) screw and nut which hold the
length adjustment bracket in place.
3. Using a screwdriver and a nut driver (pliers or vise-grips will work as well), remove the
forward-most screw and nut.
4. Slide the length adjustment bracket to the rear of the rail until it stops.
5. Slide the inner rail mechanism to the rear of the rail until the 26"-30" mark is visible. If
the inner mechanism is locked, depress the leaf spring to free it.
6. Adjust the hardware to make sure the mounting holes are aligned with the mounting
slots.
7. Secure the length adjustment bracket in place using the screw and nut that were
removed earlier.
8. Repeat for the other rail.
3. To change the length of the rail to 30-34"" (longest setting) do the following:
1. Orient one of the rails to identify the front of the rail so that the inside of the rail is visible
with the spacing markings visible.
2. Locate the two screws and nuts which hold the length adjustment bracket in place.
3. Using a screwdriver and a nut driver (pliers or vise-grips will work as well), remove both
screws and nuts. The length adjustment bracket will be free of the rail.
4. Move the length adjustment bracket to the rear of the rail and align the mounting slots
with the mounting holes near the rear of the rail.
Page 13 of 38
Figure 4. 30"-34" Marking
5. Slide the inner rail mechanism to the rear of the rail until the 30-34" mark is visible. If the
inner mechanism is locked, depress the leaf spring to free it.
6. Adjust the hardware to make sure the mounting holes are aligned with the mounting
slots.
7. Secure the length adjustment bracket in place using both screws and nuts that were
removed earlier.
8. Repeat for the other rail.
4. Once the rails are adjusted to the proper length, install the rails in the rack.
Installing rails
About this task
Install the rails from the front of the cabinet into which you are installing the . The 4U includes "inner
rails" that slide into the cabinet rail assembly.
CAUTION: Exercise care when installing the short rails. Exposed metal edges may be sharp and
could damage cabling or cause injury to personnel.
Steps
Rail Pins from kit Part Number and Description Suggested Use
Page 14 of 38
036-028-018 - Custom screw, M4 x Used for any non- rack. Can be used in
10MM (Quantity: 4 per kit) racks with threaded holes.
036-028-016 - 3.8MM Alignment Pin Used in racks that have M5, #10, or #12
(Quantity: 8 per kit) threaded holes.
4. Install the right rail to the rack rear channel. Later sections will detail how to adjust rails, if
necessary.
Page 15 of 38
Figure 1. Rail installation
1. Align the right rail with the lower U of the allotted 4U space.
NOTE: Each of the rail alignment pins must be located in the middle holes of the bottom two U
spaces of the 4U space.
2. With the release latch on the outer (rear) part of the rear channel, place the catch
mechanism over the channel.
3. Push the rail back to secure the rail adaptors in the cabinet channel. An audible click
indicates that the rail is secure in the channel.
Page 16 of 38
4. Make sure the rear post/catch mechanism is secure and attached.
Page 17 of 38
Figure 3. Installing the right rail to the front channel
If for any reason you feel that the rails installed in the rack are not appropriate for the installation, do not
continue. Contact your EMC Service Representative immediately.
NOTE: Use of a server lift or other appropriate lift�assist equipment is strongly recommended for
installation of the HD400.
Four (4) nut clips are required on the front NEMA channels to secure the DAE chassis to the front of the
cabinet.
Steps
Page 18 of 38
o On the middle hole of the top U section on the left NEMA channel. (or 3rd hole above
the top rail pin)
o On the top hole of the middle U section on the left NEMA channel. (or 1st hole above the
top rail pin)
o On the middle hole of the top U section on the right NEMA channel. (or 3rd hole above
the top rail pin)
o On the top hole of the middle U section on the right NEMA channel. (or 1st hole above
the top rail pin)
2. After installing, make sure the nut clips line up with the their respective holes and adjust if
needed.
If a node with all of the FRUs removed is being installed, the chassis can be installed without using the
lift. If the node is populated with FRUs prior to installing, then this task requires the use of a portable lift.
CAUTION: DO NOT ATTEMPT to install a populated node without a mechanical lift. Attempting to
install a populated node without a lift could damage the equipment and cause injury to personnel
CAUTION: Secure the enclosure to the portable lift using the securing straps before moving the lift.
Page 19 of 38
Steps
1. If the portable lift is not available or cannot access the rack, the node must be de-populated
before it is installed on the rails. Do the following:
1. Refer to the procedure for removing the Suitcase and remove the Suitcase.
2. Refer to the procedure for removing the disk drives and remove the disk drives. Label
each disk drive as to its exact location so that it can be re-installed once the chassis is
installed in the cabinet.
2. Manually, or using the portable lift (shown below), align the chassis rails with the inner rails
attached to the cabinet.
3. Manually slide the inner rail over the chassis rail 2-3 inches to line them up.
NOTE: You may need to release sagging tension on the node by pulling the lift arms/tray up slightly.
Page 20 of 38
4. Release the lift casters and carefully slide the node into the cabinet as far as the lift will allow.
5. Secure the lift casters on the floor.
6. Carefully push the node off the lift arms/tray and into the cabinet.
CAUTION: Make sure to leave the lift under the chassis until the node is safely balanced and
secured within the cabinet.
7. If the node was de-populated prior to installation, re-populate the node as follows:
1. Re-install the disk drives in the exact location from which they were removed.
2. Slide the node into the cabinet.
3. From the rear of the cabinet, re-install the Suitcase.
How the chassis is inserted and secured into the cabinet depends upon which configuration of securing
mechanism is installed on the shelf. The first configuration has orange self-locking latches above the
enclosure latch handles. The second configuration has captive shoulder screws which attach the chassis
to the cabinet.
Steps
1. If your shelf has the orange self-locking latches above the enclosure latch handles, proceed as
follows:
Page 21 of 38
Figure 1. Inserting and securing the chassis to the cabinet
1. Using the orange enclosure latch handles, push the shelf completely into the cabinet.
Make sure the self-locking latches are pushed in and fully engaged, and the enclosure
cannot slide back out of the cabinet.
2. Secure the two knurled black captive screws to the NEMA channel and nut clips. These
screws secure the chassis cover and prevent the cover from coming out of the cabinet
during service.
2. If your shelf has the two-shoulder screw configuration, proceed as follows:
Page 22 of 38
Figure 2. Inserting and Securing the Chassis to the Cabinet (Shoulder Screw Configuration)
1. If the shelf is being installed in a non- rack, proceed to substep b. For racks, use the
orange enclosure latch handles to push the completely into the cabinet. Align the two
semi-captive M5 shoulder screws on each side with the mounting holes on the cabinet.
Thread the shoulder screws into the mounting holes and finger-tighten the shoulder
screws.
2. To install the shelf into a non- rack (not compatible with the M5 shoulder screws), do the
following:
Page 23 of 38
3. Remove the semi-captive M5 screws by sliding them from the ears.
4. For non-threaded racks, place tinnerman clips which match the truss head screws to be
used over the mounting holes on the rack. Refer to the table at the end of this
procedure.
5. Use the orange enclosure latch handles to push the shelf completely into the cabinet.
Secure the enclosure to the rack using four truss-head screws.
3. NOTE The top cover can secure to the cabinet in one of two ways, depending upon your
configuration. Some configurations do not have any hardware installed into the top cover. In
these configurations, the appropriate truss head screw must be used to attach the top cover to
the cabinet. Some configurations have semi-captive screws in the top cover that will attach to
cabinets. If non- cabinets are being used, the semi-captive screws can be removed and truss
Page 24 of 38
head screws can be used as required to attach the top cover to the cabinet. To secure the top
cover using a top cover that does not have any mounting hardware, secure the top cover to the
rack using the screws or pins from the kit that accompanies the device. These screws secure the
chassis cover and prevent the cover from coming out of the cabinet during operation. Secure the
top cover to the rack as follows:
1. If the shelf is being installed into the rack, secure the top cover to the rack using M5
truss head screws from the kit. Tighten the screws until they are finger tight.
2. If the shelf is being installed into a non- rack, identify the mounting holes on the rack that
will line up with the mounting holes on the top cover. Identify which truss head screws
will be used to secure the top cover to the rack (refer to the following table for guidance).
For non-threaded racks, place tinnerman clips over the rack mounting holes. Attach the
top cover to the rack using the appropriate truss head screws from the hardware kit that
comes with the shelf.
Truss Head Screw from Part Number and Description Suggested Use
kit
Page 25 of 38
036-032-011 - Screw, M6-1.0x12, Can be used in non- racks.
Truss Head Phillips with patch
4. To secure the top cover using a top cover with semi-captive screws, do the following:
1. For the rack, align the semi-captive screws with the mounting hole in the cabinet and
thread the screw into the mounting hole.
5. If a non- rack is being used that is not compatible with the semi-captive screw, remove the semi-
captive screw by pulling the screw assembly out the side of the top cover. Identify the mounting
holes on the rack that will line up with the mounting holes on the top cover. Identify which truss
head screws will be used to secure the top cover to the rack. For non-threaded racks, place
tinnerman clips over the rack mounting holes. Attach the top cover to the rack using the
appropriate truss head screws from the hardware kit that comes with the shelf.
There are two sets of screws (4 total) used to secure the chassis to the cabinet. Refer to Installing the
Chassis Securing Screws while performing this task.
Page 26 of 38
Figure 1. Installing the Chassis Securing Screws
Steps
Using a Philips driver, install the four screws to secure the chassis to the cabinet.
Back panel
The back panel provides connections for power, network access, and serial communication, as well as
access to the power supplies.
Page 27 of 38
4. Gigabit Ethernet external network ports
1. With an InfiniBand cable, connect the int-a port to the network switch for the Internal A network.
2. If the network topology supports a second internal network, connect the int-b port to a separate
network switch for the int-b network.
Complete the following steps to connect the node with the switch for the external network.
Steps
1. With an ethernet cable, connect the ext-1 port on the node to the switch for the external network.
For additional 1 Gb connections, use the ext-2 port.
CAUTION: You must connect the 1 Gb ext-1 port to the external network, even if you were planning
on only connecting the 10Gb ports. If you do not connect the 1 Gb ext-1 port, and if the node cannot
authenticate to your Active Directory (AD) server, it is possible that the node will not join the cluster
and that you will experience additional downtime.
2. If your node is equipped with 10Gb ports, connect the 10gige-1 port on the node to the switch for
the external network.
Page 28 of 38
For additional connections, use the 10gige-2 port.
1. Connect the power supply cables to the power connectors on the back panel of the node.
2. Connect each power supply cable to a separate power source.
HD400 nodes require high-line power and do not operate on 110 VAC. For more information
about power requirements, see the HD400 Site Preparation and Planning Guide.
NOTE:
Both power supplies must be connected. Operating a node using only one power supply for an extended period shortens the
life of the power supply. If the installation site has a limited number of power outlets, contact Technical Support before using
a Y-cable to power both supplies from a single power source.
Power up the node by pressing the power button on the back panel of the node. It is located in the lower
half of the back panel, to the right of the power supplies.
Page 29 of 38
Configure the node
Before using the node, you must add the node to an existing cluster.
Compliance mode controls how SmartLock directories function and limits access to the cluster in
alignment with SEC rule 17-a4(f).
A valid SmartLock license is required to configure a node in compliance mode.
CAUTION: Once you select to run a node in SmartLock compliance mode, you cannot leave
compliance mode without reformatting the node.
• vCenter
• VMware vSphere API for Storage Awareness (VASA)
• VMware vSphere API for Array Integration (VAAI) NAS Plug-In
If no serial ports are available on your client system, you can use a USB-to-serial converter.
Steps
1. Connect a null modem serial cable to the serial port of a computer, such as a laptop.
2. Connect the other end of the serial cable to the serial port on the back panel of the node.
3. Start a serial communication utility such as Minicom (UNIX) or PuTTY (Windows).
4. Configure the connection utility to use the following port settings:
Setting Value
Data bits 8
Parity None
Stop bits 1
Page 30 of 38
5. Open a connection to the node.
The following procedure assumes that there is an open serial connection to a new node.
NOTE: You can type back at most prompts to return to the previous step in the wizard.
Steps
1. For new clusters, joining a node to an existing cluster, or preparing a node to run in SmartLock
compliance mode, choose one of the following options:
o To create a cluster, type 1.
o To join the node to an existing cluster, type 2.
o To exit the wizard and configure the node manually, type 3.
o To restart the node in SmartLock compliance mode, type 4.
CAUTION: If you choose to restart the node in SmartLock compliance mode, the node restarts and
returns to this step. Selection 4 changes to allow you to disable SmartLock compliance mode.
Selection 4 is the last opportunity to back out of compliance mode without reformatting the node.
For new clusters, the following table lists the information necessary to configure the cluster. To
ensure that the installation process is not interrupted, it is recommended that you collect this
information before installation.
Setting Description
SmartLock compliance A valid SmartLock license for clusters in compliance mode only
license
Root password The password for the root user. Clusters in compliance mode do not allow
a root user to be configured request and configure a compliance
administrator (comp admin) password instead.
Cluster name The name used to identify the cluster. Cluster names must begin with a
letter and can contain only numbers, letters, and hyphens.
Page 31 of 38
Setting Description
node names.
int-a network settings The int-a network settings are for communication between nodes.
o Netmask The int-a network must be configured with IPv4.
o IP range The int-a network must be on a separate subnet from an int-b/failover
network.
int-b/failover network settings The int-b/failover network settings are optional. The int-b network is for
communication between nodes, and provides redundancy with the int-a
o Netmask
network.
o IP range
The int-b network must be configured with IPv4.
o Failover IP range
The int-a and int-b networks must be on separate subnets.
The failover IP range is a virtual IP range that is resolved to either of the
active ports during failover.
The external network settings are for client access to the cluster. The 25
External network settings Gb, and 100 Gb ports can be configured from the wizard.
o Netmask
The default external network can be configured with IPv4 or IPv6
o MTU addresses.
o IP range The MTU choices are 1500 or 9000.
Configure the external network with IPv6 addresses by entering an
integer less than 128 for the netmask value. The standard external
netmask value for IPv6 addresses is 64. If you enter a netmask value
with dot-decimal notation, use IPv4 addresses for the IP range.
In the configuration wizard, the following options are available:
Or
Page 32 of 38
Setting Description
Default gateway The IP address of the optional network gateway through which the cluster
communicates with clients outside the subnet. Enter an IPv4 or IPv6
address, depending on how the external network is configured.
Date and time settings Date and time settings for the cluster.
o Time zone
o Day and time
Cluster join mode The method that the cluster uses to add new nodes. Choose one of the
following options:
Manual join
Secure join
NOTE: If you are installing a node that contains SEDs (self-encrypting drives), the node will format
the drives during the join process unless the drives were preformatted beforehand, using the
OneFS configuration wizard. The formatting process might take up to two hours to complete.
To configure a new cluster and join all the SED nodes to the cluster using Preformat:
Steps
Page 33 of 38
1. Connect to each node using the serial console and enter Preformat in the configuration wizard
main menu.
Once preformat is complete on each node, the configuration wizard is displayed again and the
preformat option is no longer available.
2. Connect to first node using the serial console again and use the configuration wizard to create a
new cluster.
3. Connect to each subsequent node using the serial console again. Use the configuration wizard
to join an existing cluster.
LCD Interface
The LCD interface is located on the node front panel. The interface consists of the LCD screen, a round
button labeled ENTER for making selections, and four arrow buttons for navigating menus.
The LCD screen is dark until you activate it. To activate the LCD screen and view the menu, press the
square selection button.
Press the right arrow button to move to the next level of a menu.
Attach menu
The Attach menu contains the following sub-menu:
Drive
Adds a drive to the node. After you select this command, you can select the drive bay that contains the
drive you would like to add.
Status menu
The Status menu contains the following sub-menus:
Alerts
Displays the number of critical, warning, and informational alerts that are active on the cluster.
Cluster
Details
Displays the cluster name, the version of OneFS installed on the cluster, the health status of the cluster,
and the number of nodes in the cluster.
Page 34 of 38
Capacity
Displays the total capacity of the cluster and the percentage of used and available space on the cluster.
Throughput
Node
Details
Displays the node ID, the node serial number, the health status of the node, and the node uptime as
<days>, <hours>:<minutes>:<seconds>
Capacity
Displays the total capacity of the node and the percentage of used and available space on the node.
Network
Throughput
Disk/CPU
Displays the current access status of the node, either Read-Write or Read-Only. Also displays the
current CPU throttling status, either Unthrottled or Throttled.
Drives
Hardware
Displays the current hardware status of the node as <cluster name>-<node number>:<status>.
Statistics
Page 35 of 38
Displays a list of hardware components. Select one of the hardware components to view statistics
related to that component.
Update menu
The Update menu allows you to update OneFS on the node. Press the selection button to confirm that
you would like to update the node. You can press the left navigation button to back out of this menu
without updating.
Service menu
The Service menu contains the following sub-menus:
Throttle
Unthrottle
Read-Only
Read-Write
UnitLED On
UnitLED Off
Shutdown menu
The Shutdown menu allows you to shut down or reboot the node. This menu also allows you to shut
down or reboot the entire cluster. Press the up or down navigation button to cycle through the four shut
down and reboot options, or to cancel out of the menu.
Press the selection button to confirm the command. You can press the left navigation button to back out
of this menu without shutting down or rebooting.
Page 36 of 38
Update the Install Base
After all work is complete, engage the Global Asset Management Team to update the Install Base to
notify Dell of product installation, hardware upgrades, remote connection updates, or Install at Location
changes for select products.
Prerequisites
NOTE: To access the submission forms, you must be logged in as an authorized user: Partner or
Employee. Employees are noted by a black checkmark next to their name.
Steps
• https://www.dell.com/support/incidents-online/en-
us/contactus/product/isilon-onefs
Page 37 of 38
Hubs
Page 38 of 38