2016 California Mechanical Code - Part 4 - SUPPLEMENT - July 2018
2016 California Mechanical Code - Part 4 - SUPPLEMENT - July 2018
July 1, 2018
General Information:
1. The date of this Supplement is for identification purposes only. See the History Note
Appendix on the backside or accompanying page.
3. Health and Safety Code Section 18938.5 establishes that only building standards in effect
at the time of the application for a building permit may be applied to the project plans and
construction. This rule applies to both adoptions of building standards for Title 24 by the
California Building Standards Commission, and local adoptions and ordinances imposing
building standards. The new building standards provided with the enclosed blue
supplement pages must not be enforced before the effective date.
4. Not all code text on the enclosed blue supplement pages is a new building standard. New,
amended, or repealed building standards are identified by margin symbols. An explanation
of margin symbols is provided in the code before the Table of Contents.
5. You may wish to retain the superseded material with this revision record so that the prior
wording of any section can be easily ascertained.
internal moisture sources are not sufficient to meet the psychiatric hospitals, general acute-care hospitals, and
requirements of sensitive areas or rooms in Table 4-A, special treatment program service units in skilled nursing
humidification shall be provided by means of the health- facilities, psychiatric, seclusion, and holding-patient rooms
care facility air-handling systems. Temperature shall be shall be designed with security diffusers, grilles, and registers.
individually controlled for each operating and delivery
room. Burn unit patient rooms that require humidifiers
321.0 Essential Mechanical Provisions. [OSHPD 1, 2, 3
to comply with the requirements of sensitive areas or
(Surgical Clinics only) & 4] During periods of power
rooms in Table 4-A shall be provided with individual
outages essential electrical power shall be provided for the
humidity control. All humidifiers shall use dry steam.
following equipment:
Humidifiers shall be located within air handling systems
or ductwork to avoid moisture accumulation in down- 321.1 (Does not apply to OSHPD 3 surgical clinic.) All
stream components, including filters and insulation. heating equipment necessary to maintain a minimum temper-
ature of 60°F (15.6°) in patient areas which are not specified
320.1.2 Heating systems shall be designed based on the
in Section 322.0.
“Heating DB 99.6%” column of the Climatic Design
Data in ASHRAE Handbook-Fundamentals. The systems 321.2 All heating equipment necessary to maintain the
shall be thermostatically controlled with appropriate minimum temperatures listed in Table 4-A for sensitive areas
zoning to achieve the above conditions. specified in Section 322.0.
320.1.3 Cooling systems shall be designed based on the 321.3 Equipment necessary for humidification of the areas
0.4% columns of the four Annual Design Conditions listed in Section 322.0.
titled Cooling, Evaporation, Dehumidification, and 321.4 All supply, return, and exhaust fans required to maintain
Enthalpy shown by the Climate Design Data in ASHRAE the positive and negative air balances as required in Table 4-A.
Handbook-Fundamentals. The systems shall be thermo- 321.5 All control components and control systems necessary
statically controlled with appropriate zoning to achieve for the normal operation of equipment required to have essen-
the above conditions. tial electrical power.
320.2 Requirements for Skilled Nursing, Intermediate Care 321.6 Alarms for airborne infection isolation rooms and
Facilities and Basic Services Provided in Correctional protective environment rooms.
Treatment Centers. [For OSHPD 2 & 4]
320.2.1 Systems shall accommodate the provisions of 322.0 Sensitive Areas or Rooms. [OSHPD 1, 2, 3 (Surgical
Sections 320.1.2 through 320.1.3. Clinics) & 4] The following are sensitive areas or rooms:
320.2.2 Where air conditioning is provided, the system (1) Operating room, hybrid operation room
shall be thermostatically controlled in one or more zones.
(2) Cystoscopy
320.3 Requirements for Outpatient Facilities and Licensed (3) Cardiac catheterization lab
Clinics. [For OSHPD 3]
(4) Trauma/cardiac room
320.3.1 The system shall be designed to provide the
temperature and humidity’s for sensitive areas for rooms (5) Delivery room, cesarean operating room
shown in Table 4-A. (6) Gastrointestinal endoscopy procedure room
320.4 Telephone and Data Equipment Rooms. [OSHPD 1 & (7) Post-anesthesia care unit
4] Where telecommunications service entrance rooms, tech- (8) Newborn nursery
nology equipment centers, or technology distribution rooms (9) Newborn intensive-care nursery unit
are provided in accordance with Section 1224.5 of the Cali-
(10) Intensive care
fornia Building Code, the following requirements shall apply:
(11) Burn unit
320.4.1 Power for HVAC systems serving the room(s)
shall be supplied by the Equipment Branch pursuant to 322.1 The following conditions shall be met for sensitive
the California Electrical Code. Where redundant systems areas or rooms:
are provided, only one shall be required to be supplied by (1) Thermostats and humidistats shall be either locally reset-
the Equipment Branch. table and of the non-locking type or remotely resettable
320.4.2 Mechanical equipment or fixtures that are not and of the locking type.
directly related to the support of the room shall not be (2) Systems shall be capable of maintaining the rooms within
installed in or pass through the room. the temperature range in Table 4-A during normal oper-
ation. Lower or higher temperature shall be permitted
Exception: Unrelated ductwork may be installed and shall
when patients’ comfort and/or medical conditions require
be not less than 10 feet (3048 mm) above the finished floor.
those conditions.
320.4.3 HVAC systems shall be provided to maintain
(3) The humidity ranges listed in Table 4-A are the minimum
environmental conditions recommended in ASHRAE’s
and maximum limits where control is specifically needed.
Thermal Guidelines for Data Processing Environment
and the requirements of the specific equipment installed. (4) Types of intensive care service spaces are listed in the
California Building Code.
320.5 Psychiatric Services. [OSHPD 1, 2, & 4] For projects
associated with provision of psychiatric services in acute
403.0 Ventilation Rates. [Not permitted for OSHPD 1, 2, 3 Vot = ∑ all zones Voz (Equation 403.4)
& 4]
403.1 General. The design outdoor air intake flow rate for a 403.5 Multiple-Zone Recirculating Systems. For ventila-
ventilation system shall be determined in accordance with tion systems where one or more air handlers supply a mixture
Section 403.2 through Section 403.9.4. of outdoor air and recirculated air to more than one ventila-
403.2 Zone Calculations. Ventilation zone parameters shall tion zone, the outdoor air intake flow (Vot) shall be deter-
be determined in accordance with Section 403.2.1 through mined in accordance with Section 403.5.1 through Section
Section 403.2.3 for each ventilation zone served by the venti- 403.5.4. [ASHRAE 62.1:6.2.5]
lation system. [ASHRAE 62.1:6.2.2] 403.5.1 Primary Outdoor Air Fraction. The primary
403.2.1 Breathing Zone Outdoor Airflow. The outdoor outdoor air fraction (Zpz ) shall be determined for venti-
airflow required in the breathing zone of the occupiable lation zones in accordance with Equation 403.5.1.
space or spaces in a ventilation zone, i.e., the breathing [ASHRAE 62.1:6.2.5.1]
(6608 L/s) of exhaust air for each operating vehicle. 403.9.4 Class 4 Air. Class 4 air shall not be recirculated
Number of operating vehicles shall be determined or transferred to other spaces or be recirculated within
based on 2.5 percent of all parking spaces (and not the space of origin. [ASHRAE 62.1:5.16.3.4]
less than one vehicle).
403.7.2.3 Exhaust Inlet Distribution. [HCD 1 & 2] 404.0 Multiple-Zone Systems.
To ensure proper exhaust of contaminated air and
fumes from parking garages, exhaust systems 404.1 General. This section presents an alternative procedure
utilizing multiple exhaust inlets shall be designed so for calculating the system ventilation efficiency (Ev) where
that exhaust inlets are distributed in such a manner values in Table 403.5.2 are not used. The system ventilation
that no portion of the parking garage is more than efficiency shall equal the lowest zone ventilation efficiency
50 feet (15 240 mm) from an exhaust inlet. Such among the ventilation zones served by the air handler in
exhaust inlets shall be installed so that the highest accordance with Equation 404.1. [ASHRAE 62.1:A1.3]
elevation of the exhaust inlet is no greater than 12
inches (305 mm) below the lowest ceiling level. Ev = minimum (Evz) (Equation 404.1)
Exception: Garage exhaust systems designed without
distributed exhaust inlets may have their exhaust
inlets designed based on the principles of engineering 404.2 Average Outdoor Air Fraction. The average outdoor
and mechanics and shall provide the minimum air fraction (Xs) for the ventilation system shall be determined
required exhaust rate in Table 403.7. in accordance with Equation 404.2.
403.7.2.4 Exhaust System Operation. [HCD 1 & 2]
Exhaust systems shall operate continuously unless Xs =Vou/Vps (Equation 404.2)
one of the exceptions to continuous operation of
Section 403.7 is utilized.
The uncorrected outdoor air intake (Vou) shall be deter-
403.8 Dynamic Reset. The system shall be permitted to be mined in accordance with Section 403.5.3, and the system
designed to reset the outdoor air intake flow (Vot ), the space primary airflow (Vps) shall be determined at the condition
or ventilation zone airflow (Voz ) as operating conditions
analyzed. [ASHRAE 62.1:A1.1]
change. [ASHRAE 62.1:6.2.7]
403.9 Air Classification and Recirculation. Air shall be
404.3 Zone Ventilation Efficiency. The zone ventilation effi-
ciency (Evz) shall be the efficiency with which a system
«
classified, and the recirculation or transfer shall be limited in
accordance with Section 403.9.1 through Section 403.9.4. distributes outdoor air from the intake to an individual
[ASHRAE 62.1:5.16] Recirculated air shall not be taken from breathing zone, and shall be determined in accordance with
Section 404.3.1 or Section 404.3.2. [ASHRAE 62.1:A1.2]
prohibited locations in accordance with Section 311.3.
403.9.1 Class 1 Air. Recirculation or transfer of Class 1 404.3.1 Single Supply Systems. For single supply
systems, where the air supplied to a ventilation zone is a
«
air to other spaces shall be permitted. [ASHRAE
62.1:5.16.3.1] mixture of outdoor air and system-level recirculated air,
zone ventilation efficiency (Evz) shall be determined in
403.9.2 Class 2 Air. Recirculation of Class 2 air within accordance with Equation 404.3.1. Examples of single
the space of origin shall be permitted. Recirculation or
supply systems include constant-volume reheat, single-
transfer of Class 2 air to other Class 2 or Class 3 spaces
duct VAV, single-fan dual-duct, and multizone systems.
shall be permitted, provided the other spaces are used for
the same or similar purpose or task and involve the same
or similar pollutant sources as the Class 2 space. Transfer Evz = 1+Xs–Zpz (Equation 404.3.1)
of Class 2 air to toilet rooms shall be permitted. Recir-
culation or transfer of Class 2 air to Class 4 spaces shall
be permitted. Class 2 air shall not be recirculated or trans- The average outdoor air fraction for the system (Xs)
ferred to Class 1 spaces. Where using an energy recover shall be determined in accordance with Equation 404.2
device, recirculation from leakage, carryover, or transfer and the primary outdoor air fraction for the zone (Zpz)
from the exhaust side of the energy recovery device shall shall be determined in accordance with Section 403.5.1.
[ASHRAE 62.1:A1.2.1]
«
be permitted and the recirculated Class 2 air shall not
exceed 10 percent of the outdoor air intake flow. 404.3.2 Secondary-Recirculation Systems. For
[ASHRAE 62.1:5.16.3.2] secondary-recirculation systems where the supply air or a
403.9.3 Class 3 Air. Recirculation of Class 3 air within portion thereof to a ventilation zone is recirculated air
the space of origin shall be permitted. Class 3 air shall from other zones, without being directly mixed with
not be recirculated or transferred to other spaces. Where outdoor air, the zone ventilation efficiency (Evz) shall be
using an energy recover device, recirculation from determined in accordance with Equation 404.3.2(1).
leakage, carryover, or transfer from the exhaust side of Examples of secondary-recirculation systems include
the energy recovery device shall be permitted and the dual-fan dual-duct and fan-powered mixing box systems,
recirculated Class 3 air shall not exceed 5 percent of the and systems that include transfer fans for conference
outdoor air intake flow. [ASHRAE 62.1:5.16.3.3] rooms.
fumes. Plumbing vents shall be located in relation to Exception: For airborne infection isolation rooms
outdoor air intakes per California Plumbing Code. The and protective environment rooms, see Sections
bottom of outdoor air intakes shall be located as high as 414.0 and 415.0.
practicable, but not less than 10 feet (3048 mm) above 407.4.1.2 Room supply air outlets and room recir-
ground level. If installed above the roof, they shall be culation and exhaust air inlets installed in nonsen-
located 18 inches (457 mm) above roof level or 3 feet (914 sitive areas shall be located not less than 3 inches
mm) above a flat roof where heavy snowfall is anticipated.
(76 mm) above the floor.
Exceptions:
Exception: For airborne infection isolation rooms
(1) These dimensions may be reduced if it is demon- and protective environment rooms, see Sections
strated by the submission of details and calculations 414.0 and 415.0.
that location of intakes with respect to exhausts and
407.4.1.3 Corridors shall not be used to convey
their orientation, or the use of special filters,
supply, return, or exhaust air to or from any room if
provides equal performance.
the corridor is required to be of fire resistive
(2) The requirements regarding the bottom of outdoor construction per the California Building Code.
air intakes and installation through the roof do not
apply to skilled nursing facilities, intermediate-care Exceptions:
facilities or nonsensitive areas in correctional treat- (1) Mechanically exhausted toilet rooms of 50
ment centers. square feet (4.7 m2) or less and small rooms of
407.2.2 Exhaust Outlets. Exhaust outlets shall be 30 square feet (2.79 m2) or less such as janitor
located a minimum of 10 feet (3048 mm) above adjoining closets, housekeeping rooms, and electrical or
grade and 10 feet (3048 mm) from doors, occupied areas, telephone closets opening directly onto
and operable windows. corridor.
Exception: Airborne infection isolation rooms shall (2) Air transfer caused by pressure differentials in
modulating damper in the return or exhaust air for 408.2.3 Noncentral air systems serving any areas not
each zone. The damper will modulate from full open listed in Table 4-B shall be provided with filter arrange-
to minimum position in conjunction with the supply ment and efficiency specifically approved by the
air VAV terminal box. enforcing agency.
408.2.4 Noncentral recirculating air handling systems,
408.0 Filters. [OSHPD 1, 2, 3 & 4] for example, through-the-wall units, fan coil units, and
heat pumps may be utilized for single patient rooms of
408.1 General. Filter efficiencies shall be certified by the
one or more beds. Filtration for these units shall have a
manufacturer and shall be based on ASHRAE 52.2 Method
minimum weight arrestance value of 50 percent, based
of Testing General Ventilation Air-Cleaning Devices for
Removal Efficiency by Particle Size when specifically set on ASHRAE 52.2 or a minimum efficiency reporting
forth in these standards. value (MERV) of 1, based on ASHRAE 52.2. The air
ventilation system providing the minimum air changes of
408.1.1 A filter gauge shall be installed across each filter outdoor air shall comply with Table 4-B. These units may
bank serving central air systems. The gauge shall be red be used as recirculating units only. All outdoor air
lined or a filter alarm light installed to signal when the requirements shall be met by a separate central air
recommended maximum static pressure drop has been handling systems.
reached.
408.3 Filters for Skilled Nursing Facilities, Intermediate
408.1.2 Central air-handling systems are defined as any
Care Facilities, and Correctional Treatment Centers.
unit requiring duct work on the supply or inlet side that
serve more than one room. 408.3.1 The air ventilation systems shall comply with
code requirements of this section for skilled nursing facil-
408.1.3 Filter banks shall be visually inspected for torn
ities, intermediate care facilities and correctional treat-
media and bypass in filter frames by means of a flash-
ment centers and shall have filter bank efficiencies as
light or equivalent, both with fans in operation and
listed in Table 4-C.
stopped. Tears in media and bypass in filter frames shall
be eliminated in accordance with the manufacturer’s 408.3.2 Noncentral air systems serving single patient
directions and the requirements of the enforcing agency rooms of one or more beds shall comply with Table 4-C.
prior to commencing operation of the system. 408.3.3 Noncentral recirculating air-handling systems,
408.1.4 Central air-handling systems shall be maintained i.e. through the wall units, may be utilized for each
in a reasonably clean condition during construction and patient room with one or more beds. Filtration for these
shall be cleaned as necessary prior to replacement of units shall have a minimum weight arrestance value of 50
temporary filter used during construction to ensure that percent, based on ASHRAE 52.2 or a minimum efficiency
clean air will be delivered to the occupied spaces. reporting value (MERV) of 1, based on ASHRAE 52.2.
408.1.5 Filter bank No. 1 shall be located upstream of The air ventilation system providing the minimum air
the air-conditioning equipment. Filter bank No. 2 and changes of outdoor air shall comply with Table 4-C.
filter bank No. 3 shall be located downstream of the These units may be used as recirculating units only. All
supply fan and all cooling and humidification equipment outdoor air requirements shall be met by a separate
with efficiencies as indicated in Table 4-B or Table 4-C. central air handling system.
Exception: Dry steam-type humidifiers for local room 408.3.4 Airborne infection isolation rooms, protective
humidity control may be installed in the supply air duct environment rooms, and sensitive areas in correctional
downstream of the final filter bank where designs are treatment centers shall comply with Section 408.2.
specifically approved by the enforcing agency. Dry steam 408.4 Filters for Outpatient Facilities.
is that which is defined in the ASHRAE HVAC Systems 408.4.1 The air ventilation systems shall comply with
and Equipment Handbook. code requirements of this section for outpatient facilities
408.1.6 Filter bank No. 2 and filter bank No. 3 media and shall have filter bank efficiencies as listed in Table
shall be rigid or supported (noncollapsing type) and 4-B.
shall operate on the principles of impingement, straining, 408.4.2 Noncentral air systems serving individual rooms
and diffusion. shall comply with Table 4-B.
408.2 Filters for Hospitals.
408.2.1 All air-ventilation systems shall comply with 409.0 Ducts. [OSHPD 1, 2, 3 & 4]
code requirements of this section and shall have filter
bank efficiencies as listed in Table 4-B. 409.1 Ducts which penetrate construction, intended for X-ray
or other radiation protection, shall not impair the effective-
408.2.2 Noncentral recirculating air systems providing ness of the protection.
cooling to high heat producing equipment located in
nonsensitive areas shall have a filter with 30 percent 409.2 Duct linings and their use shall meet the requirements
average efficiency based on ASHRAE 52.2 or a minimum of Chapter 6, California Mechanical Code.
efficiency reporting value (MERV) of 8 based on 409.3 Insulation of Ducts. Cold air ducts shall be insulated
ASHRAE 52.2. wherever necessary or to prevent condensation.
409.4 The anchorage and supporting structural elements for filter with at least an 80 percent average efficiency based on
airducts shall be designed to withstand the lateral forces as ASHRAE 52.2 or a minimum efficiency reporting value
required by the California Building Code, Title 24, Part 2. (MERV) of 13, based on ASHRAE 52.2.
Exception: For skilled nursing facilities, intermediate care
410.0 Laboratory Ventilating Systems and Hoods. [OSHPD facilities and correctional treatment centers, the air from dining
1, 2, 3 & 4] area may be used to ventilate food preparation areas only after
it has passed through a filter with a 50 percent average effi-
410.1 Laboratory Ventilating Systems. Laboratory venti-
ciency based on ASHRAE 52.2 or a minimum efficiency
lating systems shall comply with NFPA 99, as required by
Section 1224.4.6.4 of the California Building Code. reporting value (MERV) of 10, based on ASHRAE 52.2.
410.2 Exhaust Hoods and Safety Cabinets. Hoods and safety
cabinets may be used for normal exhaust of a space provided 412.0 Boiler, Mechanical, and Electrical Rooms. [OSHPD
minimum air change rates are maintained. If air change stan- 1, 2, 3 & 4]
dards in Table 4-A do not provide sufficient air for proper 412.1 Boiler, heater and electrical equipment rooms shall be
operation of exhaust hoods and safety cabinets (when in use), provided with outdoor air so as to maintain combustion rates
supplementary makeup air (filtered and preheated) shall be of equipment and temperatures in the rooms and in adjoining
provided around these units to maintain the required airflow areas as rated in this chapter.
direction and exhaust velocity. Makeup systems for hoods shall 412.2 Floor surfaces in occupied spaces above such rooms
be arranged to minimize “short circuiting” of air and to avoid should not exceed a temperature of 85°F (29.4°C), and suit-
reduction in air velocity at the point of contaminant capture. able insulation may be required.
410.3 Laboratory Fume Hoods. Laboratory fume hoods shall
meet the following standards:
413.0 Odorous Rooms. [OSHPD 1, 2, 3 & 4]
410.3.1 General Standard. Average face velocity shall
be at least 75 feet per minute (0.38 meters per second). 413.1 Rooms in areas where excessive heat or moisture is
Exhaust system shall be separate from the building generated, where objectional odors or dust are present, or
exhaust system. Exhaust fan shall be located at the where flammable or toxic gases may accumulate, which are
discharge end of the system. Exhaust duct system shall be used by health facility personnel or patients, shall be provided
of noncombustible corrosion-resistant material as with exhaust ventilation to change the air a minimum of ten
required to meet the planned usage of the hood. times per hour.
410.3.2 Special Standards for Use with Strong Oxidants. 413.2 Kitchen, morgues and laundries located inside a
Fume hoods and their associated equipment in the air hospital building or skilled nursing facility in which patients
stream intended for use with perchloric acid and other are accommodated, or treated, shall be ventilated with
strong oxidants shall be constructed of stainless steel or exhaust systems which will provide a minimum of ten air
other material consistent with special exposures. Hoods changes per hour and prevent odors from entering patient
and equipment shall be provided with a water wash and areas.
drain system to permit periodic flushing of duct and hood.
When perchloric acid or other strong oxidants are only 414.0 Airborne Infection Isolations Rooms. [OSHPD 1, 2, 3
transferred from one container to another, standard labo- & 4]
ratory fume hoods and the associated equipment may be
used in lieu of stainless steel construction. 414.1 Exhaust Systems. A separate, dedicated exhaust
system shall be provided for airborne infection isolation
410.3.3 Special Standards for Use with Infectious or rooms. The dedicated system may serve more than one
Radioactive Materials. Each hood shall have a minimum
airborne infection isolation room, adjoining toilet room and
face velocity of 90 to 110 feet per minute (0.45 to 0.56
anteroom. The exhaust ducts shall be identified by appro-
meters per second) with suitable pressure-independent
priate labeling with the words "Caution Airborne Infection
air-modulating devices and alarms to alert staff of fan
Isolation Rooms Exhaust" or similar terminology. Such
shutdown or loss of airflow. Each hood shall have filters
labeling shall be in a manner which is not readily removable
with a 99.97 percent efficiency (based on the DOP test
and shall appear on the exhaust duct at intervals of not more
method) in the exhaust stream and be designed and
equipped to permit the safe removal, disposal, and than 20 feet (6096 mm) and at least once near each room
replacement of contaminated filters. Filters shall be as and each story traversed by the exhaust system. Exhaust fans
close to the hood as practical to minimize duct contam- shall comply with Section 407.1.2. The discharge from
ination. Fume hoods intended for use with radioactive exhaust fans shall be located above the roof and shall be
isotopes shall be constructed of stainless steel or other located a minimum of 25 feet (7620 mm) from areas that may
material suitable for the particular exposure. be occupied, doors, operable windows, outdoor air intakes,
or other openings into the building. The exhaust fan
discharge shall be labeled in a manner which readily iden-
411.0 Kitchen and Dining Areas. [OSHPD 1, 2, 3 & 4] tifies the precautions which should be observed. To ensure
411.1 The air from dining areas may be used to ventilate the that the airborne contaminates do not reenter the building,
food preparation areas only after it has passed through a one of the following shall be provided:
414.1.1 Exhaust discharge from fan shall extend at least near the door to the room and a visual and audible alarm
7 feet (2134 mm) above the roof and discharge vertically which annunciates at the room and at a nurses' station or other
upward. Self-draining stacks or equivalent shall be used suitable location that will provide responsible surveillance. A
for rain protection. Rain caps which divert the exhaust time delay shall be provided to allow for routine openings of
toward the roof shall be prohibited. doors. The alarm shall annunciate when the supply, return, or
414.1.2 Exhaust shall discharge above roof level and exhaust fans are interrupted and when one of the following
through an accessible HEPA filter. The HEPA filter shall conditions is not being met during closed door conditions:
be located upstream of the exhaust fan and have a (1) When the minimum air quantity difference of 75 cfm
minimum efficiency of 99.97 percent based on the DOP (35.4 L/s) required by Table 4-A is not being maintained;
method in accordance with Mil-Std. 282 or a minimum or
efficiency reporting value (MERV) of 17, based on (2) When a minimum pressure differential of 0.01 inch
ASHRAE 52.2. Filter gage shall be installed across the (0.003 kPa) of water and a minimum inward (outward
filter. For maintenance of air balance relationship, see for protective environment rooms) air velocity of 100 feet
Section 407.3.2. The 25-foot (7620 mm) dimension per minute (0.508 m/s) is not being maintained at the air
required by Section 414.1 may be reduced when a 99.97 transfer opening required by Table 4-A.
percent HEPA filter or a minimum efficiency reporting 416.2 Other acceptable alarm systems will be allowed when
value (MERV) of 17, based on ASHRAE 52.2 is used and designs are specifically approved by the enforcing agency.
the reduced dimension is specifically approved by the 416.3 [For OSHPD 4] For correctional treatment centers,
enforcing agency. the alarm system shall not create false alarms or security
414.2 Air Distribution. The supply outlets and exhaust inlets hazards.
shall be located to provide airflow patterns that prevent stag- 416.4 Prior to acceptance of the rooms, the alarm system
nation of the air and eliminate short circuiting of the supply shall be tested and operated to demonstrate to the owner or
to the exhaust, and minimize exposure of health care workers designated representative that the installation and perform-
to airborne infectious particles. Supply-air outlets shall be ance of the system conforms to design intent.
located at or near the ceiling and at the end of the airborne
infection isolation room which is opposite the head of the bed.
417.0 Testing and Balancing Airborne Infection Isolation
Exhaust registers shall be located on the wall behind the
Rooms and Protective Environment Rooms. [OSHPD 1, 2,
patient's head, or as close to that wall as practical and shall
3 & 4] Prior to acceptance of the rooms, all mechanical
be located not less than 3 inches (76 mm) nor more than 24
systems shall be tested, balanced, and operated to demon-
inches (610 mm) above the finished floor.
strate to the owner or designated representative that the
Exception: For correctional treatment centers, the location installation and performance of the systems conform to
and design of the supply outlets an exhaust or return inlets design intent. All testing and balancing shall be performed
shall not compromise the safety, security and protection of by a qualified independent agency certified by the Associated
staff, inmates and property. Air Balance Council (AABC): the National Environmental
Balancing Bureau (NEBB); or the Testing, Adjusting and
Balancing Bureau (TABB).
415.0 Protective Environment Rooms. [OSHPD 1, 2, 3 & 4]
415.1 Air Distribution. The supply outlets and exhaust and
return inlets shall be located to provide airflow patterns that 418.0 Design Requirements for Ethylene Oxide (ETO) Ster-
prevent stagnation of the air and eliminate short circuiting of ilization Areas. [OSHPD 1, 2, 3 & 4]
the supply to the exhaust or return. Supply air shall be deliv- 418.1 Air Changes. The ETO sterilization equipment room
ered at or near the ceiling and near the patient's bed. All shall be provided with minimum air changes per hour per
exhaust or return registers shall be located near the entrance Table 4-A and be maintained at a negative air balance.
to the protective environment room and not less than 3 inches 418.2 Exhaust Requirements.
(76 mm) nor more than 8 inches (203 mm) above the finished 418.2.1 All air from the ETO sterilizer equipment room
floor. shall be exhausted to the outside by a dedicated system
Exception: For correctional treatment centers, the location or other approved method.
and design of the supply outlets and exhaust or return inlets 418.2.2 The exhaust fan for the dedicated system shall
shall not compromise the safety, security, and protection of be located at the discharge point of the system and iden-
staff, inmates and property. tified as ETO Equipment Room Exhaust.
418.2.3 Discharge Point. The discharge point shall be a
416.0 Alarms – Airborne Infection Isolation Rooms and minimum of 25 feet (7620 mm) away from any outside
Protective Environment Rooms. [OSHPD 1, 2, 3 & 4] intake, operable window or personnel passage.
416.1 An alarm system which is based on static pressure 418.3 Ventilation Requirements.
control, volumetric control, or directional flow measurement 418.3.1 Aeration Units. The aeration units shall be venti-
shall be provided for each isolation room. The alarm system lated through a nonrecirculating dedicated ventilation
shall consist of a display monitor located on the corridor wall exhaust system.
TABLE 4-A
PRESSURE RELATIONSHIP AND VENTILATION REQUIREMENTS FOR GENERAL ACUTE CARE
HOSPITALS, SKILLED NURSING FACILITIES, INTERMEDIATE CARE FACILITIES, CORRECTIONAL
TREATMENT CENTERS, OUTPATIENT FACILITIES, AND LICENSED CLINICS
AIR
PRESSURE MINIMUM ALL ROOM AIR DESIGN
MINIMUM MINIMUM RECIRCULATED DESIGN
RELATIONSHIP TOTAL ACH EXHAUSTED RELATIVE
FUNCTION OR SPACE OUTDOOR TOTAL BY MEANS TEMPERATURE
TO ADJACENT IF 100% DIRECTLY TO HUMIDITY(k),
ACH ACH OF ROOM (l),°F/°C
AREAS (f) (n) O.A. OUTDOORS (j) %
UNITS (a)
Administrative NR 2 4 2 NR NR NR NR
Airborne infection isolation
(e) NR 10 10 Yes No NR NR
anteroom (u)
Airborne infection isolation
Negative 2 12 12 Yes No max 60 70-75/21-24
room (u)
Airborne infection isolation
Negative 2 12 12 Yes No NR NR
treatment/exam room
Angiography room Positive 5 15 12 NR NR NR NR
Bathing room Negative NR 10 NR Yes No NR 70-75/21-24
Bathroom Negative NR 10 10 Yes No NR 72-78/22-26
Bedpan room Negative NR 10 10 Yes No NR NR
Blood bank/tissue storage NR 2 6 6 NR NR NR NR
Blood draw/phlebotomy NR 2 6 6 NR NR NR NR
Bronchoscopy, sputum
collection, and pentamidine Negative 2 12 12 Yes No NR 68-73/20-23
administration (n)
Cardiac catheterization lab Positive 5 20 12 NR No max 60 70-75/21-24
Clean linen storage Positive NR 2 2 NR NR NR 72-78/22-26
Clean workroom (central
medical and surgical supply Positive 2 4 4 NR No max 60 72-78/22-26
space)
Clean workroom or clean
Positive 2 4 4 NR NR NR NR
holding (support)
Critical and intensive care NR 2 6 6 NR No 30-60 70-75/21-24
CT Scan NR 2 6 6 NR NR max 60 NR
Darkroom (g) Negative 2 10 12 Yes No NR NR
Delivery room (caesarean)
Positive 4 20 12 NR No 20-60 68-75/20-24
(m), (n), (o)
Dialysis treatment area NR 2 6 6 NR NR NR 72-78/22-26
Dialyzer reprocessing room Negative NR 10 NR Yes No NR NR
Dietary storage NR NR 2 2 NR No NR 72-78/22-26
Dining room NR 2 10 10 NR NR NR NR
Dishwashing room N NR 10 NR Yes NR NR NR
Electroconvulsive therapy
P 3 15 10 NR NR NR NR
procedure room
Emergency department
NR 2 6 6 NR NR max 60 70-75/21-24
exam/treatment room (p)
Endoscope cleaning Negative 2 10 10 Yes No NR NR
ER decontamination Negative 2 12 4 Yes No NR NR
ER waiting rooms Negative 2 12 12 Yes (q) NR max 65 70-75/21-24
Examination room NR 2 6 6 NR NR max 60 70-75/21-24
Fast track room NR 2 6 2 NR NR NR NR
Fluoroscopy room Negative 2 6 6 Yes No NR NR
TABLE 4-B
FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR-CONDITIONING SYSTEMS IN GENERAL ACUTE
CARE HOSPITALS, ACUTE PSYCHIATRIC HOSPITALS, OUTPATIENT FACILITIES, AND LICENSED CLINICS1
FILTER EFFICIENCY % FILTER BANK
MINIMUM NUMBER OF
AREA DESIGNATION (MINIMUM EFFICIENCY REPORTING VALUE MERV)5
FILTER BANKS
NO. 11 NO. 21 NO. 31
Orthopedic operating room,
30% 90% 99.97%3
bone marrow transplant
3
operating room, organ transplant
(8) (14) (17)
operating room
30% 90% 99.97%4
Protective environment rooms 3
(8) (14) (17)
Angiography; cardiac catheterization
labs; operating rooms; interventional
imaging procedure rooms;delivery rooms 30% 90% ––
nurseries; patient care, treatment,
cystoscopy, cesarean operating room,
2
diagnostic, and related areas; airborne
infection isolation rooms; areas
providing direct patient service or clean (8) (14) ––
supplies such as sterile and clean
processes, and patient area corridors
30% 80% ––
Laboratories 2
(8) (13) ––
Administrative, med staff support areas,
30% –– ––
bulk storage, soiled holding areas,
1
food preparation areas, public cafeterias,
(8) –– ––
and laundries
Psychiatric hospitals intended for the care 30% –– ––
and treatment of inpatients who do not require 1
acute medical services (8) –– ––
1 Based on ASHRAE 52.2.
2 Based on DOP test in accordance with MIL-STD-282 or based on ASHRAE 52.2.
3 HEPA filters at air outlet or other locations when approved by the Authority Having Jurisdiction.
4 HEPA filter located in the supply duct which serves the positive-pressure isolation room or rooms may serve more than one supply outlet and more than
one positive-pressure isolation room. HEPA filter or a filter with minimum efficiency reporting value (MERV) of 17 installation shall be designed and
equipped to permit safe removal, disposal and replacement of filters.
5 The numbers in parentheses represent MERV rating based on ASHRAE 52.2.
TABLE 4-C
FILTER EFFICIENCIES FOR CENTRAL VENTILATION AND AIR-CONDITIONING SYSTEMS IN SKILLED
NURSING FACILITIES AND INTERMEDIATE CARE FACILITIES AND CORRECTIONAL TREATMENT CENTERS1
FILTER EFFICIENCY % FILTER BANK
MINIMUM NUMBER OF
AREA DESIGNATION (MINIMUM EFFICIENCY REPORTING VALUE MERV)3
FILTER BANKS
NO. 11 NO. 21
All areas for inpatient care, treatment 30% 80%
and/or diagnosis, and those areas 2
providing direct service or cleaning supplies) (8) (13)
2 ––
Administrative, bulk storage, soiled 30%
1
holding, laundries and food prep areas (8) ––
1 Based on ASHRAE 52.2.
2 Filters are not required for evaporative coolers serving laundries and food preparation areas.
3 The numbers in parentheses represent MERV rating based on ASHRAE 52.2.
TABLE 402.1
MINIMUM VENTILATION RATES IN BREATHING ZONE1, 2, 4
[ASHRAE 62.1: TABLE 6.2.2.1]
Note: Ventilation air supply requirements for occupancies regulated by the California Energy Commission are found in the California Energy Code.
PEOPLE OUTDOOR AREA OUTDOOR DEFAULT OCCUPANT
AIR
OCCUPANCY CATEGORY4 Air Rate RP Air Rate RA Density3
CLASS
(cfm/person) (cfm/ft2) (people/1000 ft2)
CORRECTIONAL FACILITIES
Booking/waiting 7.5 0.06 50 2
Cell 5 0.12 25 2
Day room 5 0.06 30 1
Guard stations 5 0.06 15 1
EDUCATIONAL FACILITIES
Art classroom 10 0.18 20 2
Classrooms (ages 5-8) 10 0.12 25 1
Classrooms (age 9 plus) 10 0.12 35 1
Computer lab 10 0.12 25 1
Daycare (through age 4) 10 0.18 25 2
Daycare sickroom 10 0.18 25 3
Lecture classroom 7.5 0.06 65 1
Lecture hall (fixed seats) 7.5 0.06 150 1
Media centera 10 0.12 25 1
Multi-use assembly 7.5 0.06 100 1
Music/theater/dance 10 0.06 35 1
Science laboratories 10 0.18 25 2
University/college laboratories 10 0.18 25 2
Wood/metal shop 10 0.18 20 2
FOOD AND BEVERAGE SERVICE
Bars, cocktail lounges 7.5 0.18 100 2
Cafeteria/fast food dining 7.5 0.18 100 2
Kitchen (cooking) 7.5 0.12 20 2
Restaurant dining rooms 7.5 0.18 70 2
GENERAL
Break rooms 5 0.06 25 1
Coffee stations 5 0.06 20 1
Conference/meeting 5 0.06 50 1
Corridors – 0.06 – 1
Occupiable storage rooms for liquids or gelsb 5 0.12 2 2
HOTELS, MOTELS, RESORTS, DORMITORIES
Barracks sleeping areas 5 0.06 20 1
Bedroom/living room 5 0.06 10 1
Laundry rooms, central 5 0.12 10 2
Laundry rooms within dwelling units 5 0.12 10 1
Lobbies/pre-function 7.5 0.06 30 1
Multipurpose assembly 5 0.06 120 1
OFFICE BUILDINGS
Breakrooms 5 0.12 50 1
Main entry lobbies 5 0.06 10 1
Occupiable storage rooms for dry materials 5 0.06 2 1
Office space 5 0.06 5 1
Reception areas 5 0.06 30 1
Telephone/data entry 5 0.06 60 1
MISCELLANEOUS SPACES
Bank or bank lobbies 7.5 0.06 15 1
Bank vaults/safe deposit 5 0.06 5 2
Computer (not printing) 5 0.06 4 1
Freezer and refrigerated spaces (<50°F)e 10 – – 2
General manufacturing (excludes heavy
10 0.18 7 3
industrial and processes using chemicals)
c
Rate does not allow for humidity control. Additional ventilation or dehumidification shall be permitted to remove moisture. “Deck area” refers to the area
surrounding the pool that would be expected to be wetted during normal pool use, i.e., where the pool is occupied. Deck area that is not expected to be wetted
shall be designated as a space type (for example, “spectator area”).
d
Rate does not include special exhaust for stage effects, e.g., dry ice vapors, smoke.
e
Where combustion equipment is intended to be used on the playing surface or in the space, additional dilution ventilation, source control, or both shall be
provided.
f
Default occupancy for dwelling units shall be two persons for studio and one-bedroom units, with one additional person for each additional bedroom.
g
Air from one residential dwelling shall not be recirculated or transferred to other spaces outside of that dwelling.
TABLE 403.2.2
ZONE AIR DISTRIBUTION EFFECTIVENESS1, 2, 3, 4, 5
[ASHRAE 62.1: TABLE 6.2.2.2]
AIR DISTRIBUTION CONFIGURATION Ez
TABLE 403.5.2
SYSTEM VENTILATION EFFICIENCY1, 2, 3
[ASHRAE 62.1: TABLE 6.2.5.2]
MAX (ZPz) Ev
≤ 0.15 1.0
≤ 0.25 0.9
≤ 0.35 0.8
≤ 0.45 0.7
≤ 0.55 0.6
> 0.55 Use Section 404.0
Notes:
1
“Max Zpz” refers to the largest value of Zpz, calculated in accordance with Equation 403.5.1, among the
ventilation zones served by the system.
2
For values of Max (Zpz) between 0.15 and 0.55, the corresponding value of Ev shall be permitted to be
determined by interpolating the values in the table.
3
The values of Ev in this table are based on a 0.15 average outdoor air fraction for the system (i.e., the ratio
of the uncorrected outdoor air intake (Vou) to the total zone primary airflow for the zones served by the air
handler). For systems with higher values of the average outdoor air fraction, this table is capable of resulting
in unrealistically low values of Ev and the use of Section 404.0 is capable of yielding more practical results.
TABLE 403.7
MINIMUM EXHAUST RATES
[ASHRAE 62.1: TABLE 6.5]
EXHAUST RATE EXHAUST RATE AIR
OCCUPANCY CATEGORY8
(cfm/unit) (cfm/ft2) CLASS
Arenas2 – 0.50 1
Art classrooms – 0.70 2
Auto repair rooms1 – 1.50 2
Barber shops – 0.50 2
Bathroom10,11 20/50 – 2
Beauty and nail salons – 0.60 2
Cells with toilet – 1.00 2
Copy, printing rooms – 0.50 2
Darkrooms – 1.00 2
Educational science laboratories – 1.00 2
Janitor closets, trash rooms, recycling – 1.00 3
Kitchens – commercial – 0.70 2
Kitchenettes – 0.30 2
Locker rooms – 0.50 2
Locker/dressing rooms – 0.25 2
Paint spray booths – – 4
Parking garages 3
– 0.75 2
Pet shops (animal areas) – 0.90 2
Refrigerating machinery rooms6 – – 3
Residential – kitchens7 50/100 – 2
Soiled laundry storage rooms – 1.00 3
Storage rooms, chemical – 1.50 4
Toilets – private5, 9 25/50 – 2
Toilets – public4, 9 50/70 – 2
Woodwork shop/classrooms – 0.50 2
For SI units: 1 cubic foot per minute = 0.0283 m3⁄min, 1 square foot = 0.0929 m2
Notes:
1
Stands where engines are run shall have exhaust systems that directly connect to the engine exhaust and prevent escape of fumes.
2
Where combustion equipment is intended to be used on the playing surface, additional dilution ventilation, source control, or both shall be provided.
3
Exhaust rate is not required for open parking garages as defined in accordance with the building code.
4
Rate is per water closet, urinal, or both. Provide the higher rate where periods of heavy use are expected to occur, e.g., toilets in theatres, schools, and sports
facilities. Otherwise the lower rate shall be permitted to be used.
5
Rate is for a toilet room intended to be occupied by one person at a time. For continuous system operation during normal hours of use, the lower rate shall
be permitted to be used. Otherwise the higher rate shall be used.
6
For refrigeration machinery rooms, the exhaust rate shall comply with Chapter 11.
7
For continuous system operation, the lower rates shall be permitted. Otherwise the higher rate shall be used.
8
For unlisted occupancies for a proposed space not listed in the table, the requirements for the listed occupancy that is most similar in terms of occupant density
and occupancy type shall be used.
9
Exhaust air that has been cleaned in accordance with the criteria of Class 1 shall be permitted to be recirculated.
10
[HCD 1 & HCD 2] A bathroom is any room containing a bathtub, a shower, a spa, or a similar source of moisture.
11
[HCD 1 & HCD 2] ANSI/ASHRAE 62.2: Tables 5.1 and 5.2.
Chapter/Section
503.3 X X X
503.3 Exception 1 & 2 X X X
503.3.1 X X X
504.1.1 X X X
505.7 X
505.7.1 X
508.5 X X X
509.2.3 X
509.2.3.4 X
511.1.6 X X X
513.2.2 X X X
513.2.2 Exception 2 X X
513.3.2 X
513.11 X
513.11.1 X
516.2.7 Exception X
516.2.9 X
This state agency does not adopt sections identified with the following symbol: †
The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
Chapter 6 and shall be airtight as approved by the Authority Devices, such as fire or smoke dampers, that will obstruct the
Having Jurisdiction. Environmental air ducts that have an alter- flow of the exhaust shall not be used. Where joining of ducts,
nate function as a part of an approved smoke-control system the male end shall be inserted in the direction of airflow.
do not require design as Class 1 product-conveying ducts.
Exceptions:
504.4.1 Provisions for Makeup Air. Makeup air shall
be provided in accordance with the following:
«
(1) Ductless range hoods where installed in accordance with (1) Makeup air shall be provided for Type 1 clothes
the manufacturer’s installation instructions. dryers in accordance with the manufacturer’s
(2) Condensing clothes dryers where installed in accordance instructions. [NFPA 54:10.4.3.1]. Where a closet is
with the manufacturer’s installation instructions. designed for the installation of a clothes dryer, an
504.1.1 Backdraft Protection. Exhaust ducts shall opening of not less than 100 square inches (0.065
terminate outside the building and shall be equipped with m2) for makeup air shall be provided in the door or
backdraft dampers or with motorized dampers that auto- by other approved means.
matically shut where the systems or spaces served are (2) Provision for makeup air shall be provided for Type
not in use. [OSHPD 1, 2 & 4] Exception: Backdraft 2 clothes dryers, with a free area of not less than 1
dampers are not required when the exhaust fan must square inch (0.0006 m2) for each 1000 British
operate continuously. thermal units per hour (Btu/h) (0.293 kW) total input
rating of the dryer(s) installed. [NFPA 54:10.4.3.2]
Exception: Where the exhaust duct does not discharge
into a common exhaust plenum and one of the following: 504.4.2 Domestic Clothes Dryers. Where a compartment
or space for a Type 1 clothes dryer is provided, not less
«
(1) The exhaust fan runs continuously.
than a 4 inch diameter (102 mm) exhaust duct of approved
(2) The exhaust duct serves space(s) that are not mechan- material shall be installed in accordance with Section
ically heated or cooled. 504.0.
(3) The space served is maintained at positive pressure. Type 1 clothes dryer exhaust ducts shall be of rigid
504.2 Independent Exhaust Systems. Single or combined metal and shall have smooth interior surfaces. The diam-
mechanical exhaust systems shall be independent of other eter shall be not less than 4 inches nominal (100 mm)
exhaust systems. and the thickness shall be not less than 0.016 of an inch
» 504.3 Domestic Range. Ducts used for domestic kitchen
range ventilation shall be of metal and shall have smooth inte-
(0.406 mm).
504.4.2.1 Length Limitation. Unless otherwise «
rior surfaces. permitted or required by the dryer manufacturer’s
instructions and approved by the Authority Having
Exception: Ducts for domestic kitchen downdraft grill-range
Jurisdiction, domestic dryer moisture exhaust ducts
ventilation installed under a concrete slab floor shall be
shall not exceed a total combined horizontal and
permitted to be of approved Schedule 40 PVC provided:
vertical length of 14 feet (4267 mm), including two
(1) The under-floor trench in which the duct is installed shall 90 degree (1.57 rad) elbows. A length of 2 feet (610
be completely backfilled with sand or gravel. mm) shall be deducted for each 90 degree (1.57 rad)
(2) Not more than 1 inch (25.4 mm) of 6 inch diameter (152 elbow in excess of two.
mm) PVC coupling shall be permitted to protrude above 504.4.2.2 Transition Ducts. Listed clothes dryer
the concrete floor surface. transition ducts not more than 6 feet (1829 mm) in
(3) PVC pipe joints shall be solvent cemented to provide an length shall be permitted to be used to connect the
air and greasetight duct. Type 1 dryer to the exhaust ducts. Transition ducts
(4) The duct shall terminate above grade outside the building and flexible clothes dryer transition ducts shall not
and shall be equipped with a back-draft damper. be concealed within construction, and shall be
513.2.6 Water Valve Supervision. Valves controlling the shall not require more than 40 pounds-force (lbf) (178 N) of
water supply to listed fixed baffle hood assemblies, auto- force, with a pull movement not to exceed 14 inches (356
matic fire-extinguishing systems, or both shall be listed mm) to activate the automatic fire extinguishing system. The
indicating type of valve and shall be supervised open by automatic and manual means of system activation external to
one of the following methods: the control head or releasing device shall be separate and
(1) Central station, proprietary, or remote station alarm independent of each other so that failure of one will not
service. impair the operation of the other except as permitted in
(2) Local alarm service that will cause the sounding of Section 513.5.1. [NFPA 96:10.5.1 – 10.5.2]
an audible signal at a constantly attended point. 513.5.1 Location of Manual Activation Device. The
(3) Locking valves open. manual means of system activation shall be permitted to
be common with the automatic means where the manual
(4) Sealing of valves and approved weekly recorded activation device is located between the control head or
inspection. [NFPA 96:10.2.10]
releasing device and the first fusible link. [NFPA
513.3 Simultaneous Operation. Fixed pipe extinguishing 96:10.5.3]
systems in a single hazard area shall be arranged for simulta-
513.5.2 Automatic Sprinkler System. An automatic sprin-
neous automatic operation upon actuation of any one of the
kler system shall not require a manual means of system
systems. [NFPA 96:10.3.1]
activation. [NFPA 96:10.5.4]
513.3.1 Automatic Sprinkler System. Simultaneous
513.5.3 Manual Actuator(s). The means for manual acti-
operation shall not be required where the one fixed pipe
vation shall be mechanical or rely on electrical power for
extinguishing system is an automatic sprinkler system.
Where an automatic sprinkler system is used in conjunc- activation in accordance with Section 513.5.4. [NFPA
tion with a water-based fire-extinguishing system served 96:10.5.5]
by the same water supply, hydraulic calculations shall 513.5.4 Standby Power Supply. Electrical power shall
consider both systems operating simultaneously. [NFPA be permitted to be used for manual activation where a
96:10.3.2, 10.3.2.1] standby power supply is provided or where supervision
513.3.2 Dry or Wet Chemical Systems. Simultaneous is provided in accordance with Section 513.7. [NFPA
96:10.5.6]
operation shall be required where a dry or wet chemical
system is used to protect common exhaust ductwork by 513.6 System Annunciation. Upon activation of an auto-
NFPA 17A, Wet Chemical Extinguishing Systems. matic fire-extinguishing system, an audible alarm or visual
indicator shall be provided to show that the system has acti-
513.4 Fuel and Electric Power Shutoff. Upon activation of a vated. [NFPA 96:10.6.1]
fire-extinguishing system for a cooking operation, sources of
513.6.1 Signaling. Where a fire alarm signaling system is
fuel and electric power that produce heat to equipment requiring
serving the occupancy where the extinguishing system is
protection by that system shall automatically shut off. [NFPA located, the activation of the automatic fire-extinguishing
96:10.4.1] system shall activate the fire alarm signaling system.
Exception: Solid-fuel cooking operations. [NFPA 96:10.6.2]
513.4.1 Steam. Steam supplied from an external source 513.7 System Supervision. Where electrical power is required
shall not be required to automatically shut off. [NFPA to operate the fixed automatic fire-extinguishing system, the
96:10.4.2] system shall be provided with a reserve power supply and be
monitored by a supervisory alarm except as permitted in
513.4.2 Protection Not Required. A gas appliance
accordance with Section 513.7.1. [NFPA 96:10.7.1]
not requiring protection, but located under ventilating
equipment where protected appliances are located, shall 513.7.1 Automatic Fire-Extinguishing System. Where a
be automatically shut off upon activation of the extin- fixed automatic fire-extinguishing system includes auto-
matic mechanical detection and actuation as a backup
guishing system. [NFPA 96:10.4.3]
detection system, electrical power monitoring and reserve
513.4.3 Manual Reset. Shutoff devices shall require power supply shall not be required. [NFPA 96:10.7.2]
manual reset. [NFPA 96:10.4.4]
513.7.2 Supervision. System supervision shall not be
513.5 Manual Activation. A readily accessible means for required where a fire-extinguishing system(s) is inter-
manual activation shall be located between 42 inches and 48 connected or interlocked with the cooking equipment
inches (1067 mm and 1219 mm) above the floor, be acces- power source(s) so that where the fire-extinguishing
sible in the event of a fire, be located in a path of egress, and system becomes inoperable due to power failure, sources
clearly identify the hazard protected. Not less than one of fuel or electric power that produce heat to cooking
manual actuation device shall be located not less than 10 feet equipment serviced by that hood shall automatically shut
(3048 mm) and not more than 20 feet (6096 mm) from the off. [NFPA 96:10.7.3]
protected exhaust system(s) within the path of egress or at an 513.7.3 Listed Water Wash System. System supervi-
alternative location acceptable to the Authority Having Juris- sion shall not be required where an automatic fire-extin-
diction. Manual actuation using a cable-operated pull station guishing system, including automatic mechanical
For prior history, see the History Note Appendix to the Cali-
fornia Mechanical Code, 2013 Triennial Edition effective
January 1, 2014.