MOTOR DATA SHEET


CUSTOMER :
INDENT NO. : PO NO: - DATE: 09.12.2022 IE-3
PROJECT NAME : -
kW : 0.75 POLE : 4 VOLTS : 415 QTY : 1
MOTOR TAG NO :
1 Basic Performance Requirement
RATING ( kW/HP ) : 0.75/1
NO. OF POLES :4
APPLICATION :
APPLICABLE STANDARD
: IS 15999(Part 1 ) : 2021,IS 12615:2018, IS 15999 (Part 2/Sec 1) : 2011

TYPE OF DUTY : S1 - ALTITUED IN METER ≤ UPTO 1000 MSL


AREA OF APPLICATION : INDUSTRIAL TEFC SAFE AREA MOTOR Safe Area
2 Motor terminal voltage Data
VOLTAGE ( VOLTS ): 415 +10% -10% 3-ph. A.C.
FREQUENCY ( Hz ) : 50 +5% -5%
COMBINED VARIATION : 10% (Absolute)
3 Construction Data
TYPE : 3 PHASE, AC SQ.CAGE INDUCTION MOTOR
FRAME : 80
ENCLOSURE : TEFC
DEG. OF PROTECTION : IP55
TYPE OF COOLING : IC4A1A1
TYPE OF MOUNTING : AS PER GAD
INSULATION CLASS AND RISE : CLASS F, RISE CLASS B.
STATOR CONNECTION : STAR (6LEAD)
TYPE OF STARTING : DOL
TB POSITION FROM DE : TTB Cable Entry towards NDE
FAULT LEVEL OF TB : 50 KA FOR 0.25 SEC WITH APPROPRIATE FUSE PROTECTION
SPACE HEATER : NA
ACCESSORIES(RTD,THERMISTOR) : NA
PAINT SHADE : RAL 6024
4 Electrical Performance
FULL LOAD CURRENT ( A ) : 1.7
FULL LOAD SPEED ( rpm ) : 1410
EFFICIENCY CLASS : PREMIUM EFFICIENCY ''Supremo Series'' TEFC SC MOTORS IE3
Full Load 3/4 LOAD 1/2LOAD
EFFICIENCY (%) : 82.5 82.0 78.5 82.5
POWER FACTOR ( P.U.) : 0.76 0.71 0.55
AMBIENT ( 0C ) : 50
TEMP RISE BY RES. ( K ) : 70 S.F= 1.0 RISE (K)= 70
RATED TORQUE in Kgf-m : 0.5
STARTING TORQUE in Kgf-m ( % FLT) : 1.2 225
PULL OUT TORQUE in Kgf-m ( % FLT) : 1.4 275
STARTING CURRENT in Amps. ( % FLC) : 10.0 600
Hot Cold
THERMAL WITHSTAND TIME ( sec ) : 10 20

THERMAL HEATING / COOLING TIME CONST (Th/Tc) ( min ) : 42/125


APROXIMATE STARTING TIME AT 100% & 80% V ( sec ) : 2 3
STARTS PER HOUR : 2 HOT-3COLD-4 EQUALLY SPREAD
MOMENTARY EXCESS TORQUE : 1.6 TIMES OF RATED TORQUE FOR 15 Sec WITHOURT STALLING
MOTOR GD SQ. ( kg m2 ) : 0.0103
MAXIMUM LOAD GD SQ. ( kg m2 ) : ,=MOTOR GD^2
VIBRATION (AT NO LOAD ) : AS PER IS 12075
NOISE (AT NO LOAD ) : AS PER IS 12065

NOTE 1 ALL PERFORMANCE FIGURES ARE SUBJECT TO IS 15999-1:2021 TOLERANCES,PARAMETERS MAY CHANGE DURING FINAL
SUBMISSION OF DATASHEET AFTER GETTING THE ORDER.
2 STARTING CURRENT MEASUREMENT AS PER IS 12615 : 2018 CLAUSE NO 16.2.2.3.1,
WDG NO W30804LXSRAFR00HY0
2 GAD NO B43080A3T500000000000 Prepared By LH3SD01 21.11.2022
1 T BOX NO B080ATV500000040 Checked By LH3SD01 21.11.2022
NO REVISION SIGN DATE SIGN DATE
LAXMI HYDRAULICS PVT LTD. , B-11- MIDC
MKTG Ref No.: 0
CHINCHOLI , SOLAPUR.
SPEED Vs T0RQUE & CURRENT CHARACTERISTICS

CUSTOMER :
INDENT NO. : PO NO: - DATE: 09.12.2022 IE-3
PROJECT NAME :
kW : 0.75 POLE : 4 VOLTS : 415 QTY : 1

800
1.5/2.0
PO NO:

Current Speed at 100%


700 Voltage

600

% Current Speed at 80%


Voltage
F
U
L 500
L

L
O
A
400
D

T
O
R
Q 300
U
E
T-N at 100% Voltage
MOTOR
& Wt. APPROX. ( kg )

C 200
U
R
R
E
N
T 100
T-N at 80% Voltage

VARIABLE TORQUE
0
0 10 20 30 40 50 60 70 80 90 100

% SYNCHRONOUS SPEED

2 Prepared By LH3SD01 21.11.2022


1 Checked By LH3SD01 21.11.2022
NO REVISION SIGN SIGN DATE
LAXMI HYDRAULICS PVT LTD. , B-11-
MKTG Ref No.: 0
MIDC CHINCHOLI , SOLAPUR.

LOAD Vs EFF., P.F.,


CUSTOMER :
INDENT NO. : PO NO: - DATE: 09.12.2022 IE-3
PROJECT NAME :
kW : 0.75 POLE : 4 VOLTS : 415 QTY : 1

100.00 1.5/2.0 1.00

95.00

90.00 0.90

85.00

80.00 0.80

EFFICIENCY
75.00
% EFFICIENCY

70.00 0.70

P.F.P.U.
65.00

60.00 0.60

55.00
POWER
50.00 FACTOR 0.50

45.00

40.00 0.40

35.00

30.00 0.30

25.00

20.00 0.20

15.00

10.00 0.10

5.00

0.00 0.00
0 10 20 30 40 50 60 70 80 90 100

% LOAD

2 Prepared By LH3SD01 21.11.2022


1 Checked By LH3SD01 21.11.2022
NO REVISION SIGN DATE
LAXMI HYDRAULICS PVT LTD. , B-11- MIDC
MKTG Ref No.: 0
CHINCHOLI , SOLAPUR.
STARTING CURRENT VS STARTING TIME AND THERMAL WITHSTAND TIME.

CUSTOMER :
INDENT NO. : PO NO: - DATE: 09.12.2022 IE-3
PROJECT NAME :
kW : 0.75 POLE : 4 VOLTS : 415 QTY : 1

10000 1.5/2.0
PO NO:

1000

TWT-COLD

100
THERMAL WITHSTAND
TIME (sec)

TWT-HOT

10

Istg (time) at 80%V

Istg (time) at 100%V

0.1
0 100 200 300 400 500 600 700
% FULL LOAD CURRENT

L. R.CURRENT at 100% voltage : 600 % OF FLA THERMAL WITHSTAND TIME(sec):


Starting time at 100% voltage : 2 sec AT100% RATED VOLTAGE (HOT) : 10
Starting time at 80% voltage : 3 sec AT100% RATED VOLTAGE (COLD): 20