Kalkulator Dan Data Komponen
Kalkulator Dan Data Komponen
INV S101 INV1-STR1 17 INV1-STR1/1-01 PV01 MPPT 1 710.6 13.04 9.27 149
57.78 INV1-STR2 17 INV1-STR2/1-02 PV02 MPPT 1 710.6 13.04 9.27 149
106 INV1-STR3 18 INV1-STR3/2-03 PV03 MPPT 2 752.4 13.04 9.81 149
INV1-STR5 18 INV1-STR5/3-05 PV05 MPPT 3 752.4 13.04 9.81 149
INV1-STR7 18 INV1-STR7/4-07 PV07 MPPT 4 752.4 13.04 9.81 149
INV1-STR8 18 INV1-STR8/4-08 PV08 MPPT 4 752.4 13.04 9.81 149
INV S102 INV2-STR1 17 INV2-STR1/1-01 PV01 MPPT 1 710.6 13.04 9.27 149
57.78 INV2-STR2 17 INV2-STR2/1-02 PV02 MPPT 1 710.6 13.04 9.27 149
106 INV2-STR3 18 INV2-STR3/2-03 PV03 MPPT 2 752.4 13.04 9.81 149
INV2-STR5 18 INV2-STR5/3-05 PV05 MPPT 3 752.4 13.04 9.81 149
INV2-STR7 18 INV2-STR7/4-07 PV07 MPPT 4 752.4 13.04 9.81 149
INV2-STR8 18 INV2-STR8/4-08 PV08 MPPT 4 752.4 13.04 9.81 149
INV S103 INV3-STR1 18 INV3-STR1/1-01 PV01 MPPT 1 752.4 13.04 9.81 149
58.87 INV3-STR2 18 INV3-STR2/1-02 PV02 MPPT 1 752.4 13.04 9.81 149
108 INV3-STR3 18 INV3-STR3/2-03 PV03 MPPT 2 752.4 13.04 9.81 149
INV3-STR5 18 INV3-STR5/3-05 PV05 MPPT 3 752.4 13.04 9.81 149
INV3-STR7 18 INV3-STR7/4-07 PV07 MPPT 4 752.4 13.04 9.81 149
INV3-STR8 18 INV3-STR8/4-08 PV08 MPPT 4 752.4 13.04 9.81 149
INV S104 INV4-STR1 18 INV4-STR1/1-01 PV01 MPPT 1 752.4 13.04 9.81 -31
58.87 INV4-STR2 18 INV4-STR2/1-02 PV02 MPPT 1 752.4 13.04 9.81 -31
108 INV4-STR3 18 INV4-STR3/2-03 PV03 MPPT 2 752.4 13.04 9.81 -31
INV4-STR5 18 INV4-STR5/3-05 PV05 MPPT 3 752.4 13.04 9.81 -31
INV4-STR7 18 INV4-STR7/4-07 PV07 MPPT 4 752.4 13.04 9.81 -31
INV4-STR8 18 INV4-STR8/4-08 PV08 MPPT 4 752.4 13.04 9.81 -31
Tagging Kabel
Length
Vdrop Initial
(m)
Selected Inverter Area
Positif (+) Negatif(-)
165 2.07% 1C x 6 Inverter 1 Inverter 1
161 2.02% 1C x 6 INV1-STR1-PINV1-STR1-N
143 1.70% 1C x 6 INV1-STR2-PINV1-STR2-N
134 1.58% 1C x 6 INV1-STR3-PINV1-STR3-N
114 1.35% 1C x 6 INV1-STR5-PINV1-STR5-N
105 1.24% 1C x 6 INV1-STR7-PINV1-STR7-N
INV1-STR8-PINV1-STR8-N
95 1.19% 1C x 6 Inverter 2 Inverter 2
86 1.07% 1C x 6 INV2-STR1-PINV2-STR1-N
76 0.90% 1C x 6 INV2-STR2-PINV2-STR2-N
67 0.79% 1C x 6 INV2-STR3-PINV2-STR3-N
58 0.68% 1C x 6 INV2-STR5-PINV2-STR5-N
48 0.57% 1C x 6 INV2-STR7-PINV2-STR7-N
INV2-STR8-PINV2-STR8-N
146 1.72% 1C x 6 Inverter 3 Inverter 3
130 1.53% 1C x 6 INV3-STR1-PINV3-STR1-N
114 1.35% 1C x 6 INV3-STR2-PINV3-STR2-N
98 1.16% 1C x 6 INV3-STR3-PINV3-STR3-N
83 0.98% 1C x 6 INV3-STR5-PINV3-STR5-N
67 0.79% 1C x 6 INV3-STR7-PINV3-STR7-N
INV3-STR8-PINV3-STR8-N
151 1.79% 1C x 6 Inverter 4 Inverter 4
136 1.60% 1C x 6 INV4-STR1-PINV4-STR1-N
120 1.42% 1C x 6 INV4-STR2-PINV4-STR2-N
104 1.23% 1C x 6 INV4-STR3-PINV4-STR3-N
88 1.05% 1C x 6 INV4-STR5-PINV4-STR5-N
73 0.86% 1C x 6 INV4-STR7-PINV4-STR7-N
INV4-STR8-PINV4-STR8-N
Tagging Kabel
Modul Area
Positif (+) Negatif(-)
Inverter 1 Inverter 1
INV1-STR1-PINV1-STR1-N
INV1-STR2-PINV1-STR2-N
INV1-STR3-PINV1-STR3-N
INV1-STR5-PINV1-STR5-N
INV1-STR7-PINV1-STR7-N
INV1-STR8-PINV1-STR8-N
Inverter 2 Inverter 2
INV2-STR1-PINV2-STR1-N
INV2-STR2-PINV2-STR2-N
INV2-STR3-PINV2-STR3-N
INV2-STR5-PINV2-STR5-N
INV2-STR7-PINV2-STR7-N
INV2-STR8-PINV2-STR8-N
Inverter 3 Inverter 3
INV3-STR1-PINV3-STR1-N
INV3-STR2-PINV3-STR2-N
INV3-STR3-PINV3-STR3-N
INV3-STR5-PINV3-STR5-N
INV3-STR7-PINV3-STR7-N
INV3-STR8-PINV3-STR8-N
Inverter 4 Inverter 4
INV4-STR1-PINV4-STR1-N
INV4-STR2-PINV4-STR2-N
INV4-STR3-PINV4-STR3-N
INV4-STR5-PINV4-STR5-N
INV4-STR7-PINV4-STR7-N
INV4-STR8-PINV4-STR8-N
Pvsyst Simulation Settings
A. Site Location
Monthly values for Geographical site parameters
GHI : SolarGIS
Diffuse Irradiation : Meteonorm (retrivied from Meteonorm v7.3.4)
Ambient Temperature : Meteonorm (retrivied from Meteonorm v7.3.4)
Wind Velocity : Meteonorm (retrivied from Meteonorm v7.3.4)
B. Project Setting
Site Dependent Design Parameters
Lower Temperature for absolute voltage limit : 10
Winter operating temperature for Mpp max desi: 20 (default)
usual operating temperature under 1000 W/m2 : 50 (default)
Summer operating temperature for Vmpp min de: 70 (default)
C. Detailed Losses
Use specified by "global wiring resistance" and
select detailed computation, insert cable size
Ohmic Losses along with the estimated length for positive
If the
If the distance
arrays occupy a large
is unknown, area,the
use cable +
theoption
: negative
length is DC cable
filled (1 Round)
according to the average length
"loss fraction by STC" and use 1.5% value.
DC Circuit : from each string
Ensure that the value for each array is filled
: correctly
Check "significant length to be accounted for"
: and
If theinput the cable
distance size+estimated
is unknown, distanceby
fill loss fraction
AC Circuit
: STC and use 1.5% value
Module Quality - LID - Mismatch
Depend on the manufacturer For :
Module Efficiency Loss : Use default
JA solar : 2%value
LID Loss factor : Seraphim : 1%
Module mismatch losses - Power loss at MPP : REC : 1.5% value
Use default
Other than that, check the default value
String voltage mismatch - power loss at MPP : Use default value
Soilling Loss
Yearly soiling loss factor : 3%
Unavailability
Unavailability time fraction : 0%
D. Near Shading
Use in simulation : Linear shading
Calculation mode : Fast
Trina Solar - 550Wp TSM-DE19 Sungrow-SG50CX - 50 KVA Inverter type Inverter type
PV Module 550 wp Inverter 50 kW 0 kW 0 kW
Total Module 91 pcs Capacity 50.05 kWp
String Series
12 15 17 18 20 Capacity (kWp) DC/AC Ratio No. of Modules
Inv 1 (50 KTL) 5 55.00 1.100 100
Inv 2 (50 KTL) 0.00 0.000 0
Inv 3 (50 KTL) 0.00 0.000 0
Inv 4 (50 KTL) 0.00 0.000 0
Total 0 0 0 0 5 55.00 0.275 100
MCCB 4P 100A 50 kA
MCCB 3P 400A 50 kA
(3 x 1 x 1C x 120mm²)
MCCB 3P 400A 65 kA
(3 x 1 x 1C x 120mm²)