EPAS – Design & Configuration

EPAS-Gateway Device Basic


Configuration
EcoStruxureTM Power Automation System
Power Solutions Global Training
2023

Confidential Property of Schneider Electric


Internal
Safety Information
This is training presentation, reference information is in Official Technical Guides.

▪ It is advisable to read all the Safety


Information, all the time before trying to
Install, Operate, Service or Maintain it.
▪ Electrical equipment should be installed,
operated, serviced and maintained only by
qualified personnel.
▪ Work with facility IT System
Administrators to ensure that the system
adheres to the site-specific cybersecurity
policies.

Failure to follow these instructions can result


in death, serious injury, or equipment damage.

Confidential Property of Schneider Electric | Page 2


Internal
Chapter Objectives
By the completion of this chapter, you will be able to:

• Understand main concepts of Gateway


rôle.
• Configure main parameters of Gateway
device in SCE

Confidential Property of Schneider Electric | Page 3


Internal
• Terminology

▪ What does mean Gateway ?

Network B

Gateway address for Network B

router

Network A Gateway address for Network A

Confidential Property of Schneider Electric | Page 4


Internal
• Terminology

▪ What does EPAS Gateway ?


▪ Protocol conversion

Network B

Protocol for Network B

router

Protocol for Network A


Network A

Confidential Property of Schneider Electric | Page 5


Internal
• Add / Configure PACiS Gateway
▪ Under SCS/Ethernet Network
▪ Add from Object Entry window

▪Note1 : use GTW configured in starting database

▪ PACiS GTW Attributes

Timestamped …
▪How should be timestamped unknown datapoints at
scada level :
No => timestamp of latest value seen
Yes => current timestamp when unknown is detected

Network name = PC’s name


limited to 15 characters

Confidential Property of Schneider Electric | Page 6


Internal
• PACiS Gateway Sons
▪ Basic = System Infos + 22 serial ports + IEC Mapping

22 serial communication ports

List of System Information :


▪Operating Mode,
Synchronisation Status, ...

1 to 6 protocols with the


relevant SCADA mapping
▪Note : use GTW configured in starting database, all
system information are already configured

AP with IEC 61850 Mapping


Confidential Property of Schneider Electric | Page 7
Internal
• PACiS Gateway Sons
▪ Legacy networks

Up to 16 Legacy
Networks
•T101 Master
•DNP3 Master
•Modbus

Confidential Property of Schneider Electric | Page 8


Internal
• PACiS Gateway Sons
▪ Scada networks
up to 6 TBUS protocols
Up to 4 TBUS serial protocols
+ 4 redundant link possibility = 8 serial ports

Confidential Property of Schneider Electric | Page 9


Internal
Internal
Internal