Section

Selection Guide ..................................... D-3

IEC Contactors
Non-Reversing Contactors
• YS1N AC Controlled . . . . . . . . . . . D-5
• YS3N DC Controlled . . . . . . . . . . . D-6

D
Reversing Contactors
• YS1R AC Controlled . . . . . . . . . . . D-7
• YS3R DC Controlled . . . . . . . . . . . D-8

Thermal Overload Relay


• YS1T-RHA. . . . . . . . . . . . . . . . . . . D-9

Starters............................................. D-11

Accessories ....................................... D-12

Specifications
• Contactors and Starters . . . . . . . . D-16
• Overload Relays . . . . . . . . . . . . . . D-24
• Accessories. . . . . . . . . . . . . . . . . . D-28

Dimensions....................................... D-35

Mounting Diagrams ........................ D-43

Wiring Diagrams............................. D-47

Application Tables........................... D-51

www.idec.com/contactor
for more information on this product family visit
www.idec.com/contactor
Additional Web Resources
• New and updated product information
• Downloadable software demos & upgrades
• Part configuration tool & cross reference
• Online stock check & ordering
• IDEC field sales & distributor search
• Online literature request
• Downloadable manuals & CAD drawings
• Manufacturer’s suggested retail price list
• Product training schedule & locations
• Advertising & trade show schedules
• Press releases & FAQs
Selection Guide IEC Contactors

IDEC YS Series Contactors / Starters

D
IEC Contactors

YS Series: Superior performance and low maintenance

Key features include: IDEC YS Series Contactors are used in switching motor loads. Like all
• Simple, compact, rugged electromechanical devices IDEC products, each model is engineered for long life, minimum mainte-
• Meets IEC, UL, c-UL and other international standards nance, dependable operation, and superior performance.
• All Contactors, Thermal Overload Relays, and Auxiliary Contact Blocks
bear the CE mark Snap on accessories are available for the IDEC YS series, giving each
model the flexibility to meet any application requirement.
• 35mm or 75mm DIN Rail or direct panel mounting
• Bifurcated double bridge auxiliary contacts, the moving contact bridge 1. Auxiliary contact blocks
has an “H” form; suitable for interface with electronic circuit • Top mounting type (2 or 4 poles type)
• Advanced design and materials, special silver-alloy long life contacts • Side mounting type (2 poles type)
• Cadmium-free contacts for environmental safety 2. Adjustable thermal overloads
• Bimetallic thermal overload relays 3. Surge suppressor modules
• Easy operation and maintenance; Direct and simple motor control 4. Mechanical interlock blocks
• Dual frequency 50/60 Hz coils 5. PLC interface modules

D-2 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Selection Guide

Selection Guide

RELAY INTERFACE MODULE


(With Surge Suppressor Module)
YS9Z-TCU500UH
The interface module incorporates con-
tacts which are actuated upon energiza-
tion of the module from low power
24VDC sources such as outputs from
SURGE SUPPRESSOR MODULES sensors and programmable controllers.

YS9Z-TU25  for YS1N-9F to -25F


YS9Z-TU65  for YS1N-32F to -65F SECOND
YS9Z-TU125  for YS1N-80F to -125F CONTACTOR
YS9Z-TU180  for YS1N-150F to -180F
For reversing applications
YS9Z-TU300  for YS1N-220F to -300F
YS1R, AC Controlled D
YS3R, DC Controlled
(reversing type)

IEC Contactors
CONTACTORS
Non-reversing
YS1N, AC Controlled
YS3N, DC Controlled

MECHANICAL
INTERLOCK BLOCKS
Used for reversing contactors
YS9Z-TMI65 for YS1N-9F through 65F
YS9Z-TMI125 for YS1N-80F through 300F

AUX. CONTACT BLOCKS


(2P, top mounting type)
AUX. CONTACT BLOCK YS1A-TAH220F (2NO)
YS1A-TAH211F (1NO-1NC)
(2P, side mounting type) YS1A-TAH202F (2NC)
YS1A-TAS211F for YS1N-9F to -65F
for YS1N-9F to -65F

AUX. CONTACT BLOCKS


(4P, top mounting type)
YS1A-TAH440F (4NO)
YS1A-TAH431F (3NO-1NC)
YS1A-TAH422F (2NO-2NC)
YS1A-TAH413F (1NO-3NC)
YS1A-TAH404F (4NC)
for YS1N-9F to -65F

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-3
YS Series IEC Contactors
YS Series Contactors

Key features of the YS Series include:


• Compact size
• AC and DC coil, reversing and non-reversing
• Weld-resistant silver alloy contacts
• No cadium used in contacts
• Highly reliable auxiliary contacts use bifurcated double bridge contact form
• Direct panel mount with screws or 35mm DIN rail (9F to 65F)
• Conforms to IEC standards: EN60947-1, EN60947-4-1, EN-60947-5-1
• Approval standards: UL508 (UL File No. E67770, E184169)

D CE Certified
IEC Contactors

Ordering Information
 IEC CONTACTORS
 Specify the maximum AC3 current code for the contactor in place of .
 Specify the coil voltage code for the contactor in place of * * * * .
 This part number is not indicated on the label of the contactor .
YS1N- F11 ****
Completed Part Number of Contactors 4 Coil Voltage
(Rated Voltage and Frequency)
1 Product Series A024 : AC24V 50/60Hz
A048 : AC48V 50/60Hz
YS1N: Non- reversing contactor, AC controlled A110 : AC110V 50/60Hz
YS1R: Reversing contactor, AC controlled A120 : AC120V 50/60Hz
A230 : AC230V 50/60Hz AC Contactors
YS3N: Non-reversing contactor, DC controlled
A240 : AC240V 50/60Hz (all sizes)
YS3R: Reversing contactor, DC controlled A380 : AC380V 50/60Hz
A415 : AC415V 50/60Hz
2 a) Approximate Maximum AC3 Current A480 : AC480V 50/60Hz
A600 : AC600V 50/60Hz
AC or DC Controlled Contactors D024 : DC 24V
D048 : DC 48V DC Contactors
9:9A, 12:12A, 20:20A, 25:25A, 32:32A, 38:38A, D110 : DC 110V (sizes 9-65)
40:40A, 50:50A, 65:65A, 80:80A, 100:100A, 125:125A D220 : DC 220V
M100 : DC 110V DC Contactors
AC Contactors Only M200 : DC 220V (sizes 80-125)
150:150A, 180:180A, 220:220A, 300:300A
(Other Voltages Available, Contact IDEC)
b) Type of Contactor

F: AC controlled all sizes


FG2: DC Controlled, sizes 9-65
FG: DC Controlled, sizes 80-125

3 Auxiliary Contact Configuration (Built onto conctactor)


01: with 1NC, only for contactors sizes 9F-12F
10: with 1NO, only for contactors sizes 9F-12F
11: with 1NO-1NC, only for contactors sizes 20F-65F
22: with 2NO-2NC, only for contactors sizes 80F-300F

Notes:
1. Use the above ordering information only when interpreting
part numbers. Do not use for developing part numbers.
2. Please see tables on following pages for proper selection.
3. For specifications please see page D-16 through page D-34.

D-4 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors YS Series

YS1N Non-Reversing AC Contactors

IEC Contactors
IEC Contactors, AC Controlled

Ie kW AC3 Rating EN 60974-4-1 HP Rating per UL508 Auxiliary


(Amps) 3 Phase 1 Phase 3 Phase Contacts
Part Number
220- 380- 660- 200- 220- 440- 550-
AC1 AC3 500V 120V 230V N.O. N.C.
230V 400V 690V 208V 240V 480V 600V
0 1 YS1N-9F01****
20 8.5 2.2 4 5.5 5.5 1/3 1 2 2 5 5
1 0 YS1N-9F10****
0 1 YS1N-12F01****
20 11.5 3 5.5 7.5 7.5 3/4 2 3 3 7.5 5
1 0 YS1N-12F10****
30 15.5 4 7.5 10 10 1 3 5 5 10 13.5 1 1 YS1N-20F11****
30 22 5.5 11 15 15 2 3 7.5 7.5 15 15 1 1 YS1N-25F11****
50 30 7.5 15 18.5 18.5 2 5 7.5 10 20 20 1 1 YS1N-32F11****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS1N-38F11****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS1N-40F11****
80 44 15 22 30 33 3 7.5 10 15 40 40 1 1 YS1N-50F11****
80 60 18.5 30 37 37 5 10 20 20 50 40 1 1 YS1N-65F11****
135 85 22 45 55 45 7.5 15 25 25 60 60 2 2 YS1N-80F22****
150 105 30 55 65 65 - - 30 35 60 75 2 2 YS1N-100F22****
150 114 37 60 75 75 - - 40 50 100 100 2 2 YS1N-125F22****
200 138 45 75 90 100 - - 40 50 100 125 2 2 YS1N-150F22****
240 179 55 95 110 110 - - 50 60 125 125 2 2 YS1N-180F22****
260 205 65 110 132 132 - - 60 75 150 150 2 2 YS1N-220F22****
350 300 90 160 160 200 - - 75 100 200 200 2 2 YS1N-300F22****

Codes for Control Circuit AC Voltages 50/60 Hz


Volts AC 50/60 Hz 24 48 120 220 240 380 415 480
Code to replace **** A024 A048 A120 A220 A240 A380 A415 A480

Consult an IDEC representative for other coil voltages.


For accessories, see page D-12.
For specifications, see page D-16 through D-34.
For dimensions, see pages D-35.
For other application tables, see page D-51.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-5
YS Series IEC Contactors
YS3N Non-Reversing DC Contactors

D
IEC Contactors

IEC Contactors, DC Controlled

Ie KW AC3 Rating EN 60974-4-1 HP Rating per UL508 Auxiliary


(Amps) 3 Phase 1 Phase 3 Phase Contacts
Part Number
220- 380- 660- 200- 220- 440- 550-
AC1 AC3 500V 120V 230V N.O. N.C.
230V 400V 690V 208V 240V 480V 600V
0 1 YS3N-9FG201****
20 8.5 2.2 4 5.5 5.5 1/3 1 2 2 5 5
1 0 YS3N-9FG210****
0 1 YS3N-12FG201****
20 11.5 3 5.5 7.5 7.5 3/4 2 3 3 7.5 5
1 0 YS3N-12FG210****
30 15.5 4 7.5 10 10 1 3 5 5 10 13.5 1 1 YS3N-20FG211****
30 22 5.5 11 15 15 2 3 7.5 7.5 15 15 1 1 YS3N-25FG211****
50 30 7.5 15 18.5 18.5 2 5 7.5 10 20 20 1 1 YS3N-32FG211****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS3N-38FG211****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS3N-40FG211****
80 44 15 22 30 33 3 7.5 10 15 40 40 1 1 YS3N-50FG211****
80 60 18.5 30 37 37 5 10 20 20 50 40 1 1 YS3N-65FG211****
135 85 22 45 55 45 7.5 15 25 25 60 60 2 2 YS3N-80FG22****
150 105 30 55 65 65 - - 30 35 60 75 2 2 YS3N-100FG22****
150 114 37 60 75 75 - - 40 50 100 100 2 2 YS3N-125FG22****

Codes for Control Circuit DC Voltages, 9F through 65F Codes for 80F/100F/125F
Volts DC 24 48 110 220 110 220
Code to replace **** D024 D048 D110 D220 M100 M200

Consult an IDEC representative for other coil voltages.


For accessories, see page D-12.
For specifications, see pages D-16 through D-34.
For dimensions, see page D-35.
For other application tables, see page D-51.

D-6 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors YS Series

YS1R Reversing AC Contactors

D
IEC Contactors, AC Controlled

IEC Contactors
Ie kW AC3 Rating EN 60974-4-1 HP Rating per UL508 Auxiliary
(Amps) 3 Phase 1 Phase 3 Phase Contacts
Part Number
220- 380- 660- 200- 220- 440- 550-
AC1 AC3 500V 120V 230V N.O. N.C.
230V 400V 690V 208V 240V 480V 600V
0 1 YS1R-9F01****
20 8.5 2.2 4 5.5 5.5 1/3 1 2 2 5 5
1 0 YS1R-9F10****
0 1 YS1R-12F01****
20 11.5 3 5.5 7.5 7.5 3/4 2 3 3 7.5 5
1 0 YS1R-12F10****
30 15.5 4 7.5 10 10 1 3 5 5 10 13.5 1 1 YS1R-20F11****
30 22 5.5 11 15 15 2 3 7.5 7.5 15 15 1 1 YS1R-25F11****
50 30 7.5 15 18.5 18.5 2 5 7.5 10 20 20 1 1 YS1R-32F11****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS1R-38F11****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS1R-40F11****
80 44 15 22 30 33 3 7.5 10 15 40 40 1 1 YS1R-50F11****
80 60 18.5 30 37 37 5 10 20 20 50 40 1 1 YS1R-65F11****
135 85 22 45 55 45 7.5 15 25 25 60 60 2 2 YS1R-80F22****
150 105 30 55 65 65 - - 30 35 60 75 2 2 YS1R-100F22****
150 114 37 60 75 75 - - 40 50 100 100 2 2 YS1R-125F22****
200 138 45 75 90 100 - - 40 50 100 125 2 2 YS1R-150F22****
240 179 55 95 110 110 - - 50 60 125 125 2 2 YS1R-180F22****
260 205 65 110 132 132 - - 60 75 150 150 2 2 YS1R-220F22****
350 300 90 160 160 200 - - 75 100 200 200 2 2 YS1R-300F22****

Codes for Control Circuit AC Voltages 50/60 Hz


Volts AC 50/60 Hz 24 48 120 220 240 380 415 480
Code to replace **** A024 A048 A120 A220 A240 A380 A415 A480

Consult an IDEC representative for other coil voltages.


For accessories, see page D-12.
For specifications, see page D-16 through D-34.
For dimensions, see pages D-35.
For other application tables, see page D-51

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-7
YS Series IEC Contactors

YS3R Reversing DC Contactors

D
IEC Contactors, DC Controlled
IEC Contactors

Ie kW AC3 Rating EN 60974-4-1 HP Rating per UL508 Auxiliary


(Amps) 3 Phase 1 Phase 3 Phase Contacts
Part Number
220- 380- 660- 200- 220- 440- 550-
AC1 AC3 500V 120V 230V N.O. N.C.
230V 400V 690V 208V 240V 480V 600V
0 1 YS3R-9FG201****
20 8.5 2.2 4 5.5 5.5 1/3 1 2 2 5 5
1 0 YS3R-9FG210****
0 1 YS3R-12FG201****
20 11.5 3 5.5 7.5 7.5 3/4 2 3 3 7.5 5
1 0 YS3R-12FG210****
30 15.5 4 7.5 10 10 1 3 5 5 10 13.5 1 1 YS3R-20FG211****
30 22 5.5 11 15 15 2 3 7.5 7.5 15 15 1 1 YS3R-25FG211****
50 30 7.5 15 18.5 18.5 2 5 7.5 10 20 20 1 1 YS3R-32FG211****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS3R-38FG211****
60 37 11 18.5 22 30 3 7.5 10 15 30 30 1 1 YS3R-40FG211****
80 44 15 22 30 33 3 7.5 10 15 40 40 1 1 YS3R-50FG211****
80 60 18.5 30 37 37 5 10 20 20 50 40 1 1 YS3R-65FG211****
135 85 22 45 55 45 7.5 15 25 25 60 60 2 2 YS3R-80FG22****
150 105 30 55 65 65 - - 30 35 60 75 2 2 YS3R-100FG22****
150 114 37 60 75 75 - - 40 50 100 100 2 2 YS3R-125FG22****

Codes for Control Circuit DC Voltages, 9F through 65F Codes for 80F/100F/125F
Volts DC 24 48 110 220 110 220
Code to replace **** D024 D048 D110 D220 M100 M200

Consult an IDEC representative for other coil voltages.


For accessories, see page D-12.
For specifications, see page D-16 through D-34.
For dimensions, see pages D-35.
For other application tables, see page D-51

D-8 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors YS Series

Thermal Overload Relays


YS1T-RHA thermal overload relays are designed to meet the heating characteristics of induction motors with insulation class type E. Various functions can be
selected by using the reset button and adjustment button on top of the thermal overload relay.
Key features of the YS1T Series include:
• Single-phase protection
• Bi-metallic
• Compact and sturdy
• Ambient temperature compensation mechanism
• Manual/automatic reset operation
• 3 element type with phase failure protection
• Conforms to IEC Standards EN60947-1, EN60947-4-1, EN60947-5-1
• Approval standards UL508, UL File No. E158813

IEC Contactors
Ordering Information
■ THERMAL OVERLOAD RELAYS
•Part number is indicated on the label of the thermal overload relay.
Y S 1 T- R H A D

3 Current setting Adjustable Current setting Adjustable


Completed Part Number of Thermal Overload Relay range code current range range code current range

1 Product Series P13 : 0.1 - 0.16 43P : 37 - 50


P20 : 0.16 - 0.25 56P : 48 - 65
P30 : 0.25 - 0.4 68P : 55 - 80
2 Applicable Maximum Motor Current P50 : 0.4 - 0.63 80P : 65 - 95
25F: 25A, contactor sizes 9F,12F, 20F, 25F P80 : 0.63 - 1 105 : 85 - 125
1P3 : 1 - 1.6 120* : 96 - 155
38F: 40A, contactor sizes 32F, 38F 1P5 : 1.25 - 2 135 : 110 - 160
65F: 65A, contactor sizes 40F, 50F, 65F 2P0 : 1.6 - 2.5 155 : 125 - 185
3P0 : 2.5 - 4 160* : 128 - 200
125F: 125A, contactor sizes 80F, 100F, 125F 5P0 : 4-6 180* : 150 - 240
150F: 150A, contactor sizes 150F or 180F 7P0 : 5.5 - 8 240* : 192 - 300
8P5 : 7 - 10
180F: 180A, contactor sizes 150F or 180F 11P : 9 - 13
*300F: 300A, contactor size 220F or 300F 15P : 12 - 18
*400F: 400A, contactor size 220F or 300F 21P : 17 - 25
27P : 23 - 32
Note: *With Current Transformer (CT) 32P : 28 - 36
35P : 30 - 40 Note :*With CT
4 Function
D: 3-element Type with Phase Failure Protection Verify appropriate current setting range code with the
correct size overload using the complete part list on
the following page.

Notes:
1. Use the above ordering information only when interpreting
part numbers. Do not use for developing part numbers.
2. For applicable combinations of contactors and thermal
overload relays, please consult following page.
3. For specifications and settings please see pages D-16 through D-34.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-9
YS Series IEC Contactors
Thermal Overload Relays
Product Series Current Range Range Code Part Number for Overload Applicable Contactor Size
0.1-0.16A P13 YS1T-RHA25FP13D
0.16-0.25A P20 YS1T-RHA25FP20D
0.25-0.4A P30 YS1T-RHA25FP30D
0.40-0.63A P50 YS1T-RHA25FP50D
0.63-1.0A P80 YS1T-RHA25FP80D
YS1T-RHA25F
1.0-1.6A 1P3 YS1T-RHA25F1P3D
1.25-2.0A 1P5 YS1T-RHA25F1P5D YS-9F
YS-12F
1.6-2.5A 2P0 YS1T-RHA25F2P0D YS-20F
2.5-4.0A 3P0 YS1T-RHA25F3P0D YS-25F

4.0-6.0A 5P0 YS1T-RHA25F5P0D


YS1T-RHA38F 5.5-8.0A 7P0 YS1T-RHA25F7P0D

D 7.0-10.0A 8P5 YS1T-RHA25F8P5D


9.0-13.0A 11P YS1T-RHA25F11PD
IEC Contactors

12.0-18.0A 15P YS1T-RHA25F15PD


17.0-25.0 21P YS1T-RHA25F21PD
9-13A 11P YS1T-RHA38F11PD
YS1T-RHA65F 12-18A 15P YS1T-RHA38F15PD
17-25A 21P YS1T-RHA38F21PD YS-32F
23-32A 27P YS1T-RHA38F27PD YS-38F

28-36A 32P YS1T-RHA38F32PD


30-40A 35P YS1T-RHA38F35PD
12-18A 15P YS1T-RHA65F15PD
YS1T-RHA125F
17-25A 21P YS1T-RHA65F21PD
23-32A 27P YS1T-RHA65F27PD
YS-40F
28-36A 32P YS1T-RHA65F32PD YS-50F
YS-65F
30-40A 35P YS1T-RHA65F35PD
37-50A 43P YS1T-RHA65F43PD

YS1T-RHA150F 48-65A 56P YS1T-RHA65F56PD


37-50A 43P YS1T-RHA125F43PD
48-65A 56P YS1T-RHA125F56PD
YS-80F
55-80A 68P YS1T-RHA125F68PD YS-100F
YS-125F
65-95A 80P YS1T-RHA125F80PD
85-125A 105 YS1T-RHA125F105D
65-95A 80P YS1T-RHA150F80PD
YS1T-RHA180F YS-150F
85-125A 105 YS1T-RHA150F105D YS-180F
105-160A 135 YS1T-RHA150F135D
85-125A 105 YS1T-RHA180F105D
YS-150F
105-160A 135 YS1T-RHA180F135D YS-180F
125-185A 155 YS1T-RHA180F155D
96-150A 120 YS1T-RHA300F120D
*YS1T-RHA300F
*YS1T-RHA400F 150-240A 180 YS1T-RHA300F180D YS-220F
128-200A 160 YS1T-RHA400F160D YS-300F
*with current transformer
200-300A 240 YS1T-RHA400F240D

D-10 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors YS Series

YS Series Starters

Ordering Instructions for an Assembled Starter


STARTERS (Contactors with Thermal Overload Relay)

• Select the appropriate contactor (AC or DC, reversing or non-reversing) from pages D-5 through D-8.
• Select the correct size overload from page D-9 throught D-10.
• The complete assembled part number is the same as the contactor with the following changes:
(See examples below)

YS2R - FD 11 **** T###


Completed Part Number of Reversing Starter D
1 Product Series

IEC Contactors
YS1N contactor ----> YS2N AC non-reversing Starter
YS1R contactor ----> YS2R AC reversing Starter
YS3N contactor ----> YS4N DC non-reversing Starter
YS3R contactor ----> YS4R DC reversing Starter

2 Maximum AC3 Current (replaced exactly from contactor P/N)

F: is replaced by size, 9-300 for AC controlled


FG2: is replaced by size, 9-65 for DC controlled
FG: is replaced by size, 80-125 for DC controlled

3 Thermal Overload Relay


D: 3-element Type with Phase Failure Protection

4 Auxiliary Contact Configuration (Replaced exactly from contactor P/N)


01: with 1NC, for contactor sizes 9F-12F
10: with 1NO, for contactor sizes 9F-12F
11: with 1NO-1NC, for contactor sizes 20F-65F
22: with 2NO-2NC, for contactor sizes 80F-300F

5 Coil Voltage (Replaced exactly from contactor P/N)

6 Thermal Overload Relay, Type YS1T-RHA


T: Thermal Overload Relay +
###: Three character code designating of Current Setting Range Code (See page D-10.)

EXAMPLE #1 :
Contactor : Y S 1 R - 9 F 1 0 A 1 2 0 + Overload: Y S 1 T- R H A 2 5 F 5 P 0 D
1 2 4 5 6

STARTER: Y S 2 R - 9 F D 1 0 A 1 2 0 T 5 P 0
1 2 3 4 5 6

EXAMPLE #2 :
Contactor : Y S 3 N - 6 5 F G 2 1 1 D 0 2 4 + Overload: Y S 1 T- R H A 6 5 F 4 3 P D
1 2 4 5 6

STARTER: Y S 4 N - 6 5 F G 2 D 1 1 D 0 2 4 T 4 3 P
1 2 3 4 5 6

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-11
Accessories IEC Contactors
Accessories

Accessory Description Part Number Notes


Auxiliary Contact Mounting Contact Configuration
Blocks Number of Poles
Style NO NC
Side 1 1 YS1A-TAS211F
0 2 YS1A-TAH202F
2 Poles
1 1 YS1A-TAH211F
2 0 YS1A-TAH220F Auxiliary contacts only available
for contactors from 9F through 65F.
0 4 YS1A-TAH404F
Top
1 3 YS1A-TAH413F
2 2 YS1A-TAH422F
D 4 Poles
3 1 YS1A-TAH431F

4 0 YS1A-TAH440F
IEC Contactors

Replacement Auxiliary Replacements for attached auxil-


2 Poles Side 1 1 YS1A-TAS211FL iary contact blocks on contactors
Contact Block 80F through 300F
For use with YS-9F through YS-12F YS9Z-KIF411344-A
Power Wire Kits
For use with YS-20F through YS-25F YS9Z-KIF411345-A
For use with YS-32F through YS-38F YS9Z-KIF411346-A
For use with YS-40F through YS-65F YS9Z-KIF411347-A
For use with YS-80F through YS-125F YS9Z-KIF411348-A
For use with YS-150F YS9Z-KIF411588-A
For use with YS-180F YS9Z-KIF411588-B
For use with YS-220F through YS-300F YS9Z-KIF411590-A
Mechanical
Interlock YS9Z-TMI65
For use with YS-9F through YS-65F

For use with YS-80F through YS-300F YS9Z-TMI125

Marking Tags For use with YS-9F through YS-65F YS9Z-TIP66


Overload
DIN Rail
Bracket
For use with YS1T-RHA65F overload YS9Z-TIB65F

Assembled
Pushbutton for Blank Cap / No engraving HW1B-M1RS-*T
* Choose cap color
Overload Reset w/ Cap engraved with “R” HW1B-M1RS-*T-ENG-R B= Black
Extension Rod Y= Yellow
Cap engraved with “RESET” HW1B-M1RS-*T-ENG-RESET N= Gray
Sub Assembled G= Green
S= Blue
Operator HW1B-M0 R= Red
W=White
Blank Cap / No engraving HW1A-B1-*
Rod (10 inch length; adjustable) HW9Z-RS-TK2141

D-12 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Accessories

Accessories, continued

Accessory Description Part Number * Applicable Size Codes


Surge Suppressor Type Rated Voltage
50-127V AC YS9Z-TU*C120
RC Circuit
110-240V AC YS9Z-TU*C240 25 = YS-9F to YS-25F
65 = YS-32F to YS-65F
50-127V AC YS9Z-TU*V120 125 = YS-80F to YS-125F
180 = YS-150F to YS-180F
Varistor 110-240V AC YS9Z-TU*V240 300 = YS-220F to YS-300F
380-440V AC YS9Z-TU*V440
Relay Interface Module
12 = YS-9F to YS-12F
25 = YS-20F- to YS-25F
Isolates the coil of contactor from PLC output by provid- 38 = YS-32F to YS-38F
ing an easy to mount module that takes 24V DC input and
switches up to 380V AC for contactor coils.
External source required for contactor coil.
YS9Z-TCU500UH* 65 = YS-40F to YS-65F
125 = YS-80F to YS-125F D
180 = YS-150F to YS-180F
300 = YS-220F to YS-300F

IEC Contactors
Star (Wye) Delta Timer Input Voltage Contact Style
Star: Delayed SPST-NO 8-pin GT3S-1AF20
100V AC to Delta: Delayed SPST-NO 11-pin GT3S-1EAF20 See Section G for further
240V AC information
50/60 Hz Star: Delayed SPST-NO 8-pin GT3S-2AF20
Delta: Delayed SPST-NO
Instantaneous SPST-NO 11-pin GT3S-2EAF20
AC Coils for AC Contactors
For use with YS-9F through YS-12F YS9Z-KIL70461-*
For use with YS-20F through YS-25F YS9Z-KIL70462-* A024 = 24V AC 50/60 Hz
A048 = 48V AC 50/60 Hz
For use with YS-32F to YS-38F YS9Z-KIL70463-* A120 = 120V AC 50/60 Hz
A240 = 240V AC 50/60 Hz
For use with YS-40F to YS-65F YS9Z-KIL70464-* A380 = 380V AC 50/60 Hz
A480 = 480V AC 50/60 Hz
Replacement Coils For use with YS-80F to YS-125F YS9Z-KIL70518-* A600 = 600V AC 50/60 Hz
For use with YS-150F to YS-180F YS9Z-KIL70466-*
For use with YS-220F to YS-300F YS9Z-KIL70467-*
DC Coils for DC Contactors 9F through 65F
D024 = 24V DC
For use with YS-9F through YS-25F YS9Z-KIL70562-* D048 = 48V DC
For use with YS-32F through YS-38F YS9Z-KIL70564-* D110 = 110V DC
D220 = 220V DC
For use with YS-40F through YS-65F YS9Z-KI411880-*
DC Coils for DC Contactors 80F through 125F D110 = 110V DC
For use with YS-80F through YS-125F # YS9Z-KIL70519-* D220 = 220V DC

AC/DC Module for 80F through 125F DC coils only


Used in conjunction with
100V AC/DC Module for YS-80F through YS-125F YS9Z-KIFCA840546A YS9Z-KIL-70519-* for DC coils
80F through 125F only.
200V AC/DC Module for YS-80F through YS-125F YS9Z-KIFCA840546B

# — YS9Z-KIL70519* is available ONLY in 110V (D110) or 220V (D220) models.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-13
Accessories IEC Contactors
Accessories, continued

Accessory Description Part Number


each part number is for
ONE (1) main contact
Stationary Main Contacts
For use with YS-20F YS9Z-KIF409056-A
For use with YS-25F YS9Z-KIF409057-A
For use with YS-32F YS9Z-KIF410179-A
For use with YS-38F YS9Z-KIF410180-A
For use with YS-40F YS9Z-KIF409083-A
For use with YS-50F YS9Z-KIF409083-B
D For use with YS-65F YS9Z-KIF409083-C
For use with YS-80F YS9Z-KIF410697-A
IEC Contactors

6 pieces required For use with YS-100F YS9Z-KIF410697-B


per contactor For use with YS-125F YS9Z-KIF410697-C
For use with YS-150F YS9Z-KIF410853-A
For use with YS-180F YS9Z-KIF410854-A
For use with YS-220F YS9Z-KIF411841-A
For use with YS-300F YS9Z-KIF411842-A
Moving Main Contacts
For use with YS-20F YS9Z-KIF409059-A
For use with YS-25F YS9Z-KIF409060-A
For use with YS-32F YS9Z-KIF410167-A
For use with YS-38F YS9Z-KIF410168-A
For use with YS-40F YS9Z-KIF409155-A
For use with YS-50F YS9Z-KIF409155-B
For use with YS-65F YS9Z-KIF409155-C
For use with YS-80F YS9Z-KIF410698-A

3 pieces required For use with YS-100F YS9Z-KIF410698-B


per contactor For use with YS-125F YS9Z-KIF410698-C
For use with YS-150F YS9Z-KIF410856-A
For use with YS-180F YS9Z-KIF410857-A
For use with YS-220F YS9Z-KIF411843-A
For use with YS-300F YS9Z-KIF411844-A

All part numbers refer to one piece quantity (not sets).

D-14 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Accessories

Accessories, continued

Part Number Description For Use With


BAA1000

35mm Aluminum DIN Rail 7.5 mm deep YS1N-9F through YS1N-38F Contactors
1 meter long

BNDN1000

35mm Aluminum DIN Rail 10.5 mm deep. YS1N-9F through YS1N-38F Contactors
1 meter long D

IEC Contactors
YS9Z-TIP66 Markers

YS-9F through YS-65F series contactors,


Plastic replacement markers overloads relays and top mount auxiliary
sold in 100 piece packs contact blocks.

BNL8
YS1N-32F/YS1N-38F
DIN Rail End Stop used to prevent &
contactors from sliding on DIN rails YS1R reversing contactors

BNL5
YS1N-9F
YS1N-12F
DIN Rail End Stop used to prevent YS1N-20F
contactors from sliding on DIN rails YS1N-25F
Contactors

SR2P-05C
GT3S-1AF20 timer (8 pin)
8-pin DIN mount Finger-safe (IP20) GT3S-2AF20 timer (8 pin)
screw terminal socket

SR2P-06
8-pin DIN mount screw terminal socket GT3S-1AF20 timer (8 pin)
open terminal construction GT3S-2AF20 timer (8 pin)

SR3P-05C

11-pin DIN mount finger-safe (IP20) GT3S-1EAF20 timer (11pin)


screw terminal socket GT3S-2EAF20 timer (11pin)

SR3P-06

11-pin DIN mount screw terminal socket GT3S-1EAF20 (11 pin)


open terminal construction GT3S-2EAF20 (11 pin)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-15
Specifications IEC Contactors
Specifications

Contactor Circuit Supply: AC


Characteristics

Part Number YS1N– 9F 12F 20F 25F 32F 38F 40F 50F 65F 80F 100F 125F 150F 180F 220F 300F

Rated Insulation Voltage V 690 690 690 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

Conformity to Standards NFC 63-110; VDE 0660; BS 5424; JEM 1038; EN60947-1, 60947-4-1; UL508

Approvals UL, c-UL

Degree of Protection Finger-safe (according to VDE 0106)

D Dry Ambient Air Temp. for Storage 1/4C -40 to +80

Dry Ambient Air Temp. for Operation 1/4C -10 to +55 (0.85 to 1.1 Un)
IEC Contactors

Operating Altitude m 2000

Operating Position (without derating ±301/4 compared with the normal vertical mounting plane (see table on D-22)

Main Power Pole Utilization Characteristics:

Number of Poles: 3 Part No. 9F 12F 20F 25F 32F 38F 40F 50F 65F 80F 100F 125F 150F 180F 220F 300F

Rated in AC3 A 9 12 18 25 30 40 40 50 65 80 105 125 150 180 220 300


Operational
Current in AC1 A 20 20 30 30 50 60 60 80 80 135 150 150 200 240 260 350

Rated Operational Voltage V 660 660 690 690 690 690 690 690 690 690 690 690 690 690 690 690

Maximum Thermal Ith A 20 20 35 35 50 60 60 80 80 135 150 150 200 240 260 350
Current (≥55°C)

Making Capacity I rms A 150 150 280 300 480 480 800 800 800 1500 1500 1500 1800 2100 2500 3500

Breaking Capacity 220-380- A 120 150 250 300 380 480 500 600 700 800 1100 1300 1500 1800 2100 3000
415-440V

I rms 500V A 100 120 200 250 300 400 400 500 550 800 1000 1100 1200 1600 1900 2200

According to 660-690V A 90 100 120 180 250 350 350 400 430 500 750 820 1100 1200 1400 1800
EN 60158-1

Wiring, minimum-maximum wire size:

Stranded Wire (without ferrule)

mm2 1-4 1-4 1.5-10 1.5-10 4-16 4-16 5-25 5-25 5-25 8-60 8-60 8-60 8-100 8-100 14-150 14-150
1 Conductor
AWG 18-10 18-10 16-8 16-8 12-6 12-6 10-3 10-3 10-3 8-0 8-0 8-0 8-4/0 8-4/0 4- 4-
300mcm 300mcm

mm2 1-4 1-4 1.5-6 1.5-6 4-8 4-8 5-16 5-16 5-16 8-35 8-35 8-35 8-50 8-50 14-80 14-80
2 Conductors
AWG 18-10 18-10 16-10 16-10 12-8 12-8 10-5 10-5 10-5 8-2 8-2 8-2 8-1 8-1 4-3/0 4-3/0

Solid Wire (without ferrule)

mm2 1-4 1-4 1.5-6 1.5-6 4-10 4-10 5-25 5-25 5-25
1 Conductor _ _ _ _ _ _ _
AWG 18-10 18-10 16-10 16-10 12-8 12-8 10-3 10-3 10-3

mm2 1-4 1-4 1.5-6 1.5-6 4-10 4-10 5-16 5-16 5-16
2 Conductors _ _ _ _ _ _ _
AWG 18-10 18-10 16-10 16-10 12-8 12-8 10-5 10-5 10-5

D-16 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications
Control Circuit Characteristics:

Part Number YS1N- 9F 12F 20F 25F 32F 38F 40F 50F 65F 80F 100F 125F 150F 180F 220F 300F

Rated AC Control Voltage V Un: 24 to 600


(50 or 60 Hz) : Un

Coil Limits
(≤ 55°C)

Operating Limits Un 85% to 110% × Un

Drop-Out Voltage Un 30% to 70% × Un

Coil Power Consumption


(20°C) in Un

Inrush VA 55 55 85 85 150 150 170 170 170 276 276 276 819 819 805 805

Cos Ø (power factor) 0.8 0.8 0.8 0.8 0.7 0.7 0.6 0.6 0.6 0.5 0.5 0.5 0.5 0.5 0.2 0.2
AC 50 Hz
Sealed VA 8 8 8 8 15 15 16 16 16 40 40 40 53 53 100 100
D

IEC Contactors
Cos Ø (power factor) 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.37 0.37

Inrush VA 50 50 80 80 130 130 150 150 150 231 231 231 714 714 700 700

Cos Ø (power factor) 0.7 0.7 0.7 0.7 0.6 0.6 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.21 0.21
AC 60 Hz
Sealed VA 6 6 6 6 12 12 13 13 13 29 29 29 38 38 88 88

Cos Ø (power factor) 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.37 0.37

50 Hz W 1.5 to 2.5 1.5 to 2.5 1.5 to 2.5 1.5 to 2.5 3.5 to 5.0 3.5 to 5.0 3.7 to 5.2 3.7 to 5.2 3.7 to 5.2 7.5 to 11 7.5 to 11 7.5 to 11 12 to 16 12 to 16 19 to 27 19 to 27
Coil Power
Consumption
60 Hz W 1.0 to 2.0 1.0 to 2.0 1.0 to 2.0 1.0 to 2.0 3.0 to 4.5 3.0 to 4.5 3.0 to 4.5 3.0 to 4.5 3.0 to 4.5 6.0 to 8.5 6.0 to 8.5 6.0 to 8.5 9.0 to 13 9.0 to 13 16 to 23 16 to 23

Mechanical Life at Rated


Control Voltage (Un) 10 10 10 10 5 5 5 5 5 5 5 5 5 5 5 5
(× 106 operating cycles)

Mechanical 9000 9000 9000 9000 9000 9000 9000 9000 9000 7200 7200 7200 7200 7200 5000 5000
Switching ops/h
Frequency
Electrical AC3 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200 1200

Minimum-Maximum
Wire Size

mm2 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4
1 Conductor
AWG 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10
Stranded Wire
(without ferrule)
mm 2 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4
2 Conductors
AWG 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10

mm2 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4
1 Conductor
AWG 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10
Solid Wire
(without ferrule)
mm 2 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4 1-4
2 Conductors
AWG 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10 18-10

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-17
Specifications IEC Contactors
Coil Resistance:
Resistance (Ω)
Coil Voltage
YS1N-9F/12F YS1N-20F/25F YS1N-32F/38F YS1N-40F/50F/65F YS1N-80F/100F/125F YS1N-150F/180F YS1N-220F/300F
24V 50/60Hz 7.90 4.8 1.68 1.7 0.39 0.298 0.107

48V 50/60Hz 33.9 19.1 7.1 6.3 1.85 1.182 0.378

110V 50/60Hz 174.4 101 36.6 39.1 8.67 6.46 2.630

120V 50/60Hz 196.3 122 44.2 45.2 11.6 7.1 3.186

208V 50/60Hz 619.5 385 134 137.4 33.3 23.2 8.310

220V 50/60Hz 748.0 397 153 139.0 35.6 24.8 8.840

230V 50/60Hz 776.0 486 153 162.0 37.2 30 9.340

240V 50/60Hz 841.8 513 164 177.8 45.6 31.4 9.810


D
380V 50/60Hz 2577.0 1310 458 426.0 112 82 22.38
IEC Contactors

415V 50/60Hz 2821.1 1480 501 562.5 133 96.6 28.70

480V 50/60Hz 3166.4 2050 675 757.1 182 129.2 62.71

500V 50/60Hz 3272.7 2170 790 794.0 191 135.2 66.52

600V 50/60Hz 5136.3 3100 1162 1046.7 275 206 100.3

Operating Time:
Contactor 50Hz 60Hz

Basic Closing (msec) Opening (msec) Closing (msec) Opening (msec)


Frame
Part Aux. Aux. Aux. Aux. Aux. Aux. Aux. Aux.
Size Main Main Main Main
Number (NO) (NC) (NO) (NC) (NO) (NC) (NO) (NC)
YS1N-9F
12 11 to 17 11 to 17 8 to 12 5 to 13 5 to 13 7 to 14 10 to 15 10 to 15 7 to 12 5 to 13 6 to 14 7 to 15
YS1N-12F

YS1N-20F
25 14 to 22 15 to 22 9 to 16 3 to 13 6 to 13 9 to 17 13 to 20 13 to 20 9 to 13 2 to 12 7 to 13 9 to 17
YS1N-25F

YS1N-32F
38 15 to 23 15 to 23 8 to 16 6 to 15 7 to 15 12 to 23 16 to 24 16 to 24 9 to 16 5 to 14 7 to 15 11 to 21
YS1N-38F

YS1N-40F
65 YS1N-50F 14 to 22 16 to 24 10 to 16 6 to 17 5 to 17 11 to 23 15 to 22 15 to 22 9 to 16 7 to 16 7 to 16 11 to 20
YS1N-65F

YS1N-80F
125 YS1N-100F 10 to 27 10 to 26 6 to 19 6 to 20 6 to 20 10 to 26 13 to 31 12 to 30 8 to 22 6 to 18 6 to 18 10 to 24
YS1N-125F

YS1N-150F
180 17 to 34 16 to 31 13 to 31 8 to 25 8 to 28 12 to 29 21 to 39 20 to 36 13 to 29 5 to 22 7 to 22 11 to 29
YS1N-180F

YS1N-220F
300 17 to 36 16 to 36 13 to 33 8 to 27 8 to 30 12 to 31 22 to 41 21 to 38 13 to 31 5 to 24 7 to 24 11 to 31
YS1N-300F

Notes:
1. The operating time depends on the type of contactor electromagnet and its control mode.
2. The closing time is measured from the time the coil power supply is switched on to the time the main contacts first make contact.
3. The opening time is measured from the time the coil power supply is switched off to the time the main contacts separate.
4. The duration of the arcing time depends on the type of circuit switched by the poles.
5. For normal three-phase applications the duration of the arcing time is normally less than 10 ms.
6. The load is isolated from the coil power supply after a time equal to: the sum of the opening time and the arcing time.

D-18 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Contactor Circuit Supply: DC


Operating Coil Characteristics

Coil Voltage Exciting Current Pick-Up Voltage Drop-Out Voltage Coil Resistance Power Consumption
Part Number
(V) (mA) (V) (V) (1/2) (W)
24V DC 214 to 262 10 to 15 5 to 10 102 5.1 to 6.4
YS3N-9FG2 48V DC 108 to 132 21 to 30 10 to 20 404 5.1 to 6.4
YS3N-12FG2 100V DC 51 to 64 45 to 63 21 to 40 1750 5.0 to 6.5
200V DC 26 to 33 90 to 125 43 to 80 6870 5.1 to 6.8
24V DC 214 to 262 10 to 15 5 to 10 102 5.1 to 6.4
YS3N-20FG2 48V DC 108 to 132 21 to 30 10 to 20 404 5.1 to 6.4
YS3N-25FG2 100V DC 51 to 64 45 to 63 21 to 40 1750 5.0 to 6.5
200V DC 26 to 33 90 to 125 43 to 80 6870 5.1 to 6.8
24V DC 335 to 410 11 to 16 4 to 8 65.1 8.0 to 9.9
YS3N-32FG2 48V DC 165 to 202 23 to 32 8 to 16 264 7.8 to 9.8 D
YS3N-38FG2 100V DC 76 to 94 48 to 66 18 to 32 1190 7.5 to 9.5

IEC Contactors
200V DC 36 to 45 96 to 132 36 to 64 4970 7.0 to 9.1
24V DC 516 to 630 13 to 17 4 to 7 42.3 12.3 to 15.2
YS3N-40FG2 48V DC 215 to 263 27 to 33 8 to 13 203 10.3 to 12.7
YS3N-50FG2
YS3N-65FG2 100V DC 103 to 127 58 to 69 17 to 27 880 10.2 to 12.8
200V DC 53 to 66 116 to 137 35 to 53 3390 10.4 to 13.3
YS3N-80FG2 100V DC 19 to 24 76 to 84 43 to 54 — —
YS3N-100FG2
YS3N-125FG2 200V DC 11 to 15 133 to 144 86 to 98 — —

Standard Operating Time

Coil Applied Voltage 100%Uc


Part Number Closing Time (ms) Opening Time (ms)
Main Aux. (NO) Aux. (NC) Main Aux. (NO) Aux. (NC)
YS3N-9F 1NO 38 to 45 38 to 45 — 5 to 10 5 to 10 —
YS3N-12F 1NC 38 to 45 — 38 to 45 6 to 12 — 8 to 13
YS3N-20FG2, -25FG2 45 to 53 45 to 53 36 to 46 6 to 12 6 to 12 10 to 16
YS3N-32FG2, -38FG2 59 to 68 57 to 66 46 to 56 7 to 19 7 to 19 14 to 23
YS3N-40FG2, -50FG2, -65FG2 46 to 56 46 to 56 34 to 47 23 to 32 23 to 32 27 to 36
YS3N-80FG2, -100FG2, -125FG2 32 to 42 32 to 42 24 to 36 36 to 56 36 to 56 42 to 62

Operating Limited Distances

Rated Operational Voltage 100VDC Rated Operational Voltage 200VDC


Coil Applied Voltage 100VDC Coil Applied Voltage 200VDC
Part Number
Wire Sectional Area Wire Sectional Area
1.25mm2 2mm2 3.5mm2 1.25mm2 2mm2 3.5mm2
YS3N-9FG2, -12FG2 3.2 km 5.0 km 9.2 km 12.6 km 19.7 km 36.4 km
YS3N-20FG2, -25FG2 3.2 km 5.0 km 9.2 km 12.6 km 19.7 km 36.4 km
YS3N-32FG2, -38FG2 2.1 km 3.4 km 6.3 km 9.1 km 14.3 km 26.3 km
YS3N-40FG2, -50FG2, -65FG2 1.6 km 2.5 km 4.6 km 6.2 km 9.7 km 18.0 km
YS3N-80FG2, -100FG2, -125FG2 0.136 km 0.213 km 0.392 km 0.507 km 0.794 km 1.46 km

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-19
Specifications IEC Contactors
Electrical Life Curves

■ Electrical Life Curves


Fig.1 Utilization Category AC3

YS1N-38F,-40F

YS1N-100F
YS1N-125F
YS1N-150F

YS1N-180F
YS1N-220F

YS1N-300F
Millions

YS1N-12F

YS1N-20F

YS1N-50F

YS1N-65F

YS1N-80F
YS1N-9F
of Operating
Cycles
AC3 Ue < 440V
10

5
4
3

D 1

YS1N-25F
YS1N-32F
0.5
IEC Contactors

0.4
0.3

0.2
1 2 3 4 5 10 20 30 40 50 100 150 200 300 400 500 1000
9 12 18 25 65 105 125 180 209
Breaking current Ic (A) 250
0.55 0.75 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45 55 65 90 140 220 280
220V
0.55 0.75 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 55 75 110 160 200 250 450
380V
0.55 0.75 1.5 2.2 4 5.5 7.5 11 15 18.522 30 37 55 75 90 132 200 280 425
440V
Power rating in kW - 50 Hz category AC3

Control of three-phase squirrel cage motors switching off during running


The breaking current in AC3, Ic, is equal to Ie. (le= rated operational current of the motor)

Fig. 2 Utilization Category AC4


YS1N-38F,-40F

YS1N-100F
YS1N-125F
YS1N-150F

YS1N-180F
YS1N-220F

YS1N-300F

Millions
YS1N-12F

YS1N-20F

YS1N-50F
YS1N-65F

YS1N-80F
YS1N-9F

of Operating
Cycles
AC4 380V < Ue ≤440V
1

0.5
0.4
0.3

0.2

0.1

0.05
0.04
0.03
YS1N-25F

YS1N-32F

0.02

0.01
10 20 30 40 50 100 200 300 400 500 1000 2000 3000 4000 5000
51 69 102 132 180 234 360 510 702 882 1454 2850
Breaking current Ic (A) 111 272 588 1020 1998

Control of three-phase squirrel cage motors switching off with locked rotor
The breaking current in AC4, Ic, is equal to 6 x Ie. (Ie = rated operational current of the motor)

D-20 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Fig. 3 Utilization Category AC1

YS1N-38F,-40F

YS1N-100F
YS1N-125F
YS1N-150F

YS1N-180F
YS1N-220F

YS1N-300F
Millions

YS1N-12F

YS1N-20F

YS1N-50F

YS1N-65F

YS1N-80F
YS1N-9F
of Operating
Cycles
AC1 Ue < 440V
10

YS
5 1N
4 -2
5F
3

0.5
0.4 D
0.3

YS1N-32F

IEC Contactors
0.2

0.1
1 2 3 4 5 10 20 30 40 50 100 150 200 240 300 400 500
260 350
Breaking current Ic (A)

Switching a resistive circuit (cos ø ≥ 0.95)


The breaking current in AC1, Ic, is equal to Ie. (le = rated operational current of the load)

Electrical Life in Mixed AC3/AC4 Duty Applications


By calculation:
In a mixed AC3/AC4 application, electrical life can be calculated using the following formula:
L = A3

1+ P ( A3 -1 )
100 A4 L: Electrical life in mixed AC3/AC4 application
A3: Electrical life for breaking current equal to the rated current of the motor. (AC3 from Fig. 1)
A4: Electrical life for a breaking current during starting or plug braking equal to Ic = Kle, where:
K≤6
Ie = rated motor current
(AC4 from fig. 2)
P/100: ratio of switching off during starting or plug braking

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-21
Specifications IEC Contactors

Operating and Mounting Specifications for Contactors and Starters

1. Operating Specifications
Ambient Temperature -5° to +40°C
Temperature inside the control panel -5°to +55°C
Relative humidity 45% to 85% RH
Altitude No more than 2,000m
Vibration resistance 10 to 50Hz 19.6m/s2 (2G)
Shock resistance 49.0m/s2 (5G)
Storage temperature -40°C to +70°C
D
IEC Contactors

2. Mounting 30° 30°

Direct Mounting
1. Install the product in a dry area with minimal dust and vibration.
2. Standard mounting is done on a vertical surface in the directions shown in Figure 1.
However, a mounting angle up to 30 degrees is allowed in each direction as shown in Fig-
ure 2. Operational characteristics of the product, when mounted with these angles are
listed on the next page.

30°
30°

Figure 1
Figure 2
DIN Rail Mounting
YS Series electromagnetic contactors/starters YS1N/YS2N-9F through -38F models can be mounted on 35mm wide DIN rail, and YS1N/
YS2N -40F through -65F models can be mounted on 75 mm wide DIN rails, as specified in the table below. When mounting the product on
DIN rails, keep in mind the following points:
1. Spacing between the products: contributes to a temperature rise and affects the product life. Maintain the minimum spacing as specified
in the table below
2. DIN rail mounting holes: To ensure sufficient mechanical strength, the mounting holes should be placed no further apart than those spec-
ified in the table below.

Minimum Space Between Contactors (mm)


Product Category Minimum Distance between G
spacing between mounting screws
DIN rail width
contactors (mm) (mm)
Contactor Starter (mm)
(G) (L)
YS1N-9F YS2N-9F 35 5 300
YS1N-12F YS2N-12F 35 5 300 Distance Between Mounting Screws
L L L
YS1N-20F YS2N-20F 35 5 300
YS1N-25F YS2N-25F 35 5 300
YS1N-32F YS2N-32F 35 5 300
YS1N-38F YS2N-38F 35 5 300 Mounting Screw

YS1N-40F YS2N-40F 75 5 300


YS1N-50F YS2N-50F 75 5 300
YS1N-65F YS2N-65F 75 5 300

D-22 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Mounting Angle and Operational Characteristics of the YS1N, YS2N, YS1R, YS2R

Maximum turn-on voltage (V) Minimum turn-off voltage (V)


Contactor /Starter
Non- Reversing
reversing

Coil
Frequency
(Hz)

Standard/ 30° left 30° right 30° tilted 30° tilted Standard/ 30° left 30° right 30° tilted 30° tilted
normal forward backwards normal forward backwards
YS1N/ YS1R/ mounting mounting
YS2N YS2R
50 114 111 110 118 104 84 82 80 82 78
-9F -9F 60 126 123 121 129 120 102 98 95 96 90 D
50 114 111 110 118 104 84 82 80 82 78
-12F -12F 60 126 123 121 129 120 102 98 95 96 90

IEC Contactors
50 122 120 121 124 115 105 102 99 103 101
-20F -20F 60 138 136 138 140 132 119 111 112 118 117
50 122 120 121 124 115 105 102 99 103 101
-25F -25F 60 138 136 138 140 132 119 111 112 118 117
50 114 114 112 124 99 78 77 83 81 78
-32F -32F 60 132 133 130 145 114 95 93 96 96 91
50 114 114 112 124 99 78 77 83 81 78
-38F -38F 60 132 133 130 145 114 95 93 96 96 91
50 114 114 112 124 99 78 77 83 81 78
-40F -40F 60 132 133 130 145 114 95 93 96 96 91
50 116 117 116 131 107 91 88 87 86 84
-50F -50F 60 138 135 137 149 128 110 108 106 106 105
50 116 117 116 131 107 91 88 87 86 84
-65F -65F 60 138 135 137 149 128 110 108 106 106 105
50 132 132 132 137 132 83 83 83 83 83
-80F -80F 60 134 134 134 137 134 82 82 82 82 82
50 132 132 132 137 132 83 83 83 83 83
-100F -100F 60 134 134 134 137 134 82 82 82 82 82
50 132 132 132 137 132 83 83 83 83 83
-125F -125F 60 134 134 134 137 134 82 82 82 82 82

Coils with the following rated voltage were used to obtain the above values:
YS1N-9F to-65F: 200V 50Hz, 200-200V 60Hz
YS1N-80F to-125F: 200-220V 50Hz, 200-220V 60Hz

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-23
Specifications IEC Contactors
Operating and Mounting Specifications for Thermal Overload Relays

Ratings and Characteristics:


Part Number:YS1T-RHA 25F-D 38F-D 65F-D 125F-D 150F-D 180F-D 300F-D 400F-D

Contact Configuration 1NO+1NC

Number of Elements 3

Trip Free Reset Operation Convertible from manual to automatic

Ambient Temperature Compensation -25 to +55°C

Dial Designation Rated current

D Setting Scale Indication Ampere (A)

Operation Position ± 30 with respect to the normal position (See chart on page 65)
IEC Contactors

Tripping Class Conforming to UL 508, EN 60947-4 10

Rated Insulation Voltage (V) 750

Range of Setting Current (A) 0.1-25 7-40 9-65 37-125 65-160 85-185 96-240 128-320
Main Circuit

1 Conductor mm2 0.1-25 5-25 5-25 8-60 8-100 8-100 14-150 14-150
Stranded Wire
without Ferrule 2 Conductors mm2 1.5-10 5-16 5-16 8-22 8-50 8-50 14-80 14-80

1 Conductor mm2 1.5-6 5-25 5-25 - - - - -


Solid Wire
without Ferrule 2 Conductors mm2 1.5-6 5-16 5-16 - - - - -

Characteristics of Auxiliary Contacts:


Rated Thermal Current 4A

Rated Voltage 24V AC 48V AC 110V AC 220V AC 380V AC 600V AC


AC
Rated Operational (AC-15)
Rated Current 4A 4A 3A 2A 1.5A 0.3A
Current
per EN 60947-5-1 Rated Voltage 24V DC 48V DC 110V DC 220V DC
DC
(DC-13)
Rated Current 1A 0.5A 0.25A 0.1A

Stranded Wire without Ferrule 4mm2 (10AWG)


Maximum Cross Section
Solid Wire without Ferrule 4mm2 (10AWG)

Stranded Wire without Ferrule 1mm2 (18AWG)


Minimum Cross Section
Solid Wire without Ferrule 1mm2 (18AWG)

UL / c-UL Ratings of Auxiliary Contacts:


Rated Thermal Current 4A

Rated Voltage 120V AC 240V AC 480V AC 600V AC


AC
(C600) Rated Current 1.5A 0.75A 0.4A 0.3A
Rated Operational Current
per UL 508
Rated Voltage 125V DC 250V DC
DC
(R300)
Rated Current 0.2A 0.1A

D-24 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Fig. 4 Tripping Curves


Tripping Time
(sec.)
10000

5000

Average operating times,


depending on the multi- 2000
ples of the current
1000

500

200

100

50
D
20
1 Balanced operation,

IEC Contactors
10
3-phase, from cold state.

5 2 Balanced operation,
2-phase, from cold state.
1
2
2 3 Balanced operation,
1 3-phase, after a long period
3 of set current flow (hot state).
0.5
1 2 5 10 20
Multiple of Current Setting

Reset Mode Selection and Setting


H HAND AUTO A

A
Function Position AUTO
R HAND
R
H

Tripping Check NO YES YES NO


Reset Hand-Reset Hand-Reset Auto-Reset Auto-Reset
97 95 97 95 97 95
Dotted line indicates the
Contact Condition condition when the reset
button is depressed.
98 96 98 96 98 96
Insert screwdriver into The select button is set Depress the reset but- Insert screwdriver into
the select button, turn in "HAND" position, when ton to below 1 , insert the select button, turn
it clockwise to the "H" shipped from factory. screwdriver into the counter-clockwise to
position. select button, turn the "A" position.
counter-clockwise to
the "AUTO" position 2

Select Button 2
(Red)
Setting Method
Reset Button
(Gray)

Can't check manual trip when Normal position Normal position Can't check manual trip when
Remarks
in Hand-reset condition for Hand-reset for Auto-reset in Auto-reset condition

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-25
Specifications IEC Contactors
Operating Time Characteristics of Thermal Overload Relays

YS1T-RHA38F, YS1T-RHA65F YS1T-RHA25F


1000 1000

500 500

100
Operating Time (In Seconds)

100

Operating Time (In Seconds)


50 50

Load Characteristics Starting Characteristic


Load Characteristics Starting Characteristic
10 10

D 5 5
IEC Contactors

1 1

0.5 0.5

0.1 0.1
100 200 300 400 500 600 700 800 100 200 300 400 500 600 700 800
Current (% of Steady State) Current (% of Steady State)

YS1T-RHA125F YS1T-RHA150F
1000 1000

500 500

100 100
Operating Time (In Seconds)

Operating Time (In Seconds)


Starting Characteristic

Starting Characteristic
50 50

10 10

5 5

Load Characteristics
Load Characteristics

1 1

0.5 0.5

0.1 0.1
100 200 300 400 500 600 700 800 100 200 300 400 500 600 700 800
Current (% of Steady State) Current (% of Steady State)

D-26 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Operating Time Characteristics of Thermal Overload Relays, continued

YS1T-RHA180F YS1T-RHA300F, YS1T-RHA400F


1000 1000

500 500
Operating Time (In Seconds)

100 100

Operating Time (In Seconds)

Starting Characteristics
Starting Characteristics
50 50

10 10

5 5
D
Load Characteristics

Load Characteristics

IEC Contactors
1 1

0.5 0.5

0.1 0.1
100 200 300 400 500 600 700 800 100 200 300 400 500 600 700 800

Current (% of Steady State) Current (% of Steady State)

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-27
Specifications IEC Contactors
Specifications for Accessories

AC Ratings of Auxiliary Contacts


YS1N-9F to -300F
Rated Insulation Voltage (V) 660
Rated Thermal Current (A) 10
AC Ratings per
EN AC Ratings AC 200-2240V 3
Rated Operational Current
(EN-60947-5-1) AC-15 AC 380-480V 1.5
(A)
AC 500-600V 1.2
Rated Insulation Voltage (V) 600
Rated Thermal Current (A) 10

D UL / c-UL AC Ratings
(UL 508)
AC 120V 6

Rated Operational Current AC 240V 3


(NEMA A600)
IEC Contactors

AC 480V 1.5
AC 600V 1.2

Wire Sizes for Auxiliary Contacts


Minimum-Maximum Wire Size YS1N-9F to -300F
mm2 1-4
1 Conductor (AWG) (18-10)
Stranded Wire (without ferrule)
mm2 1-4
2 Conductors (AWG) (18-10)
mm2 1-4
1 Conductor (AWG) (18-10)
Solid Wire (ferrule)
mm2 1-4
2 Conductors (AWG) (18-10)

Instructions for Assembling Auxiliary Contact Blocks:


For each magnetic contactor/starter, up to four contacts of the auxiliary contact blocks can be mounted. Two contacts of the top-mount style and two contacts of
the side mount style can be combined.

YS1A-TAH2 YS1A-TAH4 YS1A-TAH2 YS1A-TAS2 YS1A-TAH2 YS1A-TAH4


YS1A-TAS2 YS1A-TAS2 YS1A-TAS2 YS1A-TAS2
YS1A-TAS2 YS1A-TAS2

Terminal Numbers and Mounting Examples of Auxiliary Contact Blocks, Side-Mount Style

YS1N-9F to -65F YS1R-9F to -65F


Note: If you would like to mount two
side-mount auxiliary contact blocks
B R S T B R S T R S TB (TAS style) to a YS1N non-reversing
F F F contactor, mount YS1A-TAS211F.
@ D @ D D @
A E A E E A
G G G
C U V W C U V W U V W C

D-28 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Mounting and Removing Auxiliary Contact Block on the Contactor

Top Mount Style


1. Position the contactor and the auxiliary contact block in the
same direction.
2. Insert the auxiliary contact block into the area of the top of
the contactor. Slide the auxiliary contact until it bottoms (Do
not force.) Make sure that the locking hook is locked into posi-
tion as shown

Removal Procedure
While lightly lifting the locking hook with your finger, slide the
auxiliary contact unit out.

IEC Contactors
Side-Mount Style
1. Contactor plunger
2. Inside this area, there are locking hooks (upper and lower areas)

DIN rail Mounting


1. Make sure that the auxiliary contact block (right or left side) and the terminal
numbers on the contactor are in the same direction.
2. Push the plunger of the contactor downwards approximately 2mm. While hold-
ing the plunger in this manner, insert the white protruding portion of the auxiliary
contact block into the square groove of the side of the contactor. Make sure that
the locking hook is locked into position.

Removal Procedure
Hold the auxiliary contact block and pull it off.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-29
Specifications IEC Contactors
Surge Suppressor Module

Connection Terminal (M3,5)


6.2 Internal Circuit

4.7
RC Type
Operational Indicator (LED)

34
Varistor

22
Type

26 22

Connection Terminal (M3,5)


6.2 Internal Circuit

47
D
RC Type
Operational Indicator (LED)
44
IEC Contactors

Varistor
32

Type
37 21 3

Figure Surge Suppressor Dimensions

B
Contactor Size
Number Module A B C D E

A
C

E
YS1N-9F 1 YS9Z-TU25 78.5 100 12 76 64
YS1N-12F 1 YS9Z-TU25 78.5 100 12 76 64
YS1N-20F 2 YS9Z-TU25 85 103 12 91 75 Figure 1
D
YS1N-32F 2 YS9Z-TU65 92 128 12 111 75
B
YS1N-38F 2 YS9Z-TU65 92 128 12 111 88
YS1N-50F 2 YS9Z-TU65 114 162 12 121 88
A
C

E
YS1N-65F 2 YS9Z-TU65 114 162 12 121 106
YS1N-80F 2 YS9Z-TU65 191 240 12.4 143.5 106
Figure 2

Mounting Procedure
1. Line up the surge suppressor module and the contactor as shown in the figure on
the right. (Make sure the orientation of the surge suppressor module is such that
the LED is visible.)
2. Insert the U-shaped indentations of the surge suppressor module into the connec-
tion flange of the contactor as shown in the figure on the right.
3. Loosen the contactor screws, insert the fork lugs of the surge suppressor module,
and re-tighten the screw terminals.
Connection indentation,
U-shaped(on both sides
of the surge suppressor
module)
Removal Procedure
1. Loosen coil screw terminals and remove the fork lugs of the surge suppressor module.
Connection flange
2. Insert a screwdriver between the U-shaped indentation of the surge suppressor mod-
ule and the connection flange of the contactor, and pry the module off the contactor.

D-30 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Specifications of Relay Interface Module


YS9Z-TCU500UH
Rated Voltage 24V DC
Maximum Allowable Voltage 130% of rated voltage
Input (coil) Power Consumption 0.2W
Pick-up Voltage (at 20°C) 70% of rated voltage
Drop-out Voltage (at 20°C) 10% of rated voltage
Maximum Operational Voltage 380V AC
Rated Operational Current (at 250V AC) 2A (cosø=0.4)
Output (contact) Thermal Current 5A
Closing Delay 3 ms
Opening Delay 1 ms
Temperature Range -20 to +55°C
D
Maximum Operational Voltage 250V AC

IEC Contactors
Surge Suppressor
Function Resistor capacitor circuit (RC)
Device
Applicable Control Coil Voltage Range Up to 240V AC (50/60 Hz)

Relay Interface Completed Part Numbers


Applicable Completed Part Dimensions
Product Series
Contactor Number W H D
YS1N-9F YS9Z-TCU500UH12 49 125 76
YS1N-12F
YS1N-20F YS9Z-TCU500UH25 49 135 91
YS1N-25F
YS1N-32F YS9Z-TCU500UH38 58 140 111
YS1N-38F
YS1N-40F
Relay Interface YS1N-50F YS9Z-TCU500UH65 75 160 121
Module YS1N-65F
YS9Z-TCU
YS1N-80F
YS1N-100F YS9Z-TCU500UH125 100 187 133
H

YS1N-125F
YS1N-150F YS9Z-TCU500UH180 130 225 158
YS1N-180F
YS1N-220F YS9Z-TCU500UH300 146 260 184 W D
YS1N-300F

NOTES: Each model is identical in electrical characteristics, mounting plate sizes representing the only difference.

 CONNECTION DIAGRAM AND INTERNAL CIRCUIT OF THE RELAY INTERFACE MODULE

b A2

(+) e c

RY MC
E
d a
(–) f A1
R
C

PLC (RELAY INTERFACE MODULE) CONTACTOR

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-31
Specifications IEC Contactors
Mechanical Interlock Blocks
Reversing Contactors
Dimensions
Contactor Size Mechanical Interlock Block
A B C D
YS1R-9F YS9Z-TMI65 78.5 100 12 76
B D
YS1R-12F YS9Z-TMI65 78.5 100 12 76 C
YS1R-20F YS9Z-TMI65 85 103 12 91
YS1R-25F YS9Z-TMI65 85 103 12 91
YS1R-32F YS9Z-TMI65 92 128 12 111

A
YS1R-38F YS9Z-TMI65 92 128 12 111
YS1R-40F YS9Z-TMI65 92 128 12 111
YS1R-50F YS9Z-TMI65 114 162 12 121
YS1R-65F YS9Z-TMI65 114 162 12 121
D YS1R-80F YS9Z-TMI125 191 240 12.4 143.5
YS1R-100F YS9Z-TMI125 191 240 12.4 143.5
IEC Contactors

YS1R-125F YS9Z-TMI125 191 240 12.4 143.5


YS1R-150F YS9Z-TMI125 239 300 12.4 169.5
YS1R-180F YS9Z-TMI125 239 300 12.4 169.5
YS1R-220F YS9Z-TMI125 269 305 12.4 195
YS1R-300F YS9Z-TMI125 269 305 12.4 195

Note: 1. The mounting holes are the same as theYS1 Series.


2. The above figures are not drawn to scale. Refer to the chart for actual dimensions.
3. YS1N-80F~-300F size contactors require an additional mounting base.
Refer to the YS1R-80F through -300F in the dimension chart.

Reversing Starters
Dimensions
Contactor Size Mechanical Interlock Block
A B C D
B D
YS2R-9F YS9Z-TMI65 78.5 100 12 76 C
YS2R-12F YS9Z-TMI65 78.5 100 12 76
YS2R-20F YS9Z-TMI65 85 103 12 91
YS2R-25F YS9Z-TMI65 85 103 12 91
A

YS2R-32F YS9Z-TMI65 92 128 12 111


YS2R-38F YS9Z-TMI65 92 128 12 111
YS2R-40F YS9Z-TMI65 92 128 12 111
YS2R-50F YS9Z-TMI65 114 162 12 121
YS2R-65F YS9Z-TMI65 114 162 12 121
YS2R-80F YS9Z-TMI125 191 240 12.4 143.5
YS2R-100F YS9Z-TMI125 191 240 12.4 143.5
YS2R-125F YS9Z-TMI125 191 240 12.4 143.5
YS2R-150F YS9Z-TMI125 239 300 12.4 169.5
YS2R-180F YS9Z-TMI125 239 300 12.4 169.5
YS2R-220F YS9Z-TMI125 269 305 12.4 195
YS2R-300F YS9Z-TMI125 269 305 12.4 195

Note: 1. The mounting holes are the same as the YS1 Series.
2. The above figures are not drawn to scale. Refer to the chart for actual dimensions.
3. YS1N-80F through 300F contactors require an additional mounting base.
Refer to the YS2R-80F~-300F in the dimension chart.

D-32 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Specifications

Mounting and Removing of Mechanical Interlock Block

Mounting Procedure (YS9Z-TMI65)


1. Position the mechanical interlock block and the contactor in the same direction. (The
name plate of the mechanical interlock block should be in the same direction as the
name plate of the contactor. Mounting base

2. Insert the connection pins of the mechanical interlock block (located on the left and The arrow-shaped
right sides of the mechanical interlock block) into the pin holes of the forward and protrusion of the
reverse contactors (the forward contactor in the right and the reverse contactor in the mechanical interlock
left in the picture). Carefully push the contactors towards the mechanical interlock block goes into this hole
to lock the entire assembly together.

3. Insert the mounting base into the bottom of the mechanical interlock block until it
bottoms. (Make sure that the arrow -shaped protrusion of the mechanical interlock as
far as it will go.

Removal Procedure Mechanical interlock


D
block
1. To remove the mechanical interlock block, insert a screwdriver into the space

IEC Contactors
between the mechanical interlock block and the mounting base.
2. Remove the mounting base from the assembly.
3. Gently pull the forward and reverse contactors apart.

Mounting Procedure (YS9Z-TMI125)


1. Position the mechanical interlock and the contactor in the same direction. (The name Mounting Base
plate of the mechanical interlock should be in the same direction as the name plate of the
contactor.)
2. Insert the connection pin of the mechanical interlock into the connection pin hole
located on the right side of the forward contactor. The 7 - shaped hook of the mechanical
interlock reaches the contactor. Position the 7 - shaped hook of the mechanical interlock
to match the ribbed area of the contactor and press the mechanical interlock block (Forward) (Reverse)
towards the forward contactor.
Contactor Contactor
3. For the reverse contactor, follow the same procedure above, but insert the connection
pin of the mechanical interlock block into the pin hole located on the left side of the
reverse contactor. (Note: The mounting order of the forward or the reverse contactor does
not make a difference in the assembly procedure.)

4. After the mechanical interlock block is installed to both contactors, mount the contac-
tors to the mounting base with the screws (4 screws for each contactor, total of 8 screws.) Mechanical Interlock Block
Make sure that the mechanical interlock block is completely locked to the contactors.
Please note that there can be operational problems if the mechanical interlock and the
contactors are not properly locked into position.

Removal Procedure
7-shaped hook
1. Insert a screwdriver into the 7-shaped hook area between either contactor and the
mechanical interlock and pry out the mechanical interlock.

Connection pin hole

Connection pin

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-33
Specifications IEC Contactors
Connector Kits for Reversing Contactors and Starters
Used as connectors on reversing contactors (YS1R series) and reversing starters (YS2R series).

A1 A1 A1 A1
1 3 5 1 3 5 1 3 5 1 3 5
2 4 6 2 4 6 2 4 6 2 4 6
A2 A2 A2 A2

D Power Wiring Kits for Reversing Contactors


Applicable Reversing
Part Number Connections Description Size
IEC Contactors

Contactors
F:L1-R:L1
F:L2-R:L2 UL1015
F:L3-R:L3 YS1R-9F
YS9Z-KIF411344-A Solid Wire AWG 14
F:T1-R:T3 YS1R-12F
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2
F:L3-R:L3 UL1015 YS1R-20F
YS9Z-KIF411345-A AWG 10
F:T1-R:T3 Stranded Wire YS1R-25F
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2
F:L3-R:L3 UL1283 YS1R-32F
YS9Z-KIF411346-A AWG 8
F:T1-R:T3 Stranded Wire YS1R-38F
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2 YS1R-40F
F:L3-R:L3 Copper Bar
YS9Z-KIF411347-A AWG 6 YS1R-50F
F:T1-R:T3 Solid Bar YS1R-65F
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2
F:L3-R:L3 Copper Bar YS1R-80F
YS9Z-KIF411348-A Solid Bar 1.6 X11 YS1R-100F
F:T1-R:T3 YS1R-125F
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2 Copper Bar
F:L3-R:L3
YS9Z-KIF411388-A Solid Bar 3 X16 YS1R-150F
F:T1-R:T3
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2 Copper Bar
F:L3-R:L3
YS9Z-KIF411388-B Solid Bar 3 X20 YS1R-180F
F:T1-R:T3
F:T2-R:T2
F:T3-R:T1
F:L1-R:L1
F:L2-R:L2 Copper Bar
F:L3-R:L3 YS1R-220F
YS9Z-KIF411590-A Solid Bar 3.5X25
F:T1-R:T3 YS1R-300F
F:T2-R:T2
F:T3-R:T1

D-34 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Dimensions

Non-Reversing AC Contactors

All Dimensions in mm.

 Non-Reversing Contactors
 YS1N-9F, YS1N-12F  YS1N-40F, YS1N-50F, YS1N-65F
8 76 9 121

(YS9Z-TU25)

(YS9Z-TU65)
89
78.5

119.5
114
D
12 44 12 110

IEC Contactors
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH)

12 75 12 154
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH)

 YS1N-20F, YS1N-25F  YS1N-80F, YS1N-100F, YS1N-125F

8 91
(YS9Z-TU25)

141
97
85

12 45.5 12 124
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH) 100 30 133

 YS1N-32F, YS1N-38F  YS1N-150F 158

9 111
(YS9Z-TU65)

180
101.5
92

12 58 12 143.5
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH)
130 188

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-35
Dimensions IEC Contactors

 Non-Reversing Contactors
 YS1N-180F  YS1N-220F, YS1N-300F

158 184

180

210
D 130 188
146 234
IEC Contactors

Non-Reversing DC Contactors
 Non-Reversing Contactors DC Operated
 YS3N -9FG2, YS3N -12FG2  YS3N -80FG, YS3N -100FG, YS3N -125FG

8 107.5

141
81.4

44
100 30 133

 YS3N -20FG2, YS3N -25FG2  YS3N -32FG2, YS3N -38FG2

9 138
8 118.5
86.5

92

45.5 58

 YS3N -40FG2, YS3N -50FG2, YS3N-65FG2

9 160
114

75

D-36 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Dimensions

Non-Reversing AC Starters

 Non-Reversing Starters
 YS2N-9F, YS2N-12F  YS2N-40F, YS2N-50F, YS2N-65F

75 121
44 76

128

168
D

IEC Contactors
45 90.5

56 105

 YS2N-80F, YS2N-100F, YS2N-125F


 YS2N-20F, YS2N-25F
100 133
45.5 91
133.5

224
45 92.5

100 117

 YS2N-32F, YS2N-38F  YS2N-150F


58 111 130 158
259.5
150

56 106 100 122

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-37
Dimensions IEC Contactors

 Non-Reversing Starters
 YS2N-180F  YS2N-220F, YS2N-300F
130 158
191.5

294.5

315
D
IEC Contactors

100 122
250

D-38 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Dimensions

Reversing AC Contactors

 Reversing Contactors
 YS1R-9F, YS1R-12F 8 76  YS1R-20F, HCA-25F 8 91

(YS9Z-TU25)

(YS9Z-TU25)
78.5
89

97
85
12 100 12 110
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH)
12
(YS1A-TAS)
103 12
(YS1A-TAS)
124
(YS1A-TAH)
D

IEC Contactors
 YS1R-32F, YS1R-38F
9 111

(YS9Z-TU65)
101.5
92

12 128 12 143.5
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH)

 YS1R-40F, YS1R-50F, YS1R-65F


9 121
(YS9Z-TU65)
119.5
114

12 162 12 154
(YS1A-TAS) (YS1A-TAS) (YS1A-TAH)

 YS1R-80F, YS1R-100F, YS1R-125F


191

240 30 143.5

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-39
Dimensions IEC Contactors

 Reversing Contactors
 YS1R-150F  YS1R-180F
169.5 169.5

239

239
300 200
D 300 200
IEC Contactors

 YS1R-220F, YS1R-300F

195
269

305 225

D-40 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Dimensions

Reversing AC Starters

 Reversing Starters
 YS2R-9F, YS2R-12F  YS2R-32F, YS2R-38F
100.5 76 128 111

128

150
D
45 90.5

IEC Contactors
56 106

 YS2R-20F, YS2R-25F  YS2R-40F, YS2R-50F, YS2R-65F


103 91
162 121
133.5

168
45 92.5

56 105

 YS2R-80F, YS2R-100F, YS2R-125F


240 143.5
250

100 127.5

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-41
Dimensions IEC Contactors

 Reversing Starters
 YS2R-150F  YS2R-180F
169.5
169.5
297.5

332.5
D 100
300
133.5
100
300 133.5
IEC Contactors

 YS2R-220F, YS2R-300F
195
373

347

D-42 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Mounting/Wiring

Non-Reversing AC Contactors

Mounting, Screw Mounting, and Rail Mounting


 Non-Reversing Contactors
 YS1N, YS1N-12F  YS1N-40F, YS1N-50F, YS1N-65F

2-4.8 DIA. 2-4.8 DIA.


MTG HOLES(M4) MTG HOLES(M4)
2-4.8 DIA. 2-4.8 DIA.
15.5 MTG HOLES(M4) DIN RAIL 75mm
MTG HOLES(M4) DIN RAIL 35mm

6
A B
48
50
52

100
95
D
5 34 4.5

IEC Contactors
35 B A

5 65 7

 YS1N-20F, YS1N-25F  YS1N-80F, YS1N-100F, YS1N-125F


4-6 DIA.
2-4.8 DIA. MTG HOLES(M5)
MTG HOLES(M4)
DIN RAIL 35mm
19
5
70
75

110

5.2 35 4.5

80
7 86

 YS1N-32F, YS1N-38F  YS1N-150F

2-4.8 DIA. 4-M6 MTG HOLES


15 100
2-4.8 DIA. MTG HOLES(M4)
MTG HOLES(M4) DIN RAIL 35mm
10.5

25
70
75

125
130

4 50 4.5

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-43
Mounting/Wiring IEC Contactors
Mounting, Screw Mounting, and Rail Mounting, continued

 Non-Reversing Contactors
 YS1N-180F  YS1N-220F, YS1N-300F

4-M6 MTG HOLES


15 100 4-M6 MTG HOLES
50.5 45

10
25
125
130

190
D
 Non-Reversing Contactors, DC Operated
Non-Reversing DC Contactors
IEC Contactors

 YS3N-9FG2, -12FG2  YS3N-80FG, YS3N-100FG, YS3N-125FG


4-6 DIA.
2-4.8 DIA. MTG HOLES(M5)
MTG HOLES(M4)
2-4.8 DIA.

19
MTG HOLES(M4) DIN Rail 35mm

110
48
50
52

34 4.5 80
35 7 86

 YS3N-20FG2, YS3N-25FG2
 YS3N-32FG2, YS3N-38FG2
2-4.8 DIA.
MTG HOLES(M4)
DIN Rail 35mm 2-4.8 DIA. DIN Rail 35mm
MTG HOLES(M4) 2-4.8 DIA.
MTG HOLES(M4)
70
75

70
75

35 4.5
50 4.5

 YS3N-40FG2, YS3N-50FG2, YS3N-65FG2


2-4.8 DIA.
MTG HOLES(M4)
2-4.8 DIA.
MTG HOLES(M4) DIN Rail 75mm

A B
100
95

B A

65 7

D-44 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Mounting/Wiring

Reversing AC Contactors

Mounting, Screw Mounting, and Rail Mounting


 Reversing Contactors
 YS1R-9F, YS1R-12F  YS1R-32F, YS1R-38F
4-4.8 DIA. 4-4.8 DIA. 4-4.8 DIA.
MTG HOLES(M4) MTG HOLES(M4) MTG HOLES(M4)
4-4.8 DIA.
35 21 35

15.5
DIN RAIL 35mm MTG HOLES(M4) DIN RAIL 35mm

10.5
48
50
52

70
75
5 34 22 34 4.5 D
4 50 20 50 4.5

IEC Contactors
 YS1R-20F, YS1R-25F
4-4.8 DIA.
MTG HOLES(M4)
DIN RAIL 35mm
5
70
75

5.2 35 22.5 35 4.5

 YS1R-40F, YS1R-50F, YS1R-65F


4-4.8 DIA. 4-4.8 DIA.
MTG HOLES(M4) MTG HOLES(M4) DIN RAIL 75mm
6

A B A B
100
95

B A B A

5 65 22 65 7

 YS1R-80F, YS1R-100F, YS1R-125F


4-7 DIA. MTG HOLES(M6)
7
10.5
8

10
175

10 220

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-45
Mounting/Wiring IEC Contactors
Mounting, Screw Mounting, and Rail Mounting, continued

 Reversing Contactors
 YS1R-150F  YS1R-180F
4-M8 MTG HOLES
10 4-M8 MTG HOLES

15
10

15
20 20

221

221
8
8

15 270 15 270

D
IEC Contactors

 YS1R-220F, YS1R-300F

4-M8 MTG HOLES


10
15

30
251
8

15 275

D-46 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Mounting/Wiring

Non-Reversing and Reversing Contactors

Wiring Diagrams

n Non-Reversing Contactors
l YS1N-9F, YS1N-12F (1NO) l YS1N-9F, YS1N-12F (1NC)
L1 L2 L3 NO L1 L2 L3 NC
A1 1 3 5 13 A1 1 3 5 21

A2 2 4 6 14 A2 2 4 6 22
T1 T2 T3 NO T1 T2 T3 NC

l YS1N-20F, YS1N-25F, YS1N-32F, YS1N-38F l YS1N-80F, YS1N-100F, YS1N-125F, YS1N-150F, YS1N-180F


YS1N-40F, YS1N-50F, YS1N-65F YS1N-220F, YS1N-300F
L1 L2 L3 NO NC L1 L2 L3 NO NC NC NO
A1 1 3 5 13 21 A1 1 3 5 13 21 31 43
D
A2 2 4 6 14 22 A2 2 4 6 14 22 32 44

IEC Contactors
T1 T2 T3 NO NC T1 T2 T3 NO NC NC NO

n Reversing Contactors
l YS1R-9F, YS1R-12F (1NOX2) l YS1R-9F, YS1R-12F (1NCX2)
L1 L2 L3 L1 L2 L3

A1 NO NO A1 A1 NC NC A1
1 3 5 13 1 3 5 14 1 3 5 21 1 3 5 21

2 4 6 14 2 4 6 13 2 4 6 22 2 4 6 22
A2 NO NO A2 A2 NC NC A2

T1 T2 T3 T1 T2 T3

l YS1R-20F, YS1R-25F, YS1R-32F, YS1R-38F, YS1R-40F, YS1R-50F, YS1R-65F


L1 L2 L3

A1 NO NC NO NC A1
1 3 5 13 21 1 3 5 13 21

2 4 6 14 22 2 4 6 14 22
A2 NO NC NO NC A2

T1 T2 T3

l YS1R-80F, YS1R-100F, YS1R-125F, YS1R-150F, YS1R-180F, YS1R-220F, YS1R-300F


L1 L2 L3

A1 NO NC NC NO NO NC NC NO A1
1 3 5 13 21 31 43 1 3 5 13 21 31 43

2 4 6 14 22 32 44 2 4 6 14 22 32 44
A2 NO NC NC NO NO NC NC NO A2

T1 T2 T3

n Non-Reversing Contactors DC Operated

l YS3N-9FG2, YS3N-12FG2 (1NO) l YS3N-9FG2, YS3N-12FG2 (1NC)


L1 L2 L3 NO L1 L2 L3 NC
A1 1 3 5 13 A1 1 3 5 21

A2 2 4 6 14 A2 2 4 6 22
T1 T2 T3 NO T1 T2 T3 NC

l YS3N-20FG2, YS3N-25FG2, YS3N-32G2F l YS3N-80FG, YS3N-100FG, YS3N-125FG


l YS3N-38FG2, YS3N-40FG2, YS3N-50FG2, YS3N-65FG2
L1 L2 L3 NO NC L1 L2 L3 NO NC NC NO
A1 1 3 5 13 21 A1 1 3 5 13 21 31 43

A2 2 4 6 14 22 A2 2 4 6 14 22 32 44
T1 T2 T3 NO NC T1 T2 T3 NO NC NC NO

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-47
Mounting/Wiring IEC Contactors
Non-Reversing and Reversing Starters

Wiring Diagrams

 Non-Reversing Starters  Reversing Starters


 YS2N-9FD, YS2N-12FD  YS2R-9FD, YS2R-12FD
(1NO) (1NC) (1NO) (1NC)
L1 L2 L3 L1 L2 L3
A1 1 L1 3 L2 5 L3 13 A1 1 L1 3 L2 5 L3 21
A1 A1 A1 A1
1 3 5 13 1 3 5 14 1 3 5 21 1 3 5 21
2 4 6 2 4 6
A2 14 A2 22 2 4 6 14 2 4 6 13 2 4 6 22 2 4 6 22
97 95 97 95 A2 A2 A2 A2
1 3 5 1 3 5
97 95 97 95
1 3 5 1 3 5
2 T1 4 T2 6 T3 98 96 2 T1 4 T2 6 T3 98 96

2 T1 4 T2 6 T3 98 96 2 T1 4 T2 6 T3 98 96
D  YS2N-20FD, YS2N-25FD, YS2N-32FD,
YS2N-38FD, YS2N-40FD, YS2N-50FD,  YS2R-20FD, YS2R-25FD, YS2R-32FD, YS2R-38FD,
YS2N-65FD YS2R-40FD, YS2R-50FD, YS2R-65FD
IEC Contactors

A1 1 L1 3 L2 5 L3 13 21 L1 L2 L3
A1 NO NC NO NC A1
2 4 6 1 3 5 13 21 1 3 5 13 21
A2 14 22
1 3 5 97 95
2 4 6 14 22 2 4 6 14 22
A2 NO NC NO NC A2
97 95
2 T1 4 T2 6 T3 98 96 1 3 5

 YS2N-80FD, YS2N-100FD, YS2N-125FD,


YS2N-150FD, YS2N-180FD 2 T1 4 T2 6 T3 98 96
A1 1 L1 3 L2 5 L3 13 21 31 43
 YS2R-80FD, YS2R-100FD, YS2R-125FD, YS2R-150FD,
2 4 6 YS2R-180FD
A2 14 22 32 44
97 95 L1 L2 L3
1 3 5
A1 NO NC NC NO NO NC NC NO A1
1 3 5 13 21 31 43 1 3 5 13 21 31 43

2 T1 4 T2 6 T3 98 96 2 4 6 14 22 32 44 2 4 6 14 22 32 44
A2 NO NC NC NO NO NC NC NO A2

 YS2N-220FD, YS2N-300FD 1 3 5
97 95

A1 1 L1 3 L2 5 L3 13 21 31 43

2 T1 4 T2 6 T3 98 96
2 4 6
A2 14 22 32 44
 YS2R-220FD, YS2R-300FD
1 3 5 97 95 L1 L2 L3
A1 NO NC NC NO NO NC NC NO A1
1 3 5 13 21 31 43 1 3 5 13 21 31 43
2 4 6 98 96
2 4 6 14 22 32 44 2 4 6 14 22 32 44
A2 NO NC NC NO NO NC NC NO A2

 Thermal Overload Relays 97 95


1 3 5

 YS1T-RHA F D
2 4 6
1 L1 3 L2 5 L3 98 96
97 95

2 T1 4 T2 6 T3 98 96

D-48 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Mounting/Wiring

Auxiliary Contact Blocks

Wiring Diagrams

 Auxiliary Contact Blocks


 YS1A-TAH404F  YS1A-TAH413F  YS1A-TAH422F  YS1A-TAH431F  YS1A-TAH440F
4NC 1NO+3NC 2NO+2NC 3NO+1NC 4NO
NO NC NC NC NO NC NC NC NO NC NC NO NO NC NO NO NO NO NO NO
51 61 71 81 53 61 71 81 53 61 71 83 53 61 73 83 53 63 73 83

52 62 72 82 54 62 72 82 54 62 72 84 54 62 74 84 54 64 74 84
NO NC NC NC NO NC NC NC NO NC NC NO NO NC NO NO NO NO NO NO

IEC Contactors
 YS1A-TAH202F  YS1A-TAH211F  YS1A-TAH220F
2NC 1NO+1NC 2NO
NC NC NO NC NO NO
51 61 53 61 53 63

52 62 54 62 54 64
NC NC NO NC NO NO

 YS1A-TAS211F
1NO+1NC
NO NC
53 61

54 62
NO NC

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-49
Mounting/Wiring IEC Contactors
Appendix

STANDARDIZED UTILIZATION CATEGORIES [Excerpt from EN60947]

■ Class of AC Magnetic Contactors

Contactors
Typical applications Conditions of making and breaking cor- Conditions of making and breaking cor-
for AC switching responding to normal operation (dura- responding to occasional operation

Category Making Breaking Making Breaking


I U cos I U cos I U cos I U cos
D Resistive,
non-inductive or AC1 Ie Ue 0.95 Ie Ue 0.95 1.5Ie 1.05Ue 0.8 1.5Ie 1.05Ue 0.8
IEC Contactors

slightly inductive

Slip-ring motors AC2 2.5Ie Ue 0.65 2.5Ie Ue 0.65 4Ie 1.05Ue 0.65 4Ie 1.05Ue 0.65
Starting, switching

Squirrel cage motors


Starting, switching AC3 6Ie Ue (1) Ie 0.17Ue (1) 10Ie 1.05Ue (2) 8Ie 1.05Ue (2)
off

Squirrel cage motors


Starting, plugging AC4 6Ie Ue (1) 6Ie Ue (1) 12Ie 1.05Ue (2) 10Ie 1.05Ue (2)
inching (jogging)

Notes : (1) cos = 0.65 for Ie ≤17A cos = 0.35 for Ie > 17A
(2) cos = 0.45 for Ie ≤ 100A cos = 0.35 for Ie > 100A

■ Class of Auxiliary Contacts

Auxiliary Contacts
Typical applications Conditions of making and breaking cor- Conditions of making and breaking cor-
for AC switching responding to normal operation (dura- responding to occasional operation

Category Making Breaking Making Breaking


I U cos I U cos I U cos I U cos

Control of electromagnets
< 72 VA sealed
AC14 6Ie Ue 0.3 Ie Ue 0.3 6Ie 1.1Ue 0.7 6Ie 1.1Ue 0.7
> 72 VA sealed AC15 10Ie Ue 0.3 Ie Ue 0.3 10Ie 1.1Ue 0.3 10Ie 1.1Ue 0.3

D-50 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Application Tables

Application Tables

AC 1 Ratings:
(International Applications)
Non-inductive or slightly inductive loads, resistance furnaces:
Power Ratings of Three-Phase Motors (50/60Hz) Maximum
Instantaneous
Operational
Category AC1 Auxiliary
Current
(Star Connection) Contacts Completed Part Number
AC1

220V 380V 660V


415V 440V 500V θ<55ºC NO NC
230V 400V 690V
D
kW kW kW kW kW kW A

IEC Contactors
7.5 13 14 15 17 23 20 0 1 YS1N-9F01 * * * *

7.5 13 14 15 17 23 20 1 0 YS1N-9F10 * * * *

7.5 13 14 15 17 23 20 0 1 YS1N-12F01 * * * *

7.5 13 14 15 17 23 20 1 0 YS1N-12F10 * * * *

11 20 21 23 26 34 30 1 1 YS1N-20F11 * * * *

11 20 21 23 26 34 30 1 1 YS1N-25F11 * * * *

19 32 35 38 43 57 50 1 1 YS1N-32F11 * * * *

23 40 43 45 52 68 60 1 1 YS1N-38F11 * * * *

23 40 43 45 52 68 60 1 1 YS1N-40F11 * * * *

30 52 57 61 69 91 80 1 1 YS1N-50F11 * * * *

30 52 57 61 69 91 80 1 1 YS1N-65F11 * * * *

51 88 97 102 116 154 135 2 2 YS1N-80F22 * * * *

57 98 107 114 129 171 150 2 2 YS1N-100F22 * * * *

57 98 107 114 129 171 150 2 2 YS1N-125F22 * * * *

76 132 144 152 173 229 200 2 2 YS1N-150F22 * * * *

91 158 173 183 208 274 240 2 2 YS1N-180F22 * * * *

99 171 187 198 225 297 260 2 2 YS1N-220F22 * * * *

133 230 252 267 303 400 350 2 2 YS1N-300F22 * * * *

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-51
Application Tables IEC Contactors

AC2 Ratings: Slip-ring motors; starting, switching off running motors


(International Applications)
AC4 Ratings: Squirrel-cage motors; starting, plugging, inching
Power Ratings of Three-Phase Motors (50/60Hz) Instantaneous
Auxiliary
Category AC2 or AC4 Contacts Completed Part Number
220V 380V 660V
415V 440V 500V NO NC
230V 400V 690V

kW kW kW kW kW kW

D 2.2 4 4 4 5.5 5.5 0 1 YS1N-9F01 * * * *

2.2 4 4 4 5.5 5.5 1 0 YS1N-9F10 * * * *


IEC Contactors

3 5.5 5.5 5.5 5.5 7.5 0 1 YS1N-12F01 * * * *

3 5.5 5.5 5.5 5.5 7.5 1 0 YS1N-12F10 * * * *

4 7.5 9 9 9 9 1 1 YS1N-20F11 * * * *

5.5 9 9 9 10 10 1 1 YS1N-25F11 * * * *

7.5 11 11 11 15 15 1 1 YS1N-32F11 * * * *

11 15 15 15 15 18.5 1 1 YS1N-38F11 * * * *

11 15 15 15 15 18.5 1 1 YS1N-40F11 * * * *

15 18.5 18.5 22 22 22 1 1 YS1N-50F11 * * * *

18.5 22 22 30 25 25 1 1 YS1N-65F11 * * * *

22 30 33 33 37 33 2 2 YS1N-80F22 * * * *

30 45 45 45 45 45 2 2 YS1N-100F22 * * * *

37 51 51 51 51 51 2 2 YS1N-125F22 * * * *

45 63 63 63 63 63 2 2 YS1N-150F22 * * * *

55 80 80 80 80 75 2 2 YS1N-180F22 * * * *

65 90 90 90 90 90 2 2 YS1N-220F22 * * * *

90 129 129 129 110 140 2 2 YS1N-300F22 * * * *

D-52 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Application Tables

AC3 Ratings:
(International Applications)
Squirrel-cage motors—starting & switching off running motors:
Maximum Instantaneous
Power Ratings for Three - Phase Motors 50/60Hz Category AC3 Completed Part
Operational Auxiliary
—for ambient air temperature around contactor 55° C Number
Current Contacts

220V 380V 660V AC3 Duty


415V 440V 500V NO NC
230V 400V 690V 380-440V

kW/HP kW/HP kW/HP kW/HP kW/HP kW/HP A


D
2.2/3 4/5.5 4/5.5 4/5.5 5.5/7.5 5.5/7.5 8.5 0 1 YS1N-9F01 * * * *

IEC Contactors
2.2/3 4/5.5 4/5.5 4/5.5 5.5/7.5 5.5/7.5 8.5 1 0 YS1N-9F10 * * * *

3/4 5.5/7.5 5.5/7.5 5.5/7.5 7.5/10 7.5/10 11.5 0 1 YS1N-12F01 * * * *

3/4 5.5/7.5 5.5/7.5 5.5/7.5 7.5/10 7.5/10 11.5 1 0 YS1N-12F10 * * * *

4/5.5 7.5/10 9/12 9/12 10/13.5 10/13.5 15.5 1 1 YS1N-20F11 * * * *

5.5/7.5 11/15 11/15 11/15 15/20 15/20 22 1 1 YS1N-25F11 * * * *

7.5/10 15/20 15/20 15/20 18.5/25 18.5/25 30 1 1 YS1N-32F11 * * * *

11/15 18.5/25 22/30 22/30 22/30 30/40 37 1 1 YS1N-38F11 * * * *

11/15 18.5/25 22/30 22/30 22/30 30/40 37 1 1 YS1N-40F11 * * * *

15/20 22/30 25/35 30/40 30/40 33/44 44 1 1 YS1N-50F11 * * * *

18.5/25 30/40 37/50 37/50 37/50 37/50 60 1 1 YS1N-65F11 * * * *

22/30 45/54 45/60 45/60 55/75 45/60 85 2 2 YS1N-80F22 * * * *

30/40 55/75 55/75 60/80 65/87 65/87 105 2 2 YS1N-100F22 * * * *

37/50 60/80 63/85 63/85 75/100 75/100 114 2 2 YS1N-125F22 * * * *

45/60 75/100 80/110 80/110 90/125 100/136 138 2 2 YS1N-150F22 * * * *

55/75 95/130 100/136 110/150 110/150 110/150 179 2 2 YS1N-180F22 * * * *

65/87 110/150 110/150 110/150 132/180 132/180 205 2 2 YS1N-220F22 * * * *

90/125 160/220 160/220 160/220 160/220 200/270 300 2 2 YS1N-300F22 * * * *

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-53
Application Tables IEC Contactors
DC Loads:
DC1, DC14 L/R=1ms DC2, DC4 L/R=15ms DC11 L/R=100ms No. of Series
Part No.
Resistance Load (A) DC Motor Load (A) Inductive Load (A) Connection
48V 110V 220V 48V 110V 220V 48V 110V 220V
12 10 1 3 1.5 0.25 1 0.7 0.8 1
12 10 6 6 4 1.2 5 3 0.6 2 YS1N-9F##****
12 12 12 40 8 4 8 4 1.5 3
13 10 1 3 1.5 0.25 1 0.7 0.2 1
13 10 6 6 4 1.2 5 3 0.6 2 YS1N-12F##****
13 13 13 13 8 4 8 4 1.5 3
13 10 1 3 2 0.25 1 0.7 0.25 1
13 10 6 6 4 1.2 5 3 0.6 2 YS1N-20F11****
13 13 13 13 8 4 8 4 1.5 3
15 12 1.5 8 2 0.4 3 1.2 0.3 1
20 15 10 15 8 2 12 5 1.2 2 YS1N-25F11****
D 20 20 15 20 15 8 15 10 2 3
26 15 2 10 3 0.4 3 1.2 0.4 1
IEC Contactors

26 26 15 20 10 3 20 5 1.5 2 YS1N-32F11****
26 26 26 25 20 10 20 15 2 3
30 15 2 10 3 0.4 5 1.5 0.4 1
30 30 20 30 15 3 20 5 1.5 2 YS1N-38F11****
35 35 30 35 20 10 25 15 2 3
30 15 2 10 3 0.4 5 1.5 0.4 1
30 30 20 30 15 3 20 5 1.5 2 YS1N-40F11****
35 35 30 35 20 10 25 15 2 3
30 15 2 15 3 0.4 5 1.5 0.4 1
50 35 20 35 15 3 20 5 1.5 2 YS1N-50F11****
50 50 35 40 20 10 25 15 2 3
50 30 2 20 4 0.4 5 1.5 0.4 1
65 50 20 40 25 3 20 5 1.5 2 YS1N-65F11****
65 65 50 50 30 20 25 15 2 3
65 35 3 30 4 0.5 — — — 1
80 65 30 65 40 4 — — — 2 YS1N-80F11****
80 80 65 65 65 30 — — — 3
80 35 3 30 4 0.5 — — — 1
93 80 40 80 50 4 — — — 2 YS1N-100F11****
93 93 80 80 65 40 — — — 3
80 35 3 30 4 0.5 — — — 1
100 100 50 85 50 4 — — — 2 YS1N-125F11****
125 125 100 100 65 50 — — — 3
125 35 4 50 5 0.5 — — — 1
125 100 65 125 80 5 — — — 2 YS1N-150F11****
150 150 125 150 100 65 — — — 3
125 35 4 50 5 0.5 — — — 1
150 125 80 125 80 5 — — — 2 YS1N-180F11****
180 180 150 180 100 80 — — — 3

1 Series Connection 2 Series Connection 3 Series Connection


+V DC -V DC +V DC +V DC -V DC

L1 L1 T3 L1 L2 T3
LOAD
LOAD

LOAD

T1 T1 L3 T1 T2 L3

-V DC

D-54 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Application Tables

Application to Star (Wye)-Delta Motor Starters


3-Phase Motor Power Rating
Type of Magnetic Contactors Type of Overload Relay
Voltage (V) Capacity Current
Frequency (Hz) (kW) (HP) (A) Main Star Delta Part Number
3.7 5 17.5 YS-9F YS-9F YS-9F RHA-25F/15DP
5.5 7.5 26 YS-9F YS-9F YS-9F RHA-25F/21DP
7.5 10 34 YS-9F YS-9F YS-20F RHA-65F/25D + TIB-65F
11 15 48 YS-20F YS-9F YS-25F RHA-65F/43D + TIB-65F
15 20 65 YS-32F YS-20F YS-32F RHA-65F/56D + TIB-65F
18.5 25 79 YS-32F YS-20F YS-38F RHA-125F/68DP
22 30 93 YS-32F YS-32F YS-50F RHA-125F/80DP
200-240V
30 40 125 YS-50F YS-32F YS-65F RHA-125F/105DP

50/60 Hz
37
45
50
60
148
180
YS-50F
YS-80F
YS-32F
YS-50F
YS-80F
YS-100F
RHA-150F/135DP
RHA-180F/155DP
D
55 75 220 YS-125F YS-50 YS-100F RHA-300F/180D (with CT)

IEC Contactors
75 100 300 YS-180F YS-80F YS-150F RHA-400F/240D (with CT)
90 125 360 YS-220F YS-80F YS-180F RHA-500F/300D (with CT)
110 150 440 YS-300F YS-80F YS-220F RHA-500F/300D (with CT)
132 175 528 YS-300F YS-80F YS-300F RHA-750F/450D (with CT)
160 215 640 YS-400F YS-150F YS-300F RHA-750F/450D (with CT)
3.7 5 8.7 YS-9F YS-9F YS-9F RHA-25F/8.5DP
5.5 7.5 13 YS-9F YS-9F YS-9F RHA-25F/11DP
7.5 10 17 YS-9F YS-9F YS-9F RHA-25F/15DP
11 15 24 YS-9F YS-9F YS-12F RHA-25F/21DP
15 20 32.5 YS-20F YS-9F YS-20F RHA-65F/32D + TIB-65F
18.5 25 39.5 YS-20F YS-9F YS-25F RHA-65F/35D + TIB-65F
22 30 46.5 YS-20F YS-20F YS-25F RHA-65F/43D + TIB-65F
30 40 62.5 YS-32F YS-20F YS-38F RHA-65F/56D + TIB-65F
380-440V 37 50 74 YS-32F YS-20F YS-38F RHA-125F/68DP
45 60 90 YS-32F YS-32F YS-50F RHA-125F/80DP

50/60 Hz 55 75 110 YS-50F YS-32F YS-50F RHA-125F/105DP


75 100 150 YS-80F YS-32F YS-80F RHA-150F/135DP
90 125 180 YS-80F YS-50F YS-100F RHA-180F/155DP
110 150 220 YS-80F YS-50F YS-125F RHA-300F/180D (with CT)
132 175 264 YS-80F YS-50F YS-150F RHA-400F/240D (with CT)
160 215 320 YS-150F YS-80F YS-180F RHA-400F/240D (with CT)
200 267 400 YS-150F YS-80F YS-220F RHA-500F/300D (with CT)
250 333 500 YS-220F YS-80F YS-300F RHA-500F/450D (with CT)
300 — 600 YS-220F YS-150F YS-400F RHA-500F/450D (with CT)

1. Regarding Star operation time is as follows: In case of small inertia (e.g. Non-load, MG set, fan, compressor) is less than 30 seconds. The limit for number
of continuity starting is 3 times, more than need off time.
2. The term of electrical endurance is more than 0.5 million operations.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-55
Application Tables IEC Contactors
Application to Transformers
Single Phase (2-Poles series connection) Three Phase
Contactor Type
(kVA) (A) (kVA) (A) (kVA) (A) (kVA) (A)

YS1N-9F 1.5 7.5 2 5 3 7.5 4 5

YS1N-12F 2 9 3 7 3.5 9 5 7

YS1N-20F 2.5 10 4 9.5 5 13 7.5 9.5

YS1N-25F 4 17 7.5 16 6.5 17 12 16

YS1N-32F 5 25 10 24 10 25 18 24

YS1N-38F 7 32 10 24 12 32 25 62

YS1N-40F 7 32 10 24 12 32 25 32
D
YS1N-50F 9 40 18 40 15 40 30 40
IEC Contactors

YS1N-65F 10 46 20 45 18 46 35 45

YS1N-80F 15 62 35 55 35 62 42 55

YS1N-100F 17 75 33 75 30 75 42 55

YS1N-125F 20 90 33 75 35 90 60 75

YS1N-150F 25 110 40 90 42 110 70 90

YS1N-180F 25 110 50 110 42 110 85 110

YS1N-220F 25 110 57 130 42 110 100 130

YS1N-300F 33 150 57 130 57 150 100 130

1. At the moment when transformer connected with the supply source, large transient inrush current will flow, and its value is much larger than the normal
current (about 20 times greater). The duration may be a few cycles.

Application to Lamp Loads


Tungsten Lamp

100V 200V
Contactor 100W 150W 200W 250W 300W 500W 1000W 1500W 100W 150W 200W 250W 300W 500W 1000W 1500W
1A 1.5A 2A 2.5A 3A 5A 10A 15A 0.5A 0.75A 1A 1.25A 1.5A 2.5A 5A 7.5A
YS1N-9F 11 7 5 4 3 2 1 — 22 14 11 8 6 4 2 1
YS1N-12F 13 8 6 5 4 2 1 — 28 18 14 10 8 5 2 1
YS1N-20F 13 8 6 5 4 3 1 1 30 20 15 12 10 6 2 2
YS1N-25F 19 12 9 7 6 3 1 1 40 26 20 16 13 8 4 2
YS1N-32F 26 17 13 10 8 5 2 1 50 33 26 20 16 10 5 3
YS1N-38F 35 23 17 14 11 7 3 2 70 46 35 28 23 14 7 4
YS1N-40F 35 23 17 14 11 7 3 2 70 46 35 28 23 14 7 4
YS1N-50F 50 33 25 20 16 10 5 3 100 66 50 40 33 20 10 6
YS1N-65F 65 42 32 26 21 13 6 4 130 86 65 52 43 26 13 8

1. When tungsten lamp is lit, its inrush current is about 30 times the normal current and the duration is about 10 milliseconds. In general application to tung-
sten lamp load, magnetic contactors should be selected so that the rated operational current of the contactor will be no less than two times the normal cur-
rent of tungsten lamp load, considered its making current capacity.
2. The value of above table shows available quantities as connected in parallel.

D-56 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Application Tables
Fluorescent Lamp (rapid start time)

100V 200V
40W 60W 80W 100W 220W 40W 60W 80W 100W 220W
Contactor
1 2 1 2
1 1 1 2 1 1 1 1 2 1 2
0.59A 0.96A 0.29A 0.48A
0.92A 1.17A 1.55A 2.5A 2.7A 0.46A 0.58A 0.78A 1.3A 1.35A 2.5A
(1.2A) (1.1A) (0.6A) (0.55A)
18 11 37 22
YS1N-9F (9) (10) 11 9 5 4 4 (18) (20) 23 18 14 8 8 4

23 14 48 29
YS1N-12F (11) (12) 15 11 9 5 5 (23) (25) 30 24 17 10 10 5

25 15 51 31
YS1N-20F (12) (13) 16 12 9 6 5 (25) (27) 32 25 19 11 11 6

33 20 68 41
YS1N-25F (16) (18) 21 17 12 8 7 (33) (36) 43 34 25 15 14 8

42 26 86 52
YS1N-32F 27 21 16 1 9 54 43 32 20 18 10
(20)
59
(22)
36
(41)
120
(45)
72
D
YS1N-38F (29) (31) 38 29 22 14 12 (58) (63) 76 60 44 26 25 14

IEC Contactors
59 36 120 72
YS1N-40F (29) (31) 38 29 22 14 12 (58) (63) 76 60 44 26 25 14

84 52 172 104
YS1N-50F (41) (45) 54 42 32 20 18 (83) (90) 108 86 64 38 37 20

100 67 224 135


YS1N-65F (54) (59) 70 55 41 26 24 (108) (118) 141 112 83 50 48 26

1. When fluorescent lamp lights, generally the starting current is a few times the normal current and its duration may be within a few seconds. Magnetic con-
tactors should be selected so the rated operation current will be the same as the total load current of the fluorescent lamp loads.
2. The values of above table show available quantities as connected in parallel.
3. ( ) values in above table show in the case of the light for Low power factor type.

Mercury Lamp

100V (low power factor type/high power factor type) 200V (low power factor type/high power factor type)
40W 100W 200W 250W 300W 400W 700W 1000W 40W 100W 200W 250W 300W 400W 700W 1000W
Contactor
1.25A/ 2.6A/ 4.6A/ 5.1A/ 6.0A/ 8.0A/ 14.5A/ 21A/ 0.53A/ 1.0A/ 1.9A/ 2.1A/ 2.5A/ 3.3A/ 5.9A/ 8.3A/
0.55A 1.4A 2.6A 3.0A 3.7A 4.9A 8.5A 12A — 0.65A 1.2A 1.5A 1.8A 2.3A 4.1A 5.8A
YS1N-9F 8/20 4/7 2/4 2/3 1/2 1/2 –/1 –/– 20/– 11/16 5/9 5/7 4/6 3/4 1/2 1/1
YS1N-12F 11/25 5/10 3/5 2/4 2/3 1/2 –/1 –/1 26/– 14/21 7/11 6/9 5/7 4/6 2/3 1/2
YS1N-20F 12/27 5/10 3/5 2/3 2/4 1/3 1/1 –/1 28/– 15/23 7/12 7/10 6/8 4/6 2/3 1/2
YS1N-25F 16/36 7/14 4/7 3/6 3/5 2/4 1/2 –/1 37/– 20/30 10/16 9/13 8/11 6/8 3/4 2/3
YS1N-32F 20/45 9/17 5/9 4/8 4/6 3/5 1/2 1/2 47/– 25/38 13/20 11/16 10/13 7/10 4/6 3/4
YS1N-38F 28/63 13/25 7/13 6/11 5/9 4/7 2/4 1/2 66/– 35/53 18/29 16/23 14/19 10/15 5/8 4/6
YS1N-40F 28/63 13/25 7/13 6/11 5/9 4/7 2/4 1/2 66/– 35/53 18/29 16/23 14/19 10/15 5/8 4/6
YS1N-50F 40/90 19/35 10/19 9/16 8/13 6/10 3/5 2/4 94/– 50/76 26/41 23/33 20/27 15/21 8/12 6/8
YS1N-65F 52/118 25/46 14/25 12/21 10/17 8/13 4/7 3/5 122/– 65/100 34/54 30/43 26/36 19/28 11/15 7/11

1. When mercury lamp lights, the starting current is about 1.5–1.8 times the normal current and its duration may be a few minutes (within 8 times). Magnetic
contactors should be selected so the rated operational current will be the same as the total load current of the mercury lamp loads.
2. The values of above table show available quantities as connected in parallel.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-57
Application Tables IEC Contactors
Application to Capacitor-Switching
Single Phase (2 pole series connection) Three Phase
Contactor Type 200-240V 380-440V 200-240V 380-440V
(kVA) (A) (kVA) (A) (kVA) (A) (kVA) (A)
YS1N-9F 1.2 6 1.7 4.3 2 6 3 4.3
YS1N-12F 1.8 9 2.4 6 3 9 5 8
YS1N-20F 1.8 9 3.2 8 3 9 6 9
YS1N-25F 3 15 4.8 12 5 15 10 15
YS1N-32F 4 20 6 15 7 20 15 23
YS1N-38F 5 25 8 20 8 23 20 30
YS1N-40F 5 25 8 20 8 23 20 30
YS1N-50F 7.5 38 12 30 13 38 26 40
D YS1N-65F 9 45 16 40 15 45 30 46
YS1N-80F 10 50 20 50 20 58 35 53
IEC Contactors

YS1N-100F 13 65 20 50 26 75 50 76
YS1N-125F 15 75 26 65 26 75 50 76
YS1N-150F 18 90 30 75 35 105 70 105
YS1N-180F 20 100 36 90 40 115 75 114
YS1N-220F 26 130 40 100 45 130 80 120
YS1N-300F 30 150 60 150 50 150 100 150

1. The making and breaking capacity of the contactor are more than 15 times the rated operational current for capacitor loads in this table.
2. For applications without series reactor: The contactor should be selected to have the making current capacity which is more than 1.5 times the inrush cur-
rent of the capacitor according to percentage impedance of transformer and impedance of the electric circuit.
3. Large transient inrush current may occur at the moment of switching the capacitors. So when inrush current of capacitor exceeds 15 times the rated opera-
tional current of the magnetic contactor, series reactor which has 6% of capacitor reactance shall be connected in the circuit.
4. At single phase application, two poles are used for switching of the capacitor.

D-58 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC
IEC Contactors Application Tables

TYPICAL FULL LOAD CURRENT OF INDUCTION MOTORS


Single-Phase Motors Three-Phase, 4-Pole Motors 50/60 Hz
kW hp 220V 240V kW hp 220-230V 380-400V 415V 440V 500V 660-690V
A A A A A A A A
0.37 0.5 3.9 3.6 0.37 0.5 1.8 1.03 - 0.99 1 0.6
0.55 0.75 5.2 4.8 0.55 0.75 2.75 1.6 - 1.36 1.21 0.9
0.75 1 6.6 6.1 0.75 1 3.5 2 2 1.68 1.5 1.1
1.1 1.5 9.6 8.8 1.1 1.5 4.4 2.6 2.5 2.37 2 1.5
1.5 2 12.7 11.7 1.5 2 6.1 3.5 3.5 3.06 2.6 2
1.8 2.5 15.7 3.6 2.2 3 8.7 5 5 4.42 3.8 2.8
2.2 3 18.6 4.8 3 4 11.5 6.6 6.5 5.77 5 3.8
3 4 24.3 6.1 3.7 5 13.5 7.7 7.5 7.1 5.9 4.4
4 5.5 29.6 8.8 4 5.5 14.5 8.5 8.4 7.9 6.5 4.9
4.4 6 34.7 11.7 5.5 7.5 20 11.5 11 10.4 9 6.6
5.2 7 39.8 36.5 7.5 10 27 15.5 14 13.7 12 8.9 D
5.5 7.5 42.2 38.7 9 12 32 18.5 17 16.9 13.9 10.6
6 8 44.5 40.8 10 13.5 35 20 - - 15 11.5

IEC Contactors
7 9 49.5 45.4 11 15 39 22 21 20.1 18.4 14
7.5 10 54.4 50 15 20 52 30 28 26.5 23 17.3
18.5 25 64 37 35 32.8 28.5 21.3
22 30 75 44 40 39 33 25.4
25 35 85 52 47 45.3 39.4 30.3
30 40 103 60 55 51.5 45 34.6
33 45 113 68 60 58 50 39
37 50 126 72 66 64 55 42
40 54 134 79 71 67 60 44
45 60 150 85 80 76 65 49
51 70 170 98 90 83 75 57
55 75 182 105 100 90 80 61
59 80 195 112 105 97 85 66
63 85 203 117 115 109 89 69
75 100 240 138 135 125 105 82
80 110 260 147 138 131 112 86
90 125 295 170 165 146 129 98
100 136 325 188 182 162 143 107
110 150 356 205 200 178 156 118
129 175 420 242 230 209 184 135
132 180 425 245 240 215 187 140
140 190 450 260 250 227 200 145
147 200 472 273 260 236 207 152
150 205 483 280 270 246 210 159
160 220 520 300 280 256 220 170
180 245 578 333 320 289 254 190
185 250 595 342 325 295 263 200
200 270 626 370 340 321 281 215
220 300 700 408 385 353 310 235
250 340 800 460 425 401 360 274
257 350 826 475 450 412 365 280
280 380 900 510 475 450 400 305
295 400 948 546 500 473 416 320
300 410 980 565 510 481 420 325
315 430 990 584 535 505 445 337
335 450 1100 620 550 518 472 355
355 480 1150 636 580 549 500 370
375 500 1180 670 610 575 527 395
400 545 1250 710 650 611 540 410
425 580 1330 760 690 650 574 445
445 600 1400 790 730 680 595 455
450 610 1410 800 740 690 608 460
475 645 1490 850 780 730 645 485
500 680 1570 900 820 780 680 515
Notes : 1. The full load current of the motor varies with the supply voltage, frequency, number of poles, and number of phases (single- or three-phase).
2. For selection of contactors and thermal overload relays, confirm the actual full load current of the motor.

www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC D-59
Application Tables IEC Contactors

D
IEC Contactors

D-60 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada: (888) 317-IDEC