M850 Comprehensive User Manual - 03 2011a
M850 Comprehensive User Manual - 03 2011a
March 2011
Table of Contents
This symbol indicates that the operator must refer to an explanation in the operating instructions.
Please see Chapter 3, Electrical Installation, for important safety information regarding installatio
and hookup of the M850 ‐MP1 MultiPower meter.
Chapter 1: Meter Overview and Specifications
1.1
Hardware Overview
The four front control buttons are used for scrolling up or down through the parameters being measured and
displayed. These buttons also allow programming of different current and voltage transformer ratios, demand
times, baud rates, etc.
1.1.1
Voltage and Current Inputs
Voltage inputs allow measurement from 28V to 330V line‐to‐neutral and 48V to 600V line‐to‐line. This insures
proper meter safety when wiring directly to high voltage systems. The M850‐MP1 has an input overload rating of
800V,AC continuous. The aux power required is 100 to 440V,AC / 100 to 420V,DC systems.
power A separate unit
have an auxiliary voltage supply of 19 to 69V,DC is available. The M850‐MP1 MultiPower operates at 45‐65Hz
standard; another unit is available for 400Hz applications.
General Specifications:
The auxiliary supply can be connected in parallel with the measuring input
voltage, but this restricts the measuring
range of the input voltage to ± 15% of nominal. If the auxiliary is separate the measuring range of the voltage input
is 10‐120%.
Current Transformers:
Internally the M850‐MP1 MultiPower fitted to either 5 Amps or 1 Amp. The current circuit is designed for
connection to the secondary of external CT. These transformers should conform to at least accuracy class 1 or
preferably ANSI C57.13 or equal.
But if the ratio change was 800/1A, the M850‐MP1 would have to be returned to the factory to have the internal
circuits changed to 1 Amp.
Voltage Transformers:
Connection of voltages higher than the rated voltage that is specified on the M850‐MP1 data label, is possible using
external voltage transformers. These transformers must be at least Class 1 accuracy.
The secondary of these transformers must have the same nominal voltage as that specified on the data onlabel
the
side of the M850‐MP1. (For example: If the M850‐MP1 had a voltage specified as 110V,AC line‐to‐line, then a
transformer with Ratio of 6600/110V,AC volt can be used, once this ratio has been programmed into the M850‐
MP1. But if the ratio was 6600/400V,AC the unit
would have to be returned to the factory or distributor to have
internal component changes to accommodate for the 400V,AC input.)
1.1.2
Model Number plus Option Codes
1.2
Specifications
Input
Range: 28V to 330V (L‐N); 48V to 600V (L‐L)
Burden: <0.5 VA per phase
In: 0.5A to 6A via current transformer
Frequency: 45 – 65Hz standard; 400Hz unit also available
Secondary of CT’s must be connected to earth
Overload
UN: 800V (L‐L) continuous
IN: 10 In for 1 second
10 x In
Accuracy
Voltage (V): 0.5% ± 2 digits
Current (I): 0.5% ± 2 digits
Power (W, VAr, VA): 1.0% ± 2 digits
Power Factor (PF): 1% of range (reading) ± 2 digits
Frequency (Hz): 0.1 Hz ± 1 digit
Energy (kWh,VARh): IEC 1036 Class 1
Auxiliary Voltage
Range: 100V to 440V,AC (45 to 65Hz) / 100V to 420V,DC
Burden: <10VA
Display
Digits: 3 lines, 9999, Blue LED
Digit Size: 14.2mm, 7 segment
Update Time: 1 second
Brightness: User‐adjustable for 8 levels
Environment
o o o o
Working Temperature: 32 F to +140F (0 C to +60C) (Extended ranges available)
o o o o
Storage Temperature: ‐ 40 F to +185F (‐40 C to +85C)
Relative Humidity: 0‐95% non‐condensing
Shock: 30G in 2 planes
Faceplate Rating: IP52 Front Panel (IP 55/NEMA4 available)
Enclosure
Standard DIN case: 96 mm x 96 mm x 60 mm
Panel Mounting: 4 retaining clips
Cutout: 92.8 mm x 92.8 mm
Applied Standards
Immunity to:
‐ Electrostatic discharges: IEC 61000‐4‐2‐Level III
‐ Radiated radio‐Hz fields: IEC 61000‐4‐3‐Level III
‐ Electrical fast transient / IEC 61000‐4‐4‐Level III
bursts:
‐ Impulse waves: IEC 61000‐4‐5‐Level III
‐ Conducted disturbances: IEC 61000‐4‐6‐Level III
‐ Voltage dips & short IEC 61000‐4‐11
interruptions:
Emissions to:
‐ Conducted ad radiated CISPR11‐Class A
Safety: IEC 1010; BSEN 601010
UL: File No. E337752
Options
Plug‐In Modules: RS485 (Modbus protocol)
Pulsed output (W.h and VAR.h)
Communication Format
RS485 (Modbus): Port: through back plate
Baud Rate: 38400, 19200, 9600, 4800, 2400
Parity: Odd, even, no parity
Address: 1 to 247
Data Format: 8 bit
Protocols: Modbus (RTU, Modbus), BACnet MS/TP
2.1
Introduction / Cut ‐out Details
The M850‐MP1 MultiPower is designed for panel mounting and uses a standard 96mm x 96mm DIN case. It fits
into standard 96mm DIN openings.
2.2
Panel Mounting Procedure
Terminal screws are tightened using a flat‐head screwdriver. It is recommended that the terminal screws be
tightened by hand initially. When re‐tightening with pneumatic screwdrivers, use a maximum torque of 0.5‐1.0
Newton meters (Nm) or 1.1 in.‐lbs.
Connections
of the M850 ‐MP1
L1, L2 and L3
current
connections
Terminal block
for power
supply and
RS485 Relay voltage inputs
option option
3.1
Considerations When Installing Meters
• During normal operation, dangerous voltages are present on parts of the M850 including: terminals and any
connected current transformers (CTs) and potential transformers (PTs), all inputoutput
and modules and
their circuits. All primary and secondary circuits should be regarded as capable of producing lethal voltages
and currents. Avoid contact with any energized parts.
• DO NOT use the M850‐MP1 for primary protection or in an energy‐limiting capacity. The M850‐MP1 is a
power meter. DO NOT use the meter for applications where failure of the meter may cause harm or death.
DO NOT use the M850‐MP1 for any application where there may be a risk of fire.
• DO NOTapply more than the maximum voltage the meter or any attached device can withstand. Refer to
the M850‐MP1 meter and/or device labels or see section 1.2 for meter specifications.
NOTE:
IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER,
THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
All inputs are connected to the back of the unit via high contact pressure terminal blocks. The connectors
accommodate up to AWG#12 / 2.5mm wire.
L1, L2 and
L3 current
connections
RS485 Pulsed
(optional) Output
(optional)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
L(+) Aux N( ‐) N L3 L2 L1
On models powered with AC auxiliary supply, the auxiliary supply can be connected in parallel with the measuring
AC input voltage, but thisrestricts the measuring range of the input voltage to ± 15% of nominal. If your application
has a very wide range of AC measurement, the auxiliary supply should be from a different source.
Auxiliary voltage is rated from 45 to 65Hz (AC), with a burden of <10VA (AC or DC).
3.3
Terminations to Meter
Internally the M850‐MP1is either a 5 Amp or 1 Amp rated. Current transformers must be attached externally. The
current circuit is designed for connection to the secondary of external current transformers. These transformers
should conform to at least Class 1 accuracy, or preferably ANSI C57.13 or equal.
VOLTAGE CONNECTIONS:
The secondary of these transformers must have the same nominal voltage as that specified on the data label on the
side of the M850‐MP1. Only standard voltage inputs of 5A,AC; 1A,AC or 330mV are supplied.
All connections must be made as shown ensuring all starts and finishes of current and voltage transformers are
connected as shown.
4.1
Plug ‐In Card Overview
The M850‐MP1 can provide both RS485 (Modus) communications as well as a pulsed output signal as an option.
The plug‐in units can be purchased with the MultiPower M850‐MP1 or they can be retrofitted, when required.
The RS485 plug‐in enables remote reading of up to 31 M850 units on a single 2‐wire bus using the Modbus protocol.
The RS485 Modbus protocol allows the M850‐MP1 to be used with PC, PLC, RTU, Data loggers and SCADA program
The plug‐in module can be retrofitted to the M850 if RS485 communicationsrequired
are at a later date.
An M850‐BAC unit is available for use on building automation systems running with BACnet MS/TP protocol, as well.
The M850‐BAC unit requires an RS485 plug‐in module for communications.
4.1.1
RS485 Installation:
1. Locate the RS485 port on the back of the M850, shown in figure 1.
Note: Install the RS485 card by holding the card square to the opening and only applying downward pressure. The
card will snap down into place. Do not insert the card at an angle, it may seem easier, but there is a greater chance
of bending the internal pins.
4.1.3
Pulsed Output Card
A pulsed output plug‐in module is also available. Pulses are supplied via a N/O Form A relay. The pulsed output can
be assignedto W.h. or VAr.h. The plug‐in module can be retrofitted to the M850 if pulsed output features are
required at a later date.
The relay can be set up via a sub‐menu. If two relays are installed, the secondary relay is automatically set as the
alternative type.
The pulselength of the relay can be set from a list provided in the menu (from 0 to 200 milliseconds). Pulses per
hour (PPH) are modified using the decimal point positioning from the main screen.
4.2
Using the Communications Software
4.2.1
Software Installation:
3. When thenew hardware wizard starts, point it to search the CD drive, the drivers should install
automatically.
2. When starting the software, set the COM port and communications settings to the virtual COM port that
was installed with the USB485 drivers.
MultiView software will assist you in logging and downloading the electrical parameters captured with the M850‐
MP1.
MultiLog software gives you the ability to view your voltage, current and power calculations with graphs and charts.
To access the MultiLog software, double‐click the MultiLog icon that appears on your computer’s desktop (or select
it from your computer’s hard drive.) Double clicking with the left mouse button on a graph will enlarge it or, if it’s
already full screen, will tile it. The right mouse button will enable a short‐cut menu (below).
The second tab is used to enter the logging parameters of a project to be entered.
The Graph Setup screen enablesthe user to tailor the graph screens. Logging screens can be mixed with Real Time
screens provide you with up to 12 graphs, each having 3 traces.
The time base ranges from 5 to 600 seconds in real‐time mode or 5 to 600 samples (minimum 1 second) in logging
mode. Up to 7200 samples can be stored.
The Y axis can be relative 0‐120% to enable displaying mixed signals, for example, 5A and 2000V on the same graph
or absolute.
The Port Settings screen sets up the connection to the meter. NOTE: Ensure that the network settings the same
are
as those of the meter. If the meter’s Comms Lock is disabled, successive tries to connect will result in the meter’s
network settings being changed.
The logged data can be exported as a comma separated variable file (.csv) for Excel to load. Emailing the saved file
alsopossible but the recipient must have a copy of MultiLog to view it.
4.3
Measurement Logging with MultiView
The measurements displayed in the Monitor/Log area of the MultiView program can be captured and saved to files.
A choice of 1 to 6 channels can be selected from the drop‐down menu,
‘Measurements’. The order of the registers
can be altered to make this set up more effective. See Register Order Function if none of the Trigger Points are
enabled, all of the selected measurements are logged at the user‐defined time period.
The files saved will be Tab Separated Variable types suitable for pasting directly into Excel or similar program.
There is no limit on the number of the files saved except for available disc space. (NOTE: this is not checked).
A file will have a base name, chosen by the user, and be limited in size to approximately 60,000 bytes.
Subsequent files will also be limited to 60,000 and have a ‘‐‘ and a consecutive number attached before its extension
identifier. For example, if the file name selected for
the log file is ‘SystemVoltage.log’, additional files will be System
Voltage ‐2.log, System Voltage ‐3.log etc.
NOTE: The data will always be APPENDED to the last file of the specified name if the file or sequence of files alread
exists.
Logging Examples
V1, V2 and I1 trigger points are enabled and sampled at approx. 1 sec intervals.
V1, V2 and I1 trigger points are enabled and sampled at approx. 1 sec intervals.
Response Time = 300ms, Logging Period = 3, Measurements = 4
Triggering occurred on V1 (over) and all measurements logged.
May 16 2003 13:53:41 V1 242.0 V2 242.0 V3 242.0 I1 500.0
May 16 2003 13:53:42 V1 242.0 V2 242.0 V3 242.0 I1 500.0
May 16 2003 13:53:43 V1 242.0 V2 242.0 V3 242.0 I1 500.0
V1, V2 and I1 trigger points are enabled and sampled at approx. 1 sec intervals.
Response Time = 300ms, Logging Period = 3, Measurements = 4
4.4
Network Description
A node's unique address allows the master to selectively request data from a specific
node. The master node, under
the control of a program, requests measurements from one of its slave nodes using an established protocol.
For more information on the Modbus protocol and to download relevant literature, go to http://www.modbus.org
and click on "Modbus Standard Library".
4.5
Measurement Registers (3X and duplicated 3X)
Sample Coding
Slave Address = 1
Reading 6, 3X Registers ‐ code 4
V1 = 239.9V , V2 = 239.7V, V3 = 239.7V
I1 = 499.8A, I2 = 499.3A , I3 = 499.3A
Start Address = 6, number of WORD registers required = 12hex) (0C
Number of values returned = 6, 32 bit floating point (24 bytes)
See Appendix A.1 for 3X Registers. Appendix A.2 shows the 4X Registers. These list the parameters with the
Modbus equivalent address and its address within the M850‐MP1. Any data requested that isn't applicable to the
Type & System column, will return
the value ‐ve infinity (FFFFFFFFh). The order can be altered using the MultiView
Program supplied or by a suitable SCADA program.
Retrieving Measurements
The measurement registers in Multitek's instruments are stored as 32 bit (4 byte) IEEE754
floating point numbers.
Each is arranged as 2, 16 bit words; hence the evenly numbered real Start Addresses in the tables in this document.
The Modbus protocol dictates the retrieval of data as 2 bytes (one word) at a time. To accommodate Modbus
register addressing when the registers arebytes
4 wide, the data has to be retrieved in double words. Modbus
registers in this case are merely pointers to real addresses within an instrument whether the data at that address is
2, 4 or 8 bytes wide. This makes programming a controller simpler in so far that a pointer
can be a word, double or
float type and essentially the code to retrieve data from a node remains the same.
The SLAVES require data start ADDRESSES on even numbered register locations and will reject odd numbers and
return an exception code.
Example 2
Volts L3 ‐L2 ‐ Modbus Address 30002 (Reg. Start Address 0002h)
The implied address of this measurement is 30002. The actual register addresses in the SLAVE are 0002h ,
containing the most significant bits of the floating point measurement and 0003h , containing the least
significant bits of the floating point measurement. Both of these registers are 16 bits wide.
To calculate the correct register offset within the SLAVE and the correct number of registers to retrieve, use the
following formula:
((Modbus implied 3x start address ‐ 30001)*2) for the register start address.
(Number of measurements required x 2) for registers required.
Packet Structure
A packet of data transmitted by a MASTER node will look something like the following
example:
[Address (1 byte)][Function Code (1 byte)][Register Start Address (2 bytes)][Number of Registers Required (2
bytes)][CRC error check (2 bytes)]
Request the measured voltages of a meter (Modbus addresses 30004 to 30006) from SLAVE 2.
Modbus address 30004 = Meter address (30004 ‐ 30001) * 2 = 6 = 06h
Sample Coding:
READ
Slave Address = 1
Reading 6, 3X Registers ‐ code 4
V1 = 239.9V , V2 = 239.7V, V3 = 239.7V
I1 = 499.8A, I2 = 499.3A , I3 = 499.3A
Start Address = 6, number of WORD registers required = 12 (0C hex)
Number of valuesreturned = 6, 32 bit floating point (24 bytes)
Message Packet To SLAVE
01 04 00 06 00 0C 10 0E
4.5.1
3X Registers
Internally, the M850 3X Registers are duplicated in the 4X Register area from address 41001, (internal
offset 2001 (07D1h)). This allows PLCs that can’t read floating point data in the 3X area to retrieve
measurements from the 4X area. See Appendix
A.1 for a list of the 3X Registers.
A sample read packet using code 4 to access the 3X registers will look like this:
[Node][04][start address][No. of Double Registers Requested][CRC(2 bytes)]
A sample read packet using code 3 to access the 4X registers will look like this:
[Node][03][start address][No. of Double Registers Requested][CRC(2 bytes)]
e.g. To read line to line voltages on node 23h using the duplicated measurements in the 4X area:
[23h][03h][07D0h][0006h(3, 4 byte regs)] [CRC(2 bytes)]
See Appendix A for a default order of the 3X registers in the M850. The order can be altered using the System
Monitor program, supplied on request, or by using a suitable SCADA program.
If System Monitor isn't going to be used, Modbus function code 42h (66) can be used to request this data and
Modbus function code 41h (65) can be used to send a string of data to set the order of the registers.
The order will
automatically be saved in FLASH.
UNLIKE THE 3X AND 4X REGISTERS, THESE DATA ARE WORD WIDE INTEGER.
It is important to remember that each register in the packet's data field contains two references to the registers to
be re‐ordered.
e.g. To read the 41 Modbus registers in node 23h a request to send 21 (15h) registers is made :
[23h][42h][0000h][0015h][CRC(2 bytes)]
e.g. To set the 41 Modbus registers to their default order in node 23h:
[23h][41h][0000h][0015h][29h][0102h][0304h][0506h][0708h][090Ah][0B0Ch][0D0Eh]
[0F10h][1112h][1314h][1516h][1718h][191Ah][1B1Ch][1D1Eh][1F20h][2122h]
[2324h][2526h][2728h][29xx][CRC(2 bytes)]
Sample Coding:
WRITE
1) Set the default order
Slave Address = 1
Writing ‐ code 65 (41 hex)
Slave Address = 1
Writing ‐ code 65 (41 hex)
READ
Note: Asking for more registers than the M850 supports will not result in an error. A read command will
always return the maximum number of registers.
Note: Only the first two structures are used by the M850
Format:
[node number][67h][register start(2 bytes)][number of registers(2 bytes)][number of bytes]
[<‐8, 16 byte structures + 1 relay actions + 1 padding byte (130
(82h) bytes of data)‐>][crc(2 bytes)]
In addition to sending the 8 structures, two bytes must be appended to the packet.
2nd Byte:
This is a NULL byte for padding and is ignored.
Requests 8, 16 byte structures representing the parameters for the energy relay(s).
Only the first two structures are valid.
Format:
[node address][68h][register start(2 bytes)][number of registers(2 bytes)][crc(2 bytes)]
One of the 8, 16byte structures read from the M850 is defined below.
In addition to receiving the 8 structures, two bytes will be appended to the packet.
1st Byte:
This is a one‐byte bit pattern where each bit is mapped to one physical relay.
If a bit is reset (0), the corresponding relay’s function is to operate on exceptions. If set (1) it will release.
READ/WRITE
The M850 relay’s action (energize or de‐energize) at pulse time can be written/read using the table below.
The format is a one‐byte bit pattern, where each bit is mapped to one physical relay
(bit 0 = Relay 1, bit 1 = Relay 2)
At pulse time,if a bit is reset (0), the corresponding relay’s function is to energize, if set (1) it will de‐energize.
If a bit is reset (0), the corresponding relay’s function is to operate on exceptions. If set (1) it will release.
2nd Byte:
A NULL byte for padding.
[64 05 FE 00 01 01 00
00 00 00 01 0E FE 01 00 0A]
[64 05 FE 00 01 01 00 00 00 00 01 10 FE 02 00 0A]
[64 05 00 00 01 03 00 00 00 00 01 00 00 00 00 0A]
[64 05 00 00 01 03 00 00 00
00 01 00 00 00 00 0A]
[64 05 00 00 01 03 00 00 00 00 01 00 00 00 00 0A]
[64 05 00 00 01 03 00 00 00 00 01 00 00 00 00 0A]
[64 05 00 00 01 03 00 00 00 00 01 00
00 00 00 0A]
[64 05 00 00 01 03 00 00 00 00 01 00 00 00 00 0A]
[00][FF][5B62]
* In 3 wire mode system V1, V2, V3 will have the same value as volts L2‐L1, L3‐L2, L1‐L3.
**M850‐MP1 only measures import W.h and VAr.h
The registers are listed with their Modbus addresses. See Appendix A.2 for a complete list of 4X Registers. The data
held at these addresses are Read‐Only, Write‐Only or Read+Write, as indicated below.
4X registers are read using function 03h and written using function 10h.
A sample write packet will look like this:
[Node][10][start address][No. of Double Registers][Data length in bytes][CRC(2 bytes)]
e.g. To set Node 23h Primary Voltage and Secondary Voltage together:
[23h][10h][001Ch][0004h(4, 2 byte regs)][08h(2, 4 byte regs)][CRC(2 bytes)]
READ
Packet from master format :
[Node addr][03][Register start addr.(2 bytes)][No of reg(2 bytes)][CRC
bytes)]
(2
Response from Slave format :
[Node addr][03][Byte count][Data(byte count bytes)][CRC( 2 bytes)]
Function 16 (10 hex) ‐ Preset Multiple registers (4X)
These registers contain the system settings and controls. Register addresses in the M850‐MP1 at 0, but in keeping
with Modicon Modbus codes, are designated addresses starting 40001.
SeeAppendix A for a default order of the 4X Registers in the M850. The order can be altered using the System
Monitor program, supplied on request, or by using a suitable SCADA program.
Exception Codes
A normal response from a slave is the
echoing of the function code and the supplying of the data that is requested.
Exceptions are reported in the response from a slave node by setting the msb of the function code and inserting the
applicable error code in the data field. Only the last example below will result inexception
an being reported to the
master node.
• If the slave does not receive the query due to a communication error, no response is returned. The
master node will eventually process a time‐out condition for the query.
• If the slave receives the query, but detects a communication error
(parity or CRC), no response is
returned. The master program will eventually process a time‐out condition for the query.
• If the slave receives the query without a communication error but cannot handle it (e.g. a request to
read a non‐existent register), the slave will return an exception
response informing the master of
the nature of the error.
The error codes that could be returned in the data field are:
01 ‐ Illegal or Unknown Function
02 ‐ Illegal Data Address
03 ‐ Illegal Data value
4.6
M850 ‐MP1 Communication and Programming Overview
Communication Format
Baud rate: 4800, 9600, 19200, 38400, 57600 and 76800
Low level character format:
With Odd or Even parity = 1 start bit, 8 data bits, 1 parity bit, 1 stop bit
With NO parity = 1 start bit, 8 data bits, 2 stops bits.
Modbus Format
Data format: RTU
32 bit, floating point format toIEEE‐754 standard, exponent bias 127, most significant byte transmitted first. There is
no word reversal.
Address range: 1‐247
Error Check:
Cyclic Redundancy Check (CRC), Polynomial exclusive OR value A001h Low byte sent first.
Modbus Protocol
Only the RTU (Remote Terminal Unit) form of the Modbus protocol will be supported
and all references in this sheet
refer to RTU format.
Typically, the master or controller requests data from its slaves by polling them one at a time and waiting for a pre‐
defined amount of time for a response. If a node doesn't respond within this time period the master
will try
accessing it a further two times before indicating to the SCADA system that the node has gone off‐line or there is a
fault with it. If all is well the node will respond with the data requested.
Because Modbus is a word (2 byte) orientated protocol, floating point (4 byte) register numbers are counted in
multiples of two.
This also applies to the number of registers requested. If 2 registers are requested the number of WORDS in the
packet's [Number of registers] slot should equal 4.
4.7
Factory Initial Default Settings
All units are fully programmed by the factory but there are many features that can be programmed by the User to
suit individual applications and needs.
Programmed values and parameters are stored in non volatile memory and are therefore retained in power down
situations.
To enterthe programming mode, simultaneously press the two front buttons “I” and “E”. Keep them pressed and
held for 5 seconds.
The M850‐MP1 now enters the screen setup mode and the display shows SCREEN. This mode allows the User to
customize the display to specific parameter requirements, rather than usingstandard
the parameters. (If you do
not wish to alter Screen page set up mode, then Press again and the M850‐MP1 display moves to the next
programming mode: SUPPLY set up).
For example
NOTE
When in programming mode if the control buttons are not used for more than 6 minutes the M850 returns to the
measuring mode and displays the first screen.
5.1
Introduction
All units are fully programmed by the factory but there are many features that can be programmed by the User to
suit individual applications and needs. Programmed values and parameters are stored in non volatile memory and
are therefore retained in power down situations.
To enter the programmingmode, simultaneously press the two front buttons ‘I’ and ‘E’. Keep them pressed and
held for 5 seconds.
The M850‐MP1 now enters the screen setup mode and the display shows SCREEN. This mode allows the User to
customize the display to specific parameter requirements, rather than using the standard
parameters as shown in
section 3. (If you do not wish to alter Screen page set up mode, then press again and the M850‐MP1 display moves
to the next programming mode: SUPPLY set up).
For example:
NOTE
When in programming mode, if the control buttons are not used for more than 6 minutes M850‐MP1 returns to the
measuring mode and displays
the first screen.
5.1.1
Meter Face Elements
The face of the M850‐MP1 contains a blue LED display designed to be read in a variety of conditions, including bright
sunlight over a very wide viewing angle. An optional red LED display is also available. Four, easy‐to‐access, front
control buttons are used for scrolling up and down through the parameters.
The user can measure a standard range of 16 different electrical parameters by scrolling through the buttons on the
front of the panel. LED annunciators will provide indication of measured values.
Each screen is displayed by pressing one of the four front panel buttons:
‘I’ for Current
‘V/Hz’ for Voltage and Frequency
‘P’ for Power and
‘E’ for Energy
Press the ‘I’ button to access measurements on Current. One press of the button displays line currents; two presses
of the button displays neutral current; three presses displays current demand; four presses of the ‘I’ button displays
current maximum demand; five presses of the button brings the user back thetotop of the category listing (in this
instance.)
Each press of the button steps the user to the next measurement.
It is possible to adjust the M850‐MP1 display to 8 levels of brightness to be read even in direct sunlight.
To adjust the brightness of the LED:
1. Hold down the two center buttons (‘V/Hz’ and ‘P’) simultaneously on the front panel.
2. The brightnesslevel will adjust as the buttons are held down.
3. Each individual press of the buttons steps to the next level of brightness.
5.2
Settings Menu
The main Settings menu is accessed on the M850‐MP1 by holding down the ‘I’ and the ‘E’ buttons simultaneously.
The main menu, and all sub‐menus, are scrolled through using the ‘E’ button. Any selection is made using the ‘I’
button. If no buttons arepressed for 6 minutes, the M850‐MP1 will exit the Settings menu.
There are 8 sub‐menus: Supply; Communications (485); Demand; Energy; Relay; Code; EEPROM; and, End. The u
will cycle through each sub‐menu screen as the User pushes the ‘E’ or ‘I’ button.
Display Indicates
ADDR Address for communications
ADJ (VAr) Adjust Pulses (VAr)
ADJ (W) Adjust Pulses (Power)
BAUD Baud Rate
CNCL Cancel any changes
CODE Password Code
COMMS RS485 network setting
CONF Confirm any changes
DT Demand
DTST Demand Time Set Value
EDIT Edit Pass Code
END End main menu
ENDI Endian
ENGY Energy
LOC Lock
PAR Parity
PPH Pulses per Hour
PULS LNTH Pulse Length
RLAY Relay
RST Reset
SET Set Pass Code
STOP Stop Bits
STOR EEPROM sub ‐menu
STOR Store to EEPROM
SUPP Supply
SYSA System Current
TYPE System Type
UPRI Primary Voltage
USEC Secondary Voltage
At the end of most sub‐menus is the option to CANCEL any changes made in that sub‐menu. In addition,
confirmation is required before any changes are implemented. The CONFIRM button within the sub‐menu screens
should be selected to confirm the changes. The changes are effective asas
soon
they are confirmed.
CANCEL or CONFIRM must be pressed to return to the sub‐menu title (i.e. SUPP, 485, etc.)
5.2.1
Supply (SUPP) Sub ‐Menu
This sub‐menu contains screens for monitoring: System Current; Primary Voltage; Secondary Voltage; System Type
Canceling and Confirming actions made within this section.
The VT ratio and the system current are entered using this sub‐menu. The secondary voltage (meter input) is
optimized at 280V (L‐N). Decimal point positioning and exponent selection are used in this section.
Unbalanced
1P2 1 phase 2 wire
3P3 3 phase 3 wire
3P4 3 phase 4 wire
1P3 1 phase 3 wire
Balanced
3P3B 3 phase 3 wire
3P4B 3 phase 4 wire
When entering data, numbers can be entered into the unit in the following way:
This sub‐menu contains screens for monitoring: Communications Address; Baud Rate; Stop Bits; Parity; Endian;
Lock; Canceling and Confirming actions within this section.
When using the plug‐in RS485 (Modbus protocol) option, the network settings can be detected and the unit
configured automatically. If manual configuration is preferred, the meter can be set up as follows:
Baud rate
4.8 4800 baud
9.6 9600 baud
19.2 19,200 baud
38.4 38,200 baud
57.6 57,600 baud
76.8 76,800 baud
Stop Bits
0 No stop bits
1 1 stop bit
2 2 stop bits
Parity
N No parity bit
O Odd parity bit
E Even parity bit
The unit’s baud rate, number of stop bits and parity can be selected from the list above. Floating point numbers can
be transmitted in either Big Endian (default) or Little Endian BYTE order. They can be selected using the Endian item
Locking prevents the unit hunting for a valid network if communication errors are occurring and can be set using the
LOCK item.
When entering data, numbers can be entered into When only fixed data can be entered, you can
the unit in the following way: select the values from the list:
This sub‐menu contains screens for: Reset; Demand Time; Canceling and Confirming actions within this section.
The unit integrates all measurement of Amps, Power and VA within a variable time length sliding window. The Reset
option will reset all demand and maximum demand measurements.
The Demand Time window can be set to a value of between 3 and 60 minutes (inclusive).
When entering data, numbers can be entered into the unit in the following way:
5.2.4
Energy (ENGY) Sub ‐Menu
This sub‐menu contains screens for: Adjust Pulses (W); Adjust Pulses (VAr); Reset; Canceling and Confirming actio
within this section.
There are two energy accumulators in the unit: Import Power and Import VAr. Modifications to the pulses per hour
rate can be done through this sub‐menu.
Divisor
1000
100
10
1
0.1
0.01
0.001
When entering data, numbers can be entered into When only fixed data can be entered, you can
the unit in the following way: select the values from the list:
This sub‐menu contains screens for: Relay Type; Pulse Length; Pulses per Hour; Canceling and Confirming actions
within this section.
The Pulsed Output module option of the M850‐MP1 can operate as W.h. or VAR.h. types. The principal relay can be
set up in this sub‐menu. If two relays are installed, the secondary relay is automatically set as the alternative type.
The pulse length of the relay(s) can be set from the list below (0‐200 ms). Pulses per Hour (PPH) are modified using
the decimal point positioning method.
Pulse Length
(in milliseconds)
OFF
40
60
80
100
120
140
160
180
200
When entering data, numbers can be entered into When only fixed data can be entered, you can
the unit in the following way: select the values from the list:
This sub‐menu contains screens for: Edit; Set; Canceling and Confirming actions within this section.
Within this sub‐menu, password protection can be set to prevent accidental and unauthorized tampering of the
M850‐MP1’s settings. The Pass Code can be changed using the EDIT facility in the sub‐menu. It is activated using
the SET option.
5.2.7
EEPROM (STOR) Sub ‐Menu
This sub‐menu contains screens for: Canceling and Confirming any actions to be saved to the unit’s non‐volatile
memory.
It is recommended that whenever settings have been updated that this option be used. However, the unit will save
all settings on a power down or brown‐out condition.
5.2.8
END (END) Sub ‐Menu
This selection exits the main menu and resumes displaying measurements on the M850‐MP1.
6.1
System Type Programming
1. Press “I” & “E” simultaneously and hold for 5 seconds. The unit is now in setup mode. The screen will
change to “SUPP”. (Most times, the display goes through “SUPP” directly to “SYSA”. This is due to a
timing problem with releasing the buttons.)
6. Press “E” to choose: 1P3, 1P2, 3P3, 3P4, 3P3b, or 3P4b. Press
to set.
“I” The screen returns to “Type”.
7. Press “E” until “CONF” is displayed. Then, press “I”. Now the display shows “SUPP”.
8. Press “E” until “END” is displayed. Then, press “I”. Now you are out of programming mode.
9. Check the resulting display on the meter for voltage and current
to see that the desired numeral is
10. If not, repeat procedure starting with step 1 and check that the proper numbers are programmed into
the meter.
Internally the M850‐MP1 MultiPower is fitted to either 5 Amp or 1 Amp. The current circuit is designed for
connection to the secondary of external CT. These transformers should conform to at least Class 1 as per BS7626
(IEC 185) or equivalent. The secondarythese
of external transformers must have the same nominal current input as
that specified on the data label on the M850‐MP1. For example, if the M850‐MP1 has a current ratio specified as
500/5A, then the CT could be changed to 800/5A (or any ratio with secondary 5A) andonceusedthe current ratio
has been programmed into the M850‐MP1.
But if the ratio change was 800/1A, the M850‐MP1 would have to be returned to the factory to have the internal
circuits changed to 1 Amp.
6.2.1
CT RatioProgramming
1. Press “I” & “E” simultaneously and hold for 5 seconds. The unit is now in setup mode. The screen will
change to “SUPP”
3. Press “I” button once. The screen displays the Primary Ampere setting.
4. Press “I” toselect the desired numeral to be changed. i.e.: for a CT primary of 2000Amps, the display
5. Press “E” to change to the desired digit. i.e.: for a CT primary of 2000Amps, the display will show
7. The screen then will display “E” for descriptor selection. Press button “E” to select K (kilo)/ M (mega) or
no descriptor.
11. Check the resulting display on the meter for voltage and current to see that the desired numeral is
12. If not, repeat procedure startingwith step 1 and check that the proper numbers are programmed into
the meter.
Connection of voltages higher than the rated voltage that is specified on the M850‐MP1 data label, is possible using
external voltage transformers. These transformers must be at least Class 1 accuracy.
6.3.1
VT Ratio Programming
4. Press “I” once. The screen displays the VT Primary Voltage setting.
5. Press “I” toselect the desired digit. i.e.: for a VT Primary of 280Volts, the display will show 280.0.
6. Press “E” to change to the desired digit. i.e.: for a VT Primary of 400Volts, the display will show 400.0.
8. The screen will then display “E” for descriptor selection. Press “E” to select K (kilo) / M (Mega) or no
descriptor.
11. Press “I” to select the desired numeral to be changed. i.e.: for a VT secondary of 280Volts, the display
12. Press “E” to change to the desired digit. i.e.: for a VT secondary of 400Volts, the display
show
will 400.0.
13. When the screen displays “d”, you can select a decimal location by pressing “E”. Press “I” to set.
14. The screen will display “E” for descriptor selection. Press “E” to select K(kilo) / M(mega) or no
descriptor.
16. Press “E” until “CONF” is displayed. Then, press “I”. Now the display shows “SUPP”.
17. Press “E” until “END” is displayed. Then, press “I”. Now you are out of programming mode.
19. If not, repeat procedure starting with step 1 and check that the proper numbers are programmed into
the meter.
Step 16 Step 17
The M850‐MP1 integrates all measurements of Amps, Power and VA within a variable time length, sliding window.
The reset option will reset all demand and maximum demand measurements. The time demand window can be set
to a value of between 3 and 60 minutes (inclusive).
6.4.1
Max Demand Time Setting
In this example, the maximum Demand Time setting will be made to 30 minutes. Here are the programming
instructions to set the M850 to that setting:
1. Press “I” & “E” simultaneously and hold for 5 seconds. The unit is now
setup
in mode. The screen will
change to “SUPP”
3. Press “I” button once. The screen will move into Reset “rSEt” mode.
4. Press “I” to reset any value that may have already been logged. (Press “Y” to reset the value;
press
or,
6. Press “I”. This will show what is currently set in minutes. Keep pressing “E” until you get to “0”.
8. Press “E”three times to change the 0 to 3. Now the display should show “30”.
10. If this is incorrect, press “E” to “CNCL”, then “I” and repeat the setting.
Please note: The M850‐MP1 has the capacity to be set up to 60 minutes in 1 minute increments.
A.1
3X Registers