0% found this document useful (0 votes)
16 views12 pages

Specification Chattri Hall - Fire

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views12 pages

Specification Chattri Hall - Fire

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 12

PART – 4 : SPECIFICATION

SECTION- 22 : FIRE HYDRANT CUM DOMESTIC


WATER SUPPLY SYSTEM

22.0 FIRE CUM DOMESTIC WATER SUPPLY PUMP

22.1 Submersible Pump

General

Furnishing and installation of multi-stage submersible pumps as shown on the plans and
sectional drawings and the capacities and the specific characteristics as mentioned in the
schedule of item. Each unit shall be coupled to an appropriately rated electric motor and shall
be complete with base plate, couplings, discharge elbow, mounting clamp, column pipe,
marine cable 30m long in a single length and all other standard components. Pumps & motors
shall be of submersible type.

Pump, motor, spacer unit, coupling shall be vertical mounted on a heavy base plate of
structural steel. Pump and motor must be checked for alignment after pump base has been
installed and grouted in place, in accordance with the standards of the Hydraulic Institute.
There shall be no stress transmitted to the pumps.

All the equipment shall be thoroughly cleaned, de-greased and painted with two coats of
enamel paint over a coat of primer/anti corrosive marine paint. The capacity of the pump shall
be 750gpm at 14 bar, UL Listed..

Safe working pressure for each pump shall not be less than 1102 kPa (160 psig). Pump shall
operate at a maximum synchronous speed of 2900 rpm. A unit operating at a lesser rotating
speed will be considered, but in no event a pump at more than the maximum speed specified
shall be acceptable.

The fire pump shall also be used as domestic supply pump with pressure reduction valve in the
riser to the overhead tank.

The fire pump shall be operated both in local (manual) mode as well as in auto mode signaled
from break glass call points incorporated in fire pump control panel. The function of pumps in
control panel shall be set accordingly so that one pump will be operated for domestic supply
and the other pump will be ready on auto mode as fire pump. There shall be two sets of
operation for such pumps.

There shall be signals and alarms for the roof tank water level (maximum and minimum) at
the control panel.

Casing and Impeller

Pumps shall be standard type with bronze fitted construction. Pump casing shall be constructed
of cast iron having minimum tensile strength of 240 Mpa (35,000 psi) and shall be of
sufficient thickness to withstand stress and strains at full operating pressures. Casings shall be

/conversion/tmp/activity_task_scratch/780588668.doc Fire_1
subject to hydrostatic pressure test at 150% of the specified duty point. Impeller shall be of
cast bronze free from casting defects. Impeller shall be statically and dynamically balanced
and securely fastened to the shaft by key or by taper conical sleeves. The vanes shall be
designed for high hydraulic efficiency and smooth flow of water.

Shaft

The pump shaft shall be made of high grade stainless steel-AISI-410, accurately machined to
give a true running rotating element. The rotating element shall be mounted in heavy-duty
bearings housing. The bearing housings shall be of cast iron and shall be furnished with a set
of re-grease able bearings for both radial and thrust loads. The bearings shall have an average
life of 40,000 hours and shall be mounted in machined, sand proof housings having water
cooling and lubricating arrangement.

Motor

Each pump shall be coupled to a standard bore well type vertical water filled & water cooled
and water lubricated submersible squirrel cage induction motor of appropriate horsepower
through sleeve coupling. The design, construction, testing and performance of submersible
electric motor shall conform to latest British, American, Japanese, German or equivalent
International standard in this regard. The motor shall be capable of discharging rated output
without any reduction in their expected life span when operated with 400v  10%/ 3 phase/ 50
Hz  5% power supply. The motor shall not be overloaded at the maximum discharge capacity
at low head condition. Motor shall be capable of withstanding 120% of rated speed, in either
direction of rotation, for at least 2 minutes without any mechanical damage.

The motor enclosure shall be sturdy in construction and shall permit easy removal of any
internal part of the motor for inspection and necessary repairs. The bearing shall have a life
expectancy of 40,000 hrs. The bearings shall prevent ingress of dirt, moisture, and water into
the motor and shall prevent loss of lubricant. The motors overload protection shall be
incorporated in the motor control panel. The submersible motor shall have equipped with
rubber bag at the bottom for volume compensating of the water inside the motor.

Accessories

Each pump unit shall contain steel companion flanges and pipe reducers for connection to
suction and discharge pipe lines. The Tenderer shall submit detail catalogues and performance
curves of their offered pumps along with their tender offer. The catalogues shall provide
information on materials of construction, dimensions etc in detail.

Installation

The Contractor shall be responsible for handling, lifting, erection and installation of the
pumps. They shall be responsible for all kinds of civil, mechanical and electrical works
necessary for complete erection and installation of the pumps.

The Contractor shall be responsible for construction of concrete/pipe column foundations


along with vibration isolators for installation of the pumps as per detail foundation drawing
and instruction of Engineer-in-Charge. The Contractor shall furnish and install all electrical
components and electrical cables to make the electrical connections of the pumps complete.

/conversion/tmp/activity_task_scratch/780588668.doc Fire_2
Pump, motor and their components and accessories shall be made of any recognized ISO 9001
certified company of the world.

Motor Starters

Motor starters shall be automatic Star-Delta type for motors up to and above 5 kW. For
motors having capacity below 5 kW Direct-on-Line (DOL) type starters shall be used. All
starters shall have built-in motor protection device.

Labels and Circuit Diagram

Every equipment mounted inside the control panel shall be provided with individual labels
showing equipment designation/ rating. Also the panel shall be provided with a non-rusting
label engraved with the designation of the cabinet as furnished by the user/ client, fixed on
the front. A circuit diagram engraved/printed on non-rusting metal/PVC shall be fixed on
the inside surface of the door.

Installation

The Contractor shall be responsible for installation of the main electrical control panel, along
with its circuit breakers, control wires, internal electrical connections etc. including supply of
all materials and consumable within the price quoted.

Country of Origin

Control panel and their component & accessories shall be made of any recognized ISO
9001 certified company of the world.

22.2 HYDRANT BOX

Furnish and install Hydrant Box made of M.S. sheet steel having 18 SWG thickness. The
unit shall be recessed wall mounted indoor type. The unit shall have push button type door
cam, 4 mm thick tempered clear glass on the front. The unit shall be powder coated with
red color over a coat of primer. The unit shall be complete with manually operated
swinging reel accommodating 30m long 38mm dia hose. The swinging reel shall be of good
quality, easy to operate and to the satisfaction of the Engineer-in-charge. The hose shall be
made of canvass with internal rubber lining and shall be complete with instantaneous
coupling, 20mm dia brass Jet/Fog Nozzle, stainless steel hose clips etc complete in all
respect. The box shall be complete with 25 mm dia drain valve. The disc of the hose shall
be painted red and each hose reel shall have an inlet valve with a nozzle guide. The hose
shall be able to withstand a working pressure of 690 kPa (100 psig). The rubber hose shall
be reinforced braided.

Hose, nozzle and landing valve shall be made of Germany/Japan/Korea/Taiwan or


equivalent.

22.3 HOSE & NOZZLE

/conversion/tmp/activity_task_scratch/780588668.doc Fire_3
Furnish and install 30m long 65mm dia canvas hose complete with instantaneous coupling,
Jet/Fog nozzle, and stainless steel hose clips etc complete in all respect. The hose shall be
reinforced braided and internally lined with rubber. The nozzle shall be made of brass. The
hose shall be able to withstand a working pressure of 690 kPa (100 psig).

Hose and nozzle shall be made of USA/UK/Germany/Japan/Korea/Taiwan.

22.4 LANDING VALVE

Furnish and install Landing Valve made of Gunmetal. The valves shall be Bib nose pattern,
field adjustable wet riser pressure regulating type. The valve shall be able to with stand a
working pressure of 1378 kPa (200 psig). It shall be complete with brass blank cap and
stainless steel chain. The inlet of the valve shall be male screw and outlet of the valve shall
be female instantaneous coupling type. It shall be painted “Red”.

Landing valve shall be made of USA/UK/Germany/Japan/Korea/Taiwan.

22.5 FLEXIBLE PIPE CONNECTOR

Furnish and installation be flanged end type Flexible Pipe Connector that shall be suitable for
absorbing shock and water hammering and shall reduce vibration transmission to the water
pipe. It shall be able to withstand at least 1378 kPa (200 psig) working pressure. It shall be
fitted to pipe line with the help of flanges and gaskets. The Contractor shall be responsible for
complete installation of it including supply of all materials and consumable within the price
quoted.

Flexible pipe connector shall be made of USA/UK/Germany/France/Japan/Singapore.

22.6.1 WATER VALVES

Furnish and install water valves (gate, globe, non-return, float, vent etc.) of different sizes as
per drawings and requirements. The valves shall be made of steel or cast iron with bronze
fittings. Each valve shall be strong enough to withstand an internal working pressure of at least
1725kPa (250 psig) and shall not leak at this pressure. Valves shall be flanged end type and
shall be fitted to the pipeline by means of proper flanges and gaskets. The Contractor shall be
responsible for supply and welding of flanges to the pipes for installation of water valves
including supply of all materials and consumable at the price quoted.

Water valves and fittings shall be made of USA/UK/Germany/France/Japan.

Vent Valve, 25 mm dia


Automatic Vent Valve, 25 mm dia
Float Valve, 100 mm dia
Non Return Valve, 100 mm dia
Water valves shall be made by any company recognised by ISO 9001.

22.6.2 CONVENTIONAL OS&Y VALVE

Conventional OS&Y Valve (Outside screw & yoke) functions by opening and closing via a

/conversion/tmp/activity_task_scratch/780588668.doc Fire_4
gate, lowers both in and out of the valve. The screws of the valve are held by a yolk on the
outer portion of the valve, a wheel in the valve is attached to the nut which turns, allowing the
shaft to lower or rise from the lower portion of the valve. 150mm dia.
Supplying, Installation Swing check valve 6”.
Supplying, Installation Pressure gauge up to 25 bar.
Supplying, Installation of Air relief valve

22.7 PRESSURE GAUGES

Furnish and install Bourdon type Pressure gauges with 150mm dial and stainless steel case
and ring. The range of the pressure gage shall be 0 ~1725 kPa (0 ~ 250 psi). The Contractor
shall be responsible for installation of pressure gages in the water lines at the places shown in
the drawings including supply and installation of all consumable.

Pressure gauges shall be made of USA/UK/Germany/France/Japan.

22.7.2 RED STEEL PIPES

Red Steel Pipe with special fittings as sockets, reducing sockets, unions etc. in/c necessary
welding, cutting trenches and back filling the same with rammed, cutting of R.C.C, C.C,
floor or brick work wherever necessary and mending good the damages and fixing in walls
with flat bar clamps etc. all complete in all respect.

25,65,150. 200mm dia.

22.8.3 ACCESSORIES/FITTINGS

38mm dia Gate Valve.


65 mm brass instantaneous coupling landing valve with cap and chain.
65mm dia Pressure Reducing Valve.

22.9 G.I. PIPES (Adamjee or its equivalent)

Supplying, fitting and fixing G.I. pipe with all special fittings, such as bends, elbows, sockets,
reducing sockets, Tee, unions, jumnuts etc. including cutting trenches where necessary and
fitting the same with earth duly rammed and fixing in walls with holder bats and making hole
in floors and walls and consequent mending good the damages etc. complete in all respect as
per direction of the Engineer-in-charge.

G.I. pipes shall be made of Adamjee or its equivalent and the fittings shall be best quality to
the satisfaction of Engineer-in-charge.

22.10 PIPE FITTINGS (Elbows, Tees, Reducers, etc)

Elbows, Tees, Reducers, etc. fittings related 40-S black steel pipe shall be made of high grade
steel and shall be able to withstand a minimum of 1378 kPa (200 psig) working pressure. The
inside surface of the fitting shall be very smooth so that the friction loss is minimum. The
elbows, tees and reducers shall be fitted to the pipeline by means of welding/threading or with
flange. The welding/the threading shall have no crack, leak or other defects. The outside

/conversion/tmp/activity_task_scratch/780588668.doc Fire_5
surfaces of pipe fitting shall be coated with two coats of synthetic enamel paint (red color) on a
coat of primer after cleaning the pipe fitting surfaces properly by scrapping and other
approved methods. The pipeline immersed in water/soil shall be painted with
anticorrosive/marine paint. The Contractor shall be responsible for supply and installation of
all materials and consumable for complete installation of fittings within the price quoted.

Pipe fittings shall be made of USA/UK/Germany/Japan/Korea.

22.11 PRESSURE REDUCING VALVE

Furnish and install Pressure Reducing Valve in branch hydrant lines leading to floors as
shown in the drawing. The valve shall be made of gunmetal and shall have arrow marking
on the top to indicate the direction of water flow. The unit shall be complete with two pipe
unions, one installed on the upstream and another installed in the down stream of the valve.
The valve shall be complete with facility required for adjustment/setting. The valve shall be
capable of adjusting water pressure from 1102 kPa (160psig) to 300/100 kPa (43.5/14.5
psig). The unit shall have pressure relief connection in order to bypass pressurized water in
case of occurrence of excessive pressure rise in the pipeline.

Pressure reducing valves shall be made of USA/UK/Germany/Japan.

22.12 FIRE BRIGADE CONNECTION

Furnish and install Fire Brigade connection in 150mm dia hydrant system. The connection
shall be in the form of two 150mm dia hydrant valve, with 25 mm drain valve complete with
brass blank cap, stainless steel chain, purging valve etc complete in all respect.

The fire brigade connection shall be made of USA/ UK/ Germany/ France/ Japan/
Singapore.

22.13 ELECTRICAL CABLES

Supply, lay and connect PVC insulated, PVC sheathed single core/multi-core electrical
cables/marine (power cables as well as control cables) as per requirement of submersible
pumps and other control equipment. Electrical cables shall be NYY grade or BYA grade of
Eastern Cables or equivalent and shall be approved by the Engineer-in-charge. The sizes of the
various cables shall be in accordance with the rating of connected machine/equipment, taking
consideration of maximum short circuit current, voltage drop, ambient temperature, grouping
factor etc. and shall be approved before laying/fitting. All cable lugs, terminal connections,
other materials [viz. water grade PVC conduit, conduit bends, tees, junction box, pull box etc]
and other consumable required to complete installation shall be supplied within this head.

22.14 FIRE ALARM PANEL

Supply, installation, testing & commissioning of Fire Alarm, constructed with heavy
gauged sheet steel painted with red color as fire code approved. The control indicating
panel shall be well for 24 zone fire indicator, power supply unit, alarm silence, alarm
control selection and by pass etc. complete. The panel shall be complete with battery and

/conversion/tmp/activity_task_scratch/780588668.doc Fire_6
charger and control Panel & other accessories for at least 24 hrs. Power supply shall be 220
+ 5% volt /single phase/50Hz.
The fire alarm system shall be installed for initially constructed 8-storied and a basement in
two positions in each floor and finally the building shall be extended up to 12-storied in
similar configuration.

The system shall be installed with electrical connection including supply of all necessary
materials, consumables, tested & commissioned complete in all respect as per instruction of
Engineer-in-charge.

The fire alarm panel shall be made of USA/UK/Germany/France/Japan.

22.15 FIRE ALARM BELL

The gong of the alarm bell shall be 150mm (minimum). Operating voltage shall be 24V D.C
and bell shall produce a loud clear ring of excellent tone of minimum sound out put of 90 dB
at 1 meter distance. The base plate of the bell shall be equipped with terminals to facilitate
wiring, external connections and plugging. The finish of fire bell shall be stove – enamelled
gloss RED.

Fire alarm bell shall be installed at location shown in the drawing. It shall be mounted on
the surface of the R.C.C/Brick wall. The work includes the supply & installation of rawl
plugs and all other accessories, mending good the damages, etc. complete as per direction
of Engineer-in-Charge. Installation & wiring connections shall be done as per
recommendations of the manufacturer and approval of the Engineer-in-Charge. The system
shall be tested and commissioned.

Fire alarm bell shall be made of USA/UK/Germany/Japan.

22.16 BREAK GLASS CALL POINTS

Break Glass call points shall be installed at points shown in the layout plan drawing. It shall
be surface mounted type and shall be fixed to the R.C.C/Brick wall at a height of 4-0 from
floor. Installation and wiring connections shall be done as per recommendation of the
manufacturer & approval of the Engineer-in-Charge. The works includes necessary groove
cutting on R.C.C/Brick wall (if required) & mending good all the damage as per direction of
the Engineer-in-Charge.

All the call points shall be provided with push button switch to start the fire (submersible)
pump in case of fire. The startup sequence shall be incorporated with the fire pump control
panel.

Break glass call points shall be made of USA/UK/Germany/Japan.

22.17 FIRE EXTINGUISHER

Chemical Dry Powder/Carbon Dioxide (CO2) Portable Fire Extinguisher

The body of the portable fire extinguisher shall be constructed of steel not less than the
requirements of US NEPA standard, British standard or equivalent and shall be suitably

/conversion/tmp/activity_task_scratch/780588668.doc Fire_7
protected against corrosion. The charge shall be non-toxic and retain its free flowing
properties under normal storage conditions. Any pressurizing agent used, as explants shall
be in dry state in particular compressed air. The discharge tube and gas tube, if either is
fitted, shall be made of steel, brass, copper or other suitable material. Where a hose is
provided it shall not exceed 1000 mm in length and shall be made for securing on the
nozzle when not in use. The fire extinguishers shall be of rechargeable type. The shooting
range shall be 2.5m.

The extinguisher shall be clearly marked with the following information: -

1. The words “Dry Powder or Carbon Dioxide (CO2) Fire Extinguisher” in prominent
letters.

2. Method of operation and the class/type of fire to be applied on.

3. The working pressure and the weight of the gas charge in kilograms.

4. Manufacturer’s name.

5. Relevant document shall be provided at the time of supply.

6. The words “RECHARGE AFTER USE” if rechargeable type.

7. Instructions to regularly check the weight of the pressure container (gas cartridge) or
inspect the pressure indicator on stored pressure type, and remedy and loss indicated
by either.

8. The year of manufacture.

9. The pressure to which the extinguisher was tested.

10. Complete instructions for charging the extinguisher or otherwise be supplied with the
refill.

It shall be suitable for A,B,C and E class fire and for much time use and of standard
capacity. The Contractor shall supply all materials required for installation. It shall be
installed at location specified by the Engineer.

11. Country of product: USA/China/Malaysia/Germany/U.K./Japan.

12. At least one sample test from each category is required at free of cost.

22.18 WATER TANK MANHOLE COVER

Manhole covers for roof/underground water tank of size 500mm dia with cast iron cover
including 100mm size best quality lock and fixing and fitting complete.

22.19 TESTING, BALANCING AND COMMISSIONING

/conversion/tmp/activity_task_scratch/780588668.doc Fire_8
Each pump shall be shop-tested with a calibrated motor or a dynamometer. The pumps non
return valve, the discharge casing and bowl assembly shall be hydrostatically tested to twice
the maximum pressure developed at shutoff, but not less than 250 lbs/in2. The contractor shall
collect a certificate from the manufacturer in this regard and shall provide the same to the
owner at the time of delivery of the material.

After completion of the supply and installation of the works, the Contractor shall have to carry
out the complete testing of the system to assure that all the components of the fire hydrant and
domestic water supply system are operating in accordance with the design and specifications.

The Contractor shall be responsible for all costs incurred during testing. If any breakage occurs
or any component is found to be defective during the course of testing, they shall replace or
repair it and shall complete it within the time specified in special conditions of contract. Spares
which may be imported for operational period and which appears in the bid schedule shall not
be utilized during and for commissioning and performance guarantee tests.

Pre-commissioning Testing

The Contractor shall perform such tests for adjustment and balancing of the system before
going for final tests. Each individual unit shall also be tested in order to ascertain their
satisfactory performance. No representative from the Employer side shall be required to
remain present during those tests. After the pre-commissioning tests and balancing of the
systems and when the Contractor is satisfied that the supplied and erected machines/equipment
will perform according to the specifications, they shall prepare for final commissioning test.
Final commissioning tests shall be done in presence of Employer's representative. Before final
commissioning tests the Contractor shall clean all waste materials, debris, etc. and paint all the
corrosion prone components.

Pre-commissioning Test Procedures

Appearance Test

The fire hydrant and domestic water supply system shall be checked for its workmanship and
overall appearance. All the works shall be installed with good workmanship and appearance.
Machines, pipes shall be installed to show a neat appearance. The cutting on walls, foundation
on floor shall be done in such a manner so as to give good appearance. There shall be no sharp
bend on pipes. The welding on pipes or on other parts shall be ground smooth. There shall be
no indentation on any component. All the required components shall be painted.

Mechanical Test

The installation of all the machines/equipment, pipes, fittings, electrical lines and all other
components shall be tested. Every component shall be tested whether they have been installed,
fixed or fitted properly as per specifications. All nuts, bolts, vibration isolators (spring and
rubber in shear) shall be checked before testing and after testing. If any defect is found during
or after the testing it shall be rectified and shall be put to retest.

All the machines/equipment shall be tested for their level and alignment. Each component of
the fire hydrant system shall be tested for vibration and noise generation criteria. If any
machine, equipment, pipe, or any other component creates high vibration it shall be rectified to

/conversion/tmp/activity_task_scratch/780588668.doc Fire_9
reduce its vibration and shall be put to retest. If any machine, equipment, pipe of any other
component transmits vibration to the adjoining system component, floor, wall or ceiling,
preventive measures for vibration isolation shall be taken and the unit shall be put to retest.

The noise level of the system shall be tested and if it is found out that any component or part
of it is producing unacceptable noise it must be reduced to acceptable level by appropriate
measure or by replacement.

All moving and rotating parts shall be tested for balancing and if any unbalanced part is found
it must be balanced and shall be put to retest. All bearings and couplings shall be tested for
their alignment and if any misalignment remains it must be adjusted and shall be put to retest.

Contractor shall test all the motors to see whether they are excessively heated, drawing
excessive current and producing excessive sound. If any fault is found it shall be rectified and
shall be put to retest. All other mechanical criteria of the installation shall be tested.

Leak Test

All water piping shall be leak tested. Any leaks that develop during the testing must be
repaired and the tests must then be repeated. All piping systems must be subjected to a
hydrostatic test for 48 hours of duration at a test pressure equivalent to their highest-pressure
capacity.

During testing it shall be observed whether there is any leak in the piping, valves, strainers,
flexible connections, pump glands etc. If any leak is found in any component it must be
rectified and shall be put to retest.
Electrical Test

All electrical connections shall be tested for insulation, continuity, earthing etc as per standard
practice in this regard.

Final Commissioning Testing and Performance Testing

The Contractor shall have to perform final appearance and mechanical tests in presence of the
Employer's Representative. During this test he shall have to perform all the steps as described
in the pre-commissioning tests.

The performance tests shall be done in presence of the Employer's Representative.


Performance test on individual machine/equipment and on the system as a whole shall be
carried out according to following steps:

- All pumps shall be tested for speed; flow capacity, pressure differential and ampere draw
of the pump motor.

- all controls shall be tested according to their working principles and purposes

22.20 SUBMITTALS

The renderer shall supply the following document at the time of bidding:

/conversion/tmp/activity_task_scratch/780588668.doc Fire_10
i) The make, model, country of origin of the equipment along with catalogues/brochures.

ii) Warranty certificate for pumps, motors and their component and accessories for a
period 24 months after provisional acceptance and a free service with spares, if
required without extra cost to the Owner during this warranty.

iii) The tenderer shall provide guarantee for the availability of spare parts for a period of at
least next 10 years.

The contractor shall provide the following document at the time of delivery of
equipment/materials :

i) The contractor/manufacturer shall provide a certificate that the supplied materials are
new, unused, free from any defect of material constituents or workmanship.

ii) The contractor shall show/provide original bill of lading incase of foreign materials.

22.21 SHOP DRAWING

Contractor shall prepare detail shop drawings and submit for approval before commencing
manufacturing and installation. Shop drawings shall generally be in accordance with drawings
provided by the Consultant, specification drawings. Shop drawings shall take into
consideration actual site conditions prevailing on site. Before preparation of shop drawings the
Contractor shall identify any errors/omissions (if any) in the consultant’s drawings and
interference with structures and bring these to the notice of the consultant. Any deviation and
variation shall be endorsed by the consultant. Contractor shall not be relieved of responsibility
of any subsequent detection of error/omission and interference.

Shop drawings shall cover, but not limited to the following :

- Detailed piping layout with pipe sizes, isometric views of piping system, installation
dimensions, including details of pipe fabrication, welding and other jointing details,
installation.

- Details of all structural penetrations, including dimensions of punches, sleeve placements,


up stands, flashings etc.

- Details of all equipment/machinery including layout, foundation details, support details,


piping connections (if required), electrical connections etc.

- Fabrication drawings of all non standard equipment/machinery, support fittings/fixtures


etc.

- Layout of electrical switch boards, schematic electrical wiring diagrams etc.

- Automatic control system schematics, control system equipment layout and description
etc.

/conversion/tmp/activity_task_scratch/780588668.doc Fire_11
Shop drawings shall contain details of works for the other traders associated with fire hydrant
cum domestic water supply system to enable to coordinate the requirements by the Engineer.
Contractor shall submit 4 (four) copies of each shop drawing.

22.22 TRAINING

The Tenderer shall arrange and provide adequate and proper training to essential staff of the
Employer for operation and maintenance of the machinery/equipment at no additional cost of
the contract.

The Training Program shall be drawn up and included with the offer. The Employer will
designate and depute the agreed number and category of personnel for the training which shall
be completed before completion of maintenance period.

All cost in this regard shall be on Contractor’s account.

22.23 PAINTING

The contractor shall arrange painting the pipe line, equipment and accessories with red colour
for fire fighting and green colour for domestic water supply system with flow indication. The
painting shall be made in two coats of red oxide (primer) and two coats of enamel / marine
paint of appropriate thickness and to the satisfaction of the Engineer-in-charge.

22.24 BILL OF QUANTITY

Quantity shall be counted as per actual requirement for the purpose of payment.

22.25.1 FLOW SWITCHS

Flow switches (mechanical / electrical assembly), UL Listed. Detects water flow in pipes
(doesn't turn on or off the water), used to sets off the alarms by activating electrical switches.
Having paddle across the inside of the pipe and paddle is on a lever that, when the water has
pushed aside the paddle, allows a pair of switches to activate, after a time delay as per
satisfaction of Engineer-in-Charge.

/conversion/tmp/activity_task_scratch/780588668.doc Fire_12

You might also like