Power Transformer
Power Transformer
1) Polarization index:
V1 N1
Transformation Ratio= V 2 = N 2 =K
4) Dielectric loss:
The power loss on insulating materials like oil, insulation substances in
transformers referred to as dielectric loss. It refers to heating of the dielectric
material by varying magnetic field causes heating of the material. When an
insulating material is subjected to an alternating electric field, the atoms get
stressed due to the inter atomic friction caused by repeated deformation. energy
released And due to this rotation of atomic structure (polarization) heat is
produced. It can be measured by loss tangent or tan delta. tan delta is the tangent
of the angle between the alternating field vector and the loss component of the
material. The higher the value of tan δ the greater the dielectric loss.
Definition:
Dielectric loss in bushings is the energy lost in the form of heat in the
insulating material of the bushing due to the application of an alternating voltage.
Causes:
Electrical Stress: High electrical stress across the bushing insulation can lead to
dielectric losses.
Deterioration of Insulation: Aging or degradation of the insulation material
increases dielectric losses.
Contaminants: Presence of moisture or other contaminants in the insulation
can increase dielectric losses.
Effects:
Heat Generation:
Increased dielectric loss generates heat, which can lead to overheating and
potential failure of the bushing.
Reduced Efficiency:
Higher losses reduce the overall efficiency of the transformer.
Insulation Degradation:
Continuous heat generation accelerates the aging of insulation, leading to
further losses and potential breakdown.
Monitoring:
Tan Delta Testing:
Measuring the dissipation factor (tan δ) to assess the condition of the
bushing insulation. A high tan δ indicates increased dielectric losses.
Dielectric Loss in Transformer Windings:
Definition:
Dielectric loss in winding is the energy lost as heat in the insulation
around the winding due to the alternating electric field.
Causes:
Electric Field:
The alternating electric field across the insulation of windings causes
dielectric losses.
Insulation Condition:
Degraded or aged insulation increases dielectric losses.
Effects:
Heat Generation:
Dielectric loss causes localized heating in the winding insulation, which
can lead to hot spots.
Efficiency Reduction:
Higher dielectric losses decrease the transformer's efficiency.
Accelerated Aging:
Heat generated from dielectric losses accelerates the aging process of the
insulation
.
Monitoring:
Power Factor Testing:
Assessing the power factor of the winding insulation to detect
increased dielectric losses.
Infrared Thermography:
Using thermal imaging to identify hot spots caused by dielectric
losses in the windings.
Mitigation Strategies:
Regular Maintenance:
Conduct regular inspections and testing (e.g., tan delta and power factor
tests) to monitor the condition of insulation in bushings and windings.
Perform thermographic surveys to detect and address hot spots.
Insulation Quality:
Use high quality insulation materials that have low dielectric losses and are
resistant to aging and contaminants.
Ensure proper sealing of bushings to prevent moisture ingress.
Condition Monitoring:
Implement online monitoring systems to continuously assess the dielectric
condition of insulation in bushings and windings.
Cooling Systems:
Maintain and ensure the efficient operation of cooling systems to dissipate
heat generated by dielectric losses.
The magnetic balance test is a most commonly used proactive test is performed
only on three phase transformers to detect the faults in the core and to verify the
imbalance in the magnetic circuit also to identify inter turn faults in the
transformer at the early stage of manufacturing work. The magnetic balance test
is usually done on the star side of a transformer. This is done by flux produced on
one of the limb is equal to summation of fluxes produced on other two limbs to
indicate no shorting.
The Magnetic balance test is only an indicative test for the transformer. Its results
are not absolute. It needs to be used in conjunction with other tests.
Transformer Magnetic Balance Test
Based on the results shown in the table above, if the voltage applied at one side is
equal the sum of the voltages obtained at the two other sides, this indicates that
the transformer is magnetically balanced. But If there is any short circuit between
turns, the sum of the two voltages may not be equal to the applied voltage.
6) Winding resistance:
The primary purpose of this test is to identify significant differences
between windings and detect any open connections. Measuring the resistance of
transformer windings ensures that each circuit is wired correctly and that all
connections are securely tightened.
The winding resistance in transformers can vary due to shorted turns, loose
connections, or deteriorating contacts in tap changers. Regardless of the
configuration, the resistance measurements are normally made phase to phase and
the readings are compared with each other to determine if they are acceptable.
Transformer winding resistance measurements are obtained by passing a
known DC current through the winding under test and measuring the voltage drop
across each terminal (Ohms law). Modern test equipment for this purposes
utilizes a Kelvin Bridge to achieve results.
Transformer oils are made from crude oil and are used in transformers and
other electrical equipment. The oil performs two main functions: insulation and
heat dissipation.
functional;
operational;
As for density, it is better if this parameter is low. This helps prevent the
formation of ice in the oil from water at subzero temperatures. Otherwise an
electric breakthrough becomes possible. The density of transformer oil at 20°С
must not exceed 895 kg/m3, or 897 kg/m3 at 15°С.
POUR POINT
WATER CONTENT
APPEARANCE
ACIDITY
New unused transformer oil must be neutral. During operation the acidity
gradually increases due to oxidation and aging of oil. The acid number of new oil
must not exceed 0.01 mg KOH/g.
CORROSIVE SULFUR
The presence of corrosive sulfur in the oil is not allowed due to its
aggressiveness to the copper, steel or silver surfaces in the transformer. It can
damage such components as switch contacts.
OXIDATION STABILITY
Transformer oil comes under the influence of many factors which reduce
its quality, such as high voltage, high temperature, oxygen, water etc. With time
the oil ages beyond usability in a transformer.
The oil can be restored using special equipment. Depending on the extent
of changes, purification may be sufficient. In other cases, when the oil is aged and
acidic, oil regeneration must be used.
Dissolved gas analysis (DGA) is the study of dissolved gases in transformer oil.
It is also referred to as a DGA test. Whenever a transformer undergoes abnormal
thermal and electrical stresses, certain gases are produced due to the
decomposition of the transformer oil. When the fault is major, the production of
decomposed gases are significant and they get collected in a Buchholz relay. But
when abnormal thermal and electrical stresses are not significantly high the
gasses due to decomposition of transformer insulating oil will get enough time to
dissolve in the oil.
Hence by only monitoring the Buchholz relay it is not possible to predict the
condition of the total internal healthiness of electrical power transformer. That is
In a DGA test, the gases in oil are extracted and analyzed to determine the
quantity of gasses in a specific amount of oil. By observing the percentages of
different gasses present in the oil, you can predict the internal condition of the
transformer.
Generally, the gasses found in the oil in service are hydrogen (H 2), methane
(CH4), Ethane (C2H6), ethylene (C2H4), acetylene (C2H3), carbon monoxide (CO),
carbon dioxide (CO2), nitrogen (N2) and oxygen(O2).
Most commonly used method of determining the content of these gases in oil, is
using a Vacuum Gas Extraction Apparatus and Gas Chronographs. Using this
apparatus, gasses are extracted from oil by stirring it under vacuum. These
extracted gasses are then introduced in gas Chronographs for measurement of
each component.
9)SFRA:
Red color needle tells us how much maximum temperature was rose. It mean
WTI, OTI is telling us two parameters; present temperature and maximum noted
temperature of winding and oil.
We can see 150 degrees values of OTI, which means at 150 160 degrees oil will
burn up. This is the maximum temperature value.
We can see 150 degrees values of WTI, which means at 150 160 degrees winding
will burn up. This is maximum temperature value.
We can set up an alarm for tripping at a specific temperature value and at that
value circuit breaker will ring alarm and after that at specific value there will be
tripping in circuit breaker.
We perform wiring in circuit breaker relay. In other words, if we are not able to
monitor temperature or oil values continuously, then on our set value relay
will ring alarm and trip on our pre set value.
OTI tripping:
WTI tripping:
Relay will take these values as an abnormal condition and will trip over these
values with an alarm before tripping.
On dial of WTI and OTI is for 2 degrees. So, these meters are crucial in industry
working and operation.
11)OLTC operation:
turns on the regulating winding. The raise or lower mode is dependent on the
polarity of the connection through the switch.
The neutral position is the normal position where the LTC is neither raising or
lowering voltage and/or where the tap windings are not in the circuit. The neutral
position is the only position where the reversing switch is not carrying current.
OLTC Testing:
Exciting current tests are capable of detecting a wide range of transformer tap
changer problems in both de energized and on load tap changers. Mechanical
issues such as misalignment, contact wear, loose connections, open or short
circuited turns, and much more can be identified through these tests.
DC winding resistance is a valuable test for detecting potential problems with the
current carrying path of a transformer circuit. It can identify loose electrical
connections and pinpoint partial open circuited conditions by applying a known
DC current and measuring the voltage drop between each test point.
Dynamic winding resistance is another test that measures DC current and
resistance as a function of time as the OLTC changes tap position. This test is
best used to identify potential problems with the diverter circuit or transition
resistors of an OLTC during operation.
The turns ratio of each tap should also be checked when measuring the ratio of
the main transformer windings. When performing Sweep frequency response
analysis (SFRA) on transformers, the mechanical integrity of the tap windings
and their leads are included with the mid to upper frequency ranges.
The frequency of tap changer inspection and testing varies depending on the
environmental and physical conditions of the equipment, as well as the criticality
of the tap changer and associated transformer in relation to the overall power
system. Since tap changers are mechanical devices, it is recommended to take an
oil sample each year, with electrical testing performed at least every two years.
12)Thermogram:
4. Load Analysis:
Balanced Loading: Ensuring the transformer is not experiencing unbalanced
loading which can cause localized heating and premature aging.
Overloading: Identifying overload conditions that cause excessive heating and
can lead to thermal runaway.
Benefits of Using Thermography in Transformers:
Procedure:
The core loss current can be considered the resistive loss in the core and is
in phase with the applied voltage. Core loss current determines the noload losses
of the transformer. Core loss current represents the noload losses of the
transformer and includes iron losses, small dielectric losses and copper losses
caused by flow of excitation current. Of these only the iron losses caused by
eddy currents are significant. Losses depend on frequency, maximum flux
density and characteristics of magnetic circuit. Core loss values are usually
provided from transformer factory at the time of product delivery.
Magnetizing current
Any core problem will increase the reluctance of the magnetic circuit and
consequently higher primary current. A turn to turn short will create additional
current flow in the transformer that will translate in to higher than expected
exciting current. Higher than expected/published exciting current will indicate
problems with the transformer that may need additional inspection.
Exciting current and noload loss measurements are recommended as routine
diagnostic tests and during acceptance testing or when the transformer is
subjected to extreme physical stress.
In OFAN cooling, the oil is forced through the transformer windings and core,
allowing for more efficient heat transfer. The heated oil is then cooled by natural
convection, eliminating the need for fans or pumps.
RESIDUAL LIFE ASSESSMENT
SCOPE OF STUDY:
The scope of the study broadly includes review and assessment of present
The aim of study is to assess the current health of the transformers for the
132KV substation and its recommendations of various Tests can be made the system in
service at rated capacity with an extension of life for Long term.
Available documents and drawings were studied along with the O&M records
of the substation. Also detailed interactions with the plant authorities and O & M
personnel’s of the 132KV systems were held to gain insight of the operational history
and behavior of the equipment in addition to walk down surveys and spot studies.
The results obtained from the above studies have been used as the basis for
health assessment of transformer for preparation of this detailed report. It was decided
that the testing of equipment shall be carried out in one phase. The list of equipment
within the scope of RLA study and their present testing status are as mentioned.
Ratio Measurement.
Thermo Gram.
Based on the life expenditure evaluation conducted through analysis and tests,
items can be classified into categories such as:
Condition Assessment
The condition assessment of transformers primarily involves either or both of the
following approaches:
Electrical / Non Destructive Tests (NDT): These tests determine the necessary
corrective actions for ensuring trouble free operation.
Functional / Operational Checks: These checks involve comparing operational
results with design parameters to assess the condition of the equipment.
The entire RLA study is carried out through the following steps:
1. Site Study and Data Collection: Conduct a thorough site study, collect relevant
data, and assess the current condition of the equipment.
2. Action Plan Finalization: Develop a detailed action plan for conducting the
study and tests.
3. Non Destructive Testing: Perform NDT on various plant equipment according
to the agreed plan and schedule.
4. Compilation of Test Results: Gather and compile the results of the tests
conducted.
5. Analysis of Test Results: Analyze the test results to determine the need for
refurbishment or replacement, aiming to extend the operating life by another
1520 years.
Observations / Analysis: -
i. As there is no base SFRA plot is available for this unit, and Open circuit
SFRA
ii. The Polarization index for the transformer and DC absorption ratio are
found satisfactory.
iii. No hot spot found in the transformer body, bushings and connectors etc.
iv. From the oil test result for the transformer oil Electric Strength (Break
down voltage) found low, [As per IS: 1866 the break down voltage should be
40KV RMS or more, but the value for the oil is 16 KV RMS only.
v. From the oil test result for the transformer oil, Water content (ppm) found
high, [As per IS: 1866 the Water content (ppm) should be 40ppm or less, but the
value for the oil is 58 ppm.
vi. From the oil test result (DGA) some count of Methane 28ppm and it may
be due to local over heating
viii. Ethane 11ppm, it may be due to over heating / thermal fault less then
300 Deg.C.
ix. Acetylene 1 ppm it may be due to internal arcing & Sparking / thermal
fault more then 700 Deg.C.
Method: 1
Method: 2
The moisture in oil (in ppm) is obtained from oil analysis = 58 ppm
= 0.0175<1
Thus for a designed life of hrs for normal life for the temp Class A
1%
= 3.88 %
1%
= 3.88
= 264768 hrs.
Assuming the transformer is operating for 26 years of the given 227760 hrs
since
manufacturing (1976).
The residual life of the transformer is calculated based on the assumption that it
will continue to operate under conditions similar to its current operation. If the
load or temperature increases, the expected lifespan will decrease accordingly.
The low moisture content reported in the Dissolved Gas Analysis (DGA)
suggests that the transformer is either in excellent condition or that the oil has
been recently filtered or reclaimed. This low moisture content contributes to a
longer transformer life. However, if the hotspot temperatures are higher than
currently assumed, especially during the summer, the transformer's lifespan will
decrease more significantly.
ELECTRICAL TESTS
GENERAL
Various electrical tests were carried out as per the list already furnished in
scope of study to assess the Present health and Residual life of the transformers
and also to identify major "Malfunction" conditions.
POWER TRANSFORMER - 1
Observations / Analysis:
As there is no base SFRA plot is available for this unit, and Open circuit SFRA
measurements are identical for Three Phases on 3 Different Tap, which gives
indication of no sign of any winding movement. The SFRA plot measured for
the transformer are found in order and does not indicate any abnormality by
Analyzing the 3 Different Tap’s of open and short circuit SFRA plots of unit.
This is a good reference plots for future measurement. The Polarization index for
the transformer and DC absorption ratio are found
satisfactory.
No hot spot found in the transformer body, bushings and connectors etc.
From the oil test result for the transformer oil Electric Strength (Break down
voltage) found low, [As per IS: 1866 the break down voltage should be 40KV
RMS or more, but the value for the oil is 16 KV RMS only.
From the oil test result (DGA) some count of Methane 28ppm and it may
be due to local over heating
Ethane 11ppm, it may be due to over heating / thermal fault less then 300
Deg.C.
All the above parameters are more related with the high temperature. More over
Recommendations:
Make : CGL
Rating : 18 MVA
Sl No : 24497
Frequency : 50 Hz
%Z : 9.71%