QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Overview

Enlogic by nVent G3 Basic Series Standard Power Distribution Units for HPE
Basic, reliable power distribution for your HPE IT solutions
Enlogic by nVent G3 Basic Series PDUs for HPE are designed to work precisely with HPE Infrastructure and Compute solutions
and guarantee a compatible fit for use with HPE Advanced, and Enterprise racks (and compatible with other industry-standard
server racks). Built with high-temperature grade premium components, Enlogic by nVent G3 Basic Series PDUs for HPE can
operate in temperatures up to 60°C over extended periods of time and provide reliable operation backed by a 5-year warranty.

HPE offers a range of PDU models with mounting options that promote flexible power configuration in racks. Vertical, Horizontal,
and True 0U mounting, giving you the flexibility to efficiently utilize rack space while placing access to power where you need it
most. Serviceability is further enhanced with features such as C13/C19 Combination outlets, color-coded outlets and low-profile
form factors allowing for simple and quick access to IT equipment and power cables in the rear of the rack.

HPE IEC Locking Power Cords are a supported option available for the G3 Basic PDU series. The IEC Locking Power Cords provide
secure cable retention to both the PDU and target device against vibration during shipping and ensuring that cables are not
dislodged during a service event. HPE’s IEC Locking Power Cords provide a safe and secure solution against the common issues
that lead to power-related downtime.

Why G3 Basic series PDUs?


All G3 Basic PDUs are rated for operating temperatures up to 60°C (or 140°F).
• Addition of C13/C19 Combination outlets for flexible deployment.
• Low-profile PDU form factors providing enhanced IT serviceability in the back of the rack while adhering to the rack keep
out zone.
• G3 Basic PDUs with IEC C19, C13 and combination receptacles have integrated cord retention.
• G3 Basic PDUs have color-coded receptacles to easily distinguish between the different load segments/phases.
• High-density vertical form factor providing 24 outlets in a half-height (22U) and 48 outlets in a full-height (42U).
• HPE offers multiple PDU form factors that promote efficient use of space in the rack and provide flexibility in mounting
and configuration.
• 1U Horizontal PDUs can support True 0U mounting (between the RETMA rails), minimizing the need to use valuable U
space in racks for power distribution.
• Vertical G3 PDUs use a button mounting system that allows for installation with outlets facing front, rear or center of rack.
• HPE guarantees 100% compatibility between its Rack and Power Infrastructure products and its industry-standard
compute, storage, and networking solutions, backed with a Enlogic 5-year warranty for all G3 Basic PDU models.

Enlogic by nVent G3 Metered Series Advanced Power Distribution Units for HPE

Setting new standards for reliable power distribution and metering


Enlogic by nVent G3 Metered PDUs for HPE are designed to work precisely with HPE Infrastructure and Compute solutions,
providing a highly accurate (billing grade accuracy) power distribution and metering solution for your racks. Designed for use with
HPE Advanced, and Enterprise racks (and compatible with other industry-standard server racks), G3 Metered PDUs guarantee a
compatible fit and reliable operation backed by a Enlogic 5-year warranty. G3 Metered PDUs are also rated for operating
temperatures up to 60°C, adding an increased level of operational reliability for power distribution in IT racks.

A major concern for IT administrators and facility managers is their ability to quickly diagnose and service power related problems in
their IT racks. The G3 PDU metered portfolio addresses this problem by, first, offering a wide range of models and mounting options
that promote flexible power configuration in IT racks. Vertical, Horizontal, and True 0U mounting, give you the flexibility to
efficiently utilize rack space while placing access to power where you need it most in the rack. Serviceability is further enhanced with
features such as color-coded outlets and low-profile form factors, allowing for simple and quick access to IT equipment and power
cables in the rear of the rack.

Page 1
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Overview

Enlogic by nVent G3 Metered PDUs for HPE features are also directly focused on other pain points in the data center. 1Gb Ethernet
alleviates the need to maintain older switch solutions that have been traditionally required for PDU network connectivity. High-
density outlet configurations that provide up to 48 power outlets in a full-height vertical form factor allow for simple access to power
in the rack while minimizing physical cable requirements. Support for up to eight sensors per PDU provides a cost-effective and
exhaustive solution for monitoring the environmental elements (temperature, humidity, and leakage) in both the front and rear of
the rack.

HPE IEC Locking Power Cords are a supported option available for most G3 Metered PDUs. The IEC Locking Power Cords provide
secure cable retention to both the PDU and target device, protecting against vibration during shipping and ensuring that cables are
not dislodged during a service event. The HPE IEC Locking Power Cords provide a safe and secure solution against the common
issues that lead to power-related downtime.
Why HPE Metered PDUs?
• Addition of C13/C19 Combination outlets for flexible deployment.
• load segment power metering.
• HPE guarantees 100% compatibility between its Rack and Power Infrastructure products and its industry-standard
compute, storage, and networking solutions, backed with a 5-year warranty for all G3 Metered PDU models.
• HPE offers multiple Metered PDU form factors that promote efficient use of space in the rack and provide flexibility in how
each PDU can be mounted and configured with cables.

Enlogic by nVent G3 Metered and Switched Series Enterprise Power Distribution Units for HPE
New G3 features allow for greater management of power and environment in IT racks
Enlogic by nVent G3 Metered and Switched PDUs are designed to work precisely with HPE Infrastructure and Compute solutions,
providing a highly accurate (billing grade accuracy) power distribution solution with outlet-level metering and switching for your IT
racks. Designed for use with HPE Advanced, and Enterprise racks (and compatible with other industry-standard server racks), G3
Metered and Switched PDUs guarantee a compatible fit and reliable operation backed by an Enlogic 5-year warranty. G3 Metered &
Switched PDUs are also rated for operating temperatures up to 60°C, adding an increased level of operational reliability for power
distribution in your IT racks.

A major concern for IT administrators and facility managers is their ability to quickly diagnose and service power related problems in
their IT racks. G3 Metered & Switched PDU features such as color-coded outlets and low-profile form factors allow for simple and
quick access to IT equipment and power cables in the rear of the rack.

G3 Metered & Switched PDU features are also directly focused on other pain points in the data center. 1Gb Ethernet alleviates the
need to maintain older switch solutions that have been traditionally required for PDU network connectivity. High-density outlet
configurations that provide up to 48 power outlets in a full-height vertical form factor allow for simple access to power in the rack
while minimizing physical cable requirements. Support for up to eight sensors per PDU provides a cost-effective and exhaustive
solution for monitoring the environmental elements (temperature, humidity, and leakage) in both the front and rear of the rack.

All G3 Metered & Switched PDU models feature support for the HPE IEC Locking Power Cords, a new supported option available for
most HPE G3 PDUs. The IEC Locking Power Cords provide secure cable retention to both the PDU and target device, protecting
against vibration during shipping and ensuring that cables are not dislodged during a service event. HPE’s IEC Locking Power Cords
provide a safe and secure solution against the common issues that lead to power-related downtime.

Why HPE Metered and Switched PDUs?


• Addition of C13/C19 Combination outlets for flexible deployment.
• Outlet-level metering and switching for your IT racks.
• HPE guarantees 100% compatibility between its Rack and Power Infrastructure products and its industry-standard
compute, storage, and networking solutions, backed with an Enlogic 5-year warranty for all G3 Metered PDU models.
• HPE offers multiple Metered and Switched PDU form factors that promote efficient use of space in the rack and provide
flexibility in how each PDU can be mounted and configured with cables.

Page 2
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Standard Features

Horizontal Form Factors


1U Horizontal

Top view Elevated view

Vertical Form Factors

Half-Height

Top view Elevated view

Mid-Height

Top view

Elevated view

Full-Height

Top view

Elevated view

Page 3
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Standard Features

Enlogic by nVent G3 Basic Series Power Distribution Units for HPE


Compatibility
• Designed specifically for use with HPE rack enclosures and IT solutions but can work with most 3rd party IT racks
• Addition of C13/C19 Combination outlets for flexible deployment.

Reliability/Durability
• 5-year Enlogic warranty
• High reliability at elevated operating temperature levels (up to 60°C)

Usability/Serviceability
• Wide range of mounting options including vertical, 1U/2U horizontal, and True 0U
• Modular PDU options supporting True 0U mounting between the RETMA rails of the rack
• High-density vertical power outlet configurations with up to 48 outlets on a single PDU
• Full range of single and three phase input and output power capabilities
• 1.9kVA to 22kVA power distribution to meet the needs of both small and large data centers
• Built-in three-sided button mounting system supporting flexible installations
• Low-profile PDU form factors providing enhanced IT serviceability in the back of the rack
• Color coded receptacles and circuit breaker banks to easily identify specific outlets
• Multiple extension bar options that inexpensively expand outlet configurations
• Combination outlets that can accept C13 or C19 power cords

Safety/Security
• Optional dual-locking power cords that secure both power connections
• Support for integrated individual power cord retention

True 0U Mounting
All G3 Horizontal PDUs can be installed in any U position in your rack. However, G3 1U Horizontal PDUs have a unique
architecture designed specifically for data center customers who want to maximize space efficiencies in the rack. These models can
be installed in the 0U space between the RETMA rails on HPE Advanced and Enterprise Series racks (see diagram below)

Modular PDU Form / Factor


G3 Standard series Modular PDUs combine True 0U and 1U Horizontal mounting support with the capability of adding extension
bars to expand access to power in the back of the rack. Extension Bars mount directly to the frame of the rack in multiple locations
allowing you the flexibility of placing access to power where it is needed most. Multiple extension bar options are available to help
you customize the outlet configurations you require.

HPE PDU Extension Bar / Options


G3 PDU extension bar options help expand the availability of power in the rear of the rack. Each extension bar includes a locking
input power cord that connects to the PDU and supports HPE’s new IEC Locking Power Cords (for C13/C14 and C19/C20
connections). HPE PDU extension bars can be added to Horizontal and Vertical PDU models with available C20 outlets for
additional outlets and are compatible with previous generation PDU models that offer C20 outlets (locking feature only supported
on new G3 PDU models). See the Related Options section for more information on G3 Extension Bar models.

High-Density Vertical / PDU Models


High-density vertical PDU models provide 24 outlets in a half-height (22U) form factor and 48 outlets in a full-height (42U) form
factor. This density is achieved by placing the power receptacles on one side of the PDU and access to the circuit breakers on the
opposite side without significantly impacting the height (profile) of the PDU. See the Model Matrix section for more information on
high-density Vertical PDU models.

Page 4
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Standard Features

IEC Locking Power Cords


G3 PDU models support optional IEC Locking Power Cords with an integrated locking technology on both ends of the cable.
Locking Power Cords are available for both C13/14 and C19/20 power connections, include multiple cable length options, and
can be purchased in single or six-pack kits. One IEC Locking Power Cord has been included with each PDU model that supports
either a C13 and/or C19 outlet.

Color-Coded Outlets
All G3 PDU models include color-coded outlets. Highly visible from the rear of the rack, color-coding helps to easily and clearly
identify outlets to simplify cabling and power phase balancing when configuring and maintaining power for your IT equipment.

Rated for High Operating Temperatures


G3 PDUs are rated for operating temperatures up to 60°C (or 140°F). HPE G3 PDUs are designed with high temperature rated
premium components and construction that support increased reliability levels at elevated temperatures.

5-Year Warranty
G3 Standard series PDU models are supported with a Enlogic 5-year warranty.

Enlogic by nVent G3 Metered Series Advanced Power Distribution Units for HPE
HPE G3 Metered Power Distribution Units
Power Metering and Management
• All G3 HPE Metered PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in power metering of:
− Amperage
− Voltage
− Wattage
− Kilowatts per hour
• An OLED display provides local monitoring and alert indications
• Remote PDU management and power monitoring supported through integrated web-based user interface, CLI, and third-
party software applications supporting SNMP

Compatibility
• Designed specifically for use with HPE rack enclosures, but compatible with most 3rd party IT racks
• Addition of C13/C19 Combination outlets for flexible deployment.
• Integrated web-based user interface compatible with IPv4/IPv6 and SNMPv1/SNMPv3

Usability
• Wide range of mounting options including vertical, 1U/2U horizontal, and True 0U (between the RETMA rails)
configurations
• Low-profile PDU form factors ensure integrity of rear-rack keep-out zone for IT maintenance
• Color-coded receptacles to easily distinguish between the different load segments/phases
• Integrated cord retention on all IEC C19 and C13 receptacles (does not require any additional brackets)
• Local and remote firmware updates

Security
• Local and LDAP security with multiple access levels
• Support for HTTP, HTTPS, SSH protocols
• Configurable alarm thresholds for both power and environmental monitoring
• Optional dual-locking power cords securing both power connections

HPE G3 Metered PDUs support multiple features that are unique to HPE and help to provide the best user experience.
Information on these features is summarized below with additional information found online in HPE G3 Metered PDU User’s Guide.

Page 5
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Standard Features

Rated for High Operating Temperatures


Increasing IT densities and escalating operating costs have created a need for rack infrastructure that can operate reliably at
higher operating temperatures. HPE G3 PDUs have been designed with high temperature-rated premium components and
construction that support increased reliability levels at elevated temperatures. HPE G3 PDUs are rated for operation in
temperatures up to 60°C (or 140°F) in the rear of the rack.

IEC Locking Power Cords


HPE G3 PDU models support optional IEC Locking Power Cords with an integrated locking technology on both ends of the cable.
HPE Locking Power Cord are available for both C13/14 and C19/20 power receptacles in multiple cable length options and can be
purchased in single or six-pack kits. One IEC Locking Power Cord has been included with each PDU model that supports either a
C13 and/or C19 outlet.

High-Density Vertical PDU Models


High-density Vertical PDU models provide 24 outlets in a half-height (22U) form factor and 48 outlets in a full-height (42U) form
factor. This density is achieved by placing the power receptacles on one side of the PDU and access to the circuit breakers on the
opposite side without significantly impacting the height (profile) of the PDU. See the Model Matrix section for more information on
high-density Vertical PDU models.

Color-Coded Outlets
All HPE G3 PDU models now include color-coded outlets which are highly visible from the rear of the rack. The color-coding helps
to easily and clearly identify outlets to simplify cabling and power phase balancing when configuring your IT equipment.

1Gb Ethernet Support


HPE is the first IT solutions company to standardize on 1Gb Ethernet for PDU network connectivity. This eliminates the need to
maintain older switching solutions needed for the 10/100 connectivity provided by most other PDU manufacturers.

Environmental Sensors
HPE G3 Metered PDU models include two environmental sensor ports (can be upgraded to six ports with the addition of up to two
G3 PDU Sensor Port Hubs) that can monitor and record up to eight sensor measurements. Multiple senor options are available
providing the ability to monitor temperature, humidity, water leakage, and intrusion for each rack. Please review the Related
Options section for a list of the options available.

Flexible Mounting
Most vertical HPE G3 PDU models support mounting on the back and both sides of the PDU using a button and keyhole mounting
system for easy drop-in installation. This provides a flexible mounting capability that allows power cables to be configured toward
the front, middle, or rear of the rack, allowing users to customize their cable management strategy specifically for each rack.

True 0U Mounting
HPE Horizontal PDUs have a unique design specifically for data center customers who want to maximize space efficiencies in the
rack. All HPE 1U Horizontal PDUs can be installed in any U position in your rack or can be installed in the 0U space between the
RETMA rails on HPE Advanced and Enterprise Series racks (see figure below).

Page 6
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Standard Features

HPE PDU Extension Bar Options


HPE PDU extension bar options help expand the availability of power in the rear of the rack. Each extension bar includes a locking
input power cord that connects to the PDU and supports HPE’s new IEC Locking Power Cords for C13/C14 and C19/C20 outlets.
HPE PDU extension bars can be added to Horizontal and Vertical PDU models, with available C19 outlets, to add additional power
outlets and expand access to power in the back of the rack when needed. Extension Bars mount directly to the frame of the rack in
multiple locations allowing you the flexibility of placing access to power where it is needed most (see figure above). Multiple
extension bar options are available to help you customize the outlet configurations you require extension bars are also compatible
with previous generation PDU models that offer C20 outlets (locking feature only supported on new G3 PDU models). See the
Related Options section for more information on G3 Extension Bar models.

5-Year Warranty
All Enlogic by nVent G3 Series Power Distribution Units for HPE are supported with a 5-year Enlogic warranty. Please visit
https://www.nvent.com/en-us/data-solutions/support/hpe for product registration and support.

nVent warranties that Enlogic by nVent G3 Series Power Distribution Units for HPE shall be free from manufacturing defects for a
period of five (5) years from the invoice date to the original purchaser.

Enlogic by nVent G3 Metered and Switched Series Enterprise Power Distribution Units for HPE
Power Metering and Management
• All G3 HPE Metered & Switched PDUs meet IEC 62053-21, Class 1 standards for ±1% or better accuracy in outlet-level
power metering of:
− Amperage
− Voltage
− Wattage
− Kilowatts per hour
• OLED display provides local monitoring and alert indications
• Remote PDU management and power monitoring supported through integrated web-based user interface, CLI, and third-
party software applications supporting SNMP

Compatibility
• Designed specifically for use with HPE rack enclosures, but compatible with most 3rd party IT racks
• Integrated web-based user interface compatible with IPv4/IPv6 and SNMPv1/SNMPv3

Usability
• Multiple full-height vertical models with a range of outlet configurations
• Low-profile form factors ensure integrity of rear-rack keep-out zone for IT maintenance
• Color-coded receptacles to easily distinguish between the different load segments/phases
• Integrated cord retention for all IEC C19 and C13 receptacles
• Optional dual-locking power cords securing both power connections
• Local and remote firmware updates

Security
• Outlet-level on/off power switching that can be accessed locally and remotely
• Local and LDAP security with multiple access levels
• Support for HTTP, HTTPS, and SSH protocols
• Configurable alarm thresholds for both power and environmental monitoring
HPE G3 Metered & Switched PDUs support multiple features that are unique to HPE and help to provide the best user experience.
Information on these features is summarized below with additional information found online in HPE G3 Metered & Switched PDU
User’s Guide.

Page 7
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Standard Features

Rated for High Operating Temperatures


Increasing IT densities and escalating operating costs have created a need for rack infrastructure that can operate reliably at higher
operating temperatures. HPE G3 PDUs have been designed with high temperature-rated premium components and construction
that support increased reliability levels at elevated temperatures. HPE G3 PDUs are rated for operation in temperatures up to 60°C
(or 140°F) in the rear of the rack.

IEC Locking Power Cords


HPE G3 PDU models support optional IEC Locking Power Cords with an integrated locking technology on both ends of the cable.
HPE Locking Power Cord are available for both C13/14 and C19/20 power receptacles in multiple cable length options, and can be
purchased in single or six-pack kits. One IEC Locking Power Cord has been included with each PDU model that supports either a
C13 and/or C19 outlet.

High-Density Vertical PDU Models


High-density Vertical PDU models provide 48 outlets in a full-height (42U) form factor. This density is achieved by placing the
power receptacles on one side of the PDU and access to the circuit breakers on the opposite side without significantly impacting the
height (profile) of the PDU. See the Model Matrix section for more information on high-density PDU models.

Color-Coded Outlets
All HPE G3 PDU models now include color-coded outlets which are highly visible from the rear of the rack. The color-coding helps to
easily and clearly identify outlets to simplify cabling and power phase balancing when configuring your IT equipment.

1Gb Ethernet Support


HPE is the first IT solutions company to standardize 1Gb Ethernet for PDU network connectivity. This eliminates the need to maintain
older switching solutions needed for the 10/100 connectivity provided by most other PDU manufacturers.

Environmental Sensors
HPE G3 Metered & Switched PDU models include two environmental sensor ports (can be upgraded to six ports with the addition of
up to two G3 PDU Sensor Port Hubs) that can monitor and record up to eight sensor measurements. Multiple senor options are
available providing the ability to monitor temperature, humidity, water leakage, and intrusion for each rack. Please review the Related
Options section for a list of the options available.

Flexible Mounting
Most vertical HPE G3 PDU models support mounting on the back and both sides of the PDU using an industry-standard button and
keyhole mounting system for easy drop-in installation. This provides a flexible mounting capability that allows power cables to be
configured with outlets facing toward the center, back, or front of the rack.

HPE PDU Extension Bar Options


HPE PDU extension bar options help expand the availability of power in the rear of the rack. Each extension bar includes a locking
input power cord that connects to the PDU and supports HPE’s new IEC Locking Power Cords for C13/C14 and C19/C20 outlets.
HPE PDU extension bars can be added to Horizontal and Vertical PDU models, with available C19 outlets, to add additional power
outlets and expand access to power in the back of the rack when needed. Extension Bars mount directly to the frame of the rack in
multiple locations allowing you the flexibility of placing access to power where it is needed most (see figure above). Multiple
extension bar options are available to help you customize the outlet configurations you require extension bars are also compatible
with previous generation PDU models that offer C20 outlets (locking feature only supported on new G3 PDU models). See the
Related Options section for more information on G3 Extension Bar models.

Page 8
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Configuration Information

HPE Power Advisor


HPE has created the HPE Power Advisor utility that provides meaningful estimates of the power needs for HPE Enterprise Solutions.
Our tool is used for estimating power use of the major components within a rack to determine power distribution, power redundancy,
and battery backup requirements for computer facilities. Power Advisor allows you to configure each individual server or node. You
can then duplicate the server configuration as often as necessary to populate an enclosure or rack, and then duplicate a rack. The
outcome is that you can build a complete data center quickly. Click Here to access the HPE Power Advisor.

Enlogic by nVent G3 Basic Series Standard Power Distribution Units for HPE
100-240V Input, Single Phase, WW
Enlogic by nVent G3 Basic 1-phase 3.6kVA/IEC60320 C20 16A/100-240V PDU for HPE P59407-B21
200-240/346-415V Input, Three Phase, WW
Enlogic by nVent G3 Basic 3-phase 22kVA/IEC60309 532P6 32A/200-240V PDU for HPE P59418-B21
200-240V Input, Single Phase, North America/Japan
Enlogic by nVent G3 Basic 1-phase 4.9kVA/L6-30P 24A/200-240V PDU for HPE P59420-B21
Enlogic by nVent G3 Basic 1-phase 4.9kVA/L6-30P 24A/200-240V PDU for HPE P59519-B21
220-240V Input, Three Phase, North America/Japan
Enlogic by nVent G3 Basic 3-phase 17.2kVA/IEC60309 460P9 48A/200-240V PDU for HPE P59415-B21
Enlogic by nVent G3 Basic 3-phase 8.6kVA/L15-30P 24A/200-240V PDU for HPE P59521-B21
Enlogic by nVent G3 Basic 3-phase 8.6kVA/L15-30P 24A/200-240V PDU for HPE P60344-B21
200-240V Input, Single Phase, INTL
Enlogic by nVent G3 Basic 1-phase 7.3kVA/IEC60309 332P6 32A/200-240V PDU for HPE P59421-B21
Enlogic by nVent G3 Basic 1-phase 7.3kVA/IEC60309 332P6 32A/200-240V PDU for HPE P59520-B21
Enlogic by nVent G3 Metered Series Advanced Power Distribution Units for HPE
200-240/346-415V Input, Three Phase, WW
Enlogic by nVent G3 Metered 3-phase 11kVA/IEC60309 516P6/520P6 16A/200-240V PDU for HPE P59412-B21
Enlogic by nVent G3 Metered 3-phase 22kVA/IEC60309 532P6 32A/200-240V PDU for HPE P59417-B21
Enlogic by nVent G3 Metered 3-phase 22kVA/IEC60309 532P6 32A/200-240V PDU for HPE P67672-B21
100-120V Input, Single Phase, North America/Japan
Enlogic by nVent G3 Metered 1-phase 2.8kVA/L5-30P 24A/120V PDU for HPE P59406-B21
200-240V Input, Single Phase, North America/Japan
Enlogic by nVent G3 Metered 1-phase 4.9kVA/L6-30P 24A/200-240V PDU for HPE P59408-B21
Enlogic by nVent G3 Metered 1-phase 8.3kVA/CS8265C 40A/200-240V PDU for HPE P59410-B21
200-240V Input, Three Phase, North America/Japan
Enlogic by nVent G3 Metered 3-phase 8.6kVA/L15-30P 24A/200-240V PDU for HPE P59411-B21
Enlogic by nVent G3 Metered 3-phase 17.2kVA/IEC60309 460P9 48A/200-240V PDU for HPE P59414-B21
200-240V Input, Single Phase, INTL
Enlogic by nVent G3 Metered 1-phase 14.4kVA/IEC60309 363P6 63A/200-240V PDU for HPE P59413-B21
Enlogic by nVent G3 Metered and Switched Series Enterprise Power Distribution Units for HPE
200-240V Input, Three Phase, WW
Enlogic by nVent G3 Metered Switched 3-phase 22kVA/IEC60309 532P6 32A/200-240V PDU for HPE P59419-B21

Page 9
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Related Options

Extension Bars
HPE G2 IEC C20 Input/(8) C13 Expansion Outlets/PDU Extension Bar Kit P9Q66A
Notes: kit include 2 extension bars with a locking C19 input power cord (1.8m).

IEC Locking Power Cords


HPE C13 - C14 WW 250V 10Amp 0.7m Black Locking Power Cord Q0P67A
HPE C13 - C14 WW 250V 10Amp 0.7m Black 6-pack Locking Power Cord Q0Q02A
HPE C13 - C14 WW 250V 10Amp 1.4m Black Locking Power Cord Q0P68A
HPE C13 - C14 WW 250V 10Amp 1.4m Black 6-pack Locking Power Cord Q0Q03A
HPE C13 - C14 WW 250V 10Amp 2m Black Locking Power Cord Q0P69A
HPE C13 - C14 WW 250V 10Amp 2m Black 6-pack Locking Power Cord Q0Q04A
HPE C13 - C14 WW 250V 10Amp 3m Black Locking Power Cord Q0P70A
HPE C19 - C20 WW 250V 16Amp 0.7m Black Locking Power Cord Q0R19A
HPE C19 - C20 WW 250V 16Amp 2m Black Locking Power Cord Q0P72A
HPE C19 - C20 WW 250V 16Amp 2m 6-pack Black Locking Power Cord Q0R17A
Notes: HPE Locking Power Cords are only supported on either C13/14 or C19/20 outlets using HPE G2 PDUs.

IEC Standard Power Cords


HPE C13 - C14 WW 250V 10Amp 1.4m Jumper Cord 142257-006
HPE C13 - C14 WW 250V 10Amp 2.0m Jumper Cord A0K02A
HPE C13 - C14 WW 250V 10Amp Flint Gray 2.0m Jumper Cord AF573A
HPE C13 - C14 WW 250V 10Amp 2.5m Jumper Cord 142257-002
HPE C13 - C14 WW 250V 10Amp 3.0m Jumper Cord 142257-003
HPE C20 - C13 WW 250V 15Amp 2.0m Jumper Cord AF590A
HPE C19 - C20 WW 250V 16Amp Flint Gray 1.20m Jumper Cord AF575A
HPE C19 - C20 WW 250V 16Amp Flint Gray 2.0m Jumper Cord AF574A
HPE C19 - C20 WW 250V 16Amp 2.5m Jumper Cord 295633-B22

Country-Specific Power Cords


HPE C13 - Nema 5-15P US/CA 110V 10Amp 1.83m Power Cord AF556A
HPE C13 - Nema 5-15P TH/PH 250V 10Amp 1.83m Power Cord AF559A
HPE C19 - CEE-VII EU 250V 16Amp 3.6m Power Cord AF576A
HPE C19 - Nema L6-20P NA/JP 250V 20Amp High Voltage 3.6m Power Cord AF593A
HPE 240 VAC 4.5M Unterminated End NA Power Cord E7806A

HPE Mounting Brackets


HPE Vertical PDU 10K G2 Mounting Kit H6L32A
Notes: This kit allows for vertical HPE G3 PDU models to be mounted in HPE 10000 G2 series racks and in the HPE Standard
Series rack.

Page 10
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Related Options
Environmental Sensors
G3 Metered PDUs include 2 physical sensor ports and can monitor and record up to eight sensor measurements. Data collected by
each sensor can be viewed and managed through the integrated graphical user interface (GUI), or by third-party applications that
communicate through SNMP or through a Redfish supported API. Consult the G3 Metered PDU User Guide for more information on
use with third-party software applications.
HPE G3 PDU Environmental Temperature Sensor P9T00A
Notes: Requires one input port and monitor/records one sensor measurement.
HPE G3 PDU Environmental Temperature and Humidity Sensor P9T01A
Notes: Requires one input port and monitors/records two sensor measurements.
HPE G3 PDU Environmental 3 Temperature and 1 Humidity Sensor P9T02A
Notes: Requires one input port and monitors/records four sensor measurements.
HPE G3 PDU Open Door Sensor P9T03A
Notes: Requires two input ports and monitors/records two sensor measurements.
HPE G3 PDU Leak Detection Sensor P9T04A
Notes: Requires one input port and monitors/records one sensor measurement. Kit covers up to six linear meters and can be
expanded to cover up to thirty linear meters with the addition of up to four HPE G3 PDU Leak Detection Sensor Extension Kits
(P9T08A).
HPE G3 PDU Sensor Port Hub P9T07A
Notes: This is an adapter that expands a single physical sensor port into three physical sensor ports.
HPE G3 PDU Leak Detection Sensor Extension Kit P9T08A
Notes: Leak Detection Sensor (P9T04A) must be purchased separately to use in conjunction with this kit. Up to four Extension
Kits can be added to a single Leak Detection Sensor to cover up to a maximum of thirty linear meters.

Page 11
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Technical Specifications

Model Matrix – Form Factor/Mounting Options


Mounting options for Horizontal 1U PDU models
Model WxHxD Unit Weight U Height Horizontal Mounting True 0U Mounting
(inches) (lbs.)
P59420-B21 1.713 x 17.441 x 7.835 10.56 1U  
P59421-B21 1.713 x 17.441 x 7.835 10.12 1U  
P60344-B21 1.713 x 17.441 x 7.835 11.66 1U  

Mounting options for Vertical PDU models in HPE Advanced and Enterprise racks (1075mm depth)
Model WxHxD Unit Weight Vertical Height Maximum PDUs per Side of Rack
(inches) (lbs.) 22U 36U 42U 48U
P59407-B21 2.047 x 32.165 x 2.087 4.84 Half-Height 2 2 4 4
P59519-B21 2.047 x 32.165 x 2.087 8.58 Half-Height 2 2 4 4
P59520-B21 2.047 x 32.165 x 2.087 7.92 Half-Height 2 2 4 4
P59521-B21 2.047 x 33.071 x 2.087 9.9 Half-Height 2 2 4 4
*P59415-B21 2.047 x 34.646 x 4.409 20.46 Half-Height 1 1 2 2
Double sided
*P59418-B21 2.047 x 34.646 x 4.409 15.62 Half-Height 1 1 2 2
Double sided
*P67671-B21 2.047 x 34.646 x 4.409 21.34 Half-Height 1 1 2 2
Double sided
*P67672-B21 2.047 x 34.646 x 4.409 16.94 Half-Height 1 1 2 2
Double sided
P59406-B21 2.047 x 58.661 x 2.087 11.88 Mid-Height n/a 2 2 2
P59408-B21 2.047 x 58.661 x 2.087 13.86 Mid-Height n/a 2 2 2
P59409-B21 2.047 x 58.661 x 2.087 13.42 Mid-Height n/a 2 2 2
P59410-B21 2.047 x 58.661 x 2.087 16.94 Mid-Height n/a 2 2 2
P59412-B21 2.047 x 58.661 x 2.087 13.64 Mid-Height n/a 2 2 2
**P59411-B21 2.047 x 58.661 x 15.62 Mid-Height n/a 2 2 2
2.087/2.953 (With
doghouse)
P59413-B21 2.047 x 68.898 x 2.087 22.66 Full-Height n/a n/a 2 2
*P59414-B21 2.047 x 68.898 x 4.409 28.6 Full-Height n/a n/a 1 1
Double sided
*P59416-B21 2.047 x 71.654 x 4.409 32.78 Full-Height n/a n/a 1 1
Double sided
*P59417-B21 2.047 x 68.898 x 4.409 23.76 Full-Height n/a n/a 1 1
Double sided
*P59419-B21 2.047 x 71.654 x 4.409 27.72 Full-Height n/a n/a 1 1
Double sided

Notes:
− HPE G2 Advanced and Enterprise 1200mm deep racks include an extra set (2) of PDU trays in the rear of the rack
enabling support of up to 2x the number of PDUs listed above for 1075mm deep racks.
− *HPE high density model mounts on its side with outlets facing the back of the rack
− **The only one PDU model with doghouse

Page 12
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Technical Specifications

Model Matrix – Input Power


Model Region Phase & Nominal Input Amps Circuit Breaker Input Plug Type Input Cord
Voltage Length
P59407-B21 WW 1-ph, 230V 16A None IEC 60320 C20 10’
(detachable)
P59420-B21 NA/JP 1-ph, 208V 24A (2) 2-pole 20A L6-30P 10’
P59421-B21 INTL 1-ph, 230V 32A (2) 1-pole 16A IEC32A, 1-ph 12’

P59519-B21 NA/JP 1-ph, 208V 24A (2) 2-pole 20A L6-30P 10’
P59520-B21 INTL 1-ph, 230V 32A (2) 1-pole 16A IEC32A, 1-ph 10’
P59415-B21 NA/JP 3-ph, 208V 48A (6) 2-pole 20A IEC60A, 3-ph 10’
P59418-B21 WW 3-ph, 200-240V 32A (6) 1-pole 16A IEC32A, 3-ph 10’
3-ph, 346-415V
P59521-B21 NA/JP 3-ph, 208V 24A (3) 2-pole 20A L15-30P 10’
P60344-B21 NA/JP 3-ph, 208V 24A (3) 2-pole 20A L15-30P 12’
P59406-B21 NA/JP 1-ph, 120V 24A (2) 1-pole 16A L5-30P 10’
P59408-B21 NA/JP 1-ph, 208V 24A (2) 2-pole 20A L6-30P 10’
P59409-B21 INTL 1-ph, 230V 32A (2) 1-pole 16A IEC32A, 1-ph 10’
P59410-B21 NA/JP 1-ph, 208V 40A (3) 2-pole 20A CS8265C 10’
P59413-B21 WW 1-ph, 230V 63A (6) 1-pole 16A IEC63A, 1-ph 10’
P59411-B21 NA/JP 3-ph, 208V 24A (3) 2-pole 20A L15-30P 10’
P59412-B21 WW 3-ph, 200-240V 16A None IEC16A, 3-ph 10’
3-ph, 346-415V
P59414-B21 NA/JP 3-ph, 208V 48A (6) 2-pole 20A IEC60A, 3-ph 10’
P59417-B21 WW 3-ph, 200-240V 32A (6) 1-pole 16A IEC32A, 3-ph 10’
3-ph, 346-415V
P67671-B21 NA/JP 3-ph, 208V 48A (6) 2-pole 20A IEC60A, 3-ph 10’
P67672-B21 WW 3-ph, 200-240V 32A (6) 1-pole 16A IEC32A, 3-ph 10’
3-ph, 346-415V
P59416-B21 NA/JP 3-ph, 208V 48A (6) 2-pole 20A IEC60A, 3-ph 10’
P59419-B21 WW 3-ph, 200-240V 32A (6) 1-pole 16A IEC32A, 3-ph 10’
3-ph, 346-415V
Notes: All Input Circuit Ratings for NA/JP models have been de-rated according to NEC requirements.
Nominal Input Voltage Ratings used for calculating output power are as follows:
• 100 – 120V: 120V
• 100 – 240V: 230V
• 200 – 208V: 208V
• 220 – 240V: 230V
• 200 – 240V/346 – 415V: 230V

Page 13
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Technical Specifications

Model Matrix – Output Power


Model Region kVA Output Voltage Output Receptacles Support Extension Bar Support Locking
Range Options Power Cord Options

P59407-B21 WW 3.6 100-240V (20) C13, (2) Combo  


P59420-B21 NA/JP 4.9 200-208V (4) C13, (8) Combo  

P59421-B21 INTL 7.3 220-240V (4) C13, (8) Combo  


P59519-B21 NA/JP 4.9 200-208V (16) C13, (4) Combo  
P59520-B21 INTL 7.3 220-240V (16) C13, (4) Combo  
P59415-B21 NA/JP 17.2 200-208V (18) C13, (12) Combo  

P59418-B21 WW 22 200-240V (18) C13, (12) Combo  


P59521-B21 NA/JP 8.6 200-208V (12) C13, (6) Combo  
P60344-B21 NA/JP 8.6 200-208V (6) C13, (6) Combo  
P59406-B21 NA/JP 2.8 100-120V (24) 5-20R n/a n/a
P59408-B21 NA/JP 4.9 200-208V (32) C13, (6) Combo  
P59409-B21 INTL 7.3 220-240V (32) C13, (6) Combo  
P59410-B21 NA/JP 8.3 200-208V (24) C13, (6) Combo  
P59413-B21 WW 14.4 200-240V (18) C13, (12) Combo  
P59411-B21 NA/JP 8.6 200-208V (30) C13, (6) Combo  
P59412-B21 WW 11 200-240V (36) C13, (6) Combo  
P59414-B21 NA/JP 17.2 200-208V (36) C13, (12) Combo  
P59417-B21 WW 22 200-240V (36) C13, (12) Combo  
P67671-B21 NA/JP 17.2 200-208V (18) C13, (6) Combo  
P67672-B21 WW 22 200-240V (12) C13, (12) Combo  
P59416-B21 NA/JP 17.2 200-208V (24) C13, (24) Combo  n/a
P59419-B21 WW 22 200-240V (24) C13, (24) Combo  n/a

Operating 50° to 140° F (10° to 60° C)


Temperature
Operating Relative 10% to 90%
Humidity (%)
Operating Elevation 0 to 10,000 ft. (0 to 3000 m)
Storage Temperature -4° to 140° F (-20° to 60° C)
Storage Relative 5% to 95%
Humidity (%)
Storage Elevation 0 to 30,000 ft. (0 to 9144 m)
Conformance UL or CSA, CB Test+ FCC, ICES, VCCI - NA/JPN models
Standards CE, DEMKO, EAC, KC+KCC, ACMA, Ukraine - INTL models
UL or CSA, CB Test+CE, DEMKO, EAC, FCC, ICES, KCC, KC, VCCI ACMA, Ukraine - WW models
Kit Contents All G3 Metered & Switched PDU models ship with:
• Mounting brackets/hardware
• Quick start guide
• Safety guideline
• Warranty card

Page 14
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Technical Specifications
PDU Plug Types
Voltage Amps # Wires Plug Name Sample Plug Image
(color may vary by manufacturer)
100-125 V 15 A 3 NEMA 5-15P
Single Phase

30 A 3 NEMA L5-30P

200-240 V 20 A 3 IEC C20


Single Phase

12 A 3 IEC C13

20 A 3 C13/C19 Combo

30 A 3 NEMA L6-30P

32 A 3 IEC 309 32A

50 A 3 CS8265C

63 A 3 IEC 309 63A

200 - 208 V 30 A 5 NEMA L15-30P


NA/JPN
Three Phase

30 A 5 NEMA L21-30P

50 A 4 CS8365C

Page 15
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Technical Specifications
60 A 4 IEC 309 60A

200 – 240 V and 16 A 5 IEC 309 16 A


346 – 415 V
INTL
Three Phase
32 A 5 IEC 309 32 A

Page 16
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Summary of Changes

Date Version History Action Description of Change


05-Aug-2024 Version 3 Updated Overview, Standard Features, Service and Support, Configuration
Information, Technical Specifications were updated
01-Jul-2024 Version 2 Updated Overview, Standard Features, Service and Support were updated
03-Jun-2024 Version 1 New New QuickSpecs

Page 17
QuickSpecs Enlogic by nVent G3 Enterprise Power Distribution Units for HPE

Copyright

Make the right purchase decision.


Contact our presales specialists.

Get updates
© Copyright 2024 Hewlett Packard Enterprise Development Company, L.P.
The information contained herein is subject to change without notice.

The only warranties for Hewlett Packard Enterprise products and services are set forth in the express
warranty statements accompanying such products and services. Nothing herein should be construed as
constituting an additional warranty. Hewlett Packard Enterprise shall not be liable for technical or editorial
errors or omissions contained herein.

a50009202enw - 17234 - Worldwide - V3 - 05-August-2024