0% found this document useful (0 votes)
197 views

IOM1242

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
197 views

IOM1242

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 94

Installation, Operation, IOM 1242-3

and Maintenance Manual Group: Chiller


Part Number: IOM1242-3
Date: May 2019

Pathfinder®
Air-cooled Screw Chillers
Model AWV
100 to 565 Tons (350 to 1985 kW)
HFC-134a Refrigerant
60/50 Hz
Table of Contents

Table of Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and Application Considerations . . . . . . 7
Installation and Application Considerations - Remote
Evaporators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Dimensions - Remote Evaporators . . . . . . . . . . . . . 32
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . 35
Isolator Information . . . . . . . . . . . . . . . . . . . . . . . . . 38
Pressure Drop Data . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . 42
Unit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Circuit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Alarms and Events . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Using the Controller . . . . . . . . . . . . . . . . . . . . . . . . . 80
Startup and Shutdown . . . . . . . . . . . . . . . . . . . . . . . 82
System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 87
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

Manufactured in an ISO 9001 & ISO 14001 certified facility

©2019 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 2 www.DaikinApplied.com


Pre-Start Checklist – Screw Chillers
Must be completed, signed and provided to Daikin Applied at least 2 weeks prior to requested start date.
Job Name
Installation Location
Customer Order Number
Model Number(s)
G.O. Number(s)
Chilled Water and Condenser Water for Water-cooled Chiller Yes No N/A Initials
Piping complete
Water strainer(s) installed in piping per manual requirements
Water System – flushed, filled, and vented; Water treatment in place
Cooling tower flushed, filled, vented; Water treatment in place (if applicable)
Pumps installed and operational (rotation checked, strainers installed and cleaned)
Controls operational (3-way valves, face/bypass dampers, bypass valves, etc.)
Water system operated and tested; flow meets unit design requirements
Flow switch(es) - installed, wired, and calibrated
Vent installed on evaporator
Glycol at design % (if applicable)
Electrical Yes No N/A Initials
Building controls operational
*Power leads connected to power block or optional disconnect
Power leads have been checked for proper phasing and voltage
All interlock wiring complete and compliant with Daikin specifications
Power applied at least 24 hours before startup
Oil heaters energized at least 24 hours before startup (not applicable for WWV models)
Chiller components (EXV Sensors Transducers) installed and wired properly
*Wiring complies with National Electrical Code and local codes (see notes)
Remote EXV wired with shielded cable (if applicable)
Miscellaneous Yes No N/A Initials
Unit control switches all off
Remote Evaporator Piping factory reviewed and approved (if applicable)
All refrigerant components/piping leak tested, evacuated and charged
Thermometers, wells, gauges, control, etc., installed
Minimum system load of 80% capacity available for testing/adjusting controls
Document Attached: Technical Data Sheet from Selection Software
Document Attached: Final Order Acknowledgement
Cut Here 

Document Attached: Remote evaporator piping approval (if applicable)


Notes: The most common problems delaying start-up and affecting unit reliability are:
1. Field installed compressor motor power supply leads too small. Questions: Contact the local Daikin sales representative*. State size, number and
type of conductors and conduits installed:
a. From Power supply to chiller
* Refer to NEC Article 430-22 (a)
2. Remote Evaporator piping incomplete or incorrect. Provide approved piping diagrams.
3. Items on this list incorrectly acknowledged may result in delayed start and extra expenses incurred for return trips.

Contractor Representative Daikin Applied Sales Representative


Signed: Signed:
Name: Name:
Company: Company:
Date: Date:
Phone/Email: Phone/Email:

©2019 Daikin Applied Form SF-18003 19 Feb 2019


Introduction

Introduction

This manual provides installation, operation, and maintenance information for Daikin Pathfinder® model AWV screw chillers with the
MicroTech® III controller.

WARNING
Electric shock hazard. Improper handling of this equipment can cause personal injury or equipment damage. This equipment must
be properly grounded. Connections to and service of the MicroTech® III control panel must be performed only by personnel that are
knowledgeable in the operation of the equipment being controlled.

CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can cause damage to the components. Use
a static strap before performing any service work. Never unplug any cables, circuit board terminal blocks, or power plugs while
power is applied to the panel.

CAUTION
When moving refrigerant to/from the chiller using an auxiliary tank, a grounding strap must be used. An electrical charge builds
when halo-carbon refrigerant travels in a rubber hose. A grounding strap must be used between the auxiliary refrigerant tank and
the chiller’s end sheet (earth ground), which will safely take the charge to the ground. Damage to sensitive electronic components
could occur if this procedure is not followed.

CAUTION
This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with this instruction
manual, it may cause interference with radio communications. Operation of this equipment in a residential area may cause harmful
interference in which case the owner will be required to correct the interference at the owner’s own expense.
Daikin Applied disclaims any liability resulting from any interference or for the correction thereof.

HAZARD IDENTIFICATION INFORMATION

DANGER
Dangers indicate a hazardous situation, which will result in death or serious injury if not avoided.

WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not
avoided.

CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.

www.DaikinApplied.com 5 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Introduction

General Description
Daikin Pathfinder® model AWV chillers are complete, self- protection and operating controls are included.
contained, automatically controlled, liquid-chilling units All Daikin Applied screw chillers must be commissioned by
featuring variable speed screw compressors. All model a Daikin Applied service technician or an authorized service
AWV chillers are equipped with a single evaporator and provider. Failure to follow this startup procedure can affect the
microchannel condenser coils along with two compressors. equipment warranty (see “Receiving and Handling” on page
Pathfinder® chillers are designed for outdoor installation only. 7).
The chillers use refrigerant HFC-134a that has no ozone The standard limited warranty on this equipment covers parts
depletion level. that prove defective in material or workmanship. Specific
Only normal field connections such as water piping, electric details of this warranty can be found in the warranty statement
power, and control interlocks are required, thereby simplifying furnished with the equipment.
installation and increasing reliability. Necessary equipment

NOMENCLATURE

A W V ### A XXX
Air-cooled Compressor Code
World Vintage

Variable Speed Chiller Number of Fans

Table 1: Operating Limits for AWV Chillers


Maximum standby ambient temperature
130°F (54.4°C)
NOTE: Maximum operating ambient temperature is determined by unit configuration.
Minimum operating ambient temperature - standard ambient control 32°F (0°C)
Minimum starting ambient temperature - low ambient control option -10°F (-23.3°C)
Minimum operating ambient temperature - low ambient control option -20°F (-28.9°C)
Leaving chilled water temperature 40°F to 70°F (4.4°C to 21.1°C)
Leaving chilled fluid temperatures (with antifreeze) -
17°F to 70°F (-8.3°C to 21.1°C)
NOTE: Unloading is not permitted with fluid leaving temperatures below 25°F (-3.9°C).
Operating chilled water Delta T range 6°F to 20°F (3.3°C to 11.1°C)
Maximum evaporator operating inlet fluid temperature 88°F (31.1°C)
Maximum evaporator non-operating inlet fluid temperature 100°F (38°C)

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 6 www.DaikinApplied.com


Installation and Application Considerations

Installation and Application Considerations

Nameplates Avoid rough handling shock due to impact or dropping the unit.
Identification nameplates on the chiller:
Do not push or pull the unit. Never allow any part of the unit
• The unit nameplate is located on the exterior of the Unit to fall during unloading or moving as this can result in serious
Power Panel. Both the Model No. and Serial No. are damage.
located on the unit nameplate; the Serial No. is unique to
the unit. These numbers should be used to identify the To lift the unit, lifting tabs with 3” (76 mm) diameter holes are
unit for service, parts, or warranty questions. This plate provided on the base of the unit. All lifting holes must be used
also has the unit refrigerant charge and electrical ratings. when lifting the unit. Spreader bars and cables should be
• Vessel nameplate is located on the evaporator. They arranged to prevent damage to the unit. (see Figure 1).
have a National Board Number (NB) and a serial number,
either of which identify the vessel (but not the entire unit). Figure 1: AWV Unit Rigging
• Compressor nameplate is located on each compressor NUMBER OF FANS MAY SPREADER BARS MUST BE
and gives pertinent electrical information. VARY FROM THIS DIAGRAM USED TO PREVENT CABINET
BUT LIFTING METHOD DAMAGE. LOCATE BARS
ABOVE UNIT TO CLEAR FAN
Receiving and Handling
REMAINS THE SAME.
ALL PROVIDED RIGGING HOLES GRILLES. MINIMUM DISTANCE
MUST BE USED. LIFT ONLY FROM ACROSS UNIT BETWEEN
BASE POINTS AS SHOWN. CABLE OR CHAINS IS
The unit should be inspected immediately after receipt for 90 INCHES.
possible damage. All Daikin Applied screw air-cooled chillers
are shipped FOB factory and all claims for handling and
shipping damage are the responsibility of the consignee.
Startup by a Daikin Applied service representative is included
on all Pathfinder® units sold for installation within the U.S.
and Canada and must be performed by them to initiate the
standard Limited Product Warranty. Startup by any party other
than a Daikin Applied service representative will void the
Limited Product Warranty. Two-week prior notification of startup
is required. The contractor should obtain a copy of the Startup
Scheduled Request Form from the sales representative or from
L7
the nearest Daikin Applied service office. Completed Request L8 OPPOSITE
L5
Form and check list on page 3 are required before startup can L6 OPPOSITE
SIDE - (NOT ON
ALL MODELS)
be scheduled. CONTROL
L3 SIDE
L4 OPPOSITE
PANEL L1 SIDE
Installation and maintenance are to be performed only by L2 OPPOSITE
SIDE REPRESENTATIVE LIFTING SCHEMATIC -
qualified personnel who are familiar with local codes and COMPRESSORS, EVAPORATOR, AND PIPING
regulations, and experienced with this type of equipment. NOT SHOWN FOR DRAWING SIMPLICITY.

CAUTION NOTE: 1. Crosswise and lengthwise spreader bars must be


Extreme care must be used when rigging the unit to prevent used to avoid damage to unit. The spreader bars in
damage to the control panels and unit frame. See the certified Figure 1 are a representation only and may not reflect
dimension drawings included in the job submittal for the the appearance of the actual spreader bars needed.
weights and center of gravity of the unit. If the drawings are
not available, consult the local Daikin Applied sales office for 2. Unit with 8 lifting points illustrated above; the actual
assistance. unit configuration may vary from this diagram. See
the dimensional drawing section beginning on page
35 to identify the lifting point locations and weights
WARNING based on specific unit model.
Sharp edges and coil surfaces are a potential injury hazard.
Avoid contact with them.
Unit Placement
WARNING Locate the unit outdoors and provide proper airflow to the
Escaping refrigerant can displace air and cause suffocation. condenser, see Figure 2. Using less clearance than shown for
Immediately evacuate and ventilate the equipment area. required clearances can cause discharge air recirculation to
If the unit is damaged, follow Environmental Protection the condenser and could significantly reduce unit performance.
Agency (EPA) requirements. Do not expose sparks, arcing
equipment, open flame or other ignition source to the Pathfinder® units are for outdoor applications and can be
refrigerant. mounted either on a roof or at ground level. For roof mounted
applications, install the unit on a steel channel or I-beam
DANGER frame to support the unit above the roof. Spring isolators
Improper rigging, lifting, or moving of a unit can result in are recommended for all roof-mounted installations due to
property damage, severe personal injury or death. Follow vibration transmission considerations. Isolator information can
rigging and moving instructions carefully. be found on page 38.

www.DaikinApplied.com 7 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

For ground level applications, the unit must be installed Clearance Requirements
on a substantial base that will not settle. Use a one-piece
concrete slab with footings extended below the frost line. Sufficient clearance must be maintained between the unit and
The foundation must be level within 13 mm (1/2 inch) over adjacent walls or other units to allow the required unit air flow
its length and width and strong enough to support the unit to reach the coils, see Figure 2 and Figure 3. Failure to do so
operating weight as listed in Dimensional Drawings beginning will result in a capacity reduction and an increase in power
on page 35. The addition of neoprene waffle pads (supplied consumption. Graphs on the following pages give the minimum
by customer) under the unit may allow water to drain from clearance for different types of installations and also capacity
reduction and power increase if closer spacing is used. The
inside the frame, which can act as a dam. Installation of
graphs are based on individual cases and should not be
optional spring or rubber-in-shear isolators can also assist with
combined with other scenarios.
drainage, see page 38 for information.
The clearance requirements shown are a general guideline,
On ground level applications, protection against vandalism is
based on individual cases, and cannot account for all
recommended; either by the optional factory-installed lower
scenarios. Such factors as prevailing winds, additional
wire mesh guards or louvers, or by a field installed screening
equipment within the space, design outdoor air temperature,
fence. Note that the fence must allow free flow of air to the
and numerous other factors may require more clearance than
condenser coil for proper unit operation. Upper wire mesh coil
what is shown. Additional clearances may be required under
guards are standard.
certain circumstances. No solid obstructions are allowed above
the unit at any height, see Case 5 on page 12. If low ambient
Mounting Hole Access temperature operation is expected, optional louvers should be
The inside of the base rail is open to allow access for securing installed if the unit has no protection against prevailing winds.
mounting bolts, etc. Mounting location dimensions are given in
Dimensional Drawings beginning on page 35. Figure 3: Spacing Guidelines for Sufficient Airflow
No obstructions.

Service Access
Recommended area
is applicable for
service access ONLY.
Performance

The control panels are located on the end of the chiller and Minimum = 4 feet (1.2 m)
clearance graphs are
provided in submittal
(Must have 8 ft. on one documents and may
require a minimum of four feet of clearance in front of the side for coil removal) require additional
spacing.
panels. Compressors, filter-driers, and manual liquid line
Minimum 8 feet (2.4 m) service
shutoff valves are accessible on each side or end of the unit. clearance on this end for
Minimum = 4 feet

Control Panel
(1.2 m)
shell and tube evaporator
The evaporator heater is located on the barrel. Do not block Minimum 4 feet (1.2 m) service
access to the sides or ends of the unit with piping or conduit. clearance on this end for
braze plate evaporator

These areas must be open for service access.


Minimum service clearance spacing on one side of the unit Minimum = 4 feet (1.2 m)

should be increased to 8 feet to allow for coil removal, see


Figure 3. The condenser fans and motors can be removed
from the top of the unit. The complete fan/motor assembly can
be removed for service. The fan blade must be removed for
access to wiring terminals at the top of the motor.

DANGER
Disconnect, lockout and tag all power to the unit before
servicing condenser fan motors or compressors. Failure to do
so can cause bodily injury or death.

Figure 2: Air Flow


NOTE: 1. There should be no obstruction above the fan deck
to interfere with fan discharge.
2. Electrical conduit and field installed electrical
devices should not block service access to any chiller
components.
3. For installations of 2 or more units, refer to Case 2
and Case 3.
4. Stated spacing guidelines are for achieving
sufficient airflow without incurring performance
losses. See Cases 1, 2 and 3 for capacity reduction
and power increases when sufficient airflow cannot
be achieved.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 8 www.DaikinApplied.com


Installation and Application Considerations

Case 1: Building or Wall on One Side of Unit Figure 6: Case 1 for AWV012-014 Models
For all models, maintain a 4 foot minimum from a wall of any % Full Load Capacity Reduction (AWV012-014)
height; however, performance may be affected at this distance 1.2%
due to air recirculation and elevated condenser pressure. 4 Feet
1.0%
Assuming all service clearance requirements are met, Figure 5

% Capacity Reduction
to Figure 9 depict Case 1 performance adjustments as the wall 0.8%
height and distance increases.
0.6% 5 Feet

Figure 4: Building or Wall on One Side of Unit 0.4%


6 Feet
0.2%

0.0%
8 12 16 20 24
Height of Wall - Feet

Height % Full Load Power Increase (AWV012-014)


Distance Control Panel
of Between
Wall
2.5%
Wall
and 4 Feet
Unit 2.0%

% Power Increase
1.5%

1.0% 5 Feet

6 Feet
Figure 5: Case 1 for AWV 008-010 Models 0.5%

% Full Load Capacity Reduction (AWV008-010) 0.0%


1.2% 8 12 16 20 24
4 Feet Height of Wall - Feet
1.0%
% Capacity Reduction

0.8% Figure 7: Case 1 for AWV016-018


0.6% 5 Feet % Full Load Capacity Reduction (AWV016-018)
1.4%
0.4%
6 Feet 1.2% 4 Feet
0.2%
% Capacity Reduction

1.0%
0.0%
0.8%
8 12 16 20 24
5 Feet
Height of Wall - Feet 0.6%
0.4%
% Full Load Power Increase (AWV008-010) 6 Feet
0.2%
2.5%
4 Feet 0.0%
2.0% 8 12 16 20 24
% Power Increase

Height of Wall - Feet


1.5%

5 Feet
1.0% % Full Load Power Increase (AWV016-018)
6 Feet 3.0%
0.5%

0.0% 2.5% 4 Feet


% Power Increase

8 12 16 20 24
Height of Wall - Feet 2.0%

1.5%
5 Feet
1.0%
6 Feet
0.5%

0.0%
8 12 16 20 24
Height of Wall - Feet

www.DaikinApplied.com 9 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

Figure 8: Case 1 for AWV020-024 Case 2: Two Units Side-by-Side


% Full Load Capacity Reduction (AWV020-024) For all models, there must be a minimum of 6 feet between
1.4% two units placed side-by-side; however, performance may
4 Feet
1.2% be affected at this distance due to air recirculation and
elevated condenser pressure. Assuming all service clearance
% Capacity Reduction

1.0%
requirements are met, Figure 11 and Figure 12 depict Case 2
0.8% performance adjustments as the distance between two units
5 Feet
0.6% increases.
0.4%
6 Feet Figure 10: Two Units, Side-by-Side
0.2%
0.0%
8 12 16 20 24
Height of Wall - Feet

% Full Load Power Increase (AWV020-024)


3.0%
4 Feet
D
2.5%
% Power Increase

2.0%

1.5%
5 Feet
1.0%
6 Feet
0.5%
Figure 11: Case 2 - Full
FullLoad
Load Capacity
Capacity Reduction
Reduction
0.0%
6.0
8 12 16 20 24
Height of Wall - Feet
5.0
% Capacity Reduction

Figure 9: Case 1 for AWV026-030


4.0
% Full Load Capacity Reduction (AWV026-030)
1.6%
4 Feet 3.0
1.4%
% Capacity Reduction

1.2%
2.0
1.0%
0.8%
5 Feet 1.0
0.6%
0.4% 6 Feet
0.0
0.2% 6 8 10 12
0.0% Distance Between Units (ft)
8 12 16 20 24
AWV008 AWV010 AWV012 AWV014
Height of Wall - Feet AWV016 AWV018 AWV020 AWV022
AWV024 AWV026 AWV028 AWV030

% Full Load Power Increase (026-030)


3.5%
3.0% 4 Feet
% Power Increase

2.5%
2.0%
1.5% 5 Feet

1.0%
6 Feet
0.5%
0.0%
8 12 16 20 24
Height of Wall - Feet

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 10 www.DaikinApplied.com


Installation and Application Considerations

Figure 12: Case 2 - PowerFull


Increase
Load Power Increase Figure 14: Case 3 - Full
FullLoad
Load Capacity Reduction
Capacity Reduction
7.0
7.0

6.0

% Capacity Reduction
6.0
5.0
% Power Increase

4.0
5.0

3.0

4.0
2.0

1.0
3.0 8 12 16 20
Distance Between Units
AWV008 AWV010 AWV012 AWV014
AWV016 AWV018 AWV020 AWV022
2.0
AWV024 AWV026 AWV028 AWV030

1.0
6 8 10 12
Figure 15: Case 3 - Power Increase
Full Load Power Increase
9.0
Distance Between Units (ft)

AWV008 AWV010 AWV012 AWV014 8.0

% Power Increase
AWV016 AWV018 AWV020 AWV022
AWV024 AWV026 AWV028 AWV030 7.0

6.0

5.0

Case 3: Three or More Units, Side-by-Side 4.0

For all models, there must be a minimum of 8 feet between


3.0
any units placed side-by-side; however, performance may be
affected at this distance. Figure 14 and Figure 15 depict Case 2.0
3 performance adjustments as the distance between units 8 12 16 20

increases. Distance Between Units (ft)

AWV008 AWV010 AWV012 AWV014


NOTE: Data in Figure 14 and Figure 15 is for the middle unit AWV016 AWV018 AWV020 AWV022
with a unit on each side. See Case 2 adjustment AWV024 AWV026 AWV028 AWV030
factors for the two outside units.

Figure 13: Three or More Units, Side-by-Side

www.DaikinApplied.com 11 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

Case 4: Open Screening Walls Case 5: Pit/Solid Wall Installation


Decorative screening walls are often used to help conceal a Pit installations can cause operating problems resulting from
unit either on grade or on a rooftop. When possible, design air recirculation and restriction and require care that sufficient
these walls such that the combination of their open area air clearance is provided, safety requirements are met and
and distance from the unit (see Figure 16) do not require service access is provided. A solid wall surrounding a unit is
performance adjustment. If the wall opening percentage is less substantially a pit and this data should be used. Derates are
than recommended for the distance to the unit, it should be based on single chiller installation only.
considered as a solid wall. It is assumed that the wall height is Steel grating is sometimes used to cover a pit to prevent
equal to or less than the unit height when mounted on its base accidental falls or trips into the pit. The grating material
support. If the wall height is greater than the unit height, see and installation design must be strong enough to prevent
Case 5: Pit/Solid Wall Installation. The distance from the sides such accidents, yet provide abundant open area to avoid
of the unit to the side walls must be sufficient for service, such recirculation problems. Have any pit installation reviewed by
as opening control panel doors. For uneven wall spacing, the the Daikin Applied sales representative prior to installation to
distance from the unit to each wall can be averaged providing ensure it has sufficient air-flow characteristics and approved by
no distance is less than 4 feet. Values are based on walls on all the installation design engineer to avoid risk of accident.
four sides.
Figure 18: Pit Installation
Figure 16: Allowable Wall Open Area

Control
H D Panel

Figure 19: Case 5 for AWV008-010


Full Load Capacity Reduction (AWV008-010)
6.0

Figure 17: Case 4 - Adjustment Factor 5.0


% Capacity Reduction

Wall Free Area vs. Distance 4.0

13.0 3.0
Distance from Wall to Unit (ft)

12.0 2.0

11.0 1.0

10.0 0.0
0 8 10 12 13 14

9.0 Depth of Pit / Wall Height (ft)

Distance = 6 ft Distance = 8 ft Distance = 10 ft


8.0

7.0 Power Increase (AWV008-010)


9.0

6.0 8.0

7.0
5.0
% Power Increase

6.0
4.0
0 10 20 30 40 50 5.0

% Open Wall Area 4.0

AWV008-010 AWV012-014 AWV016 AWV018 3.0


AWV020 AWV022 AWV024 AWV026
2.0
AWV028 AWV030
1.0

0.0
0 8 10 12 13 14

Depth of Pit / Wall Height (ft)

Distance = 6 ft Distance = 8 ft Distance = 10 ft

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 12 www.DaikinApplied.com


Installation and Application Considerations

Figure 20: Case 5 for AWV012-014 Figure 22: Case 5 for AWV020-024
Full Load Capacity Reduction (AWV012-014)
Full Load Capacity Reduction (AWV020-024)
6.0 6.0

5.0 5.0
% Capacity Reduction

% Capacity Reduction
4.0 4.0

3.0 3.0

2.0 2.0

1.0 1.0

0.0 0.0
0 8 10 12 13 14 0 8 10 12 13 14
Depth of Pit / Wall Height (ft) Depth of Pit / Wall Height (ft)

Distance = 6 ft Distance = 8 ft Distance = 10 ft Distance = 6 ft Distance = 8 ft Distance = 10 ft

Power Increase (AWV012-014) Power Increase (AWV020-024)


9.0
9.0
8.0 8.0
7.0 7.0

% Power Increase
6.0
% Power Increase

6.0
5.0 5.0

4.0 4.0

3.0 3.0

2.0 2.0

1.0 1.0

0.0 0.0
0 8 10 12 13 14 0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Depth of Pit / Wall Height (ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft

Figure 23: Case 5 for AWV026-030


Figure 21: Case 5 for AWV016-018
Full Load Capacity Reduction (AWV026-030)
Full Load Capacity Reduction (AWV016-018) 7.0
6.0
6.0
5.0
% Capacity Reduction

5.0
% Capacity Reduction

4.0
4.0

3.0 3.0

2.0 2.0

1.0 1.0

0.0
0.0
0 8 10 12 13 14
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Depth of Pit / Wall Height ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft

Power Increase (AWV016-018) Power Increase (AWV026-030)


9.0 11.0
10.0
8.0
9.0
7.0
8.0
% Power Increase
% Power Increase

6.0 7.0
5.0 6.0
5.0
4.0
4.0
3.0
3.0
2.0 2.0
1.0 1.0
0.0
0.0
0 8 10 12 13 14
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Depth of Pit / Wall Height (ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft

www.DaikinApplied.com 13 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

Chilled Water Piping


Figure 24: Typical Chilled Water Piping, Braze Plate
Air
Vent
Strainer

Inlet
Isolation
P Vibration
Valves
Eliminators

Outlet
Flow
Switch
Drain
WELDED PIPE CONNECTIONS ARE NOT ALLOWED
BETWEEN THE STRAINER AND EVAPORATOR DUE
TO THE CHANCE OF SLAG ENTERING THE EVAPORATOR

Figure 25: Typical Chilled Water Piping, Shell and Tube Evaporator


 VENT
 3/8” PIPE PLUG LEAVING FLUID
 TEMP. SENSOR

OUTLET
VIBRATION
ELIMINATOR

FLOW
INLET SWITCH
VALVED
PRESSURE
GAUGE GATE
VALVE
VIBRATION BALANCING
ELIMINATOR VALVE
DRAIN GATE
WATER VALVE FLOW
STRAINER
PROTECT ALL FIELD PIPING
AGAINST FREEZING
WELDED PIPE CONNECTIONS ARE NOT ALLOWED FLOW
BETWEEN THE STRAINER AND EVAPORATOR DUE TO THE
CHANCE OF SLAG ENTERING THE EVAPORATOR

Startup procedures should confirm that the chilled water piping 5 feet (1500 mm) of pipe length from the evaporator
system had been properly flushed out before being connected inlet connection and downstream of any welded
to the chiller vessel. connections (no welded connections between strainer
and evaporator).
All evaporators have OGS-type grooved water connections
(adhering to Standard AWWA C606) or optional flange • AWV models require a strainer as specified in Inlet
connections. The installing contractor must provide matching Strainer Guidelines on page 15.
mechanical connections. PVC and CPVC piping should not • A water flow switch must be installed in the horizontal
be used. Be sure water inlet and outlet connections match piping of the supply (evaporator outlet) water line to avoid
certified drawings and nozzle markings. evaporator freeze-up under low or no flow conditions.
See page 16 for more information.
CAUTION
• Purge air from the water system before unit startup to
To prevent damage to the evaporator and potential chiller provide adequate flow through the evaporator.
failure, a supply strainer is required in the inlet water piping
which connects to the evaporator. This strainer must be • Piping for units with brazed plate evaporators must have
installed prior to operation of the chilled liquid pumps. a drain and vent connection provided in the bottom of
the lower connection pipe and to the top of the upper
Field installed water piping to the chiller must include: connection pipe, respectively, see Figure 24. These
• A cleanable strainer installed at the water inlet to the evaporators do not have drain or vent connections due to
evaporator to remove debris and impurities before they their construction.
reach the evaporator. Install cleanable strainer within

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 14 www.DaikinApplied.com


Installation and Application Considerations

• Adequate piping support, independent from the unit, The strainer is sized per Table 2 and has the pressure drop
to eliminate weight and strain on the fittings and shown in the Strainer Pressure Drop graph. Connection sizes
connections. are given in the Pressure Drop Data section on page 39.
It is recommended that the field installed water piping to the 2. A field-supplied strainer to same specifications as factory
chiller include: installed option.
• Thermometers at the inlet and outlet connections of the
Table 2: Strainer Sizing Data
evaporator.
Strainer Maximum Perforation Size Strainer Weight
• Water pressure gauge connection taps and gauges at
Size (in.) in. (mm) (lbs)
the inlet and outlet connections of the evaporator for
measuring water pressure drop. 6 0.063” (1/16”, 1.6 mm) 120
• Shutoff valves to isolate the unit from the piping during 6 120
unit servicing. 8 0.125” (1/8”, 3.2 mm) 220
• Minimum bends and changes in elevation to minimize 10 514
pressure drop.
• An expansion tank and regulating valve to maintain Figure 26: Strainer Pressure Drop
adequate water pressure. Tank becomes required
for closed loop systems based on water volume and
temperature ranges.
• Vibration eliminators in both the supply and return water
lines to reduce transmissions to the building.
• Flushing the system water piping thoroughly before
making connections to the unit evaporator.
• Piping insulation, including a vapor barrier, helps prevent
condensation and reduces heat loss.
• Regular water analysis and chemical water treatment
for the evaporator loop is recommended immediately at
equipment startup.
WARNING
Daikin Applied recommends against the use of PVC and
CPVC piping for chilled water systems. In the event the pipe
is exposed to POE oil used in the refrigerant system, the pipe
can be chemically damaged and pipe failure can occur.
Installing Inlet Strainer (Field-installed Kit)
Inlet Strainer Guidelines The extension pipe is located adjacent to the evaporator with
the strainer then mounted to it. The strainer must be mounted
An inlet water strainer kit must be installed in the chilled water per manufacturer’s instruction with the arrows in the direction
piping within 5 feet of the evaporator inlet. Two paths are of flow; inlet and outlet are noted along with the arrows.
available to meet this requirement:
Use one grooved clamp to mount the extension pipe to the
1. A field-installed kit shipped loose with the unit is available evaporator and the second to mount the strainer to the pipe.
for all unit sizes and consists of: The clamps to mount the field piping to the strainer are field
• Y-type area strainer with 304 stainless steel perforated supplied. The piping and strainer must be supported to prevent
basket, Grooved pipe connections and strainer cap any stress on the evaporator nozzle.
—— a strainer with perforations no larger than 0.063”
(1/16”, 1.6 mm) diameter for AWV models with a
braze plate evaporator System Water Volume
—— a strainer with perforations no larger than 0.125” All chilled water systems need adequate time to recognize a
(1/8”, 3.2 mm) diameter for AWV models with a direct load change, respond to that load change and stabilize, without
expansion evaporator undesirable short cycling of the compressors or loss of control.
• Extension pipe with two couplings that may be used In air conditioning systems, the potential for short cycling
for gauges and sensors. The pipe provides sufficient usually exists when the building load falls below the minimum
clearance from the evaporator for strainer basket chiller plant capacity or on close-coupled systems with very
removal. small water volumes. Some of the things the designer should
consider when looking at water volume are the minimum
• ½-inch blowdown valve cooling load, the minimum chiller plant capacity during the low
• Two grooved clamps load period and the desired cycle time for the compressors.

www.DaikinApplied.com 15 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

Assuming that there are no sudden load changes and that water pumps. Use one of the following recommendations for
the chiller plant has reasonable turndown, a rule of thumb of additional protection:
“gallons of water volume equal to two to three times the chilled • If the unit will not be operated during the winter, drain
water gpm flow rate” is often used. A storage tank may have evaporator and chilled water piping and flush with
to be added to the system to reach the recommended system glycol. Drain and vent connections are provided on the
volume. Refer to Daikin Applied Chiller Application Guide, AG evaporator for this purpose.
31-003, for method of calculating “Minimum Chilled Water
Volume”. • Add a year-round glycol solution to the chilled water
system to provide freeze protection. Freeze point should
The water quality provided by the owner/occupant/operator/ be approximately 10°F (5.6°C) below minimum design
user to a chiller system should minimize corrosion, scale ambient temperature or 10°F (5.6°C) below the lowest
buildup, erosion, and biological growth for optimum efficiency design leaving water temperature, whichever is lower.
of HVAC equipment without creating a hazard to operating The use of glycol antifreeze is generally considered
personnel or the environment. Strainers must be used to the safest protection against freeze-up; however, it will
protect the chiller systems from water-borne debris. Daikin will reduce the performance of the unit, depending on the
not be responsible for any water-borne debris damage or water concentration. Take this into consideration during initial
side damage to the chiller heat exchangers due to improperly system design and selection. On glycol applications, a
treated water. minimum fluid concentration should be based on Burst
Water systems should be cleaned and flushed prior to chiller Protection limits.
installation. Water testing and treatment should be verified • The field addition of thermostatically controlled heat
during initial chiller installation/commissioning and maintained tracing and insulation to exposed piping, dependent on
on a continuous basis by water treatment professionals (see power availability.
Limited Product Warranty). • Continuous circulation of water through the chilled water
CAUTION piping and evaporator, with ability to control temperature
The improper use of detergents, chemicals, and additives within chiller safety limits. (Dependent on power
in the chiller system water may adversely affect chiller availability).
performance and potentially lead to repair costs not covered • The evaporator immersion heater is factory-wired to the
by warranty. Any decision to use these products is at the 115-volt circuit in the control box. This power can be
discretion of the owner/occupant/operator/user as such they supplied from a separate source, or it can be supplied
assume full liability/responsibility for any damage that may from the control circuit. Operation of the heater cable
occur due to their use. is automatic through the fluid sensing thermostat that
energizes the evaporator heater cable for protection
against freeze-up. Unless the evaporator is drained in
Flow Switch the winter, the disconnect switch to the evaporator heater
A flow switch must be included in the chilled water system must be closed. Conversely, do not apply heat to the
to prove that there is adequate water flow to the evaporator evaporator if it is drained.
before the unit can start, or to shut down the unit if water flow is
interrupted. A solid state, thermal dispersion flow switch that is Chilled Water Pump
factory-mounted in the chiller leaving water nozzle and factory-
wired is available. A field-installed version is also available as It is important that the chilled water pumps be wired to, and
an option. controlled by, the chiller’s microprocessor. The chiller controller
has the capability to selectively send the signal to a pump
Installation should be per manufacturer’s instructions included relay (by others) to start pump A or B or automatically alternate
with the switch. Flow switches should be calibrated to shut off pump selection and also has standby operation capability.
the unit when operated below the minimum flow rate for the The controller will energize the pump whenever at least one
unit. Flow switch installation and calibration is further discussed circuit on the chiller is enabled to run, whether there is a
on page 84. call for cooling or not. This helps ensure proper unit startup
sequence. To help prevent evaporator freeze-up, the pump
will also be turned on when the water temperature is equal to
Evaporator Freeze Protection or goes below the Freeze Set Point for at least three seconds.
Evaporator freeze-up can be a concern in the application of Connection points are shown in the Field Wiring Diagrams on
air-cooled water chillers in areas experiencing below freezing page 19 and page 20.
temperatures. To protect against freeze-up, insulation and an
CAUTION
electric immersion heater are furnished with the evaporator.
This helps protect the evaporator down to -20°F (-29°C) Adding glycol or draining the system is the recommended
ambient air temperature. Although the evaporator is equipped method of freeze protection. If the chiller does not have
with freeze protection, it does not protect water piping external the ability to control the pumps and the water system is
to the unit or the evaporator itself if there is a power failure or not drained in temperatures below freezing, catastrophic
heater burnout, or if the chiller is unable to control the chilled evaporator failure may occur.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 16 www.DaikinApplied.com


Installation and Application Considerations

Failure to allow pump control by the chiller may cause the


CAUTION
following problems:
Do not use automotive grade antifreeze. Industrial grade
1. If any device other than the chiller attempts to start the
glycols must be used. Automotive antifreeze contains
chiller without first starting the pump, the chiller will lock
inhibitors that will cause plating on the copper tubes within the
out on the No Flow alarm and require manual reset.
chiller evaporator. The type and handling of glycol used must
2. If the evaporator water temperature drops below the be consistent with local codes.
“Freeze Set Point” the chiller will attempt to start the
water pumps to avoid evaporator freeze. If the chiller Performance Adjustment Factors
does not have the ability to start the pumps, the chiller
AWV chillers are designed to operate with leaving antifreeze
will alarm due to lack of water flow.
solution temperatures per software range limits. Consult the
3. If the chiller does not have the ability to control the local Daikin Applied sales office for performance outside
pumps and the water system is not to be drained in these temperatures. Leaving chilled fluid temperatures below
temperatures below freezing, the chiller may be subject 40°F (4.4°C) result in evaporating temperatures at or below
to catastrophic evaporator failure due to freezing. The the freezing point of water and a glycol solution is required.
freeze rating of the evaporator is based on the immersion MicroTech® III control inhibits compressor unloading at leaving
heater and pump operation. The immersion heater itself fluid temperatures below 25°F (-3.9°C).
may not be able to properly protect the evaporator from
Low fluid temperatures or high equipment room humidity for
freezing without circulation of water.
remote evaporators may require optional double evaporator
insulation. The system designer should determine its necessity.
Variable Speed Pumping The use of glycol will reduce unit performance depending on its
concentration and should be considered during initial system
Reducing evaporator flow in proportion to load can reduce
design.
system power consumption. Daikin Applied chillers are
designed for variable water flow duty provided that the rate of
change is less than ten percent of the design flow per minute,
and the minimum and maximum flow rates for the evaporator,
Electrical Connections
beginning on page 39, are not exceeded. If flow drops Pathfinder® units can be ordered with either standard multi-
below the minimum allowable, large reductions in heat transfer point power or optional single point power connections
can occur. If the flow exceeds the maximum rate, excessive and with various disconnect and circuit breaker options.
pressure drop and tube erosion can occur. For example, if the Power wiring connections to the chiller may be done with
maximum design flow is 200 gpm and it will be reduced to a either copper or aluminum wiring. All wiring must be done in
flow of 140 gpm, the change in flow is 60 gpm. Ten percent of accordance with applicable local and national codes, including
200 gpm equals 20 gpm change per minute, or a minimum of NECA/AA 10402012, Standard for Installing Aluminum Building
three minutes to go from maximum to desired flow. Wire and Cable (ANSI). Wiring within the unit is sized in
accordance with the NEC®. Refer to the unit nameplate and
the unit selection report for the correct electrical ratings.
Ice Mode
DANGER
Optional double evaporator insulation is recommended for ice Qualified, licensed electricians must perform wiring. Electrical
mode operation. The standard controller software will require shock hazard exists that can cause severe injury or death.
“ice” set point changes and a digital signal into the controller
is required to change to the ice mode and back to standard The field power wiring required varies depending on unit
cooling. See the Field Wiring Diagrams on page 19 and model. See page 19 and page 20 for wiring information.
page 20 for the connection location. In ice mode, the unit These wiring diagrams are also provided with the chiller.
will operate at full load until the shutoff temperature set point is NOTE: Wiring, fuse, and wire size must be in accordance
reached. with the NEC ®. The voltage to these units must be
within ±10% of nameplate voltage (415V units must
Glycol Solutions have voltage within -13% and +6% of nameplate
voltage) and the voltage unbalance between phases
Test coolant with a clean, accurate glycol solution hydrometer must not exceed 2%. Since a 2% voltage unbalance
(similar to that found in service stations) or refractometer to will cause a current unbalance of 6 to 10 times the
determine the freezing point. Obtain percent glycol from the voltage unbalance per the NEMA MG-1 Standard, it
freeze point table on page 83. On glycol applications, the is most important that the unbalance between phases
supplier normally recommends that a minimum of 25% solution be kept at a minimum.
by weight be used for protection against corrosion or that
additional inhibitors should be employed.

www.DaikinApplied.com 17 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

CAUTION Transfer Back to Grid Power


Do not use power factor correction capacitors with AWV Proper transfer from stand-by generator power back to grid
chillers. Doing so can cause harmful electrical resonance in power is essential to avoid chiller damage and must be used to
the system. Correction capacitors are not necessary since ensure proper function of the unit.
VFDs inherently maintain high power factors.
WARNING
Table 3: SCCR Ratings (kAmps) Stop the chiller before transferring supply power from the
generator back to the utility power grid. Transferring power
Standard Short High Short Circuit while the chiller is running can cause severe chiller damage.
Voltage/Hz
Circuit Panel Rating Panel Rating
The necessary procedure for reconnecting power from the
380/60 10kA 65kA
generator back to the utility grid is as follows:
460/60 10kA 65kA
575/60 5kA 25kA 1. Set the generator to always run five minutes longer than
400/50 10kA 65kA the unit start-to-start timer, which can be set from two to
sixty minutes, while keeping the chiller powered by the
generator until the fully synchronized Automatic Transfer
Field-supplied disconnect switches are required if not factory- Switch properly hands over chiller power from the site.
supplied with the unit. Disconnecting means are addressed by 2. Configure the transfer switch provided with the
Article 440 of the NEC®, which requires “disconnecting means generator to automatically shut down the chiller before
capable of disconnecting air conditioning and refrigerating transfer is made. The automatic shut-off function can
equipment including motor-compressors, and controllers from be accomplished through a BAS interface or with the
the circuit feeder.” Select and locate the disconnect switch per “remote on/off” wiring connection shown in the field
the NEC® guidelines. wiring diagrams.
Terminals are provided in a unit control panel for optional A start signal can be given anytime after the stop signal since
field hookup of the control circuit to a separate fused 115-volt the start-to-start timer will be in effect. The default timer setting
power supply in lieu of the standard factory installed control is 5 minutes but adjustable as low as 3 minutes.
transformer.

Long Term Storage


Use with On-Site Generators This information applies to new units being stored waiting
Switching from site grid power to generator power and vice for startup or to existing units that may be inoperative for an
versa requires that the chiller must either be powered down extended period of time.
or the power must be off for more than five seconds to avoid The chiller must be stored in a dry location and protected from
sending out of phase voltage to the chiller. A properly installed, any damage or sources of corrosion. A Daikin Applied service
fully synchronized Automatic Transfer Switch must be used to representative must perform an inspection and leak test of
transfer power if the chiller is running under load. the unit on a minimum quarterly schedule, to be paid by the
owner or contractor. Daikin Applied will not be responsible for
Generator Sizing any refrigerant loss during the storage time or for repairs to the
unit during the period of storage, or while moving the unit from
WARNING the original location to a storage facility and back to any new
Generator must be sized by an electrical engineer familiar installation location. If there is concern about the possibilities of
with generator applications. damage and loss of charge during storage, the customer can
have the charge removed and stored in recovery cylinders.

CAUTION
If the temperature of where the chiller is located is expected to
exceed 130°F (54.4°C), then the refrigerant must be removed.

For additional tasks required, contact a Daikin Applied service


representative.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 18 www.DaikinApplied.com


Installation and Application Considerations

Figure 27: Field Wiring Diagram - Single Point Power


PANEL

POWER BLOCK
CIRCUIT BREAKER OR
(BY OTHERS) DISCONNECT SWITCH

L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
OR CIRCUIT 1
L3 T3

EARTH F120 F120


GROUND
T1

DISCONNECT
(BY OTHERS)
MQ
17 N
115 FUSE OPTIONAL
Q12 VAC 20A for 2KVA FIELD SUPPLIED
MQ 30A for 3KVA CONTROL POWER
12 120 VAC
(BY OTHERS)
OPEN Q12 IF SUPPLY IS SEPARATE 120 VAC SOURCE

M5
M5
21
28 120 VAC
CHWR1 ** USE DRY CONTACTS ONLY, SEE NOTE 2
EVAP. WATER (BY OTHERS) MODE SWITCH
PUMP RELAY No. 1 EVAP. WATER PUMP RELAY IF MODE SWITCH IS USED, REMOVE
(BY OTHERS) 120VAC @ 0.25AMP MAX M5 LEAD 322 BETWEEN M5-21 AND MS-10.
MQ
57
17 N (735)
(718)
OFF TIME
M5 CLOCK
M5 58
** USE DRY CONTACTS ONLY, SEE NOTE 2 AUTO
49 120 VAC REMOTE
CHWR2 IF REMOTE SWITCH IS USED, SWITCH
EVAP. WATER (BY OTHERS)
(BY OTHERS) REMOVE MECHANICAL JUMPER ON
PUMP RELAY No. 2
EVAP. WATER PUMP RELAY M5 BETWEEN M5 TERMIONALS 58 & 59.
(BY OTHERS)
120VAC @ 0.25AMP MAX 59
MQ MANUAL (737)
17 N
(830)

(BY OTHERS)
120VAC @ 0.25AMP MAX M5
26 120 VAC

ALARM OUTPUT M5 EA1

MQ 5
17 N ** USE DRY CONTACTS ONLY, SEE NOTE 2
(721) EXTERNAL
IF EXTERNAL ALARM IS USED, REMOVE ALARM
M5 LEAD 402 BETWEEN M5 TERMINALS 5 & 15
15
(828)
M5 BC1
61

FOR RAPID
BACKUP
** USE DRY CONTACTS ONLY, SEE NOTE 2 RESTORE OPTION
CHILLER
ONLY
M5
62 (856)
(858)
M5
35 +

4-20 mA
SETPOINT OVERRIDE
(BY OTHERS)
M5
_
36
(720)
M5
38 +

4-20 mA
DEMAND LIMIT
(BY OTHERS)
M5
_
37
(833)

M5
FLow Switch Contacts
8 M

**USE DRY CONTACS ONLY


SEE NOTE 2
M5

(735)
23 DI2 TO/FROM BAS
CLA (CUSTOMER
LON
CLB CONNECTION)
NOTE: For Factory Supplied Thermal 910170645_1RC
Dispersion Flow Switch wiring, see wiring GND CONNECT TO GROUND
AT ONE END ONLY.
instruction in Kit. NOTE:
1) ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1 WIRING
SYSTEM WITH CONDUCTOR RATED
600 VOLTS.
2)**=USE "DRY CONTACTS" ONLY.
DO NOT SUPPLY FIELD POWER TO
THIS CIRCUIT.
3)DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.

www.DaikinApplied.com 19 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

Figure 28: Field Wiring Diagram - Multiple Point Power


PANEL

POWER BLOCK
CIRCUIT BREAKER OR
(BY OTHERS) DISCONNECT SWITCH

L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
OR CIRCUIT 1
L3 T3

EARTH F120 F120


GROUND
T1
Note: Separate grounding is DISCONNECT
(BY OTHERS)
required if fed from different MQ

transformers. Otherwise a 115


17
FUSE
N
OPTIONAL
VAC 20A for 2KVA
single ground is acceptable. Q12
MQ 30A for 3KVA
FIELD SUPPLIED
CONTROL POWER
CIRCUIT BREAKER 12 120 VAC
POWER BLOCK OR (BY OTHERS)
(BY OTHERS)
DISCONNECT SWITCH OPEN Q12 IF SUPPLY IS SEPARATE 120 VAC SOURCE

L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR
SOURCE AND FAN MOTORS
CIRCUIT 2
L3 T3

M5
M5
21
28 120 VAC
CHWR1 ** USE DRY CONTACTS ONLY, SEE NOTE 2
EVAP. WATER (BY OTHERS) MODE SWITCH
PUMP RELAY No. 1 EVAP. WATER PUMP RELAY IF MODE SWITCH IS USED, REMOVE
(BY OTHERS) 120VAC @ 0.25AMP MAX M5 LEAD 322 BETWEEN M5-21 AND MS-10.
MQ
57
17 N (735)
(718)
OFF TIME
M5 CLOCK
M5 58
** USE DRY CONTACTS ONLY, SEE NOTE 2 AUTO
49 120 VAC REMOTE
CHWR2 IF REMOTE SWITCH IS USED, SWITCH
EVAP. WATER (BY OTHERS)
(BY OTHERS) REMOVE MECHANICAL JUMPER ON
PUMP RELAY No. 2
EVAP. WATER PUMP RELAY M5 BETWEEN M5 TERMIONALS 58 & 59.
(BY OTHERS)
120VAC @ 0.25AMP MAX 59
MQ MANUAL (737)
17 N
(830)

(BY OTHERS)
120VAC @ 0.25AMP MAX M5
26 120 VAC

ALARM OUTPUT M5 EA1

MQ 5

17 N ** USE DRY CONTACTS ONLY, SEE NOTE 2


(721) EXTERNAL
IF EXTERNAL ALARM IS USED, REMOVE ALARM
M5 LEAD 402 BETWEEN M5 TERMINALS 5 & 15
15
(828)
M5 BC1
61

FOR RAPID
BACKUP
** USE DRY CONTACTS ONLY, SEE NOTE 2 RESTORE OPTION
CHILLER
ONLY
M5
62 (856)
(858)
M5
35 +

4-20 mA
SETPOINT OVERRIDE
(BY OTHERS)
M5
_
36
(720)
M5
38 +

4-20 mA
DEMAND LIMIT
(BY OTHERS)
M5
_
37
(833)

M5
FLow Switch Contacts
8 M

**USE DRY CONTACS ONLY


SEE NOTE 2
M5

(735)
23 DI2 TO/FROM BAS
CLA (CUSTOMER
LON
CLB CONNECTION)
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring, see wiring GND CONNECT TO GROUND
AT ONE END ONLY.
910170646_1RC

instruction in Kit.
NOTE:
1) ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1 WIRING
SYSTEM WITH CONDUCTOR RATED
600 VOLTS.
2)**=USE "DRY CONTACTS" ONLY.
DO NOT SUPPLY FIELD POWER TO
THIS CIRCUIT.
3)DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 20 www.DaikinApplied.com


Economizer

PACKAGE CHILLER

www.DaikinApplied.com
CONDENSER
AIR
ASSEMBLY
FLOW
OIL PRESS.
DISCHARGE SCHRADER DISCHARGE TRANSDUCER
TUBING VALVE TRANSDUCER
SHUT-OFF WITH SCHRADER SHUT-OFF
VALVE VALVE VALVE
(OPTIONAL)

BALL CHARGING
VALVE VALVE RELIEF
VALVE
AIR
FLOW SUCTION
DISCHARGE TRANSDUCER
OUTSIDE AIR TEMP. SENSOR F3/F4
TEMPERATURE COMPRESSOR
(WAA)

21
LIQUID SUCTION
INJECTION TUBING
TUBING
(OPTIONAL)

STRAINER SOLENOID
BALL
VALVE
LIQUID VALVE
TUBING

WATER OUT
WATER IN
(WOE) (WIE)
TEMP. SENSOR TEMP. SENSOR

SOLENOID
FILTER CHARGING SCHRADER VALVE SCHRADER EXPANSION CHARGING DX EVAPORATOR RELIEF SUCTION
DRYER VALVE VALVE (OPTIONAL) VALVE VALVE VALVE VALVE TEMP. SENSOR

NOTE:
PIPING SHOWN FOR ONE SYSTEM OF UNIT.
UNIT HAS TWO INDEPENDANT SYSTEMS.
Figure 29: Representative Refrigerant Diagram - Packaged Unit With Shell & Tube Evaporator Without Optional

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations
Installation and Application Considerations

Figure 30: Representative Refrigerant Diagram - Packaged Unit With Shell & Tube Evaporator With Optional Economizer

WITH OPTIONAL ECONOMIZER


PACKAGE CHILLER

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 22 www.DaikinApplied.com


Installation and Application Considerations

Figure 31: Representative Refrigerant Diagram - Packaged Unit With Braze Plate Evaporator Without Optional Economizer

PACKAGE CHILLER
W/O ECONOMIZER

PIPING SHOWN FOR ONE SYSTEM OF UNIT.


UNIT HAS TWO INDEPENDANT SYSTEMS.
NOTE:

www.DaikinApplied.com 23 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations

Representative Refrigerant Diagram - Packaged Unit With Braze Plate Evaporator With Optional Economizer

WITH OPTIONAL ECONOMIZER


PACKAGE CHILLER

PIPING SHOWN FOR ONE SYSTEM OF UNIT.


UNIT HAS TWO INDEPENDANT SYSTEMS.
NOTE:

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 24 www.DaikinApplied.com


Installation and Application Considerations - Remote Evaporators
Installation and Application Considerations - Remote Evaporators

Shipment Method 7. The condenser cannot be used for refrigerant charge


AWV chillers with remote evaporators ship in three pieces. isolation for service. The circuit charge will need to be
recovered for major service events.
• Outdoor condensing unit
• Remote evaporator IMPORTANT NOTE
• Refrigerant specialties kit with the unit has the following Service Form SF99006 (current version available from the
components for field installation: local sales office) must be submitted to Daikin Technical
—— Filter-drier housing and cores for field piping Response Center and reviewed at least two weeks prior to
—— Sight glass beginning piping installation.
—— Electronic expansion valve The following applies to all size units:
—— Solenoid valve
• New refrigerant piping must be used for all equipment
—— Evaporator vent and drain shutoff valves - waterside installations. Refrigerant piping must be properly sized for
—— Charging valve (on non-economizer models) the circuit capacity and unit refrigerant.
—— Suction coupling and flange to attachment evaporator • Piping system must be brazed if copper or welded if steel
—— Schrader valve and have the proper lay out with all required components.
—— Liquid/saturated coupling and flange to evaporator • Copper (Type L) piping is recommended; carbon steel
piping is allowed (see Table 8). Piping must be installed
per industry standards and local codes. Any welded pipe
Performance Data requires a replaceable suction line filter at chiller connect
AWV performance data is available from the current version of point.
Daikin Sales Tools or the local sales office. There is a derate to • Measured actual pipe length cannot exceed 200 feet.
the performance of an AWV with remote evaporator due to field • Maximum total equivalent length (TEL) cannot exceed
installed refrigerant line losses, exceeding those found on the 300 feet (75 feet for vertical suction lines). The evaporator
packaged arrangement. Use the recommended pipe sizes from cannot be located more than 20 feet above or 30 feet
Table 5 through Table 9 for design purposes. below the outdoor unit.
• Suction line connection at unit = 4 1/8-inch OD each.
Derate Procedure
• Underground refrigerant piping is not permitted.
1. Sketch the liquid and suction piping, including the actual • Field piping must include adequate service taps for
pipe lengths and all fittings. checking filter-drier, subcooling, and superheat.
2. From Table 4, add up the equivalent pressure drop for • Insulate complete suction lines. Liquid lines may be
the fittings in the suction line. Add this value to the actual insulated to prevent collection of condensation or loss of
linear feet of tubing to determine the total equivalent subcooling if required.
length (TEL) for the piping run. • Ensure the braze rod used is appropriate for the
materials being joined.
3. Using Daikin Sales Tools, enter TEL values to determine
adjusted unit performance. Consult the Daikin Technical
Table 4: Fitting Losses Equivalent Feet of Pipe
Response Center for all remote evaporator piping
installations for review and approval. 90-Degree 90-Degree
Line Size In. Angle Globe
Std. Radius Long Radius
OD Valve Valve
Elbow Elbow
Remote Evaporator Refrigerant Piping
2 5/8 29.0 69.0 6.0 4.1
Careful design of refrigerant piping is necessary for proper 3 1/8 35.0 84.0 7.5 5.0
system operation. Refer to the latest version of the ASHRAE 3 5/8 41.0 100.0 9.0 5.9
Handbook and the Daikin Applied Refrigerant Piping Design
4 1/8 47.0 120.0 10.0 6.7
Guide, AG31-011, for recommended refrigerant piping
5 1/8 58.0 140.0 13.0 8.2
practices. Size piping per Table 5 to Table 9. Design the
refrigerant piping to accomplish the following: 6 1/8 70.0 170.0 16.0 10.0
6 Steel 70.0 170.0 16.0 10.0
1. Assure proper refrigerant feed to the evaporator.
SOURCE: ASHRAE 2014 Handbook Refrigeration
2. Provide practical and economical refrigerant line sizes
NOTE: TEL values for the filter-drier and solenoid valve are already
without excess pressure drop. included and should not be added to the liquid line drop.
3. Maintain uniform oil return to the compressor under all
load conditions. Remote Evaporator Field Wiring Notes:
4. Keep the refrigerant suction line pressure drop to a
1. The 110-V liquid line solenoid valves (LSV) have to
maximum of 2°F in saturated temperature equivalent.
be wired back to the outdoor unit. All the conduit and
5. The velocity of each suction line must be sufficient to wiring is to be field supplied (14 gauge, red and white
return oil at 25% of the circuit rating for the application. wires, 3/8” conduit with straight and 90 degree fittings).
6. When facing the unit control box, the left-hand If additional length is required, use 14 gauge wire up to
compressor is circuit #1, and the right-hand is circuit #2. a maximum of an additional 100 feet. A din connector

www.DaikinApplied.com 25 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations - Remote Evaporators

is supplied with refrigerant specialties kits. Field to wire in the control cabinet. Use water tight boxes at splice
directly into compressor terminal box terminal block: locations that may be exposed to weather. Individual
connections must be soldered and shrink wrapped.
• Compressor #1: (LSV-1) wire 740-1A (red) wires
An outer shrink wrap is also required and should be
into compressor #1 terminal box terminal block at
wrapped with electical tape to be made more water
TB1-2-9. Wire 740-1B (white) wires to TB1-2-10.
resistant. The expansion valve wiring cannot run in
• Compressor #2: (LSV-2) wire 740-2A (red) wires conduit with other wiring that is over 24 Volts AC.
into compressor #2 terminal box terminal block at
TB2-2-9. Wire 740-2B (white) wires to TB2-2-10. 6. A flow switch must be installed in the leaving chilled
water line per manufacturer’s instructions and wired to
2. Two evaporator water temperature sensors with 100
terminals 8 and 23 on terminal block M5 in the chiller
feet of cable coiled up and attached to the unit base
control panel. See Unit Field Wiring Diagrams - Figure 27
for extension to the evaporator and insertion in fittings
and Figure 28.
located on the side of the inlet and outlet nozzles.
7. Do not reduce the wire lengths of factory wiring, except
3. One suction line refrigerant temperature sensor per as specifically noted in item #5.
circuit with 100 feet of cable coiled up and attached to
the unit base for extension to the evaporator.
Piping Layout
4. One suction line pressure transducer per circuit with 100
Figure 33 shows the piping layout for one of the two refrigerant
feet of cable coiled up and attached to the unit base for
circuits for AWV units with a remote evaporator with and
extension to the evaporator.
without the optional economizer circuit. The outdoor unit, the
5. The electronic expansion valve has a 30 foot long cable evaporator, and a kit of refrigerant components are shipped
attached and can be used when the outdoor unit is less as separate pieces for field mounting, wiring, and piping. The
than 30 feet away. For lengths greater than 30 feet but suction shutoff valve is standard on remote evaporator units.
no more than 200 feet, cut the factory supplied 22 AWG All components between the “Field Connection Points” should
cable/wire as close to the M12 connector (connects to be located as close to the evaporator as possible.
the EXV Stepper Motor) as possible to make a splice
using 14 AWG Wire Gauge size, reference Figure 32. Note: Field insulation of the suction lines and the liquid line on
NOTE: 14 AWG will use Belden part number 83754 or circuits with economizers is required. The outdoor unit will have
equivalent. For distances greater than 200 feet, 12 AWG a refrigerant charge equal to that of a packaged unit pumped
wire is recommended (Belden part number 83804 or down into the condenser. Any additional charge of refrigerant
equivalent). and oil required by the field piping is supplied by the customer.
The location and size of the refrigerant connections are shown
The inner foil shield and the outer Braid Shield should
on dimensional drawings available from a Daikin Applied sales
be grounded as close as possible to the EXV module
representative.
Figure 32: Remote EXV Field Wiring

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 26 www.DaikinApplied.com


Installation and Application Considerations - Remote Evaporators

Figure 33: Piping Schematic, Remote Evaporator (One of Two Circuits)


REMOTE CHILLER

NOTE:
PIPING SHOWN FOR ONE SYSTEM OF UNIT.
UNIT HAS TWO INDEPENDANT SYSTEMS.

REMOTE CHILLER
WITH OPTIONAL ECONOMIZER

www.DaikinApplied.com 27 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations - Remote Evaporators

Table 5: Sizing Guidelines for Horizontal or Downflow Suction Lines and Liquid Lines
Recommended Horizontal or Downflow Suction Line Size Recommended Liquid Line Size
Nominal Nominal
Circuit Estimated Line Suction Line Circuit Estimated Line Liquid Line Size
Capacity TEL (ft) Line Material Size (Inches) Capacity TEL (ft) Line Material (Inches)
65 50 Copper 3 5/8 65 50 Copper 1 5/8
90 50 Copper 3 5/8 90 50 Copper 1 5/8
115 50 Copper 3 5/8 115 50 Copper 1 5/8
140 50 Copper 4 1/8 140 50 Copper 1 5/8
165 50 Copper 4 1/8 165 50 Copper 2 1/8
190 50 Copper 4 1/8 190 50 Copper 2 1/8
215 50 Copper 5 1/8 215 50 Copper 2 1/8
240 50 Copper 5 1/8 240 50 Copper 2 1/8
265 50 Copper 5 1/8 265 50 Copper 2 1/8
65 75 Copper 3 5/8 65 75 Copper 1 5/8
90 75 Copper 3 5/8 90 75 Copper 1 5/8
115 75 Copper 4 1/8 115 75 Copper 2 1/8
140 75 Copper 4 1/8 140 75 Copper 2 1/8
165 75 Copper 5 1/8 165 75 Copper 2 1/8
190 75 Copper 5 1/8 190 75 Copper 2 1/8
215 75 Copper 5 1/8 215 75 Copper 2 1/8
240 75 Copper 5 1/8 240 75 Copper 2 1/8
265 75 Copper 5 1/8 265 75 Copper 2 5/8
65 100 Copper 3 5/8 65 100 Copper 1 5/8
90 100 Copper 3 5/8 90 100 Copper 1 5/8
115 100 Copper 4 1/8 115 100 Copper 2 1/8
140 100 Copper 5 1/8 140 100 Copper 2 1/8
165 100 Copper 5 1/8 165 100 Copper 2 1/8
190 100 Copper 5 1/8 190 100 Copper 2 1/8
215 100 Copper 5 1/8 215 100 Copper 2 5/8
240 100 Copper 6 1/8 240 100 Copper 2 5/8
265 100 Copper 6 1/8 265 100 Copper 2 5/8
65 125 Copper 3 5/8 65 125 Copper 1 5/8
90 125 Copper 4 1/8 90 125 Copper 1 5/8
115 125 Copper 4 1/8 115 125 Copper 2 1/8
140 125 Copper 5 1/8 140 125 Copper 2 1/8
165 125 Copper 5 1/8 165 125 Copper 2 1/8
190 125 Copper 5 1/8 190 125 Copper 2 5/8
215 125 Copper 6 1/8 215 125 Copper 2 5/8
240 125 Copper 6 1/8 240 125 Copper 2 5/8
265 125 Copper 6 1/8 265 125 Copper 2 5/8

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 28 www.DaikinApplied.com


Installation and Application Considerations - Remote Evaporators

Table 6: Sizing Guidelines for Horizontal or Downflow Suction Lines and Liquid Lines
Recommended Horizontal or Downflow Suction Line Size Recommended Liquid Line Size
Nominal Nominal
Circuit Estimated Line Suction Line Circuit Estimated Line Liquid Line Size
Capacity TEL (ft) Line Material Size (Inches) Capacity TEL (ft) Line Material (Inches)
65 150 Copper 3 5/8 65 150 Copper 1 5/8
90 150 Copper 4 1/8 90 150 Copper 2 1/8
115 150 Copper 4 1/8 115 150 Copper 2 1/8
140 150 Copper 5 1/8 140 150 Copper 2 1/8
165 150 Copper 5 1/8 165 150 Copper 2 1/8
190 150 Copper 6 1/8 190 150 Copper 2 5/8
215 150 Copper 6 1/8 215 150 Copper 2 5/8
240 150 Copper 6 1/8 240 150 Copper 2 5/8
265 150 Copper 6 1/8 265 150 Copper 2 5/8
65 175 Copper 4 1/8 65 175 Copper 1 5/8
90 175 Copper 4 1/8 90 175 Copper 2 1/8
115 175 Copper 4 1/8 115 175 Copper 2 1/8
140 175 Copper 5 1/8 140 175 Copper 2 1/8
165 175 Copper 5 1/8 165 175 Copper 2 5/8
190 175 Copper 6 1/8 190 175 Copper 2 5/8
215 175 Copper 6 1/8 215 175 Copper 2 5/8
240 175 Copper 6 1/8 240 175 Copper 2 5/8
265 175 Copper 6 1/8 265 175 Copper 2 5/8
65 200 Copper 4 1/8 65 200 Copper 1 5/8
90 200 Copper 4 1/8 90 200 Copper 2 1/8
115 200 Copper 4 1/8 115 200 Copper 2 1/8
140 200 Copper 5 1/8 140 200 Copper 2 1/8
165 200 Copper 5 1/8 165 200 Copper 2 5/8
190 200 Copper 6 1/8 190 200 Copper 2 5/8
215 200 Copper 6 1/8 215 200 Copper 2 5/8
240 200 Copper 6 1/8 240 200 Copper 2 5/8
265 200 Copper 6 1/8 265 200 Copper 3 1/8
65 225 Copper 4 1/8 65 225 Copper 2 1/8
90 225 Copper 4 1/8 90 225 Copper 2 1/8
115 225 Copper 4 1/8 115 225 Copper 2 1/8
140 225 Copper 5 1/8 140 225 Copper 2 5/8
165 225 Copper 5 1/8 165 225 Copper 2 5/8
190 225 Copper 6 1/8 190 225 Copper 2 5/8
215 225 Copper 6 1/8 215 225 Copper 2 5/8
240 225 Copper 6 1/8 240 225 Copper 3 1/8
265 225 Copper 6 1/8 265 225 Copper 3 1/8

www.DaikinApplied.com 29 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Installation and Application Considerations - Remote Evaporators

Table 7: Sizing Guidelines for Horizontal or Downflow Suction Lines and Liquid Lines
Recommended Horizontal or Downflow Suction Line Size Recommended Liquid Line Sizes
Nominal Nominal
Circuit Estimated Line Suction Line Circuit Estimated Line Liquid Line Size
Capacity TEL (ft) Line Material Size (Inches) Capacity TEL (ft) Line Material (Inches)
65 250 Copper 4 1/8 65 250 Copper 2 1/8
90 250 Copper 4 1/8 90 250 Copper 2 1/8
115 250 Copper 4 1/8 115 250 Copper 2 1/8
140 250 Copper 5 1/8 140 250 Copper 2 5/8
165 250 Copper 5 1/8 165 250 Copper 2 5/8
190 250 Copper 6 1/8 190 250 Copper 2 5/8
215 250 Copper 6 1/8 215 250 Copper 2 5/8
240 250 Copper 6 1/8 240 250 Copper 3 1/8
265 250 Copper 6 1/8 265 250 Copper 3 1/8
65 275 Copper 4 1/8 65 275 Copper 2 1/8
90 275 Copper 4 1/8 90 275 Copper 2 1/8
115 275 Copper 4 1/8 115 275 Copper 2 1/8
140 275 Copper 5 1/8 140 275 Copper 2 5/8
165 275 Copper 5 1/8 165 275 Copper 2 5/8
190 275 Copper 6 1/8 190 275 Copper 2 5/8
215 275 Copper 6 1/8 215 275 Copper 3 1/8
240 275 Copper 6 1/8 240 275 Copper 3 1/8
265 275 Copper 6 1/8 265 275 Copper 3 1/8
65 300 Copper 4 1/8 65 300 Copper 2 1/8
90 300 Copper 4 1/8 90 300 Copper 2 1/8
115 300 Copper 4 1/8 115 300 Copper 2 1/8
140 300 Copper 5 1/8 140 300 Copper 2 5/8
165 300 Copper 5 1/8 165 300 Copper 2 5/8
190 300 Copper 6 1/8 190 300 Copper 2 5/8
215 300 Copper 6 1/8 215 300 Copper 3 1/8
240 300 Copper 6 1/8 240 300 Copper 3 1/8
265 300 Copper 6 1/8 265 300 Copper 3 1/8

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 30 www.DaikinApplied.com


Installation and Application Considerations - Remote Evaporators

Table 8: Alternate Sizing Guidelines for Horizontal or Table 9: Sizing Guidelines for Upflow Lines
Downflow Suction Lines - Steel Recommended Upflow Suction Line Size
Recommended Horizontal or Downflow Suction Line Size
Nominal Circuit Suction Line Estimated Line
Nominal Circuit Estimated Line Suction Line Capacity Line Material Size (Inches) TEL (ft)
Capacity TEL (ft) Line Material Size (Inches)
65 Copper 3 5/8 50
240 100 Steel 6
90 Copper 3 5/8 50
265 100 Steel 6
115 Copper 3 5/8 50
215 125 Steel 6
140 Copper 4 1/8 50
240 125 Steel 6
165 Copper 4 1/8 50
265 125 Steel 6
190 Copper 5 1/8 50
190 150 Steel 6
215 Copper 5 1/8 50
215 150 Steel 6
240 Copper 5 1/8 50
240 150 Steel 6
265 Copper 5 1/8 50
265 150 Steel 6
65 Copper 3 5/8 75
190 175 Steel 6
90 Copper 3 5/8 75
215 175 Steel 6
115 Copper 3 5/8 75
240 175 Steel 6
140 Copper 4 1/8 75
265 175 Steel 6
165 Copper 4 1/8 75
190 200 Steel 6
190 Copper 5 1/8 75
215 200 Steel 6
215 Copper 5 1/8 75
240 200 Steel 6
240 Copper 5 1/8 75
265 200 Steel 6
265 Copper 5 1/8 75
190 225 Steel 6
215 225 Steel 6
240 225 Steel 6
265 225 Steel 6
190 250 Steel 6
215 250 Steel 6
240 250 Steel 6
265 250 Steel 6
190 275 Steel 6
215 275 Steel 6
240 275 Steel 6
265 275 Steel 6
190 300 Steel 6
215 300 Steel 6
240 300 Steel 6
265 300 Steel 6
NOTE: FOR STEEL LINES ONLY
For use in horizontal and down flow applications only where
the evaporator is at or below the chiller elevation.
Recommend schedule 40 steel pipe.
Carbon steel pipe shall be ASTM Standard A 53 Grade B,
Type E (electric resistance welded) or Type S (seamless); or
ASTM Standard A 106 Grade B (seamless). Standard A 53
Type F is not permitted.
Refrigeration piping design and fabrication should be in
accordance with the applicable sections of ASME B31.5 -
Refrigeration Piping and Heat Transfer Components for the
steel piping.

www.DaikinApplied.com 31 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Dimensions - Remote Evaporators

D imensions - R emote E vaporators

Table 10: Evaporator Data for AWV Remote Evaporator Models


Shipping Weight Operating Weight Water Volume
Evaporator Model
(lb) (kg) (lb) (kg) (gal) (L)
EV40271010/9 1197 543 1761 799 67 255
EV40271111/7 1219 553 1773 804 66 250
EV40271212/7 1239 562 1770 803 63 240
EV50271414/7 1739 789 2631 1193 106 403
EV50271717/5 1819 825 2648 1201 99 374
EV50391212/11 2077 942 3365 1526 154 582
EV66331515/7 2593 1176 4475 2030 225 851
EV66391414/11 2875 1304 5145 2334 271 1027
EV66391616/9 2956 1341 5157 2339 263 995
EV66391717/7 2998 1360 5164 2342 259 979

Figure 34: Evaporator Model EV4027


2918 42
114.9 1.6 REF
2750
108.3
1375 103
54.1 4.1
HEATER
WIRES

BLOCK-OFF
EVAPORATOR EV4027 WITH PLATES,
SPACERS, AND BOLTS
332532100 80 (M14 X 1.50 X 50MM LONG)
3.2
470
18.5
100
3.9 110
16 4.33
.63

2412 169
95.0 6.7 110
4.33
18
.7
ALL Ø0.25
COUPLINGS
303
11.9
455 EVAPORATOR 455
17.9 NAME PLATE 17.9 SHRADER FITTING 75 75
66 66 FOR REFRIGERANT 2.95 2.95
2.58 2.58 ASME/CRN PRESSURE (2)
1.625 IDS 1/4" NPTF NAME PLATE 1/4" NPTF
LIQUID FERRULE
PART # E44070016
FLANGE # E44060007
O RING # E44130152 INLET
OUTLET
1/2" NPTF
485 3000# HALF CPLG. 406 ASME/ CRN EVAPORATOR
NAME PLATE NAME PLATE
19.1 SENSOR WELL QTY 2 16.0
QTY 2
250 (SEE NOTE 9)
9.8
SUCTION O RING
# E44130201
168 C C
1/2" NPTF 120
10 6.63 PIPE QTY 2 463
4.7
.39 GROOVED 18.2
QTY 2 FEET MOUNTING
2123 270
83.6 10.6 528
18MM X 43MM 20.8
SLOTS
40 33 (QTY. 4)
60
1.57 1.3
2.36
60
2.36
60
2.4
SECTION C-C

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 32 www.DaikinApplied.com


Dimensions - Remote Evaporators

Figure 35: Evaporator Model EV5027


42
2935
1.6
115.6
REF
2750 110
108.3 4.3
1375
54.1
HEATER
WIRES
BLOCK-OFF
WITH PLATES,
EVAPORATOR EV5027 80 SPACERS, AND BOLTS
3.1 (M14 X 1.50 X 50MM LONG)
332532200

572
22.5
138
5.43
64 16
100
2.5 .6
3.9

138
2360 195 5.43
92.9 7.7
12
.5
ALL Ø.25
COUPLINGS
DETAIL A
354
219 13.9
445 8.63 PIPE EVAPORATOR
17.5 GROOVED NAME PLATE 445 94 94
75 75 QTY 2 17.5 SHRADER FITTING 3.70 3.70
1/4" NPTF ASME/CRN FOR REFRIGERANT
3.0 3.0 NAME PLATE 1/4" NPTF PRESSURE (2)

1.625 IDS HEATER


WIRES
LIQUID FERRULE
PART # E44070016 1/2" NPTF 508 ASME/ CRN EVAPORATOR
644 FLANGE # E44060007 3000# HALF CPLG. 20.0 NAME PLATE NAME PLATE

25.4 O RING # E44130152 QTY 2

358 OUTLET INLET


14.1 SUCTION O RING
# E44136600
1/2" NPTF SENSOR WELL
QTY 2 QTY 2
10 C C (SEE NOTE9) 120
.4 443
4.7
2123 262 17.4
18MM X 43MM
SLOTS 83.6 10.3 FEET MOUNTING
(QTY. 4) 528
20.8
51
2.0 40
1.6 60 33
51 1.3
2.4
2.0
SECTION C-C

Figure 36: Evaporator Model EV5039


33
18MM X 43MM
1.3 SLOTS
(QTY. 4)

60
2.4
SECTION C-C
4085 42
160.8 1.6 REF

3900 110
153.5 4.3
1950 BLOCK-OFF
76.8 WITH PLATES,
SPACERS, AND BOLTS
HEATER (M14 X 1.50 X 50MM LONG)
WIRES

EVAPORATOR EV5039
80
332532300 3.2

572 16 137.9
22.5 .63 5.43

100
3.9

137.9
5.43
64
2.5
3510 195
138.2 7.7

140 DETAIL A
1.625 IDS 5.5
LIQUID FERRULE SCHRADER FITTING
PART # E44070016 FOR REFRIGERANT
FLANGE # E44060007 219.2 PRESSURE (2)
EVAPORATOR
O RING # E44130152 635 8.63 PIPE NAME PLATE 354
25.0 GROOVED 635 13.9
75 75 QTY 2 25.0
ASME/CRN 94 94
2.95 2.95 1/4" NPTF NAME PLATE 3.70 3.70
1/4" NPTF

638
25.1
HEATER
1/2" NPTF 508 WIRES
ASME/ CRN EVAPORATOR
644 3000# HALF CPLG. 20.0
NAME PLATE NAME PLATE

25.4 QTY 2

358 OUTLET INLET


14.1

SENSOR WELL
C C QTY 2 SUCTION
(SEE NOTE9) 120 O RING
1/2" NPTF 4.7 443
# E44136600
10 3283 QTY 2 262 17.4
.39 129.3 10.3 FEET MOUNTING
528
40 20.8
1.57
12
51 2X .5
2.01 51 ALL Ø.25
2.01 COUPLINGS

www.DaikinApplied.com 33 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Dimensions - Remote Evaporators

Figure 37: Evaporator Model EV6633


3527
138.9 REF

77 3300 150
3.0 129.9 5.9
HEATER WIRE 42
APPROX. LOCATION 1.6 REF
BLOCK-OFF WITH PLATES,
SPACERS, AND BOLTS
(M14 X 1.50 X 50MM LONG

EVAPORATOR EV6633 1650


65.0
332945000
664
26.1

100
3.9

2830 [235]
111.4 9.25 LIQUID AND SUCTION CAST HEAD
DETAILS ARE FOR REFERENCE ONLY
635
25.0
466 466 430
273 EVAPORATOR NAMEPLATE
18.3 10.7 PIPE 18.3 16.9
106 106 1/4" NPTF 362 GROOVED 362 106 106
4.2 4.2 ASME/CRN NAMEPLATE 14.3
QTY 2 14.3 QTY 2 4.16 4.16

1/2" NPTF
QTY 2
689 660 167
26.0 1/2" NPTF 6.57
27.1 3000# HALF CPLG
OUTLET QTY 2
357 INLET
14.1
Ø6.38 [162]

120 167
  4.7 6.57
54 2123 189 SUCTION O RING
2.13 12 83.6 7.4 #E44136670
68
2X .5 SENSOR WELL
2.68 QTY 2
ALL Ø0.25
(18MM).71 X (43MM)1.69 (SEE NOTE 9)
COUPLINGS
SLOTS QTY 4
68
2.68 528 463
Ø2.125 IDS
LIQUID FERRULE 20.8 18.2
PART # E4470043 33
FLANGE # E44060009 1.3
O RING # E44130170

60
2.4

Figure 38: Evaporator Model EV6639


33 (18MM).71 X (43MM)1.69
1.3 SLOTS (QTY. 4)

60
2.4
SECTION C-C
4145 42
163.2 REF 1.6 REF
BLOCK-OFF
95 3900 150 WITH PLATES,
3.7 153.5 5.9 SPACERS, AND BOLTS
HEATER (M14 X 1.50 X 50MM LONG)
WIRES

80 166.9
EVAPORATOR EV6639 14 6.57
3.2 .55
332532400 1950
76.8
664 166.9
26.1 6.57

99.8
3.9
162
6.38

LIQUID AND SUCTION


3430 230 CAST HEAD DETAILS
12
2X .5 135.0 9.1 ARE FOR REF. ONLY
ALL Ø0.25
COUPLINGS EVAPORATOR
273 NAME PLATE 640 430
10.7 PIPE 25.2 16.9
105.8 105.8 662 QTY 2 ASME/CRN 662 105.8 105.8
4.2 4.2 26.1 NAME PLATE 26.1 4.16 4.16

1/4" NPTF 1/4" NPTF

INLET
20.1
OUTLET .8
688.9 1/2" NPTF 660 ASME/ CRN EVAPORATOR
NAME PLATE NAME PLATE
3000# HALF CPLG. 26.0
27.1 SENSOR WELL QTY 2
QTY 2
357 (SEE NOTE9)
14.1

C C
463 HEATER
1/2" NPTF 32.5 WIRES
QTY 2 120 18.2
1.3 MOUNTING FEET
4.7
10.5
3282 231 528
68 .41 2.125 IDS
LIQUID FERRULE 129.2 9.1 20.8
2.68
PART # E44070043
FLANGE # E44060009 SUCTION O RING
60 O RING # E44130170 # E44136670
68 2.36
2.68
DETAIL B

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 34 www.DaikinApplied.com


Dimensional Drawings

Dimensional Drawings

Figure 39: Reference Dimensional Drawing - 08 Fan to 14 Fan Configurations With Brazed Plate Evaporator

43.8
WATER
INLET / OUTLET
MINI CONTROL BOX
(ALL TURBOSCREW UNITS)
L1 / L2
L3 / L4 87.6
L5 / L6 (10, 12 & 14 FAN) DOES NOT INCLUDE
LIFTING LUGS

100.1
FIELD POWER ENTRY
AT BOTTOM OF BOX

Ø6.0 GROOVED
CONNECTION CG Y
37.21

13.00

CG Z
CG X
A (WATER INLET) 5.20 BASE
B (WATER OUTLET) RAIL WIDTH
TYP.
Z (BASE LENGTH)

M7 / M8 (12 & 14 FAN)


M5 / M6
.750 M3 / M4
TYP. M1 / M2

2.60
TYP.

Table 11: Unit Dimensions by Configuration with Brazed Plate Evaporator

# OF L1 / L3 / L5 / M1 / M3 / M5 / M7 /
EVAP A B Z CG X CG Y CG Z
FANS L2 L4 L6 M2 M4 M6 M8

ACH1000DQ-166 152.8 169.1


Refer to Submitted As-Built Drawings

8 179.3 148 N/A 160


ACH1000DQ-206 156.5 172.8

ACH1000DQ-206 156.5 172.8 N/A

10 ACH1000DQ-250 160.7 177 217.2 105 169 190

ACH1000DQ-330 168.3 184.6


20 12 93
ACH1000DQ-206 156.5 172.8

12 ACH1000DQ-250 160.7 177 255.1 105 202 136 197

ACH1000DQ-330 168.3 184.6

ACH1000DQ-250 160.7 177.0


14 293.0 139.0 228.0 136.0 250.0
ACH1000DQ-330 168.3 184.6

www.DaikinApplied.com 35 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Dimensional Drawings

Figure 40: Reference Dimensional Drawing - 12 Fan and 14 Fan Configurations with Shell and Tube Evaporator
87.6
DOES NOT INCLUDE
LIFTING LUGS

100.1

WATER INLET
WATER CG Y
OUTLET

CG X
CG Z 5.2 BASE
B A FIELD POWER ENTRY FROM
BOTTOM FOR SMALL RAIL WIDTH
Z (BASE LENGTH) CONTROL BOX (SHOWN),
FROM SIDE FOR LARGE
CONTROL BOX,

M7 / M8 M5 / M6 M3 / M4 M1 / M2

2.60

D RH
(OPTIONAL
RH WATER D LH .750
CONN.) (STANDARD MOUNTING HOLE SIZE
TYP
LH WATER
CONN.)

2.60
L5 / L6 L3 / L4 L1 / L2

Figure 41: Reference Dimensional Drawing - 16 Fan - 30 Fan Configurations with Shell and Tube Evaporator
87.6
DOES NOT INCLUDE
LIFTING LUGS

100.1

WATER INLET
WATER CG Y
OUTLET

CG X
CG Z
5.2 BASE
B A FIELD POWER ENTRY FROM
BOTTOM FOR SMALL RAIL WIDTH
Z (BASE LENGTH) CONTROL BOX (SHOWN),
FROM SIDE FOR LARGE
CONTROL BOX,

M9 / M10 M7 / M8 M5 / M6 M3 / M4 M1 / M2

2.60

D RH
(OPTIONAL
RH WATER D LH .750 MOUNTING HOLE SIZE
CONN.) (STANDARD TYP
LH WATER
CONN.)

2.60
L7 / L8 L5 / L6 L3 / L4 L1 / L2

NOTE: Water connection sizes are given in Pressure Drop Data starting on page 39.
“L” refers to Lifting Eye Point locations. “M” refers to Mounting Point locations.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 36 www.DaikinApplied.com


Dimensional Drawings

Table 12: Unit Dimensions by Configuration with Shell and Tube Evaporator

# OF L1 / L3 / L5 / L7 / M1 / M3 / M5 / M7 / M9 /
EVAP A B C D LH D RH Z CG X CG Y CG Z
FANS L2 L4 L6 L8 M2 M4 M6 M8 M10

12 EV 4027 148.4 95.0 17.0 31.9 55.7 258.1 23 121.3 199.6 15 80.3 135.3 200.5
EV 4027 169.7 95.0 17.0 31.9 55.7 296 N/A N/A
14 23 146.1 249.3 15 80.3 160.2 249.3
EV 5027 171.1 92.9 21.2 29.9 57.8 296
EV 4027 169.7 95.0 17.0 31.9 55.7 334
16 EV 5027 171.1 92.9 21.2 29.9 57.8 334 23 78 190 319.3 15 80.3 135.3 200.5 290.5
EV 5039 171.1 138.2 21.2 29.9 57.8 334
EV 4027 169.7 95.0 17.0 31.9 55.7 371.7
18 EV 5027 171.1 92.9 21.2 29.9 57.8 371.7 23 78 190 313 15 80.3 135.3 200.5 310

Refer to Submitted As-Built Drawings


EV 5039 171.1 138.2 21.2 29.9 57.8 371.7
EV 5027 171.1 92.9 21.2 29.9 57.8 409.6
20 EV 5039 171.1 138.2 21.2 29.9 57.8 409.6 23 135 209 320 15 80.3 160.2 238 363
EV 6633 175.5 111.4 21.2 26.9 60.1 409.6
EV 5027 171.1 92.9 21.2 29.9 57.8 447.5
EV 5039 171.1 138.2 21.2 29.9 57.8 447.5
22 23 135 209 365 12 80.3 160.2 280 380
EV 6633 175.5 111.4 21.2 26.9 60.1 447.5
EV 6639 173.7 135.0 21.2 26.9 60.1 447.5
EV 5027 171.1 92.9 21.2 29.9 57.8 485.4
EV 5039 171.1 138.2 21.2 29.9 57.8 485.4
24 23 135 250 400 15 80.3 160.2 280 400
EV 6633 175.5 111.4 21.2 26.9 60.1 485.4
EV 6639 173.7 135.0 21.2 26.9 60.1 485.4
EV 6633 175.5 111.4 21.2 26.9 60.1 523.2
26 23 135 250 400 15 80.3 160.2 280 450
EV 6639 173.7 135.0 21.2 26.9 60.1 523.2
EV 6633 175.5 111.4 21.2 26.9 60.1 561.0
28 23 135 250 447 15 80.3 160.2 280 450
EV 6639 173.7 135.0 21.2 26.9 60.1 561.0
EV 6633 175.5 111.4 21.2 26.9 60.1 598.9
30 23 135 321 488 15 80.3 200 280 490
EV 6639 173.7 135.0 21.2 26.9 60.1 598.9

www.DaikinApplied.com 37 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Isolator Information

Isolator Information

Isolator Installation Figure 43: Spring Isolator - 2 Spring Schematic

Transfer and place the unit as indicated in the Installation


section beginning on page 7. In all cases, set the unit in
place and level. If anti-skid pads are used, do not use hold
down bolts. If hold down bolts are used, do not use anti-skid
pads.
Mounting locations for each model configuration can be
found in the Dimensional Drawings section beginning on
page 35 or in the Submittal As-Built Drawings, available
from a Daikin Applied sales representative. Submittal As-
Built Drawings also specify the correct isolator color for each
mounting location, if ordered.
When spring isolators are required, install springs under the
main unit supports. Then unit should be set initially on shims or
blocks at the listed spring free height. Isolator springs should
not be loaded until all unit installation tasks are complete,
then the springs should be adjusted to the vendor listed
compression for the load point. When securing the isolator, do
not overtighten the mounting bolts. Overtightening may result
in cracking of the cast isolator housing and will have a negative Figure 44: Spring Isolator - 4 Spring Schematic
impact on the isolation effect.
Installation of spring isolators requires flexible piping
connections and at least three feet of flexible electrical conduit
to avoid straining the piping and transmitting vibration and
noise.
Neoprene waffle pads, supplied by customers, should be
mounted at the defined mounting point locations along the full
rail width.

Figure 42: Rubber-in-Shear Isolator Schematic


6.25
5.00
3.75
3.00 .500-13NC-2B

R4

4.63
3.87
VM&C
VM&C

.56 TYP. R .28


TYP.

R4

R.250 TYP. Figure 45: Mounting Location Reference Drawing


RECESSED
GRIP RIBS R.750 TYP.
AWV - Approximate Mounting Locations
See Dimensional Drawing for exact location
DURULENE
MATERIAL
1.13 .25
APPROX. M9 M7 M5 M3 M1
CONTROL PANEL

1.63
.38

RAISED GRIP RIBS

M10 M8 M6 M4 M2

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 38 www.DaikinApplied.com


Pressure Drop Data
Pressure Drop Data

Table 13: Evaporator Flow Limits Figure 48: Model ACH1000DQ-250AH


Conn. Minimum Maximum Evaporator ACH1000DQ-250AH
EVAP
Size (in.) gpm ft H gpm ft H 20

ACH1000DQ-166AH 5 157.0 1.7 528.0 17.1


ACH1000DQ-206AH 5 197.0 2.0 660.0 16.9
ACH1000DQ-250AH 5 239.0 2.0 766.0 16.8
ACH1000DQ-330AH 5 315.0 2.3 925.0 16.9
EV40271010/09 6 148.8 2.1 595.7 26.7 PD
(ft)
EV40271111/07 6 188.0 2.0 748.0 26.0 10
EV40271212/07 6 188.0 2.3 748.0 28.1
EV50271414/07 8 219.3 2.4 876.6 28.4
EV50271717/05 8 290.6 2.6 1171.2 30.4
EV50391212/11 8 207.8 3.0 834.8 35.7
EV66331515/07 10 336.4 2.7 1329.7 30.4
EV66391414/11 10 260.6 3.7 1042.6 40.6
EV66391616/09 10 317.4 3.7 1261.9 41.6 0
0 100 200 300 400 500 600 700 800 900
EV66391717/07 10 398.5 2.7 1586.8 32.3 Flow Rate (gpm)

NOTE: Flow rates and pressure drops reflect water only and do not
apply to glycol solutions.

Figure 46: Model ACH1000DQ-166AH Figure 49: Model ACH1000DQ-330AH


Evaporator ACH1000DQ-166AH Evaporator ACH1000DQ-330AH

20 20

PD PD
(ft) (ft)
10 10

0 0
0 100 200 300 400 500 600 0 200 400 600 800 1000
Flow Rate (gpm) Flow Rate (gpm)

Figure 47: Model ACH1000DQ-206AH Figure 50: Model EV40271010/09


Evaporator ACH1000DQ-206AH Evaporator EV40271010/09

20 30

20

PD
PD
(ft) (ft)
10

10

0
0 0 100 200 300 400 500 600 700
0 100 200 300 400 500 600 700
Flow Rate (gpm)
Flow Rate (gpm)

www.DaikinApplied.com 39 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Pressure Drop Data

Figure 51: Model EV40271111/07 Figure 54: Model EV50271717/05

Evaporator EV40271111/07 Evaporator EV50271717/05

30
40

30

20
PD
PD (ft)
(ft)
20

10

10

0 0
0 100 200 300 400 500 600 700 800 0 200 400 600 800 1000 1200 1400

Flow Rate (gpm) Flow Rate (gpm)

Figure 52: Model EV40271212/07 Figure 55: Model EV50391212/11


Evaporator EV40271212/07 Evaporator EV50391212/11

30 40

30

20

PD
PD (ft)
(ft) 20

10

10

0
0 100 200 300 400 500 600 700 800 0
0 100 200 300 400 500 600 700 800 900
Flow Rate (gpm) Flow Rate (gpm)

Figure 53: Model EV50271414/07 Figure 56: Model EV66331515/07


Evaporator EV66331515/07
Evaporator EV50271414/07
40
30

30

20

PD PD
(ft) (ft)
20

10

10

0 0
0 200 400 600 800 1000 0 200 400 600 800 1000 1200 1400
Flow Rate (gpm) Flow Rate (gpm)

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 40 www.DaikinApplied.com


Pressure Drop Data

Figure 57: Model EV66391414/11


Evaporator EV66391414/11

50

40

PD 30
(ft)

20

10

0
0 200 400 600 800 1000 1200

Flow Rate (gpm)

Figure 58: Model EV66391616/09

Evaporator EV66391616/09

50

40

PD 30
(ft)

20

10

0
0 200 400 600 800 1000 1200 1400

Flow Rate (gpm)

Figure 59: Model EV66391717/07


Evaporator EV663917170/7

40

30

PD
(ft)
20

10

0
0 200 400 600 800 1000 1200 1400 1600 1800

Flow Rate (gpm)

www.DaikinApplied.com 41 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Controller Operation

Controller Operation

Operator Responsibilities General Description


It is important that the operator become familiar with the The MicroTech® III control system consists of a controller and
equipment and the system before attempting operation. During a number of extension input/output (I/O) modules, which vary
the initial startup of the chiller, the Daikin Applied service depending on the unit size and configuration. The control
technician will be available to answer any questions and system provides the monitoring and functions required for the
instruct the proper operating procedures. It is recommended controlled, efficient operation of the chiller. The MicroTech® III
that the operator maintain an operating log for each individual controllers used on Pathfinder® chillers are not interchangeable
chiller unit. In addition, a separate maintenance log should be with previous MicroTech® II controllers.
kept of the periodic maintenance and servicing activities. The operator can see all critical operating conditions by
using the screen located on the main controller. In addition
Operator Schools to providing all normal operating controls, the MicroTech®
III control system will take corrective action if the chiller is
Training courses for Pathfinder® Air-Cooled Screw operating outside of its normal design conditions.
Maintenance and Operation are held throughout the year at the
Daikin Learning Institute in Verona, Virginia. The class includes The control panel is located on the front of the unit at the
instruction on basic refrigeration, MicroTech® III controllers, compressor end. There are three doors. The control panel is
enhancing chiller efficiency and reliability, MicroTech® III behind the left-hand door. The power panels are behind the
troubleshooting, system components, and other related middle and right-hand doors. The control power transformer is
subjects. For more information, refer to the back cover of this located in the power panel adjacent to the control panel.
document for Training contact information.
Controller Features
Software Version • Readout of the following temperature and pressure
readings:
The unit software and BSP (Board Support Package) versions —— Entering and leaving chilled water temperature
can be viewed using the keypad/display. From the Main Menu, —— Saturated temperatures and pressures for evaporator
turn the knob to the right to reach the About Chiller menu and and condenser
press Enter (the knob). The software version is displayed as —— Outside air temperature
“App Version =”. Scroll down in this menu (turn knob to the
—— Suction and discharge temperatures with calculated
right), the BSP version will also be displayed (“BSP Version=”).
superheat for discharge and suction lines
—— Oil pressure and temperature
—— Suction and discharge pressure
WARNING
• Automatic control of primary and standby chilled water
Electric shock hazard: can cause personal injury or
pumps. The control will start one of the pumps (based
equipment damage. This equipment must be properly
on lowest run-hours) when the unit is enabled to run (not
grounded. Connections to, and service of, the MicroTech® III
necessarily running on a call for cooling) and when the
control panel must be performed only by personnel who are
water temperature reaches a point of freeze possibility.
knowledgeable in the operation of this equipment .
• Three levels of security protection against unauthorized
changing of set points and other control parameters.
CAUTION • Warning and fault diagnostics to inform operators of
Static sensitive components. A static discharge while conditions in plain language. All events and alarms are
handling electronic circuit boards can cause damage to the time and date-stamped for identification of when the fault
components. Use a static strap before performing any service condition occurred.
work. Never unplug any cables, circuit board terminal blocks, • Twenty-five previous alarms are available.
or power plugs while power is applied to the panel. • Remote input signals for chilled water reset, demand
limiting, and unit enable.
NOTICE • Test mode allows the service technician to manually
This equipment generates, uses, and can radiate radio control the outputs and can be used for a system check.
frequency energy and, if not installed and used in accordance • Building Automation System (BAS) communication
with this instruction manual, can cause interference to radio capability via LonTalk®, Modbus®, or BACnet® standard
communications. Operation of this equipment in a residential protocols for all BAS manufacturers.
area can cause harmful interference, in which case the user
• Pressure transducers for direct reading of system
will be required to correct the interference at the user’s own
pressures.
expense. Daikin disclaims any liability resulting from any
interference or for the correction thereof. NOTE: The Emergency Switch Relay, located on the front of
the control panel door when ordered, de-energizes
the control power of all circuits when activated,
causing an immediate compressor and fan shutdown.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 42 www.DaikinApplied.com


Controller Operation

System Architecture Modbus Communication - Unit


The overall controls architecture uses the following: The unit controller (UC) communicates to the compressor
VFD’s and the EXV modules via the Modbus RTU connection
• One MicroTech® III unit controller
on the controller itself. Communication to the VFD’s and EVAP
• I/O extension modules (sometimes referred to as EXV MODULE is required for operation in all configurations.
“controllers”) as needed depending on the configuration Communication to ECON EXV MODULE is required only if the
of the unit chiller is configured with economizers.
• Up to three BAS interface modules as needed based on
installed options

Figure 60: System Architecture Schematic

Compressor Compressor
VFD 1 VFD 2

Modbus

Evap EXV Economizer EXV


BAS Comm BAS Comm BAS Comm
Unit Controller Module Module
Interface Interface Interface
Module Module Module

Peripheral Bus

Alarm/Limit Circuit 1 Circuit 2 RapidRestore®


I/O Extension I/O Extension I/O Extension I/O Extension

DC
Fan
DC
Fan
DC
Fan ... DC
Fan

Modbus

DC Fan Controller

NOTE: Graphic shows typical chiller controller arrangement; individual chiller configurations will be as ordered.

www.DaikinApplied.com 43 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Controller Operation

MicroTech® III Inputs/Outputs CC Modules - Circuit #1 and #2


Unit Controller - UC Module Table 18: Analog Inputs - For Each Circuit

# Description Signal Source


Table 14: Analog Inputs - Evaporator
X1 Discharge Temperature NTC Thermister (10K@25°C)
# Description Signal Source X2 Suction Temperature NTC Thermister (10K@25°C)
AI1 Evap Entering NTC Thermister X5 Evaporator Pressure Ratiometric 0.5-4.5 Vdc
Water Temp (10K@25°C)
X6 Oil Pressure Ratiometric 0.5-4.5 Vdc
AI2 Evap Leaving NTC Thermister
Water Temp (10K@25°C) X7 Condenser Pressure Ratiometric 0.5-4.5 Vdc
AI3 Outside Ambient NTC Thermister
Temperature (10K@25°C) Table 19: Digital Outputs - For Each Circuit
X4 LWT Reset 4-20 mA Current
# Description Output Off Output On

Table 15: Analog Outputs - Fan VFD DO1 Compressor Run Compressor Off Compressor
Command On
# Description Output Signal DO2 Liquid Line SV Solenoid Closed Solenoid Open
X5 Fan VFD #1 0-10 Vdc DO3 Liquid Injection SV Solenoid Closed Solenoid Open
X6 Fan VFD #2 0-10 Vdc DO4 100% VR SV Solenoid Closed Solenoid Open
DO5 75% VR SV Solenoid Closed Solenoid Open
Table 16: Digital Inputs DO6 50% VR SV Solenoid Closed Solenoid Open
# Description Signal Off Signal On X8 Economizer SV Solenoid Closed Solenoid Open
DI1 GFP Relay 1 Fault No Fault
DI2 Evaporator Flow Switch No Flow Flow EEXV Modules - Circuit #1 and #2
DI3 Mode Switch Cool mode Ice mode
DI4 Remote Switch Unit disable Unit enable Table 20: Digital Inputs
DI5 Unit Switch Unit disable Unit enable # Description Signal Off Signal On
DI6 Emergency Stop Unit off Unit enable DI1 Mechanical Low Pressure Switch Fault No Fault
X8 GFP Relay 2 Fault No Fault
Table 21: Digital Outputs
Table 17: Digital Outputs # Description Output OFF Output ON

# Description Output OFF Output ON DO1 Economizer SV Solenoid Closed Solenoid Open

DO1 Evaporator Water Pump 1 Pump Off Pump On


Table 22: EEXV Stepper Motor Output
DO2 Alarm Relay Alarm not Alarm Active
Active # Description
DO3 Circuit #1 Fan Output #1 Fan(s) Off Fan(s) On M1+
Circuit # Evaporator EXV Stepper Coil 1
DO4 Circuit #1 Fan Output #2 Fan(s) Off Fan(s) On M1-
DO5 Circuit #1 Fan Output #3 Fan(s) Off Fan(s) On M2+
Circuit # Evaporator EXV Stepper Coil 2
DO6 Circuit #1 Fan Output #4 Fan(s) Off Fan(s) On M2-
DO7 Circuit #2 Fan Output #1 Fan(s) Off Fan(s) On
DO8 Circuit #2 Fan Output #2 Fan(s) Off Fan(s) On Evaporator EXV Module
DO9 Circuit #2 Fan Output #3 Fan(s) Off Fan(s) On
DO10 Circuit #2 Fan Output #4 Fan(s) Off Fan(s) On Table 23: EXV Stepper Outputs

Driver Description
A Evaporator EXV Circuit #1
B Evaporator EXV Circuit #2

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 44 www.DaikinApplied.com


Controller Operation

Economizer EXV Module Compressor VFDs


Table 24: Analog Inputs Table 30: Digital Inputs
# Description Signal Off Signal On
# Description Signal Source
H1 Circuit # Alarm No Alarm
S1 Economizer Pressure Circuit #1 Ratiometric 0.5-4.5 Vdc
Mechanical High
S6
S2 Economizer Temperature Circuit #1 NTC 10K Thermister Pressure Switch
S3 Economizer Pressure Circuit #2 Ratiometric 0.5-4.5 Vdc
S4 Economizer Temperature Circuit #2 NTC 10K Thermister

Table 25: EXV Stepper Outputs

Driver Description
A Economizer EXV Circuit #1
B Economizer EXV Circuit #2

Alarm/Limit Module
Table 26: Analog Inputs

# Description Signal Source


X3 Demand Limit 4-20 mA

Table 27: Digital Inputs

# Description Signal Off Signal On


X1 External Alarm External Device Failure External
Device OK
X5 Circuit #1 Switch Circuit Off Circuit On
X6 Circuit #2 Switch Circuit Off Circuit On

Table 28: Digital Outputs

# Description Output Off Output On


DO1 Evaporator Water Pump 2 Pump Off Pump On
DO3 Circuit #1 Fan Output #5 Fan(s) Off Fan(s) On
DO4 Circuit #1 Fan Output #6 Fan(s) Off Fan(s) On
DO5 Circuit #2 Fan Output #5 Fan(s) Off Fan(s) On
DO6 Circuit #2 Fan Output #6 Fan(s) Off Fan(s) On

RapidRestore® Module
Table 29: Digital Inputs

# Description Signal Off Signal On


DI1 RapidRestore Lock Out Option Unlock Option
Unlock
DI2 Backup Chiller Normal Chiller Backup Chiller

www.DaikinApplied.com 45 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Controller Operation

Set Points
The following parameters are remembered during power off (permanent memory), are factory set to the Default value, and can be
adjusted to any value in the Range column. Read and write access to these set points is determined by the Global HMI (Human
Machine Interface) Standard Specification.

Unit Level Set Points


All of these settings require the unit switch to be off in order to make a change and require rebooting the controller in order to apply
a change. Unit modes Cool/Ice and Ice will both require Evaporator Glycol set point to have Yes selected.

Table 31: Set Point Default and Range


Description Default Range
Basic Unit Configuration
Input Voltage Not Set Not Set, 380, 400, 460, 575
Evaporator Configuration Not Set Not Set, Packaged, Remote
Ground Fault Protection Option No No, Single Point, Multi Point
Economizers Yes No, Yes
Economizer Piping Not Set Not Set, Steel, Copper
Liquid Line Solenoid Valves No No, Yes
Liquid Injection No No, Yes
Condenser Fan Configuration Not Set Not Set, No VFD, 1st Fan VFD, All Fan VFD
RapidRestore No No, Yes
Evaporator Glycol No No, Yes - Modes Cool/Ice and Ice will require Evaporator Glycol to be Yes.
Available Modes Cool Cool, Cool/Ice, Ice
Compressor VFD Parameter Set No No, Yes
Circuit #1 Compressor Type Not Set Not Set, F3ALVVR60, F3ALVVR86, F3BLVVR86, F4ALVVR80
Circuit #2 Compressor Type Not Set Not Set, F3ALVVR60, F3ALVVR86, F3BLVVR86, F4ALVVR80
Circuit #1 Compressor Max Speed 45 Hz 45 to 60, 45 to 70, 45 to 80, 45 to 86, 45 to 90 - Dependent on type
Circuit #2 Compressor Max Speed 45 Hz 45 to 60, 45 to 70, 45 to 80, 45 to 86, 45 to 90 - Dependent on type
Circuit 1 Compressor VFD Input RLA 100 1 to 1000 amps
Circuit 2 Compressor VFD Input RLA 100 1 to 1000 amps
Circuit #1 Number of Fans Not Set Not Set, 4, 6, 8, 10, 12, 14, 16
Circuit #2 Number of Fans Not Set Not Set, 4, 6, 8, 10, 12, 14, 16
Circuit #1 Evaporator EXV Type Not Set Not Set, E6V, ETS50, ETS100, ETS250, ETS400
Circuit #2 Evaporator EXV Type Not Set Not Set, E6V, ETS50, ETS100, ETS250, ETS400
Unit Mode and Enabling
Unit Enable Enable Disable, Enable
Unit Enable Initial Value Enable Disable, Enable
Control source Local Local, Network
Unit Test Mode Off Off, On
Staging and Capacity Control
Cool LWT 6.67°C (44°F) See Dynamic Set Point Ranges section
Ice LWT -3.89°C (25°F) -8.33°C to -2.22°C (17°F to 28°F)
Startup Delta T 2.7°C (4.9°F) 1.67 to 5.0°C (3 to 9.0°F)
Shut Down Delta T 1.5°C (2.7°F) 0 to 2°C (0 to 3.6°F)
Stage Up Delta T 1.0°C (1.8°F) 0 to 2°C (0 to 3.6°F)
Stage Down Delta T 1.0°C (1.8°F) 0 to 1.7°C (0 to 3.1°F)
Stage Up Delay 3 minutes 0 to 60 minutes
Stage Delay Clear No No, Yes
EWT Pulldown Limit Max 3°C/min (5.4°F/min) 2 to 6°C/min (3.6 to 10.8°F/min)
Light Load Stage Down 40% 20 to 50%
High Load Stage Up 80% 50 to 90%
Max Number of Circuits Running 2 1-2
Sequence Number Circuit #1 - #2 1 1-2
Ice Cycle Delay 12 1-23 hours
Clear Ice Delay No No, Yes
RapidRestore Max Power Off Time 15 seconds 15 to 180 seconds

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 46 www.DaikinApplied.com


Controller Operation

Table 32: Set Point Default and Range (continued)


Description Default Range
Evaporator Pump Control
Evap Pump Control Configuration #1 Only #1 Only, #2 Only, Auto, #1 Primary, #2 Primary
Evap Recirc Timer 90 seconds 0 to 300 seconds
Evap Pump 1 Run Hours 0 0 to 999999 hours
Evap Pump 2 Run Hours 0 0 to 999999 hours
Evap Pump 1 Starts 0 0 to 999999 starts
Evap Pump 2 Starts 0 0 to 999999 starts
Power Conservation and Limits
LWT Reset Enable Disable Disable, Enable
Max Reset 5.0°C (9.0°F) 0 to 10.0°C (0 to 18.0°F)
Demand Limit Enable Off Off, On
Unit Sensor Offsets
Evap LWT Sensor Offset 0°C (0°F) -5.0 to 5.0°C (-9.0 to 9.0°F)
Evap EWT Sensor Offset 0°C (0°F) -5.0 to 5.0°C (-9.0 to 9.0°F)
OAT Sensor Offset 0°C (0°F) -5.0 to 5.0°C (-9.0 to 9.0°F)
Circuit Configuration - Applied to All Circuits
Pumpdown Pressure Max 160 kPa (23.2 psi) 70 to 280 kPa (10.2 to 40.6 psi)
Pumpdown Time Limit 120 seconds 0 to 180 seconds
Liquid Injection Activation 85.0°C (185.0°F) 50.0°C to 110.0°C (122.0°F to 230.0°F)
Start-Start Time Delay 20 minutes 15-60 minutes
Stop-Start Time Delay 5 minutes 3-20 minutes
Alarm and Limit Settings - Unit
Evaporator Fluid Freeze 2.2°C (36.0°F) See Dynamic Set Point Ranges section
Evaporator Flow Loss Delay 15 seconds 5 to 15 seconds
Evaporator Recirculate Timeout 3 minutes 1 to 10 minutes
Low OAT Lockout 0°C (32°F) See Dynamic Set Point Ranges section
Low OAT Lockout Configuration1 Lockout & Stop Lockout & Stop, Lockout Only, Disabled
Low OAT Lockout BAS Alert Off Off, On
Alarm and Limit Settings - Circuits
Low Evap Pressure-Unload 160 kPa (23.2 psi) See Dynamic Set Point Ranges section
Low Evap Pressure-Hold Offset 15 kPa (2.2 psi) 10 to 50 kPa (1.5 to 7.3 psi)
High Oil Press Difference Delay 60 seconds 10-600 seconds
High Oil Press Difference Minimum Compressor Type Dependant Compressor Type Dependant
High Discharge Temperature 110.0°C (230.0°F) 65.0 to 110.0°C (149.0 to 230.0°F)
High Cond Pressure Delay 5 seconds 0 to 5 seconds
High Cond Pressure Hold Offset2 2.8°C (5°F) 2.8 to 8.3°C (5 to 15°F)
High Cond Pressure Unload Offset 1.7°C (3°F) 1.7 to 7.2°C (3 to 13°F)
Low Pressure Differential/Ratio Delay 120 seconds 120 to 300 seconds
Low DSH Limit 2.0°C (3.6°F) 1.0°C to 15.0°C (1.8 to 27°F)
Pumpdown Time Limit 120 seconds 0 to 180 seconds
NOTE: 1. Low Ambient Lockout Configuration will not be available unless Fan VFD Configuration is set to 1st Fan VFD or All Fan VFD.
2. High Condenser Pressure Hold Offset is forced to be at least 1.1°C (2°F) greater than High Condenser Pressure Unload Offset.

www.DaikinApplied.com 47 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Controller Operation

Table 33: Unit Test Mode Set Points

Description Default Range


Test Unit Alarm Output Off Off, On
Test Evaporator Pump Output 1 Off Off, On
Test Evaporator Pump Output 2 Off Off, On
NOTE: Unit test mode set points can be changed only when the unit mode is Test. When the unit mode is no longer Test, all unit
test mode set points will be changed back to the ‘off’ values.

Table 34: Administration and Service Support

Description Default Range


Unit G.O. Number “Enter Data” Alphanumeric string of up to 16 characters
Unit Serial Number “Enter Data” Alphanumeric string of up to 20 characters
Next Maintenance Month January January through December
Next Maintenance Year 2009 2009 - 2100
Service Support Reference 999-999-9999 Any 10 digit phone number
Controller Time From Controller Time clock 00:00:00 to 23:59:59
Controller Date From Controller Time clock 1/1/2000 to 12/31/2050
UTC Difference -60 minutes -3276 to 32767 minutes
Daylight Savings Time Enable Yes No, Yes
Daylight Savings Time Start Month March January through December
Daylight Savings Time Start Week 2nd Week 1st through 5th Week
Daylight Savings Time End Month November January through December
Daylight Savings Time End Week 1st Week 1st through 5th Week
Operator Password Disable Off Off, On
Apply Changes No No, Yes
Active Alarm Clear Off Off, On
Alarm Log Clear No No, Yes
Power Restore Event Log - Day Selection Current Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
Display Units English English, Metric

Dynamic Set Point Ranges


The following settings have different ranges of adjustment
based on other settings.

Table 35: Cool LWT Set Point Ranges Table 37: Low Ambient Lockout
Evaporator Glycol Range Condenser Fan VFD Range
No 4.44 to 21.12°C (40 to 70°F) None 0 to 15°C (32 to 59°F)
Yes -3.89 to 21.12°C (25 to 70°F) 1st Fan VFD, All Fan VFD -28.89 to 15°C (-20 to 59°F)
NOTE: Unless Low Ambient Lockout is disabled.
Table 36: Evaporator Fluid Freeze
Evaporator Glycol Range Table 38: Low Evaporator Pressure Unload
No 1.1 to 6°C (34 to 42.8°F) Evaporator Glycol Range
Yes -28.89 to 6°C (-20 to 42.8°F) No 150 to 510 kPa (21.8 to 74 psi)
Yes 0 to 510 kPa (0 to 74 psi)

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 48 www.DaikinApplied.com


Controller Operation

Circuit Level Set Points


The settings in this section all exist for each individual circuit.

Table 39: Set Points for Individual Circuits


Description Default Range
Mode, Enabling, Configuration
Circuit Mode Enable Disable, Enable, Test
Capacity Control Auto Auto, Manual
Manual Speed See Note 1
Condenser Control
Condenser Temp Target Max 50.0°C (122°F) 30.0°C to 55.0°C (86°F to 131°F)
Fan Staging Deadbands See Table 40 and Table 41 1 to 10°C (1.8 to 18°F)
Sensor Offsets
Evap Pressure Offset 0 kPa (0 psi) -100 to 100 kPa (-14.5 to 14.5 psi)
Cond Pressure Offset 0 kPa (0 psi) -100 to 100 kPa (-14.5 to 14.5 psi)
Oil Pressure Offset 0 kPa (0 psi) -100 to 100 kPa (-14.5 to 14.5 psi)
Economizer Pressure Offset 0 kPa (0 psi) -100 to 100 kPa (-14.5 to 14.5 psi)
Suction Temp Offset 0°C (0°F) -5.0 to 5.0°C (-9.0 to 9.0°F)
Discharge Temp Offset 0°C (0°F) -5.0 to 5.0°C (-9.0 to 9.0°F)
Economizer Temp Offset 0°C (0°F) -5.0 to 5.0°C (-9.0 to 9.0°F)
Administrative and Service Support
Clear Cycle Timers No No, Yes
Service Pumpdown Off Off, On
Compressor Run Hours 0 0 to 999999 hours
Compressor Starts 0 0 to 65535
Low Press Hold, Low Press Unload, High Press Hold, Hi Press
Unload, Low Pr Diff/Ration, Hi Motor Amps Hold, Hi Motor Amps
Event Log - Event Selection Low Pressure Hold
Unload, Hi VFD Amps Hold, Hi VFD Amps Unld, Hi VFD Temp Hold, Hi
VFD Temp Unld, Comp Start Fail, Part Load Shutdown
Event Log - Day Selection Current Current, 2nd Day, 3rd Day, 4th Day, 5th Day, 6th Day, 7th Day
NOTE: The Manual Speed value will follow the compressor speed command while Speed Control = Auto. When Speed Control
= Manual, the Manual Speed set point can be set to the desired value. Manual Speed set point should have a maximum
value equal to the Maximum Compressor Speed set point for that circuit.

Fan Staging Deadbands


Fan Stage Deadband settings will only be visible if Fan VFD Configuration is set to None or 1st Fan VFD. The condenser fan
staging deadbands have different default values based on the Fan VFD Configuration set point. When that set point is changed, a
set of default values for the fan staging deadbands is loaded as shown.

Table 40: Fan VFD Configuration = None Table 41: Fan VFD Configuration = 1st Fan VFD
Set Point Default Value Loaded Set Point Default Value Loaded
Fan Stage Up Deadband 0 4°C (7.2°F) Fan Stage Up Deadband 0 2.5°C (4.5°F)
Fan Stage Up Deadband 1 5°C (9°F) Fan Stage Up Deadband 1 2.5°C (4.5°F)
Fan Stage Up Deadband 2 5.5°C (9.9°F) Fan Stage Up Deadband 2 4°C (7.2°F)
Fan Stage Up Deadband 3 6°C (10.8°F) Fan Stage Up Deadband 3 5°C (9°F)
Fan Stage Up Deadband 4 6.5°C (11.7°F) Fan Stage Up Deadband 4 4°C (7.2°F)
Fan Stage Up Deadband 5 6.5°C (11.7°F) Fan Stage Up Deadband 5 4°C (7.2°F)
Fan Stage Down Deadband 1 10°C (18°F) Fan Stage Down Deadband 1 4°C (7.2°F)
Fan Stage Down Deadband 2 8°C (14.4°F) Fan Stage Down Deadband 2 3.5°C (6.3°F)
Fan Stage Down Deadband 3 5.5°C (9.9°F) Fan Stage Down Deadband 3 3°C (5.4°F)
Fan Stage Down Deadband 4 4°C (7.2°F) Fan Stage Down Deadband 4 2.5°C (4.5°F)
Fan Stage Down Deadband 5 4°C (7.2°F) Fan Stage Down Deadband 5 2.5°C (4.5°F)

www.DaikinApplied.com 49 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Controller Operation

Circuit Test Mode Set Points


Circuit test mode set points can be changed when either the unit mode is Test, or the circuit mode is Test. When neither the unit nor
the circuit are in Test mode, all the circuit test mode set points for the circuit are automatically changed back to their ‘off’ values.

Description Default Range


Test 100% VR Solenoid Output Off Off, On
Test 75% VR Solenoid Output Off Off, On
Test 50% VR Solenoid Output Off Off, On
Test Liquid Line Solenoid Output Off Off, On
Test Liquid Injection Solenoid Output Off Off, On
Test Evaporator EXV Position 0% 0 to 100%
Test Economizer EXV Position 0% 0 to 100%
Test Condenser Fan Output 1 Off Off, On
Test Condenser Fan Output 2 Off Off, On
Test Condenser Fan Output 3 Off Off, On
Test Condenser Fan Output 4 Off Off, On
Test Condenser Fan Output 5 Off Off, On
Test Condenser Fan Output 6 Off Off, On
Test Condenser Fan VFD Speed 0% 0 to 100%
NOTE: Settings for outputs should be available based on the selected unit configuration settings.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 50 www.DaikinApplied.com


Unit Functions

Unit Functions

Calculations Unit Mode Selection


The operating mode of the unit is determined by set points and
Evaporator inputs to the chiller. The Available Modes set point determines
what modes of operation can be used. This set point also
Error determines whether the unit is configured for glycol use. The
Control Source set point determines where a command to
LWT Error = Evaporator LWT - Active LWT Set Point change modes will come from. The Mode Switch digital input
switches between cool mode and ice mode if they are available
Slope and the control source is set to Local. The BAS mode request
The slope represents the change or trend in either EWT or switches between cool mode and ice mode if they are both
LWT over a time frame of one minute. It is calculated by taking available and the control source is set to Network.
readings of the temperature every 10 seconds and subtracting The Available Modes Set Point should only be changed when
them from the previous value, over a rolling one minute the unit switch is off. This is to avoid changing modes of
interval. operation inadvertently while the chiller is running.

Pulldown Rate Unit Mode is set according to the following table.

A pulldown rate is calculated by inverting the slope value and Table 43: Unit Mode Combinations
limiting to a minimum value of 0°C/min. Available Control
Mode BAS
Modes Source Unit Mode
Switch Request
Unit Set Point Set Point
Cool - - - Cool
Capacity Cool/Ice Local Off - Cool
The unit capacity is the total of the circuit target capacities Cool/Ice Local On - Ice
divided by the number of circuits. Cool/Ice Network - Cool Cool
Cool/Ice Network - Ice Ice
Total Power Ice - - Ice

An estimate of the total unit power is calculated by adding the NOTE: A “-” Indicates that the value is ignored.
power estimate for each circuit. All values are in units of kW.
Glycol Configuration
Unit Enable If the Available Modes set point is set to an option “w/Glycol,”
then Evaporator Glycol set point must be selected as Yes.
Enabling and disabling the chiller is accomplished using set
Glycol operation opens up the ranges for several set points to
points and inputs to the chiller. The Unit Switch, Remote Switch
allow lower values.
Input, and Unit Enable Set Point are all required to be On/
Enable for the unit to be enabled when the control source is
set to Local. The same is true if the control source is set to
Network, with the additional requirement that the BAS Enable
set point be Enable.
Table 42: Enable Combinations
Control Remote Unit BAS
Unit Unit
Source Switch Enable Enable
Switch State
Set Point Input Set Point Set Point
Off - - - - Disable
- - - Disable - Disable
- - Disable - - Disable
On Local Enable Enable - Enable
- Network - - Disable Disable
On Network Enable Enable Enable Enable
NOTE: A “-” indicates that the value is ignored.
All of the methods for disabling the chiller, discussed in this
section, will cause a normal shutdown of any running circuits.
When the controller is powered up, the Unit Enable Set Point
will be initialized to Disable if the Unit Enable Initial Set Point is
set to Disable. The chiller will remain disabled after powering
up until the Unit Enable Set Point is set to Enable.

www.DaikinApplied.com 51 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Unit Functions

Unit Control States T1 - Off to Auto. All of the following are required:

The unit will always be in one of three states: • Unit is enabled


• No unit alarm requiring shutdown is active
1. Off – Unit is not enabled to run.
• At least one circuit is enabled to start
2. Auto – Unit is enabled to run.
• If unit mode = Ice, Ice Delay is not active
3. Pumpdown – Unit is doing a normal shutdown.
• Low Ambient Lockout is not active
• Basic unit configuration is complete
• Control system has rebooted since configuration changed
• If Cond Fan Config = All Fan VFD, DC controller = Auto

T2 - Auto to Pumpdown. Any of the following are required:


• Unit is disabled
3

3
• Unit Mode = Ice and LWT target is reached
• Unit alarm requiring normal shutdown is active
• Low Ambient Lockout is active

T3 - Pumpdown to Off. Any of the following are required:


• Unit alarm requiring normal shutdown is active
• All circuits complete pumpdown
• Cond Fan Config = All Fan VFD, DC controller = Auto

T4 - Auto to Off. Any of the following are required:


• Unit alarm requiring normal shutdown is active
• No circuits enabled and all circuits in Off state

Unit Status
Unit Status is displayed to indicate the general condition of the unit. The following table lists the text displayed for each unit status
and the conditions that enable each status. If more than one status is enabled at the same time, the highest numbered status
overrides the others and is displayed.

Table 44: Unit Status Conditions

Enum Status Conditions


1 Auto Unit State = Auto
2 Auto: Sound Reduction Unit State = Auto and Sound Reduction is active
3 Off: Ice Mode Timer Unit State = Off, Unit Mode = Ice, and Ice Delay = Active
4 Off: Low OAT Lockout Unit State = Off and Low OAT Lockout is active
5 Off DC not ready Unit State = Off, Condenser Fan Configuration = All Fan VFD, and DC controller is not in auto control
6 Off: All Cir Disabled Unit State = Off and all circuits unavailable to start (temporary conditions are not considered)
7 Off: Unit Alarm Unit State = Off and manual reset Unit Alarm active
8 Off: Keypad Disable Unit State = Off and Unit Enable Set Point = Disable
9 Off: Remote Switch Unit State = Off and Remote Switch input is off
10 Off: BAS Disable Unit State = Off, Control Source = Network, and BAS Enable = false
11 Off: Unit Switch Unit State = Off and Unit Switch input is off
12 Off: Test Mode Unit State = Off and Unit Test Mode = On
13 Auto: Wait for Load Unit State = Auto, no circuits running, and LWT is less than the active set point + startup delta
14 Auto: Evap Recirculate Unit State = Auto and Evaporator State = Start
15 Auto: Wait for flow Unit State = Auto, Evaporator State = Start, and Flow Switch input is off
16 Auto: Pumpdown Unit State = Pumpdown
17 Auto: Max Circuit Run Unit State = Auto, Unit Mode = Cool, number of running circuits is limited by the Max Cir Run set point
18 Auto: Unit Cap Limit Unit State = Auto, unit capacity limit has been met or exceeded
19 Auto: RapidRestore Unit State = Auto, unit is performing RapidRestore operation
20 Off: Invalid Config The unit configuration is not a valid combination or not complete.
21 Off: Cfg Chg, Rst Ctlr Unit configuration set point has changed, and reboot of controller is required

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 52 www.DaikinApplied.com


Unit Functions

Ice Mode Start Delay BAS Annunciation


An adjustable start-to-start Ice Cycle Delay timer will limit the Low Ambient Lockout is not an alarm, but it can be
frequency with which the chiller may start in Ice Mode. The annunciated to the BAS as if it is one. When the Low OAT
timer starts when the first compressor starts while the unit is in Lockout BAS Alert set point is set to On and the low ambient
Ice Mode. While this timer is active, the chiller cannot restart lockout is active, the following will occur:
in Ice Mode. The time delay is user adjustable. The Ice Cycle • Chiller alarm status parameter will show alarm state
Delay timer may be manually cleared to force a restart in Ice
• Active Problem Alarm Code will be set to 16642
Mode. A set point specifically for clearing the Ice Cycle Delay
(assuming no higher code is active)
is available, Clear Ice Delay. Cycling controller power will also
clear the timer. • Active Problem Alarm Index will be set to 65 (assuming
no higher index is active)
Low Ambient Lockout • Digital parameter AmbTempLow will show alarm state
• Intrinsic alarming will show low ambient temperature via
The operation of the chiller in response to OAT dropping below
the LowOATemp object
the Low OAT Lockout set point is configurable if the Fan VFD
Configuration set point is set to 1st Fan VFD or All Fan VFD. In
that case, there are three options: Evaporator Pump Control
• Lockout and Stop – chiller will shut down and lockout Only one source can be in control of the pumps at any given
• Lockout only – chiller does not shut down running circuits, time. Three evaporator pump control states for control of the
will lock out circuits that are off evaporator pumps:
• Disabled – chiller does not shut down or lock out 1. Off - No pump on.
If the Fan VFD Configuration set point is set to None, there is
2. Start – Pump is on, water loop is being recirculated.
no configuration and the chiller will always operate according
to the first option shown above. Descriptions of the operation 3. Run – Pump is on, water loop has been recirculated, and
for each option are in the following sections. circuits can start if needed.

Lockout and Stop Operation


If the OAT drops below the low ambient lockout set point and
the OAT sensor fault is not active, then low ambient lockout
is triggered. The unit will go into the pumpdown state if any
circuits are running. If no circuits are running the unit will go
directly into the off state. Once all circuits complete pumpdown,
3

the unit will remain in the off state until the lockout has cleared.
This condition will clear when OAT rises to the lockout set point
plus 2.5°C (4.5°F).
RUN START
Lockout Only Operation 5

If OAT drops below the low ambient lockout set point and
any circuits are running, then those circuits will be allowed
to remain running and the unit will not enter the low ambient T1 - Off to Start - All of the following are required:
lockout condition. Circuits that are not running will enter a • Unit state = Auto
circuit level lockout condition when OAT drops below the
• Freeze protection started
lockout set point. This condition will clear at the circuit level
when OAT rises to the lockout set point plus 2.5°C (4.5°F). T2 - Start to Run - Requires the following to be true:
If the OAT is below the low ambient lockout set point, the OAT • Flow ok for time longer than evaporator recirculate time
sensor fault is not active, and no circuits are running, then low set point
ambient lockout is triggered. The unit will go directly into the T3 - Run to Off - Requires all of the following to be true:
off state and will remain in the off state until the lockout has
• Unit state = Off
cleared. This condition will clear when OAT rises to the lockout
set point plus 2.5°C (4.5°F). • Freeze protection not active
T4 - Start to Off. - Requires all of the following to be true:
Disabled Operation • Unit state = Off
When low ambient lockout is disabled, the unit will not enter • Freeze protection not active
the low ambient lockout condition or shut down any running T5 - Run to Start. - Requires the following to be true:
circuits, regardless of the OAT.
• Flow switch input is low for longer than the flow proof set
point

www.DaikinApplied.com 53 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Unit Functions

Freeze Protection Table 45: LWT Targets Control Source


Available Control BAS
To protect the evaporator from freezing, the evaporator pump Mode
Modes Source Mode BAS LWT Target
will start if the manual reset flow loss alarm is not active and Switch
Set Point Set Point Command
either of the following are true: Cool Local - - Cool LWT Set Point
• LWT equal to or less than the Evap Freeze set point for at Cool Network - - BAS Cool Set Point
least three seconds and LWT sensor fault is not active Cool/Ice Local Off - Cool LWT Set Point
• EWT equal to or less than the Evap Freeze set point for Cool/Ice Local On - Ice LWT Set Point
at least three seconds and EWT sensor fault is not active Cool/Ice Network - Cool BAS Cool Set Point
Cool/Ice Network - Ice BAS Ice Set Point
Freeze protection will end when manual reset flow loss alarm
is active or all of the following are true: Ice Local - Ice LWT Set Point
Ice Network - - BAS Ice Set Point
• LWT is at least 1.11°C (2°F) above the Evap Freeze set
point or LWT sensor fault is active The base LWT target may be reset to a higher value if the
• EWT is at least 1.11°C (2°F) above the Evap Freeze set unit is in Cool Mode and it is configured for a reset. The type
point or EWT sensor fault is active of reset to be used is determined by the LWT Reset Type set
• Pump has been running for at least 15 minutes point.
When the active reset increases, the Active LWT Target is
Pump Selection changed at a rate of 0.1°C (0.18°F) every 10 seconds. When
The pump output used when evaporator state is Run will be the active reset decreases, the Active LWT Target is changed
determined by Evap Pump Control set point. This setting all at once.
allows the following configurations: After resets are applied, the LWT target can never exceed a
• #1 only – Pump 1 will always be used value of 21.12°C (70°F). Since the Cool LWT set point can be
set as high as 21.12°C, the amount of reset may be limited in
• #2 only – Pump 2 will always be used
order to meet this requirement to clamp the active LWT target
• Auto – The primary pump is the one with the least run to 21.12°C.
hours, the other is used as a backup
• #1 Primary – Pump 1 is used normally, with pump 2 as a Reset Type – None
backup The Active LWT target is set equal to the base LWT target.
• #2 Primary – Pump 2 is used normally, with pump 1 as a
backup 4-20 mA External Signal Reset
The Active LWT target is adjusted by the 4-20 mA reset analog
Primary/Standby Pump Staging input. Parameters used:
The pump designated as primary will start first. If the 1. Max Reset set point
evaporator state is Start for a time greater than the recirculate 2. LWT Reset signal
timeout set point and there is no flow, then the primary
pump will shut off and the standby pump will start. When the Reset is 0 if the reset signal is less than or equal to 4 mA.
evaporator is in the run state, if flow is lost for more than half of Reset is equal to the Max Reset Delta T set point if the reset
the Flow Loss Delay set point value, the primary pump will shut signal equals or exceeds 20 mA. The amount of reset will vary
off and the standby pump will start. Once the standby pump linearly between these extremes if the reset signal is between
is started, the flow loss alarm logic will apply if flow cannot be 4 mA and 20 mA. An example of the operation of 4-20 mA reset
established in the evaporator start state, or if flow is lost in the in Cool Mode follows.
evaporator run state.
Figure 61: 4-20 mA Reset - Cool Mode
4 -20 mA Reset
Auto Control Base LWT
Target + Max
If auto pump control is selected, the primary/standby logic Reset

above is still used. When the evaporator is not in the run state,
the run hours of the pumps will be compared. The pump with Active
LWT
the least hours will be designated as the primary at this time. Max Reset
Target

Leaving Water Temp (LWT) Reset Base LWT


Target

LWT Target 0 4 20

The evaporator LWT Target varies based on settings and Reset Signal (mA)
inputs and is selected as follows:

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 54 www.DaikinApplied.com


Unit Functions

Unit Capacity Control starts


• if starts are equal, it must have the least run hours
Unit capacity control will be performed as described in this
section. A combination of starting/stopping compressors and • if run hours are equal, it must be the lowest numbered
loading/unloading compressors is used to control the overall circuit
unit capacity. The next compressor to unload must meet the following
requirements:
Maximum Circuits Running Highest capacity of the running compressors
If the number of compressors running is equal to the Max • if capacities are equal, it must have the lowest sequence
Circuits Running set point, no additional compressors should number of the compressors that are running
be started. This applies in both Cool Mode and Ice Mode • if sequence numbers are equal, it must have the most run
operation. hours
When both circuits are running and the Max Circuits Running • if run hours are equal, it must have the least starts
set point is changed to one, a circuit should shut down. • if starts are equal, it must be the lowest numbered
compressor
Cool Mode Operation
In Cool Mode, unit capacity is adjusted via circuit staging Stage Up Delay
and capacity changes on each circuit. LWT error and Any time the number of running circuits changes, the stage up
EWT pulldown rate are the primary factors in unit capacity delay will start and run for a time equivalent to the Stage Up
adjustments. This section details all the logic for unit capacity Delay set point.
control in Cool Mode.
Any time there are no circuits running, the stage up delay will
be cleared.
Staging Sequence
For the purpose of this section, a “running” circuit is a circuit in
This section defines which circuit is the next one to start or
the Preopen, Start, or Run state.
stop if the logic does not call for simultaneous start or stop of
both circuits. In general, circuits with fewer starts will normally
Staging Circuits On
start first, and circuits with more run hours will normally stop
first. Staging sequence can also be determined by an operator Unit capacity control will command at least one circuit to start if
defined sequence via set points. all of the following are true:
The next circuit to start must meet the following requirements: • Unit State = Auto
Lowest sequence number of those circuits available to start • Evaporator Pump State = Run
• LWT error > Startup Delta T set point
• if sequence numbers are equal, it must have the least
starts • Pulldown Hold is not active
• if starts are equal, it must have least run hours Both circuits are able to start at the same time if the following
conditions are true (in addition to the above conditions):
• if run hours are equal, it must be the lowest numbered
circuit • Demand limit > 40% if Demand Limit = Enable
The next circuit to shut down must meet the following • Network limit set point > 40% if Control Source = Network
requirements: If one circuit is running, unit capacity control will command the
Lowest sequence number of the circuits that are running second circuit to start if all of the following are true:

• if sequence numbers are equal, it must have the most run • One circuit running at full capacity (see circuit details for
hours determination of full capacity)
• if run hours are equal, it must have the least starts • Stage Up Delay has completed
• if starts are equal, it must be the lowest numbered circuit • LWT Error > Stage Up Delta T set point
• Capacity Increase command is active
Load/Unload Sequence • Max Number Circuits Running set point = 2
This section defines which circuit is the next one to load or
unload if the logic does not call for simultaneous load or unload
of both circuits.
The next circuit to load must meet the following requirements:
Lowest capacity of the running circuits
• if capacities are equal, it must have the lowest sequence
number of the circuits that are running
• if the sequence numbers are equal, it must have the least

www.DaikinApplied.com 55 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Unit Functions

Staging Circuits Off Ice Mode Operation


Unit capacity control will command a single circuit to shut down In Ice Mode, running circuits will load up simultaneously at the
if both circuits are running and any of the following are true: maximum possible rate that allows for stable operation of the
• LWT error < - (Stage Down Delta T set point) individual circuits.
• LWT error < Stage Up Delta T set point, both circuits
Staging Of Circuits
speed < Light Load Stage Down set point, and neither
circuit has an active capacity hold event Both circuits should start when LWT error is greater than the
• A unit capacity limit is active, both circuits capacity < Light Startup Delta T set point and the Max Circuits Running set
Load Stage Down set point, and neither circuit has an point is set to 2. If only one circuit can start, the other circuit
active capacity hold event should start as soon as possible after the stage up delay has
expired.
• Max Number Circuit Running set point changes to 1
If one circuit is running the capacity control logic will command Both circuits should be staged off when LWT error is 0 or less.
it to shut down if the following conditions are true for 15
minutes:
Unit Capacity Limits
• Compressor running at 14 Hz
Unit capacity limits are used to limit total unit capacity in Cool
• LWT Error < -0.4°C
Mode only. Multiple limits may be active at any time, and the
Unit capacity control will command all circuits to shut down if lowest limit is always used in the unit capacity control.
LWT Error < - (Shut Down Delta T set point).
Soft load, demand limit, and network limit use a deadband
Circuit Capacity Change Commands around the actual limit value, such that unit capacity increase
is not allowed within this deadband. If unit capacity is above
Load commands are issued when the following are true: the deadband, capacity is decreased until it is back within the
• LWT Error > Load Deadband deadband, which is 8%.
• Time > Load Delay has passed since the last unit The unit capacity will be adjusted as needed via circuit staging
capacity increase and capacity changes to meet the lowest active limit, but the
• EWT Pulldown Rate Hold is not active last running compressor cannot be turned off to meet a limit
lower than the minimum unit capacity.
Unload commands are issued when:
• Either LWT Error < - (Unload Deadband), or EWT Demand Limit
Pulldown Rate Unload is active
The maximum unit capacity can be limited by a 4-20 mA signal
• Time > Load Delay has passed since the last unit
on the Demand Limit analog input at the unit controller. This
capacity decrease
function is only enabled if the Demand Limit set point is set to
Load Balancing ON.

In Cool Mode, capacity of the circuits is controlled so that when As the signal varies from 4 mA up to 20 mA, the maximum unit
possible their capacities are balanced. Circuits will generally capacity changes from 100% to 0%.
maintain a capacity imbalance that does not exceed 15%.
If a capacity change has not occurred for at least one minute
Network Limit
and the difference in capacity between the two running circuits The maximum unit capacity can be limited by a network
is more than 15%, then the circuit capacities will be adjusted. command. This function is only enabled if the unit control
The circuit at the lower capacity will load and the circuit at the source is set to Network. The signal will be received through
higher capacity will unload simultaneously. the BAS interface on the unit controller.
If either circuit is running in manual capacity control or running This network limit command directly sets a maximum unit
with active capacity limiting events, then no load balancing capacity from 0% to 100%.
adjustments will be made.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 56 www.DaikinApplied.com


Unit Functions

RapidRestore®
The option allows the capability to restart more quickly and to
load faster than normal when power is lost and restored.

Enabling
Changing the RapidRestore® set point to Enable will require
the following to be true:
• RapidRestore® module is present at address 22
• DI1 on the RapidRestore® module has a signal
If any of the above are no longer true, the RapidRestore® set
point will be changed to Disable.

Operation Following Cycling of Power


The chiller will enter RapidRestore® upon powering up when
the following conditions are met:
• RapidRestore® is enabled
• Power failure lasts less than the value of the Max Power
Failure Time set point
• Power failure lasts at least one second
• Unit is enabled
• LWT Error is at least equal to the Stage Up Delta T set
point
RapidRestore® will end if any of the following conditions occur:
• LWT Error is less than the Stage Up Delta T set point
• Unit capacity = 100%
• All circuits become disabled for any reason
• Unit becomes disabled for any reason
• 10 minutes have passed since unit powered up

Unit Level Changes


During RapidRestore® operation, unit capacity control logic
allows both circuits to start simultaneously.
In the event that both circuits do not start simultaneously, the
requirement for the running circuit to reach maximum capacity
will be ignored for staging the other circuit on.

Circuit Level Changes


When RapidRestore® is triggered, all compressor cycle timers
are cleared to allow for starting more quickly. The limit of four
starts per hour will remain in effect and will not be cleared by
triggering RapidRestore®.

www.DaikinApplied.com 57 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Circuit Functions

Circuit Functions

Circuit Functions described as follows.


Components controlled at the circuit level include:
Table 46: Saturated Condenser Temperature Conditions
• Compressor VFD
• Compressor VR Solenoid Valves Saturated Evap Max Cond Saturated
Condition
• Evaporator EXV Temp or LWT Temp (°C)
• Economizer EXV EXV state is Start LWT ≤ 0°C 1.589 X LWT + 68.3
Pressure Control LWT > 0°C 68.3
• Liquid Line Solenoid Valve
• Liquid Injection Solenoid Valve EXV state is SSH Te ≤ 0°C 1.589 X Te + 68.3
• Condenser Fans or MOP Control Te > 0°C 68.3
All other conditions n/a 68.3
Calculations High Saturated Condenser – Hold Value
Calculations are for each circuit.
High Cond Hold Value = Max Saturated Cond Value – High
Cond Press Hold Offset set point
Approach Values
Evaporator Approach = LWT – Evap Saturated Temp High Saturated Condenser – Unload Value
Condenser Approach = Cond Saturated Temp – OAT High Cond Unload Value = Max Saturated Cond Value – High
Cond Press Unload Offset set point
Superheat Values
Suction superheat = Suction Temp – Evap Saturated Temp High Motor Current Limits
Discharge superheat = Discharge Temp – Cond Saturated Max Motor Current = Minimum of (VFD Rated Current, Motor
Temp Rated Current)

Economizer Superheat = Econ Temp – Econ Saturated Temp where:


- VFD Rated Current is read from the compressor VFD
Differential Pressure Values - Motor Rated Current is determined by the compressor type
Oil Pressure Differential = Cond Pressure - Oil Pressure and the voltage configuration:
Pressure Difference = Cond Pressure – Evap Pressure Motor Rated Current (Amps)
Compressor
Pressure Ratio Type
380V 400V 460V 575V
Pressure Ratio = (Cond Press +101.325) ÷ (Evap Press + F3ALVVR60 222.8 222.8 183.3 167.0
101.325)
F3ALVVR86 375.6 375.6 311 253.5
Feedback Capacity F3BLVVR86 527.9 527.9 434.1 N/A

Feedback capacity is a representation of the actual capacity as F4ALVVR80 692.1 692.1 574.8 N/A
a percentage of full capacity based on feedback regarding the
actual speed of the compressor.
Compressors vary capacity via changes to the speed. The Pumpdown Target Value
actual compressor speed is read from the VFD. Feedback The pressure target for pumpdown when the circuit enters the
capacity for a compressor with a VFD is: pumpdown state is selected as follows:
Actual Compressor Speed x 100 ÷ Maximum Speed If Service Pumpdown set point = Disable
Then Pumpdown Target = Evaporator Pressure at
pumpdown start – 20 kPa with value limited to the range
Saturated Condenser Temperature Limit from 35 kPa to the Pumpdown Pressure Max set point
The maximum saturated condenser temperature calculation If Service Pumpdown set point = Enable
is based on the compressor operational envelope. This value
Then Pumpdown Target = 35 kPa
is used for triggering high condenser pressure alarms and as
a reference for the trigger values of the high pressure hold
and unload events. Chiller software is designed to calculate
a dynamic maximum saturated condenser temperature.
High saturated condenser hold and unload offset values are

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 58 www.DaikinApplied.com


Circuit Functions

Circuit Availability T1 – Off to Preopen - All of the following are required:

A circuit is available to start if the following conditions are true: • Circuit is available to start per the previous section
• Adequate pressure in the evaporator and condenser (see
• Circuit switch input is on
No Pressure At Start Alarm)
• No manual reset circuit fault alarms are active
• Unit capacity control logic requires the circuit to start
• Circuit Mode set point is set to Enable
T2 – Preopen to Start
• BAS Circuit Mode set point is set to Auto
Evaporator EXV completes preopen operation.
• No cycle timers are active
• Oil Sump Check = Ready T3 – Start to Run
Compressor speed ≥ 19 Hz for at least 30 seconds
Oil Sump Check T4 – Run to Pumpdown - Any of the following are required:
Oil sump check is to make sure that oil in the sump is of
• Unit capacity control logic requires this circuit to stop
sufficient quality prior to starting the compressor.
• Unit state is pumpdown
Oil sump check is set to Ready when
• A pumpdown alarm occurs on the circuit
Discharge Temperature > Saturated Oil Temperature + 5°C
• Circuit switch input is off
Oil sump check is set to Not Ready when
Discharge Temperature < Saturated Oil Temperature + 4.5°C • Control Source = Network and BAS Circuit Mode = Off
T5 – Pumpdown to Off - Any of the following are required:
Circuit States • Evaporator Pressure drops below Pumpdown Target
There are five distinct states of control for the circuit as shown. Value
• Circuit state has been pump down for longer than the
Figure 62: Circuit State Transitions Pumpdown Time Limit set point
• Unit state is Off
T1 • Rapid stop alarm occurs on the circuit
POWER
ON
OFF PREOPEN T6 – Run to Off - Any of the following are required:
T9 • Unit state is Off
• Rapid stop alarm occurs on the circuit
T2
T7 – Start to Off - Any of the following are required:
• Unit state is Off
• Rapid stop alarm occurs on the circuit
T7 T8 T8 – Start to Pumpdown - Any of the following are required:
START

• Unit capacity control logic requires this circuit to stop


• Unit state is pumpdown
T3 • A pumpdown alarm occurs on the circuit
• Circuit switch is open
• Control Source = Network and BAS Circuit Mode = Off
T6 RUN
T9 – Preopen to Off - Any of the following are required:
• Unit state is Off
• A rapid stop alarm occurs on the circuit
T4 • A pumpdown alarm occurs on the circuit
• Circuit switch input is off
• Control Source = Network and BAS Circuit Mode = Off
T5
PUMPDOWN

www.DaikinApplied.com 59 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Circuit Functions

Circuit Status Compressor Control


Circuit Status is displayed to indicate the general condition of The compressor is controlled via:
the circuit. The following table lists the text displayed for each • a digital output to give the run command to compressor
circuit status and the conditions that enable each status. If VFD
more than one status is enabled at the same time, the highest
• a modbus speed command to control compressor speed
numbered status overrides the others and is displayed.
• digital outputs for compressor VR solenoids to control VR
Table 47: Circuit Status • a digital output for liquid injection to the compressor

Enum Status Conditions Run Command Output


Circuit is ready to start when The compressor run command output should be on when the
1 Off:Ready
needed circuit state is Start, Run, or Pumpdown. It should be off when
Circuit is off & cannot start due to the circuit state is Off or Preopen.
2 Off:Cycle Timer
active cycle timer

3 Off:OAT Low
Circuit is off & cannot start due to Cycle Timers
low ambient lockout
A minimum time must pass between starts of each compressor.
Off: Max Starts Circuit is off & cannot start due to When the compressor starts, a timer starts which will run for a
4
Per Hr exceeding 4 starts/hr time determined by the Start-Start Timer set point.
Circuit is off & cannot start due to
5 Off:BAS Disable BAS Circuit Mode input being set A minimum time must pass between the stop and start of each
to Off compressor. When the compressor stops, a timer starts which
will run for a time determined by the Stop-Start Timer set point.
Circuit is off & cannot start due to
Off:Keypad While either timer is running, the compressor cannot start. Both
6 Circuit Mode set point on HMI is
Disable cycle timers will be enforced even through cycling of power to
set to Disable
Off:Circuit the chiller. These timers may be cleared via the Clear Cycle
7 Circuit is off & circuit switch is off Timers set point.
Switch
Circuit is off & Oil Sump Check =
8 Off:Oil Heating
Not Ready
Starts Per Hour Limit
Circuit is off & cannot start due to In addition to the cycle timers, a limit of four starts per hour
9 Off:Alarm is enforced. A buffer of start times for the last four starts is
active circuit alarm
10 Off:Test Mode Circuit is in test mode maintained. If the current time is an hour or less after the first
timestamp in the buffer, the next start will be delayed.
11 EXV Preopen Circuit is in preopen state
12 Run:Pumpdown Circuit is in pumpdown state This limit is cleared if the Clear Cycle Timers set point is set to
Circuit is in run state & running Yes.
13 Run:Normal
normally
Circuit is in start or run state & Capacity Control
Run:Evap Press
14 cannot load due to low evaporator The compressor will vary capacity via changes to the motor
Low
pressure speed (frequency).
Circuit is in start or run state &
Run:Cond Press
15 cannot load due to high condenser Auto Capacity Control
High
pressure The normal speed change is 1 Hz for all compressor
Circuit is in start or run state & configurations.
Run:VFD
16 cannot load due to high VFD line
Current High Circuit State = Off - Speed command is 0 Hz.
current
Circuit is in start or run state & Circuit State = Preopen - Speed command is set to the
Run:VFD Temp minimum for the configuration.
17 cannot load due to high VFD
High
temperature Circuit State = Start - Immediately after starting, the
Circuit is in start or run state & compressor speed will be set to the minimum for the
Run:Motor
18 cannot load due to high motor configuration and held there while circuit state is Start.
Current High
current
Circuit State = Run - After the circuit enters the Run state,
Circuit is in start or run state & changes to the speed are performed based on load and unload
Run:High LWT cannot load due to the evaporator commands coming from the unit capacity control logic (see
19
Limit LWT exceeding the limit for unit capacity control section). The speed is constrained to a
allowing full capacity range from the minimum based on the configuration up to the
Compressor Maximum Speed set point.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 60 www.DaikinApplied.com


Circuit Functions

When a capacity increase occurs, a time delay starts; and Table 49: VR Solenoid Valve Control Stages
when a capacity decrease occurs, a separate time delay starts.
50 75 100
While either of these delays is active, no normal capacity Stage Up Stage Down
Stage VR VR VR VR
changes will occur. The load and unload delay times are SV SV SV
Condition Condition
calculated values.
Pressure
0 1.6 Off Off Off n/a
Circuit State = Pumpdown - Speed command will drop 2 Hz Ratio > 2.10
every second until reaching the minimum for the configuration. Pressure Pressure
1 1.8 On Off Off
Ratio > 2.85 Ratio < 1.90
Manual Speed Control 2 2.4 Off On Off
Pressure Pressure
Ratio > 3.85 Ratio < 2.65
The speed of the compressor may be controlled manually.
Pressure
Manual speed control is enabled via a set point with choices 3 3.1 On On On n/a
Ratio < 3.65
of Auto or Manual. Another set point allows setting the
compressor speed. However, the resulting compressor speed When the circuit state becomes Pumpdown or Off, all VR
is still limited to the range from the minimum speed based on solenoids should be turned off.
configuration up to the Compressor Maximum Speed set point.
The compressor speed will be stepped up or down until it is
equal to the speed that corresponds to the manual speed set
Condenser Fan Control
point. Changes to the speed will be made as fast as allowed by Condenser fan control will vary in operation based on the Fan
the calculated load and unload delays. Speed control may be VFD Configuration set point.
set to Manual only when circuit state is Start or Run.
Capacity control shall revert back to automatic control if either: Table 50: Condenser Fan Control Configurations

• the circuit state changes from Start or Run to another Fan VFD Control Type Control
state Configuration Mechanism
• capacity control has been set to Manual for four hours None Staging only Contactors
1st Fan VFD Staging and speed Contactors and
Load and Unload Delay
control of 1st fan on VFD
LWT Error determines the delays for load and unload the circuit
commands.
All Fan VFD Staging and speed Integrated VFD on
control of all fans each motor
Table 48: Load and Unload Delay Conditions
LWT Error Delay Physical Fan Layout
LWT Error > Startup Delta Load command delay is 5 Fans are numbered as shown below (top view of chiller). Fan
T set point seconds numbers start on the left side of the circuit, closest to the
0.1°C ≤ LWT Error ≤ Load command delay will vary control box when facing the control box.
Startup Delta T set point from 5 seconds to 10 seconds Circuit #1 fans start at 101 and can run through 116 depending
– (Stage Down Delta T Unload command delay will on the number of fans on the circuit. Circuit #2 fans start at 201
set point) ≤ LWT Error ≤ vary from 3 seconds to 6 and can run through 214 depending on the number of fans on
-0.1°C seconds the circuit.
LWT Error < -(Stage Down Unload command delay is 3
Delta T set point) seconds Figure 63: Fan Numbering Diagram - Representative
Circuit 1 Circuit 2
VR Solenoid Valve Control Control
Box
101 103 105 107 109 111 113 115 201 203 205 207 209 211 213
End 102 104 106 108 110 112 114 116 202 204 206 208 210 212 214
There are three solenoid valves for changing volume ratio of
the compressor: NOTE: Number of fans vary by unit configuration
• 50 VR solenoid valve
• 75 VR solenoid valve
• 100 VR solenoid valve
The compressor should start with all three solenoid valves off.
After compressor has been running for at least 20 seconds, the
control logic will “stage” the solenoid valves. Table 49 shows
which VR solenoid valves are on at each stage as well as
stage up and stage down conditions. These staging conditions
must be active for 30 seconds to trigger each stage up or
down.

www.DaikinApplied.com 61 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Circuit Functions

Condenser Fan Control State The target value is displayed on the controller screen and is
equal to the base target, but also constrained to a calculated
There are only two control states: Off and Condensing range defined by the Minimum Target value and Maximum
Temperature Control. Target value.
When the circuit state is Off or Preopen, condenser fan control
will be in the Off state. All fans will be off. Base Target
When circuit state is Start, Run, or Pumpdown, the condenser Base Target (°C) = 0.979264 x OAT + 10.7
fan control will be in the Condensing Temperature Control
state. Fan staging and speed will be controlled as needed to Minimum Target Value
drive the saturated condenser temperature to the target. Minimum Target value is designed to keep the compressor
in its operational envelope. This value is calculated by the
Saturated Condenser Temp Target controller based on the pressure difference, pressure ratio and
There are two purposes to have a variable condenser fan stage down deadband.
saturated temperature target: First 10 minutes after compressor start, the minimum target is
a. Maintain pressure difference and pressure ratio 38°C (100.4°F).
above low limit for compressor to run within After the first 10 minutes, the minimum target range is
operational envelope gradually decreased to the calculated value at a rate of 0.1°C/
b. Achieve best performance at various conditions sec.

Fan Control – No VFD or 1st Fan VFD


Fans On Each Digital Output
The tables below show which fan numbers are on each of the fan digital outputs.

Table 51: Fan Numbers for Each Fan Digital Output

Circuit 1
# Fans 4 6 8 10 12 14 16
1 - 101 101 101 101 101 101
2 - 102 102 102 102 102 102
Fan
3 - 103 103 103,105 103,105 103,105 103,105
Output
4 - 104,106 104 104,106 104,106 104,106 104,106,107,108
#
5 - 105 105,107 107,109 107,109,111 107,109,111,113 109,111,113,115
6 - - 106,108 108,110 108,110,112 108,110,112,114 110,112,114,116

Circuit 2
# Fans 4 6 8 10 12 14 16
1 201 201 201 201 201 201 -
2 202 202 202 202 202 202 -
Fan
3 203 203 203 203,205 203,205 203,205 -
Output
4 204 204,206 204 204,206 204,206 204,206 -
#
5 - 205 105,107 207,209 207,209,211 207,209,211,213 -
6 - - 106,108 208,210 208,210,212 208,210,212,214 -

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 62 www.DaikinApplied.com


Circuit Functions

Fan Outputs Per Fan Stage


The table below shows which digital outputs are energized for each stage.

Table 52: Digital Outputs Energized for Each Stage


# Fans On
4 6 8 10 12 14 16
Circuit
0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1
2 1,3 1,3 1,3 1,2 1,2 1,2 1,2
3 1,2,3 1,3,5 1,5 1,3 1,3 1,3 1,3
4 1,2,3,4 1,2,3,5 1,3,5 1,2,3 1,5 1,2,3 1,2,3
5 - 1,3,4,5 1,2,3,5 1,3,5 1,2,5 1,5 1,5
6 - 1,2,3,4,5 1,2,3,4,5 1,2,3,5 1,3,5 1,2,5 1,2,5
7 - - 1,2,3,5,6 1,3,4,5 1,2,3,5 1,3,5 1,3,5
Fan
8 - - 1,2,3,4,5,6 1,2,3,4,5 1,3,4,5 1,2,3,5 1,2,3,5
Stage
9 - - - 1,3,4,5,6 1,2,3,4,5 1,3,4,5 1,4,5
10 - - - 1,2,3,4,5,6 1,2,3,5,6 1,2,3,4,5 1,2,4,5
11 - - - - 1,3,4,5,6 1,3,5,6 1,3,4,5
12 - - - - 1,2,3,4,5,6 1,2,3,5,6 1,2,3,4,5
13 - - - - - 1,3,4,5,6 1,4,5,6
14 - - - - - 1,2,3,4,5,6 1,2,4,5,6
15 - - - - - - 1,3,4,5,6
16 - - - - - - 1,2,3,4,5,6

Staging Concept
As long as the condenser saturated temperature is within the band defined by the active stage up deadband and active stage down
deadband, the fan stage will not change. When saturated condenser temperature is outside of the deadbands, error is accumulated
and will cause a change in the fan stage.

Figure 64: Fan Staging Conditions

Error If this error accumulation is greater than 11°C, Fan stage up.

(Target) + (stage up deadband)

Saturated Condenser
Temperature Target

(Target) - (stage down deadband)

Error If this error accumulation is greater than 3.0°C Fan stage down.

Limit Target Condenser saturated temperature

Staging Up
When the saturated condenser temperature is above the Target + the active deadband, a Stage Up error is accumulated.
Stage Up Error Step = saturated condenser temperature – (target + Stage Up Deadband)
The Stage Up Error Step is added to Stage Up Accumulator once every five seconds, only if the saturated condenser temperature
is not falling. When the Stage Up Error Accumulator is greater than 11°C (19.8°F) fan stage is increased by 1. When a stage up
occurs or the saturated condenser temperature falls back within the Stage Up deadband the Stage Up Accumulator is reset to zero.

www.DaikinApplied.com 63 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Circuit Functions

The first fan will turn on when condenser saturated Stage Up Compensation
temperature is above the target rather than using the error
In order to create a smoother transition when the fan stage
accumulator.
increases, the VFD compensates by slowing down initially. This
is accomplished by adding the new fan stage up deadband
Staging Down
to the VFD target. The higher target causes the VFD logic to
When the saturated condenser refrigerant temperature is decrease fan speed. Then, every 2 seconds, 0.1°C (0.18°F) is
below the Target – the active deadband, a Stage Down error is subtracted from the VFD target until it is equal to the saturated
accumulated. condenser temperature target set point.
Stage Down Error Step = (target - Stage Down deadband) -
saturated condenser temperature Speed Signal to VFD
The Stage Down Error Step is added to Stage Down The fan VFD is controlled using a 0-10 volt signal. When the
Accumulator once every 5 seconds. When the Stage Down fan should be off, the signal will be 0 Vdc. When the fan should
Error Accumulator is greater than 3°C (5.4°F), a fan stage is be running, the signal will vary based on the percent speed
removed. calculation.

When a stage down occurs or the saturated condenser Speed Signal = Percent Speed / 10
temperature rises back within the Stage Down deadband the
Stage Down Error Accumulator is reset to zero.
Fan Control - All Fans with VFD
Active Deadbands If Fan VFD Configuration is set to All Fan VFD, different control
Stage Up and Stage Down deadbands are determined by set logic will be used. All fan motors are DC fan motors which
points as shown in the following table: have integrated inverters and are controlled via modbus. This
configuration requires the DC Fan Controller.
Table 53: Stage Deadbands
System Architecture
Fan Stage Up Setting Stage Down Setting Architecture of the control system components involved in
stage control of the DC fan motors is shown below. Data flows in both
0 Fan Stage Up --- directions on the communication link as well as the Modbus
Deadband 0 connection.
1 Fan Stage Up Fan Stage Down
Deadband 1 Deadband 1 Figure 65: Controller Communication Architecture
2 Fan Stage Up Fan Stage Down
Deadband 2 Deadband 2
3 Fan Stage Up Fan Stage Down
Deadband 3 Deadband 3 Unit Controller DC Fan Controller

4 Fan Stage Up Fan Stage Down Fan Motors


Modbus
Deadband 4 Deadband 4
5 to 16 Fan Stage Up Fan Stage Down
Deadband 5 Deadband 5

The following control logic will reside in the DC Fan Controller:


• Automatic control
VFD on 1st Fan of Each Circuit • Alarm handling per individual fan motor
As an option, the first fan may be driven by a VFD. The VFD • Fan motor addressing process
control will vary the fan speed to drive the saturated condenser • Fan motor testing control
temperature to a target value. The target value is normally the
same as the saturated condenser temperature target. Normal Control
When Control Mode is set to Auto, the logic in this section
VFD Speed Control
will automatically control the DC fan motors for normal chiller
The VFD speed should always be 0% when the fan stage is 0. operation.
When the fan stage is greater than 0, the VFD speed will be
The VFD speed should always be 0% when the fan stage is 0.
calculated to control the saturated condenser temperature to
When the fan stage is greater than 0, the VFD speed will be
the VFD target. The minimum and maximum speed are set by
calculated to control the saturated condenser temperature to
the VFD Min Speed and VFD Max Speed set points.
the VFD target.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 64 www.DaikinApplied.com


Circuit Functions

Speed Command To Motors • MOP Control – EXV is controlling to maximum operating


pressure for compressor
All fan motors will be sent a speed command via modbus. The
speed command is in units of rpm with 800 rpm corresponding
to 100% and will vary based on the percent speed calculation.
Closed State
If the unit is configured without liquid line solenoid valves, the
Speed Command = Percent Speed Calculation x 8
EXV position should be 0% any time the EXV is in a closed
Normally the same speed command is sent to all motors on a state. The 0% position command also causes the evaporator
circuit. EXV module driver to re-initialize the valve to the zero position.
If the unit is configured with liquid line solenoid valves, the EXV
Staging position should be 0% when the EXV initially enters the closed
Calculated RPM is a value used in the fan staging logic. state, while it is re-initializing to the zero position. After the
When the circuit run flag is 0, the fan stage is always 0. Once EXV position command has been 0% for one minute, the EXV
the fan stage is more than 0, it will not be allowed to drop back should be moved to 5% to prevent excessive pressure buildup
to 0 until the circuit run flag is 0. between the EXV and liquid line solenoid valve.

The maximum fan stage is equal to the number of fans on the


circuit. When fan stage is 0, it will be set to the maximum fan
Preopen Operation
stage when the PI (proportional integral)loop reaches 100%. When the EXV state is Preopen, the EXV position command
This does not occur any time other than when the fan stage is will be 30%.
0.
Pressure Control State
Test Mode Control In Start Pressure Control, the EXV is positioned to control the
When Control Mode is set to Test, the fan motors can be evaporator pressure to a target.
manually controlled for test purposes.
Pressure Target
The test settings allow selecting values from 0% to 100%.
When the test setting for a fan is set to 12.5% or higher, the The pressure target is calculated based on evaporator LWT,
speed command corresponding to the test setting will be sent then limits are applied to keep the target in an acceptable
and the run command will be sent to the fan. range.
Speed Command = Test setting x 8 The base target value varies from 65 kPa to 420 kPa as LWT
varies from -5°C to 30°C.
When Control Mode is no longer set to Test, the following
actions should occur:
Figure 66: Evaporator EXV Pressure Target
• all the test settings set back to 0%
Base Target (kPa)
• stop command sent to all motors
• speed command of 0 rpm sent to all motors
420

Evaporator EXV Control


This section outlines the positioning logic for the Evaporator 65
EXV, which is the EXV installed in the liquid line feeding the
evaporator.
LWT (°C)
• EXV will initially be positioned to control evaporator -5 30
pressure
• EXV will normally be positioned to control SSH (suction
This base target is then limited to a range as defined by the
superheat)
Minimum Limit and Maximum Limit shown below:
• SSH target will vary based on DSH (discharge superheat)
• Minimum Limit = Low Pressure Hold set point + 25 kPa
• In some conditions, EXV will be positioned to control
evaporator pressure to keep all parameters within • Maximum Limit = Min {(Cond Pr + 101.325) / 1.7 –
operating envelope 101.325, Cond Pr – 180}
There are five EXV control states: • If Maximum Limit < Minimum Limit, then Pressure Target
= Minimum Limit
• Closed – EXV is closing or in the closed position
• Preopen – EXV is opening prior to compressor start
• Start Pressure Control – EXV is controlling to pressure
target after compressor start
• SSH Control – EXV is controlling suction superheat

www.DaikinApplied.com 65 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Circuit Functions

MOP Control State Control Concept


In MOP (Maximum Operating Pressure) Control, the EXV is • EXV will be positioned using control algorithm
positioned to control the evaporator pressure to a target. • Maintain DSH above requirements for compressor
• Maximize circuit performance at the operating conditions
MOP Target
The MOP Target is Min {450, (Cond Pr + 101.325) / 1.7 – EXV States
101.325, Cond Pr – 180}.
There are three economizer EXV states:

Superheat Control State • Closed: EXV is closing or closed


• Purge: EXV is opening to release condensed liquid in a
In superheat control, the EXV is positioned to control suction
controlled manner
superheat (SSH) to the SSH Target.
• Superheat: EXV is controlling economizer gas superheat
SSH Target
Operation – Closed State
The SSH target varies linearly based on discharge superheat
(DSH). This target is updated every 10 seconds and averaged The EXV position command should be 0% any time the EXV is
over a 100 second period (with sampling every 10 seconds). in the closed state. The 0% position command also causes the
EVD driver to re-initialize the valve to the zero position. After
one minute, the EXV position command should be set to 25%
Figure 67: Evaporator EXV Suction Superheat Target
open and remain there until the state changes.
SSH target (°C)

SSH Target Max Operation – Purge State


In the Purge state, the economizer EXV position is 0%.

SSH Target Min


Operation – Superheat Control State
In the Superheat control state, the EXV will be positioned to
DSH (°C)
DSH Range Min DSH Range Max control economizer gas superheat.

When the EXV transitions to the superheat control state, the


target will ramp up or down until it meets the calculated SSH
Liquid Injection Solenoid Valve
target. As an option, the chiller can be equipped with liquid injection
on the compressors. When configured with this option, the
• If SSH Target Min ≤ current SSH ≤ SSH Target Max, the Liquid Injection Configuration setting should be set to Yes and
target will start at the current SSH value and increase the liquid injection solenoid valve outputs can be activated.
or decrease by 0.1°C every 10 seconds until it meets
calculated SSH target. Liquid injection solenoid valve output is activated if both of the
following are true:
• If current SSH > SSH Target Max, the target value will
start ramping from SSH Target Max. Then the target • Circuit state is Run
will decrease by 0.1°C every 10 seconds until it meets • Discharge Temperature > Liquid Injection Activation set
calculated SSH target. point
• If current SSH < SSH Target Min, the target value will Liquid injection solenoid valve output will be turned off if either
start ramping from SSH Target Min. Then the target of the following are true:
will increase by 0.1°C every 10 seconds until it meets
• Discharge Temperature < Liquid Injection Activation set
calculated SSH target.
point - 15°C
• Circuit state is no longer Run
Economizer EXV Control
The economizer circuit is activated and modulated using an
EXV. This is an optional feature that will only be enabled if
the Economizer Configuration set point is set to Yes. If the
configuration set point is set to No, then the economizer
position should remain 0%.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 66 www.DaikinApplied.com


Circuit Functions

Liquid Line Solenoid Valve


As an option, the chiller can be equipped with liquid line
solenoid valves. When configured with this option, the Liquid
Line Solenoid Valve Configuration setting should be set to Yes.
If the chiller is configured with liquid line solenoid valves, the
liquid line solenoid valve output should be activated when the
circuit enters the Preopen state and remain on during the Start
and Run states. The output should be turned off 10 seconds
after the circuit enters the Pumpdown state or when the circuit
state is Off.

Circuit Capacity Overrides


The following conditions override automatic capacity control
as described. These overrides keep the circuit from entering a
condition in which it is not designed to run.

High Water Temperature Capacity Limit


If the evaporator LWT is 25°C (77°F) or higher, the circuit
capacity will be limited. If circuit capacity resulting from the
next compressor speed increase is 81.5% or more, the circuit
cannot increase in capacity.
If the circuit capacity is higher than 81.5%, the circuit will
reduce capacity until it is at 81.5% or lower.
Once this limit is triggered, it will be in effect until evaporator
LWT is less than 25°C (77°F) for at least one minute.

www.DaikinApplied.com 67 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Alarms and Events

Alarms and Events

Situations may arise that require some action from the chiller, If the problem(s) causing the alarm have been corrected, the
or that should be logged for future reference. The alarm digital alarms will be cleared, disappear from the Active Alarm list
output will be operated based on active alarm scenarios as and be posted in the Alarm Log. If not corrected, the On will
shown in the table below. immediately change back to OFF and the unit will remain in the
alarm condition.
State Scenario
Off
No alarms preventing the chiller or an individual Description of Alarms
circuit from running Details for each alarm are listed in a table format as shown
One, and only one, circuit has an alarm preventing below. The table below explains each row in the tables.
Blinking
it from running
Alarm: Description of the alarm
Unit alarm preventing chiller from running or both
On Displayed
circuits have alarms preventing them from running Text displayed on HMI in the alarm lists
Text:
For the Blinking state, the output should cycle five seconds on Trigger: Conditions required to trigger the alarm
then five seconds off while the indicated scenario is active.
Actions that should be taken when the alarm
Action Taken:
Alarm Logging triggers
Method by which the alarm can be cleared
All alarms appear in the active alarm list while active. All alarms Reset:
and conditions required for doing so, if any
are added to the alarm log when triggered and when cleared.
Entries in the log representing the occurrence of an alarm will
be preceded by ‘+’ while entries representing the clearing of an Unit Alarms
alarm will be preceded by ‘-’.
Unit GFP Fault
When an alarm occurs, the alarm type, date, and time are
stored in the active alarm buffer corresponding to that alarm Alarm: Unit GFP Fault
(viewed on the Alarm Active screens), and also in the alarm Displayed Text: Unit Ground Fault
history buffer (viewed on the Alarm Log screens). The active Trigger: All of the following are true:
alarm buffers hold a record of all current alarms. • Ground Fault Protection Option
set point = Single Point
The alarm log can be exported to a formatted SD card in the
controller. A setting called “Alarm Log Export” will be used to • GFP Relay 1 input is off for 1
second
initiate this when set to Yes. The exported log will be saved in a
text file on the SD card with each line representing an entry in Action Taken: Rapid shutdown all circuits and lock
out unit from running
the log. Only what is in the actual alarm log will be saved to the
file when the export was initiated. Reset: Auto reset when GFP Relay 1 input is
on for 5 seconds
Signaling Alarms
The following actions will signal that an alarm has occurred:
Circuit 1 GFP Fault
Alarm: Circuit 1 GFP Fault
• The unit or circuit executes a rapid or pumpdown shutoff.
Displayed Text: C1 Ground Fault
• An alarm bell icon will be displayed in the upper right-
Trigger: All of the following are true:
hand corner of all controller screens, including the
• Ground Fault Protection Option
optional remote user interface panel’s screens.
set point = Multi Point
• An optional field supplied and wired remote alarm device • GFP Relay 1 input is off for 1 sec
will be activated.
Action Taken: Rapid shutdown all circuits and lockout
Clearing Alarms/Faults unit from running.
Reset: Auto reset when GFP Relay 1 input is
Active alarms can be cleared through the keypad/display or a on for 5 seconds
BAS network. Alarms are automatically cleared when controller
power is cycled. Alarms are cleared only if the conditions Circuit 2 GFP Fault
required to initiate the alarm no longer exist. All alarms and
groups of alarms can be cleared via the keypad or network Alarm: Circuit 2 GFP Fault
via LON using nviClearAlarms and via BACnet using the Displayed Text: C2 Ground Fault
ClearAlarms object. Trigger: All of the following are true:
• Ground Fault Protection Option
To use the keypad, follow the Alarm links to the Alarms screen, set point = Multi Point
which will show Active Alarms and Alarm Log. Select Active • GFP Relay 2 input is off for 1 sec
Alarm and press the wheel to view the Alarm List (list of current Action Taken: Rapid shutdown all circuits and lockout
active alarms). They are in order with the most recent on unit from running.
top. The second line on the screen shows Alm Cnt (number Reset: Auto reset when GFP Relay 2 input is
of alarms currently active) and the status of the alarm clear on for 5 seconds
function. An active password is not necessary to clear alarms.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 68 www.DaikinApplied.com


Alarms and Events

Evaporator Flow Loss Evaporator Water Freeze Protect


Alarm: Evaporator Flow Loss Alarm: Evaporator Water Freeze Protect
Displayed Text: Evap Water Flow Loss Displayed Text: Evap Water Freeze
Trigger: 1: Evap Pump State = Run AND Evap Flow Trigger: Evaporator LWT or EWT equal to or
Digital Input = No Flow for time > Flow Proof less than Evaporator Freeze Protect
set point AND at least one circuit is not in the set point for a time at least as long
Off state as the evaporator recirculation time.
2: Evap Pump State = Start for time greater If the sensor fault is active for either
than Recirculate Timeout set point and all LWT or EWT, then that sensor value
pumps have been tried and Evap Flow cannot trigger the alarm.
Digital Input = No Flow Action Taken: Rapid shutdown all circuits and lock
Action Taken: Rapid shutdown all circuits and: out unit from running
Reset: This alarm can be cleared manually
-if an auto reset occurrence has triggered,
via the keypad, but only if evaporator
keep unit enabled and allow the evaporator
LWT and EWT are both above the
recirculation sequence to proceed
Evaporator Freeze Protect set point
-if a manual reset occurrence has been or have a sensor fault (meaning the
triggered, lock out unit from running temperature reading is not valid).
Reset: This alarm can be cleared at any time
manually via the keypad or via the BAS clear
alarm command.
Evaporator Water Temperatures Inverted
If active via trigger condition 1:
Evaporator Water Temperatures
When the alarm occurs due to this trigger, Alarm:
Inverted
it can auto reset the first two times each Displayed Text: EvapWaterTempInverted
day, with the third occurrence being manual
Trigger: All of the following are true for at least
reset. When the auto reset occurrences are
60 seconds:
triggered, the unit will remain enabled to run
• Evap EWT < Evap LWT – 1°C
(rather than going to an off state).
• at least one circuit is in Start or
For the auto reset occurrences, the alarm Run state
will reset automatically when the evaporator • EWT sensor fault not active
state is Run again. This means the alarm • LWT sensor fault not active
stays active while the unit waits for flow, then Action Taken: Normal shutdown all circuits and lock
it goes through the recirculation process out unit from running
after flow is detected. Once the recirculation Reset: This alarm can be cleared manually
is complete, the evaporator goes to the Run via the keypad or via BAS command.
state which will clear the alarm. After three
occurrences, the count of occurrences is
reset and the cycle starts over if the manual
Evaporator LWT Sensor Fault
reset flow loss alarm is cleared. Alarm: Evaporator LWT Sensor Fault
If active via trigger condition 2: Displayed Text: Evap LWT SenFault
Trigger: If any of the following occur for more
If the flow loss alarm has occurred due
than one second:
to this trigger, it is always a manual reset
• Resistance value is < 340 Ω
alarm.
• Resistance value is > 300 kΩ
• Reliability value reported for input
is anything other than ‘NoFault’
Action Taken: Rapid shutdown all circuits and lock
out unit from running
Reset: This alarm can be cleared manually
via the keypad or BAS command if
the following are true for at least 5
seconds:
• Resistance value is from 340 Ω
to 300 kΩ
• Reliability value reported for input
is ‘NoFault’

www.DaikinApplied.com 69 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Alarms and Events

Evaporator EWT Sensor Fault Emergency Stop


Alarm: Evaporator EWT Sensor Fault Alarm: Emergency Stop
Displayed Text: Evap EWT SenFault Displayed Text: Emergency Stop Switch
Trigger: If any of the following occur for more Trigger: Emergency Stop input off for 1 second
than one second: Action Taken: Rapid shutdown all circuits and lock out
• Resistance value is < 340 Ω unit from running
• Resistance value is > 300 kΩ Reset: This alarm can be cleared manually via
• Reliability value reported for input the keypad or via BAS command after
is anything other than ‘NoFault’ the emergency switch input is on for five
Action Taken: Normal shutdown all circuits and lock seconds.
out unit from running
Reset: This alarm can be cleared manually AC Module Comm Failure
via the keypad or BAS command if
Alarm: AC Module Comm Failure
the following are true for at least 5
seconds: Displayed Text: AC Module Comm Fail
• Resistance value is from 340 Ω Trigger: Communication with the module has failed.
to 300 kΩ Specifically, this means the reliability value
• Reliability value reported for input reported for the module is anything other
is ‘NoFault’ than 0 for at least 3 seconds.
Action Taken: Rapid shutdown all circuits and lock out
unit from running
Reset: This alarm can be cleared manually via the
OAT Sensor Fault keypad or BAS command after reliability
Alarm: OAT Sensor Fault value reported for the module is 0 for at
Displayed Text: OAT SenFault least five seconds.
Trigger: If any of the following occur for more
than one second: Evaporator EXV Module Comm Failure
• Resistance value is < 340 Ω
• Resistance value is > 300 kΩ Alarm: Evaporator EXV Module Comm Failure
• Reliability value reported for input Displayed Text: EvapExvModCommFail
is anything other than ‘NoFault’ Trigger: When evaporator Expansion Valve Type is
Action Taken: Normal shutdown all circuits and lock set as E6V model number (see Table 31),
out unit from running communication with the EVD module called
Reset: This alarm can be cleared manually EEXV1 has failed. Specifically, this means
via the keypad or BAS command if that 10 consecutive failures of read/write
the following are true for at least five command blocks for this modbus address
seconds: have occurred.
• Resistance value is from 340 Ω Action Taken: Rapid shutdown all circuits and lock out
to 300 kΩ unit from running
• Reliability value reported for Reset: This alarm can be cleared manually
input is ‘NoFault’ via the keypad or BAS command after
communication is restored for at least five
seconds.

External Alarm DC Fan Controller Comm Failure


Alarm: External Alarm
Alarm: DC Fan Controller Comm Failure
Displayed Text: External Alarm
Displayed Text: DcFanCtrlCommFail
Trigger: External alarm input is open for at
least 1 second. Trigger: Condenser Fan VFD Configuration set
point is set to All Fan VFD and heartbeat
Action Taken: Rapid shutdown all circuits and lock
from DC fan controller is not received for
out unit from running
30 seconds.
Reset: Auto clear when external alarm input
Action Taken: Normal shutdown all circuits and lock out
is closed for five seconds.
unit from running
Reset: This alarm can be cleared manually via the
keypad or BAS command if heartbeat from
DC fan controller has been received in the
last 30 seconds.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 70 www.DaikinApplied.com


Alarms and Events

Evaporator Pump #1 Failure Economizer EXV Module Comm Failure


Alarm: Evaporator Pump #1 Failure Alarm: Economizer EXV Module Comm Failure
Displayed Text: Evap Pump 1 Fault Text: EconExvModCommFail
Trigger: Unit is configured with primary and Trigger: Economizer Configuration set point is set to Yes
backup pumps, pump #1 is running, and communication with the economizer EXV
and the pump control logic switches to module has failed. Specifically, this means that
pump #2. 16 consecutive failures of read/write command
Action Taken: Backup pump is used blocks for this address have occurred.
Reset: This alarm can be cleared manually Action Economizer valve command is set to 0% in
via the keypad or BAS command. Taken: control logic, though without communication the
module is left to operate per logic embedded in
it. It should be set up to automatically close the
Evaporator Pump #2 Failure valves when communication is lost.
Alarm: Evaporator Pump #2 Failure Reset: This alarm can be cleared manually via the
keypad or BAS command after communication is
Displayed Text: Evap Pump 2 Fault
restored for at least 5 seconds.
Trigger: Unit is configured with primary and
backup pumps, pump #2 is running,
and the pump control logic switches to Circuit Alarms
pump #1.
Action Taken: Backup pump is used Low Evaporator Pressure
Reset: This alarm can be cleared manually via Alarm: Low Evaporator Pressure
the keypad or BAS command. Text: Cn EvapPressLow
Trigger: When circuit state = Start and OAT ≥ -8°C, any of
the following can trigger:
Bad Demand Limit Input • Evap Pressure < 0 kPa for 5 seconds
Alarm: Bad Demand Limit Input • Evap Pressure < -50 kPa for 2 seconds
Displayed Text: Bad Demand Lim Input When circuit state = Start and OAT < -8°C, any of
the following can trigger:
Trigger: Demand limit input out of range and
Demand Limit set point is set to • Evap Pressure < 0 kPa for 20 seconds
On. For this alarm, out of range is • Evap Pressure < -50 kPa for 5 seconds
considered to be a signal less than Note: for this condition where OAT is lower than
3 mA or more than 21 mA. -8°C, the first two times any of the trigger conditions
are met in a day the circuit will only shut down and
Action Taken: Demand limit function and signal are the alarm will not trigger. On the third occurrence in
ignored a day, the circuit will shut down and the alarm will
Auto clear when Demand Limit set be triggered.
Reset: point is set to Off or demand limit input For first 5 minutes circuit state = Run, any of the
back in range for 5 seconds. following can trigger:
• Evap Pressure < 0 kPa for 5 seconds
• Evap Pressure < -50 kPa for 2 seconds
• Evap Pressure < Low Pressure Unload set
Bad LWT Reset Input point for 100 seconds
Alarm: Bad LWT Reset Input After circuit state = Run for 5 minutes, any of the
following can trigger:
Displayed Text: Bad LWT Reset Input • Evap Pressure < 30 kPa for 5 seconds
Trigger: LWT Reset Type set point is 4-20 mA • Evap Pressure < -30 kPa for 2 seconds
and LWT reset input out of range. For • Evap Pressure < Low Pressure Unload set
this alarm out of range is considered point for time > Freeze Time
to be a signal less than 3 mA or more Where:
than 21 mA. • Freeze Time = 70 – 0.906 x Freeze Error,
limited to range of 20-70 seconds
Action Taken: LWT reset signal and 4-20 mA function
• Freeze Error = Low Evap Pressure Unload –
are ignored Evap Pressure
Reset: Auto clear when LWT Reset Type set For any trigger condition, the alarm cannot trigger if
point is not 4-20 mA or LWT reset input the evaporator pressure sensor fault is active.
back in range for five seconds. Action
Rapid shutdown of circuit and lock out from running
Taken:
Reset: This alarm can be cleared manually via the Unit
Controller keypad.

www.DaikinApplied.com 71 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Alarms and Events

Figure 68: Low Evaporator Pressure Fault Diagram

CIRCUIT
START
OAT ≥ -8°C OAT< -8°C
First 2 occurrences for this
Evap Pressure < 0 kPa for 5 Evap Pressure < 0 kPa for
condition will shut down
seconds 20 seconds
circuit but do not trigger the
OR OR
alarm. Third occurrence in
Evap Pressure < -50kPa for Evap Pressure < -50kPa for
the day will trigger the alarm.
2 seconds 5 seconds

{
CIRCUIT
RUN
Evap Pressure < Low
Evap Pressure < 0 kPa for 5 Evap Pressure < -50kPa for Pressure Unload set point for
5 minutes seconds 2 seconds 100 seconds

Evap Pressure < Low


Evap Pressure < 30 kPa for Evap Pressure < -30kPa for
Pressure Unload set point for
5 seconds 2 seconds
freeze time

Mechanical Low Pressure Switch


High Condenser Pressure Alarm: Mechanical Low Pressure Switch
Alarm: High Condenser Pressure Displayed Text: Cn MLP Switch
Text: Cn CondPressHigh Trigger: The alarm is triggered if all of the
Trigger: Saturated Condenser Temp > Max Saturated following are true for at least 40
Condenser Value for time longer than High seconds:
Condenser Pressure Delay set point. • Circuit state is Run
Action • MLP Switch input is off
Rapid shutdown of circuit and lock out from running
Taken:
The alarm also requires Evaporator
Reset: This alarm can be cleared manually via the Unit Configuration = Remote to trigger. This
Controller keypad if Saturated Condenser Temp < means if the Evaporator Configuration
Max Saturated Condenser Value. is set to Packaged, then the MLP
Switch inputs are ignored and the
Low Pressure Difference Or Ratio alarm is disabled.
Alarm: Low Pressure Difference Or Ratio Action Taken: Rapid shutdown of circuit and lock out
Text: Cn LowPrDiffOrRatio from running
Trigger: This alarm is triggered on the third occurrence Reset: This alarm can be cleared manually
of the below conditions within two hours. Prior via the Unit Controller keypad if the
occurrences are events. MLP Switch input is on.
Trigger 1: Pressure ratio is < 1.6 for longer than the Low
Pressure Diff/Ratio Delay set point after circuit
state transition to Run. Pressure ratio is calculated Mechanical High Pressure Switch
as shown with pressures in kPa: Alarm: Mechanical High Pressure Switch
Displayed Text: Cn MHP Switch
Ratio = (Cond Press + 101.325)/(Evap Press +
101.325) Trigger: Compressor VFD reports Safe Disable
Input alarm. This is the case when the
Trigger 2: Pressure difference is less than 180 kPa for
alarm code reported by the VFD is
longer than the Low Press Diff/Ratio Delay set
either 003BH or 003CH.
point after circuit state transition to Run. Press
difference is calculated as shown in kPa: Action Taken: Rapid shutdown of circuit and lock out
from running. Note that VFD will shut
Difference = (Cond Pressure) - (Evap Pressure) down compressor directly in response
Alarm/event cannot trigger for 5 minutes after to this alarm in the VFD. Controller
circuit state transitions to Preopen if OAT < 7°C, then needs to move circuit to the off
however the trigger logic will still run during this state, but compressor should already
window. be turned off by the VFD.
Action Rapid shutdown of circuit and lock out from Reset: This alarm can be cleared manually
Taken: running via the Unit Controller keypad after the
Reset: This alarm should auto reset every time until it has VFD is no longer reporting the Safe
triggered 3 times within 2 hours and be cleared Disable Input alarm.
manually via Unit Controller keypad or BAS.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 72 www.DaikinApplied.com


Alarms and Events

High Discharge Temperature High Motor Temperature


Alarm: High Discharge Temperature Alarm: High Motor Temperature
Displayed Text: Cn DiscTempHigh Displayed Text: Cn Motor Temp High
Trigger: The following are true for 5 seconds: Trigger: Compressor VFD reports motor
• Discharge Temp > High
overheat fault. The fault code for this
Discharge Temp set point
is 0020H.
• Discharge temp sensor fault is
not active Action Taken: Rapid shutdown of circuit and lock out
from running
Action Taken: Rapid shutdown of circuit and lock out
from running Reset: This alarm can be cleared manually
via the Unit Controller keypad when
Reset: This alarm can be cleared manually
compressor has been off for at least
via the Unit Controller keypad or via
5 minutes. When the alarm is cleared
BAS command when Discharge Temp
in the unit controller, the command to
is below the High Discharge Temp set
clear the fault in the VFD will be sent.
point.

High Oil Pressure Drop


Alarm: High Oil Pressure Drop Compressor Multiple Start Failure
Displayed Text: Cn Oil PD High Alarm: Compressor Multiple Start Failure
Trigger: Circuit is in the Start or Run state and Displayed Text: Cn CompMultiStartFail
Oil Pressure Drop > High Oil Pressure Trigger: This alarm is triggered on the third
Drop value for a time longer than High occurrence of the below conditions
Oil Pressure Drop Delay set point. within 2 hours. Prior occurrences are
High Oil Pressure Drop value is events.
calculated as shown below. All of the following must be true to
Operating PD = Condenser Pressure – trigger:
Evaporator Pressure • Compressor Run command is on
Minimum for High Oil Pressure • Compressor VFD Communication
Difference = High Oil Pressure Failure is not active
Difference Minimum set point • Either VFD Actual Speed = 0 for
more than 15 seconds or VFD
Maximum for High Oil Pressure Actual Speed < 13 Hz for more
Difference = High Oil Pressure than 30 seconds
Difference Minimum set point + 500 Action Taken: Rapid shutdown of circuit and lock out
kPa from running
Note that the set point exists Reset: This alarm can be cleared manually
individually for each circuit. via the Unit Controller keypad or via
Action Taken: Rapid shutdown of circuit and lock out BAS command.
from running
Reset: This alarm can be cleared manually via No Pressure At Start
the Unit Controller keypad or via BAS
command. Alarm: No Pressure At Start
Displayed Text: Cn No Press At Start
Figure 69: High Oil Pressure Difference Values Trigger: All of the following must be true to
High Oil Pressure trigger:
Difference Value • Circuit start requested
• Condenser Fan VFD
Configuration set point = None
Max value
• Either Evaporator Pressure or
Condenser Pressure are less
than 35 kPa (5.1 psi)
Action Taken: Abort start of circuit and lock out from
Min value running
Reset: This alarm can be cleared manually
via the Unit Controller keypad or BAS
200kPa 1500kPa command if Evap Pressure and Cond
Operating PD Pressure are at least 35 kPa (5.1 psi).

www.DaikinApplied.com 73 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Alarms and Events

Low Discharge Superheat Compressor VFD Temperature High


Alarm: Low Discharge Superheat Alarm: Compressor VFD Temperature High
Displayed Text: Cn Disc SH Low Displayed Text: Cn CompVfdTempHigh
Trigger: If all of the following are true for Trigger: VFD Heatsink temperature > Max VFD
at least 30 minutes, the alarm is Temperature for 5 seconds
triggered: Action Taken: Rapid shutdown of circuit and lock out from
• Circuit state is Start or Run running
• Liquid injection is off Reset: This alarm can be cleared manually via
• DSH < Low DSH Limit set point the Unit Controller keypad or via BAS
Action Taken: Normal shutdown of circuit command if temperature ≤ Max VFD
Reset: This alarm can be cleared manually Temperature.
via the Unit Controller keypad or via
BAS command. Compressor VFD Temperature Low
Alarm: Compressor VFD Temperature Low
Displayed Text: Cn CompVfdTempLow
Compressor VFD Current Output High Trigger: This alarm is triggered if the Compressor
High Compressor VFD Output Type is set as 3120 or 3122 and
Alarm:
Current Compressor VFD Temp ≤ -10°C for at least
Displayed Text: Cn CmpVFD Curr Out Hi 5 seconds
Trigger 1: VFD Output Current > Max Motor Action Taken: Rapid shutdown of circuit and lock out from
Current x 1.05 for at least 30 seconds running
Trigger 2: [VFD Output Current > Max Motor Reset: This alarm can be cleared manually via
Current x 0.99 AND Compressor the Unit Controller keypad or via BAS
Speed < 20 Hz] for at least 180 command if Compressor VFD temperature
seconds . > -5°C.
See the section covering circuit level
calculations for the details on the Max Compressor VFD Comm Failure
Motor Current value. Alarm: Compressor VFD Comm Failure
Action Taken: Rapid shutdown of circuit and lock out Displayed Text: Cn CompVfdCommFail
from running Trigger: Unit has compressor VFD’s and there is
Reset: This alarm can be cleared manually either a modbus configuration error or there
via the Unit Controller keypad or via are 10 consecutive modbus commands
BAS command. that failed to receive a valid response.
Action Taken: Normal shutdown of circuit and lock out
from running
Compressor VFD Current Input High Reset: This alarm can be cleared manually via
the Unit Controller keypad or via BAS
Alarm: High Compressor VFD Input Current command if communication has been
Displayed Text: Cn CmpVFD Curr In Hi restored.
Trigger: Alarm will trigger when all of the
following are true for at least 5 Compressor VFD Fault
seconds: Alarm: Compressor VFD Fault
• Unit mode is Ice Displayed Text: Cn Comp Vfd Fault
• Compressor is running Trigger: F3/F4 compressor types: Fault flag from
• VFD Input Current > VFD is set and fault code is not 0020H.
Compressor RLA set point x Other alarms trigger in response to specific
105% fault codes so if the fault is due to those
Compressor RLA set point for each codes, this alarm should not trigger.
circuit is part of the unit configuration. Action Taken: Rapid shutdown of circuit and lock out from
Action Taken: Rapid shutdown of circuit and lock out running
from running Reset: This alarm can be cleared manually
Reset: This alarm can be cleared manually via the Unit Controller keypad or via
via the Unit Controller keypad or via BAS command. When alarm is cleared,
BAS command. command to reset fault should be sent to
VFD.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 74 www.DaikinApplied.com


Alarms and Events

CC Module Comm Failure Action Taken: Rapid shutdown of circuit and lock out from
running
Alarm: CC Module Comm Failure
Reset: This alarm can be cleared manually via the
Displayed Text: CCn Module Comm Fail keypad or BAS command if sensor input
Trigger: Communication with the module has failed. voltage is 400 mv to 4600 mv for at least 5
Specifically, this means the reliability value seconds.
reported for the module is anything other
than 0 for at least 3 seconds.
Action Taken: Rapid shutdown of circuit and lock out
from running Condenser Pressure Sensor Fault
Reset: This alarm can be cleared manually via the Alarm: Condenser Pressure Sensor Fault
keypad or BAS command after reliability Displayed Text: Cn CondPressSenFault
value reported for the module is 0 for at Trigger: Trigger any time sensor input voltage is
least 5 seconds. less than 400 mv or more than 4600 mv
and UC communication with CC module is
OK for at least 1 second.
Action Taken: Rapid shutdown of circuit and lock out
EEXV Module Comm Failure from running
Alarm: EEXV Module Comm Failure Reset: This alarm can be cleared manually via the
keypad or BAS command if sensor input
Displayed Text: EEXVn Mod Comm Fail
voltage is 400 mv to 4600 mv for at least 5
Trigger: Evaporator Expansion Valve Type is set as
seconds.
an ETS model number (see Table 31) and
communication with the module has failed.
Specifically, this means the reliability value
reported for the module is anything other Oil Pressure Sensor Fault
than 0 for at least 3 seconds.
Alarm: Oil Pressure Sensor Fault
Action Taken: Rapid shutdown of circuit and lock out
from running Displayed Text: Cn OilPressSenFault
Reset: This alarm can be cleared manually via the Trigger: Trigger any time sensor input voltage is
keypad or BAS command after reliability less than 400 mv or more than 4600 mv
value reported for the module is 0 for at and UC communication with CC module is
least 5 seconds. OK for at least 1 second.
Action Taken: Normal shutdown of circuit and lock out
from running
Reset: This alarm can be cleared manually via
Evaporator Pressure Sensor Fault the keypad or BAS command if sensor
Alarm: Evaporator Pressure Sensor Fault input voltage is 400 mv to 4600 mv for at
least 5 seconds.
Displayed Text: Cn EvapPressSenFault
Trigger: Trigger any time sensor input voltage is
less than 400 mv and UC communication Suction Temperature Sensor Fault
with CC module is OK for at least 1
second. Alarm: Suction Temperature Sensor Fault
Trigger when sensor input voltage is more Displayed Text: Cn SuctTempSenFault
than 4600 mv and UC communication with Trigger: Trigger if any of the following are true for
CC module is OK for at least 1 second. at least 1 second:
However, this trigger should only occur • Sensor input value < 340 Ω
after circuit state is Start or Run for at least
• Sensor input value > 300 kΩ
90 seconds.
• Sensor reliability reported by control
Trigger if the evaporator approach is less system ≠ ‘No Fault’
than 1.11°C for more than 30 seconds. This Action Taken: Normal shutdown of circuit and lock out
trigger should only be enabled after the from running
circuit state is start or run for 30 seconds.
Reset: This alarm can be cleared manually via
The purpose of this trigger condition is to
the keypad or BAS command if sensor
prevent operation if the sensor is reading
input value is 340 Ω to 300 kΩ and
high but not out of range.
sensor reliability = ‘No Fault’ for at least 5
seconds.

www.DaikinApplied.com 75 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Alarms and Events

Discharge Temperature Sensor Fault Economizer Pressure Sensor Fault


Alarm: Discharge Temperature Sensor Fault
Alarm: Economizer Pressure Sensor Fault
Displayed Text: Cn DiscTempSenFault
Trigger: Trigger if any of the following are true for at Displayed Text: Cn EconPressSenFault
least 1 second: Trigger: The following conditions must be true to
trigger:
• Sensor input value < 340 Ω
• Economizer Configuration set point
• Sensor input value > 300 kΩ = Yes
• Sensor reliability reported by control • 8 seconds have passed since UC
system ≠ ‘No Fault’ booted up
Action Taken: Normal shutdown of circuit and lock out • Communication with EVD module
from running is OK
Reset: This alarm can be cleared manually via • Value reported is more than 3083
the keypad or BAS command if sensor kPa or less than 3.85 kPa for at least
input value is 340 Ω to 300 kΩ and sensor 1 second.
reliability = ‘No Fault’ for at least 5 seconds. Action Taken: Economizer forced to closed state and will
remain closed.
Evaporator EXV Motor Error Reset: This alarm will automatically clear if value
Alarm: Evaporator EXV Motor Error reported is from 3.85 to 3083 kPa for 5
seconds.
Displayed Text: Cn EvapExvMotorErr
Trigger: If EEXV Type is set to E6V and driver
in Evaporator EXV module reports EXV Economizer Temperature Sensor Fault
motor error. Driver A is for circuit #1 and Alarm: Economizer Temperature Sensor Fault
Driver B is for circuit #2.
Displayed Text: Cn EconTempSenFault
Action Taken: Rapid shutdown of circuit and lock out
Trigger: The following conditions must be true to
from running
trigger:
Reset: This alarm can be cleared manually via • Economizer Configuration set point
the keypad or BAS command if EXV motor = Yes
error is no longer being reported. • Communication with EVD module
is OK
• Value reported is more than 150°C
Power Loss While Running or less than -40°C for at least 1
second
Alarm: Power Loss While Running Action Taken: Economizer forced to closed state and will
Displayed Text: Cn PwrLossWhileRun remain closed.
Trigger: Circuit running when controller loses power Reset: This alarm will automatically clear if value
Action Taken: None reported is from -40°C to 150°C for 5
Reset: N/A seconds.

Economizer EXV Motor Error


Failed Pumpdown Alarm: Economizer EXV Motor Error
Alarm: Failed Pumpdown Displayed Text: Cn EconExvMotorErr
Displayed Text: Cn Pumpdown Fail Trigger: Driver in Economizer EXV module reports
EXV motor error. Driver A is for circuit #1
Trigger: Circuit state = pumpdown for time >
and Driver B is for circuit #2.
Pumpdown Time set point
Action Taken: Economizer forced to closed state and will
Action Taken: Shut down circuit
remain closed.
Reset: N/A
Reset: Automatically clear when EXV motor error
is not being reported for 5 seconds.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 76 www.DaikinApplied.com


Alarms and Events

DC Fan Motor Fault Low Evaporator Pressure - Unload


Alarm: DC Fan Motor Fault Trigger: This event will trigger when the unit mode is
Displayed Text: Cn DcFanMotorFault Cool, the circuit state is Run, and evaporator
Trigger: Any DC fan motor on the circuit has a pressure drops below the Low Evaporator
fault as indicated by a flag sent from the Pressure Unload set point for 5 seconds.
DC controller. Action Taken: Compressor speed will decrease by 1 Hz
Action Taken: None every second.
Reset: Fault flag is not set for at least one Reset: This event is reset when the evaporator
second. This alarm can be cleared pressure rises above the Low Evap Pressure
manually via the keypad or BAS Unload set point for 5 seconds. It is also reset
command if trigger condition is not true. if the circuit is no longer in the Run state or
When the alarm clear command is set via the unit operating mode is changed to Ice.
keypad or BAS, a request to clear alarms
is sent to the DC controller.

High Condenser Pressure - Hold

Events Trigger: This event will trigger when the unit mode =
Cool, compressor is running, and saturated
Situations may arise that require some action from the chiller condenser temperature > high saturated
or that should be logged for future reference, but aren’t severe condenser hold value for at least 5 seconds.
enough to track as alarms. These events are stored in a log Action Taken: Compressor will not be able to increase
separate from alarms but accessed through the alarm menu. Reset: This event is cleared when the saturated
This log shows the time and date of the latest occurrence, condenser temperature drops at least 2°C
the count of occurrences for the current day, and the count of below the high saturated condenser hold
occurrences for each of the previous seven days. value for at least 3 minutes. It is also cleared if
the circuit is no longer in the Run state or the
Unit Power Restore unit operating mode is changed to Ice.
Trigger: Unit controller is powered up.
Action Taken: None
Reset: N/A
High Condenser Pressure - Unload
Trigger: This event will trigger when the unit mode =
Cool, compressor is running, and saturated
Low Evaporator Pressure - Hold condenser temperature > high saturated
condenser unload value for at least one
Trigger: This event will trigger when the unit mode is
second.
Cool, the circuit state is Run, and evaporator
pressure drops below the low evaporator Action Taken: The compressor speed will decrease 1 Hz
pressure hold value for 5 seconds. every second.
Reset: This event is cleared when saturated
Low evaporator pressure hold value = Low condenser temperature < high saturated
Evaporator Pressure Unload set point + Low condenser unload value for at least 5
Evaporator Pressure Hold Offset set point seconds. It is also cleared if the compressor is
Action Taken: Circuit will not be able to increase in capacity. no longer in the Run state or the unit operating
Reset: This event is reset when the evaporator mode is changed to Ice.
pressure rises at least 14 kPa (2.03 psi)
above the low evaporator pressure hold value
for 3 seconds. It is also reset if the circuit is no
longer in the Run state or the unit operating
mode is changed to Ice.

www.DaikinApplied.com 77 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Alarms and Events

Low Pressure Difference Or Ratio Shutdown High VFD Output Current - Unload
Trigger: This event will trigger on the first and second Trigger: This event will trigger when all of the following
occurrence of the below conditions within are true for at least 3 seconds.
2 hours. A third occurrence within a 2 hour • Unit mode is Cool
window triggers the alarm.
• Compressor is running
Trigger 1:
• VFD Output Current > Max Motor
Pressure ratio is less than 1.6 for longer than Current x 0.99
the Low Pressure Diff/Ratio Delay set point Action Taken: Compressor speed will be reduced at a rate
after circuit state transition to Run. Pressure equivalent to 1 Hz every 2 seconds.
ratio is calculated as shown with pressures in Reset: This event is cleared when VFD Output
kPa: Current < Max Motor Current x 0.99. It is also
Ratio = (Condenser Pressure + 101.325)/ reset if the compressor is not running or the
(Evaporator Pressure + 101.325) unit operating mode is changed to Ice.
Trigger 2:
Pressure difference is less than 180 kPa for
longer than the Low Pressure Diff/Ratio Delay High VFD Line Current Hold
set point after circuit state transition to Run.
Pressure difference is calculated as shown Trigger: This event will trigger when all of the following
with pressures in kPa: are true for at least for 5 seconds.

Difference = (Condenser Pressure) - • Unit mode is Cool


(Evaporator Pressure) • Compressor is running
Alarm/event cannot trigger for 5 minutes after • VFD Line Current > Compressor RLA set
circuit state transitions to Preopen if OAT < point
7°C, however the trigger logic will still run Compressor RLA set point for each circuit is
during this window. part of the unit configuration.
Action Taken: Rapid shutdown of circuit Action Taken: Compressor will not be able to increase
Reset: This event resets immediately after triggering. speed/capacity.
Reset: This event is reset when VFD Line Current <
Compressor RLA set point x 0.99 for at least 3
minutes. It is also reset when the compressor
High VFD Output Current – Hold is not running or the unit operating mode is
changed to Ice.
This event will trigger when all of the following
are true for at least for 10 seconds.
• Unit mode is Cool
Trigger: High VFD Line Current Unload
• Compressor is running
• VFD Output Current > Max Motor Trigger: This event will trigger when all of the following
Current x 0.97 are true for at least for 5 seconds.
Compressor will not be able to increase in • Unit mode is Cool
Action Taken:
capacity/speed.
• Compressor is running
This event is set when VFD Output Current
< Max Motor Current x 0.94 for at least 60 • VFD Line Current > Compressor RLA set
Reset: seconds. It is also reset if the compressor point x 105%
is not running or the unit operating mode is Compressor RLA set point for each circuit is
changed to Ice. part of the unit configuration.
Action Taken: Compressor speed reduced 1 Hz every 2
seconds.
Reset: This event is reset when VFD Line Current ≤
Compressor RLA set point x 105%. It is also
reset when the compressor is not running or
the unit operating mode is changed to Ice.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 78 www.DaikinApplied.com


Alarms and Events

High VFD Temperature Hold


Trigger: This event will trigger when all of the following
are true for at least for 30 seconds.
• Unit mode is Cool
• Compressor is running
• VFD Heatsink Temp > Max VFD
Temperature - 6°C
Action Taken: Compressor will not be able to increase
speed/capacity.
Reset: This event is reset when VFD Heatsink Temp
< Max VFD Temperature - 6°C for at least 60
seconds. It is also reset when the compressor
is not running or the unit operating mode is
changed to Ice.

High VFD Temperature Unload


Trigger: This event will trigger when all of the following
are true for at least for 30 seconds.
• Unit mode is Cool
• Compressor is running
• VFD Heatsink Temp > Max VFD
Temperature - 3°C
Action Taken: Compressor speed reduced by 1 Hz every 10
seconds.
Reset: This event is reset when VFD Heatsink Temp
≤ Max VFD Temperature - 3°C. It is also reset
when the compressor is not running or the unit
operating mode is changed to Ice.

Compressor Start Failure


Trigger: This event will trigger on the first and second
occurrence of the below conditions within
2 hours. A third occurrence within a 2 hour
window triggers the alarm.
All of the following must be true to trigger:
• Compressor Run command is on
• Compressor VFD Communication
Failure is not active
• Either VFD Actual Speed = 0 for more
than 15 seconds or VFD Actual Speed <
13 Hz for more than 30 seconds.
Action Taken: Rapid shutdown of circuit
Reset: N/A

www.DaikinApplied.com 79 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Using the Controller

Using the Controller

Unit Controller Operation


Figure 70: Unit Controller

Alarm Button Menu Button

LCD Screen

Back Button “Push and Roll” Wheel

The keypad/display consists of a 5-line by 22-character is displayed to the far right of the line to indicate it is a “jump”
display, three buttons (keys) and a “push and roll” navigation line and the entire line is highlighted when the cursor is on that
wheel. There is an Alarm Button, Menu (Home) Button, and line.
a Back Button. The wheel is used to navigate between lines
on a screen (page) and to increase and decrease changeable Navigating
values when editing. Pushing the wheel acts as an Enter
When power is applied to the control circuit, the controller
Button and will jump from a link to the next set of parameters.
screen will be active and display the Home screen, which can
also be accessed by pressing the Menu button. The navigating
Figure 71: Typical Screen wheel is the only navigating device necessary, although the
▲▼ View/Set Unit 3 Menu, Alarm, and Back buttons can provide shortcuts as
explained later.
Status/Settings >
Set Up > Passwords
Temperatures > There are four levels of access for the user interface:
Date/Time/Schedule > • No password
• Operator level - 5321
Three types of lines exist:
• Technician/Manager level - will be provided at startup
• Menu title, displayed in the first line as in Figure 71.
• Daikin Applied service technician level
• Link (also called Jump) having an arrow ( > ) in the right
of the line and used to link to the next menu. Enter passwords from the Main Menu:
• Parameters with a value or adjustable set point. • Enter Password links to the Entry screen, which is an
The first line visible on each display includes the menu title and editable screen. Pressing the wheel goes to the edit
the line number to which the cursor is currently “pointing”, in mode where the password can be entered. The first (*)
the above menu representation, “Temperatures” is highlighted. will be highlighted; rotate the wheel clockwise to the first
number and set it by pressing the wheel. Repeat for the
The leftmost position of the title line includes an “up” arrow ▲
remaining three numbers. The password will time out
to indicate there are lines (parameters) “above” the currently
after 10 minutes with no keypad activity, and is cancelled
displayed line; and/or a “down” arrow ▼ to indicate there are
if a new password is entered or the control powers down.
lines (parameters) “below” the currently displayed items or an
“up/down” arrow to indicate there are lines “above and below” • Not entering a password allows access to a limited
the currently displayed line. number of parameters.
Information presented at the controller is relative to the
Each line on a screen can contain status-only information or
password access level; the most extensive menus are
include changeable data fields (set points).
available to service technicians.
A line in a menu may also be a link to further menus. This
Entering an invalid password has the same effect as not
is often referred to as a jump line, meaning pushing the
entering a password.
navigation wheel will cause a “jump” to a new menu. An arrow

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 80 www.DaikinApplied.com


Using the Controller

Once a valid password has been entered, the controller


allows further changes and access without requiring the user
to enter a password until either the password timer expires
or a different password is entered. The default value for this
password timer is 10 minutes.

Navigation Mode
When the navigation wheel is turned clockwise, the cursor
moves to the next line (down) on the page. When the wheel is
turned counterclockwise the cursor moves to the previous line
(up) on the page. The faster the wheel is turned the faster the
cursor moves. Pushing the wheel acts as an “Enter” button.
When the Back button is pressed, the display reverts back to
the previously displayed page. If the Back button is repeatedly
pressed, the display continues to revert one page back along
the current navigation path until the “main menu” is reached.
When the Menu (Home) button is pressed the display reverts
to the “main page.”
When the Alarm button is depressed, the Alarm Lists menu is
displayed.

Edit Mode
The Edit Mode is entered by pressing the navigation wheel
while the cursor is pointing to a line containing an editable field.
Once in the Edit Mode, pressing the wheel again causes the
editable field to be highlighted. Turning the wheel clockwise
while the editable field is highlighted causes the value to be
increased. Turning the wheel counterclockwise while the
editable field is highlighted causes the value to be decreased.
The faster the wheel is turned the faster the value is increased
or decreased. Pressing the wheel again will cause the new
value to be saved and the keypad/display to leave the Edit
Mode and return to Navigation Mode.

Figure 72: Example of Screen Menu

www.DaikinApplied.com 81 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Startup and Shutdown

Pre-startup
Startup and Shutdown

Do not turn the unit off using the “Override Stop” switch,
Inspect the chiller to ensure no components became loose or without first moving Q1 and Q2 to the “Stop” position, unless
damaged during shipping or installation, including leak test and it is an emergency, as this will prevent the unit from going
wiring check. Complete the pre-start checklist at the front of through a proper shutdown/pumpdown sequence, resulting in
this manual and return to Daikin Applied prior to startup date. possible equipment damage.
NOTICE
CAUTION
Daikin Applied service personnel or factory authorized
service agency must perform initial startup in order to activate The unit has a onetime pumpdown operation. When Q1
warranty. Return the “Screw Compressor Equipment Warranty and Q2 are in the “Pumpdown and Stop” position, the unit
Form” within 10 working days to Daikin Applied as instructed will pump down once and not run again until the Q1 and Q2
on the form to obtain full warranty benefits. switches are moved to the “Auto” position. If Q1 and Q2 are
in the “Auto” position and the load has been satisfied, the unit
CAUTION will go into onetime pumpdown and will remain off until the
Most relays and terminals in the unit control center are MicroTech® III control senses a call for cooling and starts the
powered when S1 is closed and the control circuit disconnect unit.
is on. Therefore, do not close S1 until ready for startup or the
unit may start unintentionally and possibly cause equipment CAUTION
damage. Water flow to the unit must not be interrupted before the
compressors pump down to avoid freeze-up in the evaporator.
Interruption will cause equipment damage.
Startup
1. Verify requirements from “Chilled Water Piping” on page CAUTION
14 are met. If all power to the unit is turned off, the compressor heaters
2. Verify chilled water flow rate and calibrate thermal will become inoperable. Once power is resumed to the unit,
dispersion flow switch - see instructions on page 84. the compressor and oil separator heaters must be energized
a minimum of 12 hours before attempting to start the unit.
3. Double check that the discharge shutoff valve and the
optional compressor suction butterfly valves are open. Failure to do so can damage the compressors due to
excessive accumulation of liquid in the compressor.
4. Check that the manual liquid line shutoff valves at the
outlet of the subcooler coils are open.
5. Check the leaving chilled water temperature set point Startup After Temporary Shutdown
on the MicroTech® III controller to be sure it is set at the
desired chilled water temperature. 1. Insure that the compressor and oil separator heaters
have been energized for at least 12 hours prior to
6. Start the auxiliary equipment for the installation by starting the unit.
turning on the time clock, and/or remote on/off switch,
and chilled water pump. 2. Start the chilled water pump.

7. Check to see that pumpdown switches Q1 and Q2 are in 3. With system switch Q0 in the “On” position, move
the “Pumpdown and Stop” (open) position. Throw the S1 pumpdown switches Q1 and Q2 to the “Auto” position.
switch to the “Auto” position. 4. Observe the unit operation until the system has
8. Under the “Control Mode” menu of the keypad, place the stabilized.
unit into the automatic Cool Mode.
9. Start the system by moving pumpdown switch Q1 to the Extended (Seasonal) Shutdown
“Auto” position.
1. Move the Q1 and Q2 switches to the Manual Pumpdown
10. Repeat step 7 for Q2. position.
2. After the compressors have pumped down, turn off the
Temporary Shutdown chilled water pump.

Move pumpdown switches Q1 and Q2 to the “Pumpdown and 3. Turn off all power to the unit and to the chilled water
Stop” position. After the compressors have pumped down, turn pump.
off the chilled water pump. 4. If fluid is left in the evaporator, confirm that the
evaporator heaters are operational.
CAUTION
5. Move the emergency stop switch S1 to the “Off” position.
6. Close the compressor discharge valve and the optional

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 82 www.DaikinApplied.com


Startup and Shutdown

compressor suction valve (if so equipped) as well as the Delta-T before the MicroTech® III controller will stage on
liquid line shutoff valves. cooling.
7. Tag all opened compressor disconnect switches to warn 9. Under the “Control Mode” menu of the keypad, place the
against startup before opening the compressor suction unit into the automatic Cool Mode.
valve and liquid line shutoff valves. 10. Start the system by moving pumpdown switches to the
8. If glycol is not used in the system, drain all water from “Auto” position.
the unit evaporator and chilled water piping if the unit is The following table gives glycol concentrations required for
to be shutdown during winter and temperatures below freeze protection.
-20°F can be expected. The evaporator is equipped
with heaters to help protect it down to -20°F. Chilled
water piping must be protected with field-installed Table 54: Freeze Protection Temperature
protection. Do not leave the vessels or piping open to the Percent Volume Glycol Concentration Required
atmosphere over the shutdown period.
For Freeze Protection For Burst Protection
9. Do not apply power to the evaporator heaters if the °F (°C)
Ethylene Propylene Ethylene Propylene
system is drained of fluids as this can cause the heaters
Glycol Glycol Glycol Glycol
to burn out.
20 (6.7) 16 18 11 12
10 (-12.2) 25 29 17 20
Startup After Extended (Seasonal) 0 (-17.8) 33 36 22 24
Shutdown -10 (-23.3) 39 42 26 28
1. With all electrical disconnects locked and tagged out, -20 (-28.9) 44 46 30 30
check all screw or lug-type electrical connections to be -30 (-34.4) 48 50 30 33
sure they are tight for good electrical contact. -40 (-40.0) 52 54 30 35
DANGER -50 (-45.6) 56 57 30 35
LOCK AND TAG OUT ALL POWER SOURCES WHEN -60 (-51.1) 60 60 30 35
CHECKING CONNECTIONS. ELECTRICAL SHOCK WILL
CAUSE SEVERE PERSONAL INJURY OR DEATH.
NOTE: These values are examples only and cannot be
2. Check the voltage of the unit power supply and see that appropriate to every situation. Generally, for an
it is within the ±10% tolerance that is allowed. Voltage extended margin of protection, select a temperature
unbalance between phases must be within ±2%. at least 10°F lower than the expected lowest ambient
temperature. Inhibitor levels should be adjusted for
3. See that all auxiliary control equipment is operative and solutions less than 25% glycol.
that an adequate cooling load is available for startup.
Glycol of less than 25% concentration is not
4. Check all compressor flange connections for tightness to recommended, unless inhibitors are adjusted,
avoid refrigerant loss. Always replace valve seal caps. because of the potential for bacterial growth and loss
of heat transfer efficiency.
5. Make sure system switch Q0 is in the “Stop” position and
pumpdown switches Q1 and Q2 are set to “Pumpdown
and Stop”. Throw the main power and control disconnect
switches to “On.” This will energize the crankcase
heaters. Wait a minimum of 12 hours before starting up
unit. Turn compressor circuit breakers to “Off” position
until ready to start unit.
6. Open the optional compressor suction butterfly valves,
the liquid line shutoff valves, and compressor discharge
valves.
7. Vent the air from the evaporator water side as well as
from the system piping. Open all water flow valves and
start the chilled water pump. Check all piping for leaks
and recheck for air in the system. Verify the correct flow
rate by taking the pressure drop across the evaporator
and compare to the graphs beginning on page 39.
8. Set the chilled water set point to the required
temperature. The system water temperature must be
greater than the total of the leaving water temperature
set point plus one-half the control band plus the startup

www.DaikinApplied.com 83 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Startup and Shutdown

Flow Switch Installation and Calibration pipe diameters prior to the sensor and 3 to 5 pipe diameters
of straight pipe after the sensor. Flow switch is placed in outlet
A thermal dispersion flow switch uses heat to determine pipe to reflect flow leaving the barrel. If installation on the
flow and therefore must be calibrated during system startup. inlet pipe is necessary, contact Chiller Technical Response
A thermal dispersion flow switch can be an acceptable at [email protected] to review the jobsite
replacement for paddle type flow switches and differential details.
pressure switches but care must be taken regarding wiring.
The thermal dispersion flow switch supplied by Daikin Applied, Figure 75: Mount in Direction of Flow
shown in Figure 1, comes as a 2 part unit consisting of a flow
switch and an adapter labeled E40242 by the supplier.

Figure 73: Thermal Dispersion Flow Switch and Adapter


IMPORTANT: Flow switch
MUST be calibrated before
chiller operation. Failure to
properly calibrate the switch
may result in severe chiller
damage and/or void warranty.

It is important that the flow switch be mounted so that the


probe is sufficiently inserted into the fluid stream. Figure 76
illustrates the recommended orientation of the sensor. It may
not be mounted directly on top or directly on the bottom of a
Mounting horizontal pipe.
Figure 74 highlights the position of the electrical connector and NOTE: DO NOT alter or relocate factory installed flow switch.
indentation ‘mark’ on flow switch. If issues exist, contact Chiller Technical Response at
[email protected].
Figure 74: Flow Switch Details
Figure 76: Remote Mounting Guidelines for Flow Switch

It is recommended, if possible, that the flow switch be mounted


such that the electrical connection and indentation ‘mark’ are
pointed in the direction of flow as shown in Figure 75.
If needed, the adapter is threaded into the pipe using pipe
If the flow sensor is to be mounted away from the unit, the sealant appropriate for the application. The flow sensor is
sensor should be mounted on the wall of the outlet pipe to mounted onto the adapter using silicone grease. Carefully
the evaporator, or in a run of straight pipe that allows 5 to 10 apply lubricant to the inside threads and o-ring so temperature

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 84 www.DaikinApplied.com


Startup and Shutdown

probe does not become coated with lubricant. Torque the Step 2: Once steady state minimum desired operating flow is
adapter/sensor connection to 18.5 ft/lbs. obtained, perform the ‘Teach’ function on the flow switch. The
‘Teach’ function is initiated by holding down the minus ‘-’ button
Wiring on the face of the flow switch for 15 seconds. During this 15
second period, LEDs ‘0’ and ‘9’ will be lit green. Once the
Refer to wiring diagram in the unit control panel.
‘Teach’ function is completed, the outer LEDs will flash green
Either AC or DC is used to power the flow switch. The unit as shown in .
controller’s digital input is a DC signal which is supplied
through the switch output of the flow switch for flow indication. Figure 77: Automatic Teach of Set point
It is required that the AC and DC commons of power be
separated. Contact Chiller Technical Response for alternate
wiring scenarios.

Flow Switch Setup


The flow switch comes from the factory set at a default
velocity of 20 cm/s. This value is typically well below the
minimum water flow specified for the unit’s evaporator so field
adjustment is required for adequate low flow protection. Table
55 are the calculated gallons per minute (gpm) for Schedule 40
steel pipe for various fluid velocities from 20 cm/s to 300 cm/s.
The flow switch has an overall range of adjustment from 3 cm/s
to 300 cm/s.
Step 1: Adjust flow through the evaporator to the minimum
desired operating gpm. Maintain this flow throughout the setup
procedure.

Table 55: Flow Volume Calculation


Inside US GPM at the velocities indicated below GPM
Pipe Pipe adjustment
Default
Size Diameter per '+' or '-'
(inch) (inch) 20 cm/sec 30 cm/sec 50 cm/sec 75 cm/sec 100 cm/sec 150 cm/sec 200 cm/sec 250 cm/sec 300cm/sec key input
2 2.06 6.86 10.3 17.2 25.7 34.3 51.5 68.6 85.8 102.9 1.72
2.5 2.46 9.79 14.7 24.5 36.7 49.0 73.4 97.9 122.4 146.9 2.42
3 3.07 15.1 22.7 37.8 56.7 75.6 113.4 151.2 189.0 226.8 3.78
3.5 3.55 20.2 30.3 50.6 75.8 101.1 151.7 202.2 252.8 303.3 5.06
4 4.03 26.0 39.1 65.1 97.7 130.2 195.3 260.4 325.5 390.5 6.51
5 5.05 40.9 61.4 102.3 153.5 204.6 306.9 409.2 511.5 613.7 10.2
6 6.07 59.1 88.6 147.7 221.6 295.5 443.2 590.9 738.7 886.3 14.8
8 7.98 102.3 153.5 255.8 383.7 511.6 767.5 1023.3 1279.1 1534.7 25.6
10 10.02 161.3 241.9 403.2 604.8 806.5 1209.7 1612.9 2016.2 2419.1 39.0
12 11.94 229.0 343.4 572.4 858.6 1144.7 1717.1 2289.5 2861.9 3433.8 57.2
14 13.13 276.8 415.2 692.0 1037.9 1383.9 2075.9 2767.8 3459.8 4151.3 69.2
16 15.00 361.5 542.2 903.6 1355.5 1807.3 2710.9 3614.6 4518.2 5421.2 90.4
18 16.88 457.5 686.3 1143.8 1715.7 2287.6 3431.4 4575.2 5719.0 6862.1 114.4
20 18.81 572.4 853.0 1421.6 2132.4 2843.2 4264.8 5686.4 7108.0 8528.6 142.2

www.DaikinApplied.com 85 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Startup and Shutdown

Step 3: After the ‘Teach’ function is completed and the outer procedure is performed to toggle to unlocked.
LEDs flashed, the flow switch will indicate a new set point NOTE: 1. The LED window display on flow switch represents
based upon the current flow which should still be at the steady a velocity range of 50 cm/s. The window centers on
state minimum desired operating flow. Figure 78 shows a the set point (SP). For example, if the SP was set to
typical display for this condition. All LEDs to the left of the 200 cm/s, then the LED labeled ‘0’ would represent
SP LED are lit green. The SP LED is lit RED (or may toggle a velocity of 180 cm/s when lit and the LED labeled 9
amber) which indicates that the flow switch is OPEN. Typically, would represent a velocity of 230 cm/s when lit.
an increase in fluid flow is between 15% to 30% above the 2. Each LED represents 5 cm/s, or two presses of the
‘Teach’ function flow is required for the SP LED to turn AMBER ‘+’ or ‘-’ buttons.
and the flow switch to CLOSE indicating acceptable flow. 3. When power is initially applied to the flow switch,
all green LEDs light and go out step by step. During
Figure 78: Teach Adjustment Complete this time, the output is closed. The unit is in the
operating mode.
4. When making manual adjustments to the set point
(SP), if no button is pressed for 2 seconds, the unit
returns to the operating mode with the newly set
value.
Flow below display range: The SP LED will be lit red and
the leftmost LED will be flashing green. For example, if the SP
was set to 200 cm/s, the flashing labeled ‘0’ would indicate that
the flow was below 180 cm/s. This would be shown if no flow
through chiller or lowered than desired flow.

Figure 80: Display for Flow Below Range


In Step 3, the ‘Teach’ function re-adjusted the flow switch set
point (SP) while flow was at the minimum desired operating
flow. The chiller will not operate at this flow because the
flow switch is OPEN after performing the ‘Teach’ function.
The benefit of the ‘Teach’ function is to quickly set the set
point within the desired operating range. Additional ‘manual’
adjustment of set point is required in order to allow for chiller
operation at this minimum flow. The ‘+’ and ‘-’ buttons on the
face of the flow switch allow for the manual adjustment of the
SP. Pressing the ‘+’ button reduces the flow set point while
pressing the ‘-’ button increases the flow set point. Each button
press, ‘+’ or ‘-‘, changes the flow set point by 2.5 cm/s.
Step 4: Press the ‘+’ button until LED ‘9’ begins to flash, as
shown in Figure 79. Opening of flow switch should now occur
at approximately 80% to 90% of minimum flow. Flow above display range: The SP LED will be lit amber, all
LEDs to the left and right of the SP LED with be green with the
Figure 79: Upper Range of Minimum Flow rightmost LED flashing green. For example, if the SP was set
to 200 cm/s, the flashing LED labeled ‘9’ would indicate that
the flow was above 230 cm/s. This may be a normal display
depending on range by which flow varies through chiller.

Figure 81: Display for Flow Above Range

Step 5: Once the SP is set, it is recommended that the


sensor be locked to avoid inadvertent readjustment. This
can be performed by pressing both the ‘+’ and ‘-’ buttons
simultaneously for 10 seconds. The indication goes out
momentarily indicating the unit is locked. To unlock, the same

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 86 www.DaikinApplied.com


System Maintenance

System Maintenance

General
Table 56: Oil Charge per Compressor
On initial startup and periodically during operation, it will
be necessary to perform certain routine service checks. Compressor Designation Oil Quantity (gallons)
Among these are checking the liquid line sight glasses, and 3120, 3122 3.43
the compressor oil level sight glass. In addition, check the
3AL, 3BL 4.7
MicroTech® III controller temperature and pressure readings
with gauges and thermometers to see that the unit has normal 4AL 6.6
condensing/suction pressure and superheat/subcooling
readings. Oil Filter Removal and Renewal
A Periodic Maintenance Log is located at the end of this Prior to this procedure, pump out the compressor. Isolate the
manual. It is suggested that the log be copied and a report be electrical supply to the control panels and compressor motor
completed on a regular basis. The log will serve as a useful terminal. Filter should be changed when pressure drop delta
tool for a service technician in the event service is required. goes above the linear line in Figure 82.
Initial startup date, vibration readings, compressor megger
readings and oil analysis information should be kept for Figure 82: Pressure Drop to Change Oil Filter
reference baseline data. 100
y = 0.3846x + 10.596
If the service technician has determined that the refrigerant 90
charge has been contaminated, the charge should be
80
recovered and tested for contaminates or noncondensables.
Appropriate actions should be taken based on testing and
Oil Pressure Difference = Condenser Pressure - Oil
70
Clean Air Act regulations. 60

Vibration Monitoring (Optional) 50


Recommended Filter
Delta P Change
Pressure (PSIG)

Vibration readings are often used as an indicator of a possible 40


Linear (Oil Filter
problem requiring maintenance. If vibration monitoring is part 30
Pressure Drop)
of the site PM program, the compressor can be checked with a
20
vibration analyzer on an annual basis. When doing the annual
testing, the load should be maintained as closely as possible 10
to the load of the original test. The initial vibration analysis test 0
provides a benchmark of the compressor, and when performed 0 50 100 150 200 250
routinely, can give a warning of impending problems. Operating Pressure Difference = Condenser Pressure - Evaporator Pressure (PSIG)

Lubrication
The fan motor bearings are permanently lubricated. No further WARNING
lubrication is required. Excessive fan motor bearing noise is an After the compressor has been pumped down and isolated,
indication of a potential bearing failure. the oil contained inside the filter housing will remain hot
enough to cause burns for some time afterwards. Always
POE type oil is used for compressor lubrication. This type of
allow sufficient time for the oil to cool down so that it is cool
oil is extremely hygroscopic, which means it will quickly absorb
enough not to be a danger when drained off (less than 35°C is
moisture if exposed to air and form acids that can be harmful
recommended). Severe injury from burns can result.
to the chiller. Avoid prolonged exposure of refrigerant to the
atmosphere to prevent this problem.
Figure 83: Oil Filter Location (Including Cutaway View)
CAUTION
POE oil must be handled carefully using proper protective
equipment (gloves, eye protection, etc.). The oil must not
come into contact with certain polymers (e.g. PVC) as it may
absorb moisture from this material. Also, do not use oil or
refrigerant additives to the system.
It is important that only the manufacturer’s recommended oil be
used. Acceptable POE oil types are:
• CPI/Lubrizol Emkarate RL68H
• Exxon/Mobil EAL Arctic 68
• Hatcol 3693
The compressor oil heater is 250 watts and is on when the
compressor is off and off when the compressor is on.

www.DaikinApplied.com 87 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


System Maintenance

Figure 84: Oil Filter Housing Cover Plate 4. Evacuate air and noncondensables before valving
refrigerant back into the compressor.

Electrical Terminals
DANGER
Electric equipment can cause electric shock which will cause
severe personal injury or death. Turn off, lock out and tag all
power before continuing with following service. Panels can
have more than one power source.

Oil filter assembly components are:


CAUTION
• Oil Filter – 250 mm
Periodically check electrical terminals for tightness and tighten
• Oil Filter Housing Cover
as required. Always use a backup wrench when tightening
• O-Ring – 89.5x3 electrical terminals.
• O-Ring – 76.1x3.4
• (6) M8 Bolts
All-Aluminum Condenser Coils
Disassembly Procedure
The condenser coils are an all-aluminum design including
1. Unscrew and remove two hex head side cover bolts 180° the connections, microchannel, fins (an oven brazing process
apart. Insert M8 guide studs into the vacant holes. brazes the fins to the microchannel flat tube), and headers
2. Remove remaining bolts and oil filter housing cover. (see “Microchannel Coil Cross Section”), which eliminates
the possibility of corrosion normally found between dissimilar
3. Pull the oil filter off of the spigot and withdraw the oil filter metals of standard coils.
from the housing and clean the housing.
During the condensing process, refrigerant in the coil passes
through the microchannel flat tubes, resulting in higher
efficiency heat transfer from the refrigerant to the airstream. In
the unlikely occurrence of a coil leak, contact Daikin Applied to
receive a replacement coil module.

Figure 85: Microchannel Coil Cross Section

4. Clean oil filter housing cover plate and all other


components.

Fitting a New Oil Filter Element – Reassembly


Before reassembly, remove any paint from joint faces. Inspect
parts individually for damage and ensure they are completely
clean before laying them out on a clean surface in a logical
order ready for reassembly.
Use fresh refrigerant oil to lubricate parts during reassembly.
1. Install new O-rings on the oil filter housing cover.
2. Insert new oil filter into the housing, ensuring the filter
sits tightly on the sealing spigot.
3. Replace the oil filter housing cover.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 88 www.DaikinApplied.com


System Maintenance

Cleaning Microchannel Aluminum Coils For routine quarterly cleaning, first remove surface debris and
then clean the coil with an approved coil cleaner (see approved
Maintenance consists primarily of the routine removal of dirt products list in Table 57). After cleaning the coils with the
and debris from the outside surface of the fins. approved cleaning agent, use the approved chloride remover
to remove soluble salts and revitalize the unit.
WARNING
Prior to cleaning the unit, turn off and lock out the main power Recommended Coil Cleaner
switch to the unit and close all access panels.
The following cleaning agents, assuming they are used in
Remove Surface Loaded Fibers accordance with the manufacturer’s directions on the container
for proper mixing and cleaning, have been approved for use on
Surface loaded fibers or dirt should be removed prior to water epoxy coated coils to remove mold, mildew, dust, soot, greasy
rinse to prevent further restriction of airflow. If unable to back residue, lint and other particulate:
wash the side of the coil opposite that of the coils entering air
side, then surface loaded fibers or dirt should be removed with
Table 57: Epoxy Coil Recommended Cleaning Agents
a vacuum cleaner. If a vacuum cleaner is not available, a soft
non-metallic bristle brush may be used. In either case, the tool Cleaning Agent Reseller Part Number
should be applied in the direction of the fins. Hydro-Balance Corp
Enviro-Coil P.O. Box 730
NOTE: Use of a water stream, such as a garden hose, H-EC01
against a surface loaded coil will drive the fibers and Concentrate Prosper, TX 75078
dirt into the coil. This will make cleaning efforts more 800-527-5166
difficult. Surface loaded fibers must be completely Enviro-Coil
Home Depot H-EC01
removed prior to using low velocity clean water rinse. Concentrate
Chlor*Rid Int’l, Inc.
Periodic Clean Water Rinse Chloride P.O. Box 908
Chlor*Rid DTS
A monthly clean water rinse is recommended for coils that are Remover Chandler, AZ 85244
applied in coastal or industrial environments to help to remove 800-422-3217
chlorides, dirt and debris. An elevated water temperature (not
to exceed 130ºF) will reduce surface tension, increasing the CHLOR*RID DTS™ should be used to remove soluble salts
ability to remove chlorides and dirt. Pressure washer pressure from the epoxy coated coil, but the directions must be followed
must not exceed 600 psig and the nozzle should remain at closely. This product is not intended for use as a degreaser.
least one foot from the coil to avoid damaging fin edges. Any grease or oil film should first be removed with the
approved cleaning agent.
High Velocity Water or Compressed Air 1. Remove Barrier - Soluble salts adhere themselves
High velocity water from a pressure washer or compressed air to the substrate. For the effective use of this product,
should only be used at a very low pressure to prevent fin and/ the product must be able to come in contact with the
or coil damages. The force of the water or air jet may bend the salts. These salts may be beneath any soils, grease or
fin edges and increase airside pressure drop. Reduced unit dirt; therefore, these barriers must be removed prior to
performance or nuisance unit shutdowns may occur. application of this product. As in all surface preparation,
the best work yields the best results.
No maintenance is ordinarily required except the routine
removal of dirt and debris from the outside surface of the 2. Apply CHLOR*RID DTS - Apply CHLOR*RID DTS
fins. Daikin recommends the use of non-caustic, non-acidic directly onto the substrate. Sufficient product must be
cleaners available at most air conditioning supply outlets. Flush applied uniformly across the substrate to thoroughly
the coil from the inside out. wet out surface with no areas missed. This may
be accomplished by use of a pump-up sprayer or
Cleaning Epoxy Coated Coils conventional spray gun. The method does not matter, as
long as the entire area to be cleaned is wetted. After the
The following additional cleaning procedures are substrate has been thoroughly wetted, the salts will be
recommended as part of the routine maintenance activities soluble and is now only necessary to rinse them off.
for epoxy coated coils. Documented routine cleaning of epoxy
coated coils is required to maintain warranty coverage. 3. Rinse - It is highly recommended that a hose be used
as a pressure washer will damage the fins. The water
Routine Quarterly Cleaning of Epoxy Coil used for the rinse is recommended to be of potable
quality, though a lesser quality of water may be used if a
Quarterly cleaning is essential to extend the life of an epoxy small amount of CHLOR*RID DTS is added. Check with
coated coil and is required to maintain warranty coverage. CHLOR*RID International, Inc. for recommendations on
Coil cleaning shall be part of the unit’s regularly scheduled lesser quality rinse water.
maintenance procedures. Failure to clean an epoxy coated coil
will void the warranty and may result in reduced efficiency and
durability in the environment.

www.DaikinApplied.com 89 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


System Maintenance

Harsh Chemical and Acid Cleaners through the MicroTech® III controller. When in the auto mode,
the circuit with the fewest number of starts will be started first.
Harsh chemicals, household bleach or acid cleaners should
If all circuits are operating and a stage down in the number of
not be used to clean epoxy coated coils. These cleaners can
operating compressors is required, the circuit with the most
be very difficult to rinse out of the coil and can accelerate
operating hours will cycle off first. The operator can override
corrosion and attack the epoxy coating. If there is dirt below
the MicroTech® III controller, and manually select the lead
the surface of the coil, use the recommended coil cleaners as
circuit as circuit #1 or #2.
described above.

WARNING
Use caution when applying coil cleaners. They can contain
Pump Operation
potentially harmful chemicals. Wear breathing apparatus and It is highly recommended that the chiller unit control the chilled
protective clothing. Carefully follow the cleaner manufacturer’s water pump(s). The integral chiller control system has the
MSDS sheets. Thoroughly rinse all surfaces to remove any capability to selectively start pump A or B or automatically
cleaner residue. Do not damage the fins. alternate pump selection at each start and also has pump
standby operation capability.
Liquid Line Sight Glass Failure to have the chiller control the pumps may cause the
following problems:
Observe the refrigerant sight glasses weekly. A clear glass of
liquid indicates that there is adequate refrigerant charge in the 1. If any device, other than the chiller, should try to start the
system to provide proper feed through the expansion valve. chiller without first starting the pumps, the chiller will lock
out on the No Flow alarm and require a manual reset
Bubbling refrigerant in the sight glass, during stable run
to restart. This can be disruptive to the normal cooling
conditions, may indicate that there can be an EXV problem
process.
since the EXV regulates refrigerant flow. Refrigerant gas
flashing in the sight glass could also indicate an excessive 2. In areas where freeze-up is a concern, the chiller control
pressure drop in the liquid line, possibly due to a clogged filter- senses the chilled water temperature and turns on an
drier or a restriction elsewhere in the liquid line. immersion heater in the evaporator. It also signals the
chilled water pump to start, providing flow through the
An element inside the sight glass indicates the moisture
evaporator and additional protection against evaporator
condition corresponding to a given element color. If the sight
and outside pipe freeze-up. Other pump starting
glass does not indicate a dry condition after about 12 hours of
methods will not automatically provide this protection.
operation, an oil acid test is recommended.
Note: The owner/operator must be aware that when the
Do not use the sight glass on the EXV body for refrigerant water temperature falls below freezing temperatures it
charging. Its purpose is to view the position of the valve. is imperative NOT to stop the pump(s) as immediate
freeze-up can occur.
Lead-Lag This method of freeze protection is only effective as
A feature on all Daikin Pathfinder® air-cooled chillers is a long as the facility and the chiller have power. The only
system for alternating the sequence in which the compressors positive freeze protection during power failures is to
start to balance the number of starts and run hours. Lead- drain the evaporator and blow out each tube or add the
Lag of the refrigerant circuits is accomplished automatically appropriate concentration of glycol to the system.

Compressor VFD
Table 58: Compressor VFD Inspection Areas

Inspection Area Inspection Points Corrective Action


Inspect equipment for discoloration from
Replace damaged equipment as required.
overheating or deterioration.
General
Inspect for dirt, foreign particles, or dust collection Inspect door seal if so equipped. Use dry air to clear
on components foreign matter.
Conductors and Inspect wiring and connections for discoloration,
Repair or replace damaged wire.
Wiring damage or heat stress.
Inspect terminals for loose, stripped, or damaged Tighten loose screws and replace damaged screws or
Terminals
connections. terminals.
Inspect contactors and relays for excessive noise
Check coil voltage for over or under voltage condition.
Relays and during operation.
Contactors Inspect coils for signs of overheating such as Replace damaged removable relays, contactors or circuit
melted or cracked insulation. board.

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 90 www.DaikinApplied.com


System Maintenance

Figure 86: Preventative Maintenance Schedule


Monthly Annual
Operation Weekly
(Note 1) (Note 2)
General
Complete unit log and review (Note 3) X
Inspect unit for loose or damaged components and visible leaks X
Inspect thermal insulation for integrity X
Clean and paint as required X
Electrical ( * including the VFDs)
Sequence test controls * X
Check contactors for pitting, replace as required * X
Check terminals for tightness, tighten as necessary * X
Verify solenoid plug(s) tightness and gasket integrity X
Clean control panel interior * X
Clean control box fan filter * (Note 7 ) X
Visually inspect components for signs of overheating * X
Verify compressor and oil heater operation X
Megger compressor motor X
Refrigeration/Lubricant
Leak test X
Check liquid line sight glasses for clear flow X
Check compressor oil sight glass for correct level (lubricant charge) X
Check filter-drier pressure drop (Note 6) X
Perform compressor vibration test (optional) X
Perform oil analysis test on compressor oil X
Condenser (air-cooled)
Clean condenser coils (Note 4) X
Check fan blades for tightness on shaft (Note 5) X
Check fans for loose rivets and cracks, check motor brackets X
Check coil fins for damage and straighten as necessary X
NOTE: 1 Monthly operations include all weekly operations.
2 Annual (or spring startup) operations include all weekly and monthly operations.
3 Log readings can be taken daily for a higher level of unit observation.
4 Coil cleaning can be required more frequently in areas with a high level of airborne particles.
5 Be sure fan motors are electrically locked out.
6 Replace the filter if pressure drop exceeds 20 psi.
7 The weekly fan filter cleaning schedule can be modified to meet job conditions. It is important that the filter allows full
air flow.

www.DaikinApplied.com 91 IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS


Appendix

Appendix

Definitions
Active Set Point OAT
The active set point is the setting in effect at any given Outside ambient air temperature
moment. This variation occurs on set points that can be altered Offset
during normal operation. Resetting the chilled water leaving
temperature set point by one of several methods, such as Offset is the difference between the actual value of a variable
return water temperature, is an example. (such as temperature or pressure) and the reading shown on
the controller as a result of the sensor signal.
Active Capacity Limit
Refrigerant Saturated Temperature
The active set point is the setting in effect at any given
moment. Any one of several external inputs can limit a Refrigerant saturated temperature is calculated from the
compressor’s capacity below its maximum value. pressure sensor readings for each circuit. The pressure is fitted
to an R-134a temperature/pressure curve to determine the
Deadband saturated temperature.
The deadband is a range of values surrounding a set point Soft Loading
such that a change in the variable occurring within the
deadband range causes no action from the controller. For Soft Loading is a configurable function used to ramp up the
example, if a temperature set point is 44°F and it has a unit capacity over a given time period, usually used to influence
deadband of ± 2°F, nothing will happen until the measured building electrical demand by gradually loading the unit.
temperature is less than 42°F or more than 46°F. SP
DIN Set point
Digital input, usually followed by a number designating the Suction Superheat (SSH)
number of the input.
Suction superheat is calculated for each circuit using the
Error following equation:
In the context of this manual, “Error” is the difference between Suction Superheat = Suction Temp – Evap Saturated Temp
the actual value of a variable and the target setting or set point.
Stage Up/Down Accumulator - Fans
Evaporator Approach
The accumulator can be thought of as a bank storing
The evaporator approach is calculated for each circuit. occurrences that indicate the need for an additional fan.
Evaporator Approach = LWT – Evap Saturated Temp Stage up/Stage down Delta-T
Evap Recirc Timer Staging is the act of starting or stopping a compressor or fan
A timing function, with a 30-second default, that holds off any when another is still operating. The Delta-T is the “deadband”
reading of chilled water for the duration of the timing setting. on either side of the set point in which no action is taken.
This delay allows the chilled water sensors (especially water Stage Up Delay
temperatures) to take a more accurate reading of the chilled
water system conditions. The time delay from the start of the first compressor to the start
of the second.
EXV
Startup Delta-T
Electronic expansion valve, used to control the flow of
refrigerant to the evaporator. Number of degrees above the LWT set point required to start
the first compressor.
Load Limit
Stop Delta-T
An external signal from the keypad, the BAS or a 4-20 mA
signal that limits the compressor loading to a designated Number of degrees below the LWT set point required for the
percent of full load. Frequently used to limit unit power input. last compressor to stop.

Load Balance Vdc

Load balance is a technique that equally distributes the total Volts, direct current
unit load among the running compressors on a unit or group of
units.
LWT
Leaving water temperature. The “water” is any fluid used in the
chiller circuit.
ms
Millisecond

IOM 1242-3 • PATHFINDER® MODEL AWV CHILLERS 92 www.DaikinApplied.com




DAIKIN APPLIED AMERICAS INC.


LIMITED PRODUCT WARRANTY
(North America)

Daikin Applied Americas Inc. dba Daikin Applied (“Company”) warrants to contractor, purchaser and any owner of the product
(collectively “Owner”) that Company, at it’s option, will repair or replace defective parts in the event any product manufactured by
Company, including products sold under the brand name Daikin and used in the United States or Canada, proves defective in material
or workmanship within twelve (12) months from initial startup or eighteen (18) months from the date shipped by Company, whichever
occurs first. Authorized replaced parts are warranted for the duration of the original warranty. All shipments of such parts will be
made FOB factory, freight prepaid and allowed. Company reserves the right to select carrier and method of shipment.

In addition, labor to repair or replace warranty parts is provided during Company normal working hours on products with rotary
screw compressors and centrifugal compressors. Warranty labor is not provided for any other products.

Company’s liability to Owner under this warranty shall not exceed the lesser of the cost of correcting defects in the products sold or the
original purchase price of the products.

PRODUCT STARTUP ON CENTRIFUGAL AND SCREW COMPRESSOR PRODUCTS IS MANDATORY and must be
performed by a Daikin Applied or a Company authorized service representative.

It is Owner’s responsibility to complete and return the Registration and Startup Forms accompanying the product to Company within
ten (10) days of original startup. If this is not done, the ship date and the startup date will be deemed the same for warranty period
determination, and this warranty shall expire twelve (12) months from that date.

EXCEPTIONS

1. If free warranty labor is available as set forth above, such free labor does not include diagnostic visits, inspections, travel time and
related expenses, or unusual access time or costs required by product location.
2. Refrigerants, fluids, oils and expendable items such as filters are not covered by this warranty.
3. This warranty shall not apply to products or parts which (a) have been opened, disassembled, repaired, or altered by anyone other
than Company or its authorized service representative; or (b) have been subjected to misuse, negligence, accidents, damage, or
abnormal use or service; or (c) have been operated, installed, or startup has been provided in a manner contrary to Company’s
printed instructions, or (d) were manufactured or furnished by others and which are not an integral part of a product manufactured
by Company; (e) have been exposed to contaminates, or corrosive agents, chemicals, or minerals, from the water supply source, or
(f) have not been fully paid for by Owner.

ASSISTANCE

To obtain assistance or information regarding this warranty, please contact your local sales representative or a Daikin Applied office.

SOLE REMEDY

THIS WARRANTY CONSTITUTES THE OWNER’S SOLE REMEDY. IT IS GIVEN IN LIEU OF ALL OTHER
WARRANTIES. THERE IS NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. IN NO EVENT AND UNDER NO CIRCUMSTANCE SHALL COMPANY BE LIABLE FOR INCIDENTAL,
INDIRECT, SPECIAL, CONTINGENT OR CONSEQUENTIAL DAMAGES, WHETHER THE THEORY BE BREACH OF
THIS OR ANY OTHER WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.

No person (including any agent, sales representative, dealer or distributor) has the authority to expand the Company’s obligation
beyond the terms of this express warranty or to state that the performance of the product is other than that published by Company.

For additional consideration, Company will provide an extended warranty(ies) on certain products or components thereof. The terms
of the extended warranty(ies) are shown on a separate extended warranty statement.

Form No. 933-430285Y-01-A (05/17)

www.DaikinApplied.com 93 IOM 1242-3 • MAGNITUDE® MODEL WMC CHILLERS


Daikin Applied Training and Development
Now that you have made an investment in modern, efficient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at
www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.

Warranty

All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.

Aftermarket Services

To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.

Products manufactured in an ISO Certified Facility.

IOM 1242-3 (05/19) ©2019 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com

You might also like