IOM1242
IOM1242
Pathfinder®
Air-cooled Screw Chillers
Model AWV
100 to 565 Tons (350 to 1985 kW)
HFC-134a Refrigerant
60/50 Hz
Table of Contents
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation and Application Considerations . . . . . . 7
Installation and Application Considerations - Remote
Evaporators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Dimensions - Remote Evaporators . . . . . . . . . . . . . 32
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . 35
Isolator Information . . . . . . . . . . . . . . . . . . . . . . . . . 38
Pressure Drop Data . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . 42
Unit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Circuit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Alarms and Events . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Using the Controller . . . . . . . . . . . . . . . . . . . . . . . . . 80
Startup and Shutdown . . . . . . . . . . . . . . . . . . . . . . . 82
System Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 87
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
©2019 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.
Introduction
This manual provides installation, operation, and maintenance information for Daikin Pathfinder® model AWV screw chillers with the
MicroTech® III controller.
WARNING
Electric shock hazard. Improper handling of this equipment can cause personal injury or equipment damage. This equipment must
be properly grounded. Connections to and service of the MicroTech® III control panel must be performed only by personnel that are
knowledgeable in the operation of the equipment being controlled.
CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can cause damage to the components. Use
a static strap before performing any service work. Never unplug any cables, circuit board terminal blocks, or power plugs while
power is applied to the panel.
CAUTION
When moving refrigerant to/from the chiller using an auxiliary tank, a grounding strap must be used. An electrical charge builds
when halo-carbon refrigerant travels in a rubber hose. A grounding strap must be used between the auxiliary refrigerant tank and
the chiller’s end sheet (earth ground), which will safely take the charge to the ground. Damage to sensitive electronic components
could occur if this procedure is not followed.
CAUTION
This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with this instruction
manual, it may cause interference with radio communications. Operation of this equipment in a residential area may cause harmful
interference in which case the owner will be required to correct the interference at the owner’s own expense.
Daikin Applied disclaims any liability resulting from any interference or for the correction thereof.
DANGER
Dangers indicate a hazardous situation, which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not
avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
General Description
Daikin Pathfinder® model AWV chillers are complete, self- protection and operating controls are included.
contained, automatically controlled, liquid-chilling units All Daikin Applied screw chillers must be commissioned by
featuring variable speed screw compressors. All model a Daikin Applied service technician or an authorized service
AWV chillers are equipped with a single evaporator and provider. Failure to follow this startup procedure can affect the
microchannel condenser coils along with two compressors. equipment warranty (see “Receiving and Handling” on page
Pathfinder® chillers are designed for outdoor installation only. 7).
The chillers use refrigerant HFC-134a that has no ozone The standard limited warranty on this equipment covers parts
depletion level. that prove defective in material or workmanship. Specific
Only normal field connections such as water piping, electric details of this warranty can be found in the warranty statement
power, and control interlocks are required, thereby simplifying furnished with the equipment.
installation and increasing reliability. Necessary equipment
NOMENCLATURE
A W V ### A XXX
Air-cooled Compressor Code
World Vintage
Nameplates Avoid rough handling shock due to impact or dropping the unit.
Identification nameplates on the chiller:
Do not push or pull the unit. Never allow any part of the unit
• The unit nameplate is located on the exterior of the Unit to fall during unloading or moving as this can result in serious
Power Panel. Both the Model No. and Serial No. are damage.
located on the unit nameplate; the Serial No. is unique to
the unit. These numbers should be used to identify the To lift the unit, lifting tabs with 3” (76 mm) diameter holes are
unit for service, parts, or warranty questions. This plate provided on the base of the unit. All lifting holes must be used
also has the unit refrigerant charge and electrical ratings. when lifting the unit. Spreader bars and cables should be
• Vessel nameplate is located on the evaporator. They arranged to prevent damage to the unit. (see Figure 1).
have a National Board Number (NB) and a serial number,
either of which identify the vessel (but not the entire unit). Figure 1: AWV Unit Rigging
• Compressor nameplate is located on each compressor NUMBER OF FANS MAY SPREADER BARS MUST BE
and gives pertinent electrical information. VARY FROM THIS DIAGRAM USED TO PREVENT CABINET
BUT LIFTING METHOD DAMAGE. LOCATE BARS
ABOVE UNIT TO CLEAR FAN
Receiving and Handling
REMAINS THE SAME.
ALL PROVIDED RIGGING HOLES GRILLES. MINIMUM DISTANCE
MUST BE USED. LIFT ONLY FROM ACROSS UNIT BETWEEN
BASE POINTS AS SHOWN. CABLE OR CHAINS IS
The unit should be inspected immediately after receipt for 90 INCHES.
possible damage. All Daikin Applied screw air-cooled chillers
are shipped FOB factory and all claims for handling and
shipping damage are the responsibility of the consignee.
Startup by a Daikin Applied service representative is included
on all Pathfinder® units sold for installation within the U.S.
and Canada and must be performed by them to initiate the
standard Limited Product Warranty. Startup by any party other
than a Daikin Applied service representative will void the
Limited Product Warranty. Two-week prior notification of startup
is required. The contractor should obtain a copy of the Startup
Scheduled Request Form from the sales representative or from
L7
the nearest Daikin Applied service office. Completed Request L8 OPPOSITE
L5
Form and check list on page 3 are required before startup can L6 OPPOSITE
SIDE - (NOT ON
ALL MODELS)
be scheduled. CONTROL
L3 SIDE
L4 OPPOSITE
PANEL L1 SIDE
Installation and maintenance are to be performed only by L2 OPPOSITE
SIDE REPRESENTATIVE LIFTING SCHEMATIC -
qualified personnel who are familiar with local codes and COMPRESSORS, EVAPORATOR, AND PIPING
regulations, and experienced with this type of equipment. NOT SHOWN FOR DRAWING SIMPLICITY.
For ground level applications, the unit must be installed Clearance Requirements
on a substantial base that will not settle. Use a one-piece
concrete slab with footings extended below the frost line. Sufficient clearance must be maintained between the unit and
The foundation must be level within 13 mm (1/2 inch) over adjacent walls or other units to allow the required unit air flow
its length and width and strong enough to support the unit to reach the coils, see Figure 2 and Figure 3. Failure to do so
operating weight as listed in Dimensional Drawings beginning will result in a capacity reduction and an increase in power
on page 35. The addition of neoprene waffle pads (supplied consumption. Graphs on the following pages give the minimum
by customer) under the unit may allow water to drain from clearance for different types of installations and also capacity
reduction and power increase if closer spacing is used. The
inside the frame, which can act as a dam. Installation of
graphs are based on individual cases and should not be
optional spring or rubber-in-shear isolators can also assist with
combined with other scenarios.
drainage, see page 38 for information.
The clearance requirements shown are a general guideline,
On ground level applications, protection against vandalism is
based on individual cases, and cannot account for all
recommended; either by the optional factory-installed lower
scenarios. Such factors as prevailing winds, additional
wire mesh guards or louvers, or by a field installed screening
equipment within the space, design outdoor air temperature,
fence. Note that the fence must allow free flow of air to the
and numerous other factors may require more clearance than
condenser coil for proper unit operation. Upper wire mesh coil
what is shown. Additional clearances may be required under
guards are standard.
certain circumstances. No solid obstructions are allowed above
the unit at any height, see Case 5 on page 12. If low ambient
Mounting Hole Access temperature operation is expected, optional louvers should be
The inside of the base rail is open to allow access for securing installed if the unit has no protection against prevailing winds.
mounting bolts, etc. Mounting location dimensions are given in
Dimensional Drawings beginning on page 35. Figure 3: Spacing Guidelines for Sufficient Airflow
No obstructions.
Service Access
Recommended area
is applicable for
service access ONLY.
Performance
The control panels are located on the end of the chiller and Minimum = 4 feet (1.2 m)
clearance graphs are
provided in submittal
(Must have 8 ft. on one documents and may
require a minimum of four feet of clearance in front of the side for coil removal) require additional
spacing.
panels. Compressors, filter-driers, and manual liquid line
Minimum 8 feet (2.4 m) service
shutoff valves are accessible on each side or end of the unit. clearance on this end for
Minimum = 4 feet
Control Panel
(1.2 m)
shell and tube evaporator
The evaporator heater is located on the barrel. Do not block Minimum 4 feet (1.2 m) service
access to the sides or ends of the unit with piping or conduit. clearance on this end for
braze plate evaporator
DANGER
Disconnect, lockout and tag all power to the unit before
servicing condenser fan motors or compressors. Failure to do
so can cause bodily injury or death.
Case 1: Building or Wall on One Side of Unit Figure 6: Case 1 for AWV012-014 Models
For all models, maintain a 4 foot minimum from a wall of any % Full Load Capacity Reduction (AWV012-014)
height; however, performance may be affected at this distance 1.2%
due to air recirculation and elevated condenser pressure. 4 Feet
1.0%
Assuming all service clearance requirements are met, Figure 5
% Capacity Reduction
to Figure 9 depict Case 1 performance adjustments as the wall 0.8%
height and distance increases.
0.6% 5 Feet
0.0%
8 12 16 20 24
Height of Wall - Feet
% Power Increase
1.5%
1.0% 5 Feet
6 Feet
Figure 5: Case 1 for AWV 008-010 Models 0.5%
1.0%
0.0%
0.8%
8 12 16 20 24
5 Feet
Height of Wall - Feet 0.6%
0.4%
% Full Load Power Increase (AWV008-010) 6 Feet
0.2%
2.5%
4 Feet 0.0%
2.0% 8 12 16 20 24
% Power Increase
5 Feet
1.0% % Full Load Power Increase (AWV016-018)
6 Feet 3.0%
0.5%
8 12 16 20 24
Height of Wall - Feet 2.0%
1.5%
5 Feet
1.0%
6 Feet
0.5%
0.0%
8 12 16 20 24
Height of Wall - Feet
1.0%
requirements are met, Figure 11 and Figure 12 depict Case 2
0.8% performance adjustments as the distance between two units
5 Feet
0.6% increases.
0.4%
6 Feet Figure 10: Two Units, Side-by-Side
0.2%
0.0%
8 12 16 20 24
Height of Wall - Feet
2.0%
1.5%
5 Feet
1.0%
6 Feet
0.5%
Figure 11: Case 2 - Full
FullLoad
Load Capacity
Capacity Reduction
Reduction
0.0%
6.0
8 12 16 20 24
Height of Wall - Feet
5.0
% Capacity Reduction
1.2%
2.0
1.0%
0.8%
5 Feet 1.0
0.6%
0.4% 6 Feet
0.0
0.2% 6 8 10 12
0.0% Distance Between Units (ft)
8 12 16 20 24
AWV008 AWV010 AWV012 AWV014
Height of Wall - Feet AWV016 AWV018 AWV020 AWV022
AWV024 AWV026 AWV028 AWV030
2.5%
2.0%
1.5% 5 Feet
1.0%
6 Feet
0.5%
0.0%
8 12 16 20 24
Height of Wall - Feet
6.0
% Capacity Reduction
6.0
5.0
% Power Increase
4.0
5.0
3.0
4.0
2.0
1.0
3.0 8 12 16 20
Distance Between Units
AWV008 AWV010 AWV012 AWV014
AWV016 AWV018 AWV020 AWV022
2.0
AWV024 AWV026 AWV028 AWV030
1.0
6 8 10 12
Figure 15: Case 3 - Power Increase
Full Load Power Increase
9.0
Distance Between Units (ft)
% Power Increase
AWV016 AWV018 AWV020 AWV022
AWV024 AWV026 AWV028 AWV030 7.0
6.0
5.0
Control
H D Panel
13.0 3.0
Distance from Wall to Unit (ft)
12.0 2.0
11.0 1.0
10.0 0.0
0 8 10 12 13 14
6.0 8.0
7.0
5.0
% Power Increase
6.0
4.0
0 10 20 30 40 50 5.0
0.0
0 8 10 12 13 14
Figure 20: Case 5 for AWV012-014 Figure 22: Case 5 for AWV020-024
Full Load Capacity Reduction (AWV012-014)
Full Load Capacity Reduction (AWV020-024)
6.0 6.0
5.0 5.0
% Capacity Reduction
% Capacity Reduction
4.0 4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0 0.0
0 8 10 12 13 14 0 8 10 12 13 14
Depth of Pit / Wall Height (ft) Depth of Pit / Wall Height (ft)
% Power Increase
6.0
% Power Increase
6.0
5.0 5.0
4.0 4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0 0.0
0 8 10 12 13 14 0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Depth of Pit / Wall Height (ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft
5.0
% Capacity Reduction
4.0
4.0
3.0 3.0
2.0 2.0
1.0 1.0
0.0
0.0
0 8 10 12 13 14
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Depth of Pit / Wall Height ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft
6.0 7.0
5.0 6.0
5.0
4.0
4.0
3.0
3.0
2.0 2.0
1.0 1.0
0.0
0.0
0 8 10 12 13 14
0 8 10 12 13 14
Depth of Pit / Wall Height (ft)
Depth of Pit / Wall Height (ft)
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Distance = 6 ft Distance = 8 ft Distance = 10 ft
Inlet
Isolation
P Vibration
Valves
Eliminators
Outlet
Flow
Switch
Drain
WELDED PIPE CONNECTIONS ARE NOT ALLOWED
BETWEEN THE STRAINER AND EVAPORATOR DUE
TO THE CHANCE OF SLAG ENTERING THE EVAPORATOR
Figure 25: Typical Chilled Water Piping, Shell and Tube Evaporator
VENT
3/8” PIPE PLUG LEAVING FLUID
TEMP. SENSOR
OUTLET
VIBRATION
ELIMINATOR
FLOW
INLET SWITCH
VALVED
PRESSURE
GAUGE GATE
VALVE
VIBRATION BALANCING
ELIMINATOR VALVE
DRAIN GATE
WATER VALVE FLOW
STRAINER
PROTECT ALL FIELD PIPING
AGAINST FREEZING
WELDED PIPE CONNECTIONS ARE NOT ALLOWED FLOW
BETWEEN THE STRAINER AND EVAPORATOR DUE TO THE
CHANCE OF SLAG ENTERING THE EVAPORATOR
Startup procedures should confirm that the chilled water piping 5 feet (1500 mm) of pipe length from the evaporator
system had been properly flushed out before being connected inlet connection and downstream of any welded
to the chiller vessel. connections (no welded connections between strainer
and evaporator).
All evaporators have OGS-type grooved water connections
(adhering to Standard AWWA C606) or optional flange • AWV models require a strainer as specified in Inlet
connections. The installing contractor must provide matching Strainer Guidelines on page 15.
mechanical connections. PVC and CPVC piping should not • A water flow switch must be installed in the horizontal
be used. Be sure water inlet and outlet connections match piping of the supply (evaporator outlet) water line to avoid
certified drawings and nozzle markings. evaporator freeze-up under low or no flow conditions.
See page 16 for more information.
CAUTION
• Purge air from the water system before unit startup to
To prevent damage to the evaporator and potential chiller provide adequate flow through the evaporator.
failure, a supply strainer is required in the inlet water piping
which connects to the evaporator. This strainer must be • Piping for units with brazed plate evaporators must have
installed prior to operation of the chilled liquid pumps. a drain and vent connection provided in the bottom of
the lower connection pipe and to the top of the upper
Field installed water piping to the chiller must include: connection pipe, respectively, see Figure 24. These
• A cleanable strainer installed at the water inlet to the evaporators do not have drain or vent connections due to
evaporator to remove debris and impurities before they their construction.
reach the evaporator. Install cleanable strainer within
• Adequate piping support, independent from the unit, The strainer is sized per Table 2 and has the pressure drop
to eliminate weight and strain on the fittings and shown in the Strainer Pressure Drop graph. Connection sizes
connections. are given in the Pressure Drop Data section on page 39.
It is recommended that the field installed water piping to the 2. A field-supplied strainer to same specifications as factory
chiller include: installed option.
• Thermometers at the inlet and outlet connections of the
Table 2: Strainer Sizing Data
evaporator.
Strainer Maximum Perforation Size Strainer Weight
• Water pressure gauge connection taps and gauges at
Size (in.) in. (mm) (lbs)
the inlet and outlet connections of the evaporator for
measuring water pressure drop. 6 0.063” (1/16”, 1.6 mm) 120
• Shutoff valves to isolate the unit from the piping during 6 120
unit servicing. 8 0.125” (1/8”, 3.2 mm) 220
• Minimum bends and changes in elevation to minimize 10 514
pressure drop.
• An expansion tank and regulating valve to maintain Figure 26: Strainer Pressure Drop
adequate water pressure. Tank becomes required
for closed loop systems based on water volume and
temperature ranges.
• Vibration eliminators in both the supply and return water
lines to reduce transmissions to the building.
• Flushing the system water piping thoroughly before
making connections to the unit evaporator.
• Piping insulation, including a vapor barrier, helps prevent
condensation and reduces heat loss.
• Regular water analysis and chemical water treatment
for the evaporator loop is recommended immediately at
equipment startup.
WARNING
Daikin Applied recommends against the use of PVC and
CPVC piping for chilled water systems. In the event the pipe
is exposed to POE oil used in the refrigerant system, the pipe
can be chemically damaged and pipe failure can occur.
Installing Inlet Strainer (Field-installed Kit)
Inlet Strainer Guidelines The extension pipe is located adjacent to the evaporator with
the strainer then mounted to it. The strainer must be mounted
An inlet water strainer kit must be installed in the chilled water per manufacturer’s instruction with the arrows in the direction
piping within 5 feet of the evaporator inlet. Two paths are of flow; inlet and outlet are noted along with the arrows.
available to meet this requirement:
Use one grooved clamp to mount the extension pipe to the
1. A field-installed kit shipped loose with the unit is available evaporator and the second to mount the strainer to the pipe.
for all unit sizes and consists of: The clamps to mount the field piping to the strainer are field
• Y-type area strainer with 304 stainless steel perforated supplied. The piping and strainer must be supported to prevent
basket, Grooved pipe connections and strainer cap any stress on the evaporator nozzle.
—— a strainer with perforations no larger than 0.063”
(1/16”, 1.6 mm) diameter for AWV models with a
braze plate evaporator System Water Volume
—— a strainer with perforations no larger than 0.125” All chilled water systems need adequate time to recognize a
(1/8”, 3.2 mm) diameter for AWV models with a direct load change, respond to that load change and stabilize, without
expansion evaporator undesirable short cycling of the compressors or loss of control.
• Extension pipe with two couplings that may be used In air conditioning systems, the potential for short cycling
for gauges and sensors. The pipe provides sufficient usually exists when the building load falls below the minimum
clearance from the evaporator for strainer basket chiller plant capacity or on close-coupled systems with very
removal. small water volumes. Some of the things the designer should
consider when looking at water volume are the minimum
• ½-inch blowdown valve cooling load, the minimum chiller plant capacity during the low
• Two grooved clamps load period and the desired cycle time for the compressors.
Assuming that there are no sudden load changes and that water pumps. Use one of the following recommendations for
the chiller plant has reasonable turndown, a rule of thumb of additional protection:
“gallons of water volume equal to two to three times the chilled • If the unit will not be operated during the winter, drain
water gpm flow rate” is often used. A storage tank may have evaporator and chilled water piping and flush with
to be added to the system to reach the recommended system glycol. Drain and vent connections are provided on the
volume. Refer to Daikin Applied Chiller Application Guide, AG evaporator for this purpose.
31-003, for method of calculating “Minimum Chilled Water
Volume”. • Add a year-round glycol solution to the chilled water
system to provide freeze protection. Freeze point should
The water quality provided by the owner/occupant/operator/ be approximately 10°F (5.6°C) below minimum design
user to a chiller system should minimize corrosion, scale ambient temperature or 10°F (5.6°C) below the lowest
buildup, erosion, and biological growth for optimum efficiency design leaving water temperature, whichever is lower.
of HVAC equipment without creating a hazard to operating The use of glycol antifreeze is generally considered
personnel or the environment. Strainers must be used to the safest protection against freeze-up; however, it will
protect the chiller systems from water-borne debris. Daikin will reduce the performance of the unit, depending on the
not be responsible for any water-borne debris damage or water concentration. Take this into consideration during initial
side damage to the chiller heat exchangers due to improperly system design and selection. On glycol applications, a
treated water. minimum fluid concentration should be based on Burst
Water systems should be cleaned and flushed prior to chiller Protection limits.
installation. Water testing and treatment should be verified • The field addition of thermostatically controlled heat
during initial chiller installation/commissioning and maintained tracing and insulation to exposed piping, dependent on
on a continuous basis by water treatment professionals (see power availability.
Limited Product Warranty). • Continuous circulation of water through the chilled water
CAUTION piping and evaporator, with ability to control temperature
The improper use of detergents, chemicals, and additives within chiller safety limits. (Dependent on power
in the chiller system water may adversely affect chiller availability).
performance and potentially lead to repair costs not covered • The evaporator immersion heater is factory-wired to the
by warranty. Any decision to use these products is at the 115-volt circuit in the control box. This power can be
discretion of the owner/occupant/operator/user as such they supplied from a separate source, or it can be supplied
assume full liability/responsibility for any damage that may from the control circuit. Operation of the heater cable
occur due to their use. is automatic through the fluid sensing thermostat that
energizes the evaporator heater cable for protection
against freeze-up. Unless the evaporator is drained in
Flow Switch the winter, the disconnect switch to the evaporator heater
A flow switch must be included in the chilled water system must be closed. Conversely, do not apply heat to the
to prove that there is adequate water flow to the evaporator evaporator if it is drained.
before the unit can start, or to shut down the unit if water flow is
interrupted. A solid state, thermal dispersion flow switch that is Chilled Water Pump
factory-mounted in the chiller leaving water nozzle and factory-
wired is available. A field-installed version is also available as It is important that the chilled water pumps be wired to, and
an option. controlled by, the chiller’s microprocessor. The chiller controller
has the capability to selectively send the signal to a pump
Installation should be per manufacturer’s instructions included relay (by others) to start pump A or B or automatically alternate
with the switch. Flow switches should be calibrated to shut off pump selection and also has standby operation capability.
the unit when operated below the minimum flow rate for the The controller will energize the pump whenever at least one
unit. Flow switch installation and calibration is further discussed circuit on the chiller is enabled to run, whether there is a
on page 84. call for cooling or not. This helps ensure proper unit startup
sequence. To help prevent evaporator freeze-up, the pump
will also be turned on when the water temperature is equal to
Evaporator Freeze Protection or goes below the Freeze Set Point for at least three seconds.
Evaporator freeze-up can be a concern in the application of Connection points are shown in the Field Wiring Diagrams on
air-cooled water chillers in areas experiencing below freezing page 19 and page 20.
temperatures. To protect against freeze-up, insulation and an
CAUTION
electric immersion heater are furnished with the evaporator.
This helps protect the evaporator down to -20°F (-29°C) Adding glycol or draining the system is the recommended
ambient air temperature. Although the evaporator is equipped method of freeze protection. If the chiller does not have
with freeze protection, it does not protect water piping external the ability to control the pumps and the water system is
to the unit or the evaporator itself if there is a power failure or not drained in temperatures below freezing, catastrophic
heater burnout, or if the chiller is unable to control the chilled evaporator failure may occur.
CAUTION
If the temperature of where the chiller is located is expected to
exceed 130°F (54.4°C), then the refrigerant must be removed.
POWER BLOCK
CIRCUIT BREAKER OR
(BY OTHERS) DISCONNECT SWITCH
L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
OR CIRCUIT 1
L3 T3
DISCONNECT
(BY OTHERS)
MQ
17 N
115 FUSE OPTIONAL
Q12 VAC 20A for 2KVA FIELD SUPPLIED
MQ 30A for 3KVA CONTROL POWER
12 120 VAC
(BY OTHERS)
OPEN Q12 IF SUPPLY IS SEPARATE 120 VAC SOURCE
M5
M5
21
28 120 VAC
CHWR1 ** USE DRY CONTACTS ONLY, SEE NOTE 2
EVAP. WATER (BY OTHERS) MODE SWITCH
PUMP RELAY No. 1 EVAP. WATER PUMP RELAY IF MODE SWITCH IS USED, REMOVE
(BY OTHERS) 120VAC @ 0.25AMP MAX M5 LEAD 322 BETWEEN M5-21 AND MS-10.
MQ
57
17 N (735)
(718)
OFF TIME
M5 CLOCK
M5 58
** USE DRY CONTACTS ONLY, SEE NOTE 2 AUTO
49 120 VAC REMOTE
CHWR2 IF REMOTE SWITCH IS USED, SWITCH
EVAP. WATER (BY OTHERS)
(BY OTHERS) REMOVE MECHANICAL JUMPER ON
PUMP RELAY No. 2
EVAP. WATER PUMP RELAY M5 BETWEEN M5 TERMIONALS 58 & 59.
(BY OTHERS)
120VAC @ 0.25AMP MAX 59
MQ MANUAL (737)
17 N
(830)
(BY OTHERS)
120VAC @ 0.25AMP MAX M5
26 120 VAC
MQ 5
17 N ** USE DRY CONTACTS ONLY, SEE NOTE 2
(721) EXTERNAL
IF EXTERNAL ALARM IS USED, REMOVE ALARM
M5 LEAD 402 BETWEEN M5 TERMINALS 5 & 15
15
(828)
M5 BC1
61
FOR RAPID
BACKUP
** USE DRY CONTACTS ONLY, SEE NOTE 2 RESTORE OPTION
CHILLER
ONLY
M5
62 (856)
(858)
M5
35 +
4-20 mA
SETPOINT OVERRIDE
(BY OTHERS)
M5
_
36
(720)
M5
38 +
4-20 mA
DEMAND LIMIT
(BY OTHERS)
M5
_
37
(833)
M5
FLow Switch Contacts
8 M
(735)
23 DI2 TO/FROM BAS
CLA (CUSTOMER
LON
CLB CONNECTION)
NOTE: For Factory Supplied Thermal 910170645_1RC
Dispersion Flow Switch wiring, see wiring GND CONNECT TO GROUND
AT ONE END ONLY.
instruction in Kit. NOTE:
1) ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1 WIRING
SYSTEM WITH CONDUCTOR RATED
600 VOLTS.
2)**=USE "DRY CONTACTS" ONLY.
DO NOT SUPPLY FIELD POWER TO
THIS CIRCUIT.
3)DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
POWER BLOCK
CIRCUIT BREAKER OR
(BY OTHERS) DISCONNECT SWITCH
L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR(S)
SOURCE AND FAN MOTORS
OR CIRCUIT 1
L3 T3
L1 T1
3 PHASE TO
POWER L2 T2 COMPRESSOR
SOURCE AND FAN MOTORS
CIRCUIT 2
L3 T3
M5
M5
21
28 120 VAC
CHWR1 ** USE DRY CONTACTS ONLY, SEE NOTE 2
EVAP. WATER (BY OTHERS) MODE SWITCH
PUMP RELAY No. 1 EVAP. WATER PUMP RELAY IF MODE SWITCH IS USED, REMOVE
(BY OTHERS) 120VAC @ 0.25AMP MAX M5 LEAD 322 BETWEEN M5-21 AND MS-10.
MQ
57
17 N (735)
(718)
OFF TIME
M5 CLOCK
M5 58
** USE DRY CONTACTS ONLY, SEE NOTE 2 AUTO
49 120 VAC REMOTE
CHWR2 IF REMOTE SWITCH IS USED, SWITCH
EVAP. WATER (BY OTHERS)
(BY OTHERS) REMOVE MECHANICAL JUMPER ON
PUMP RELAY No. 2
EVAP. WATER PUMP RELAY M5 BETWEEN M5 TERMIONALS 58 & 59.
(BY OTHERS)
120VAC @ 0.25AMP MAX 59
MQ MANUAL (737)
17 N
(830)
(BY OTHERS)
120VAC @ 0.25AMP MAX M5
26 120 VAC
MQ 5
FOR RAPID
BACKUP
** USE DRY CONTACTS ONLY, SEE NOTE 2 RESTORE OPTION
CHILLER
ONLY
M5
62 (856)
(858)
M5
35 +
4-20 mA
SETPOINT OVERRIDE
(BY OTHERS)
M5
_
36
(720)
M5
38 +
4-20 mA
DEMAND LIMIT
(BY OTHERS)
M5
_
37
(833)
M5
FLow Switch Contacts
8 M
(735)
23 DI2 TO/FROM BAS
CLA (CUSTOMER
LON
CLB CONNECTION)
NOTE: For Factory Supplied Thermal
Dispersion Flow Switch wiring, see wiring GND CONNECT TO GROUND
AT ONE END ONLY.
910170646_1RC
instruction in Kit.
NOTE:
1) ALL FIELD WIRING TO BE
INSTALLED AS NEC CLASS 1 WIRING
SYSTEM WITH CONDUCTOR RATED
600 VOLTS.
2)**=USE "DRY CONTACTS" ONLY.
DO NOT SUPPLY FIELD POWER TO
THIS CIRCUIT.
3)DO NOT SUPPLY FIELD POWER TO
24VAC OR 120VAC CONTROL CIRCUITS.
PACKAGE CHILLER
www.DaikinApplied.com
CONDENSER
AIR
ASSEMBLY
FLOW
OIL PRESS.
DISCHARGE SCHRADER DISCHARGE TRANSDUCER
TUBING VALVE TRANSDUCER
SHUT-OFF WITH SCHRADER SHUT-OFF
VALVE VALVE VALVE
(OPTIONAL)
BALL CHARGING
VALVE VALVE RELIEF
VALVE
AIR
FLOW SUCTION
DISCHARGE TRANSDUCER
OUTSIDE AIR TEMP. SENSOR F3/F4
TEMPERATURE COMPRESSOR
(WAA)
21
LIQUID SUCTION
INJECTION TUBING
TUBING
(OPTIONAL)
STRAINER SOLENOID
BALL
VALVE
LIQUID VALVE
TUBING
WATER OUT
WATER IN
(WOE) (WIE)
TEMP. SENSOR TEMP. SENSOR
SOLENOID
FILTER CHARGING SCHRADER VALVE SCHRADER EXPANSION CHARGING DX EVAPORATOR RELIEF SUCTION
DRYER VALVE VALVE (OPTIONAL) VALVE VALVE VALVE VALVE TEMP. SENSOR
NOTE:
PIPING SHOWN FOR ONE SYSTEM OF UNIT.
UNIT HAS TWO INDEPENDANT SYSTEMS.
Figure 29: Representative Refrigerant Diagram - Packaged Unit With Shell & Tube Evaporator Without Optional
Figure 30: Representative Refrigerant Diagram - Packaged Unit With Shell & Tube Evaporator With Optional Economizer
Figure 31: Representative Refrigerant Diagram - Packaged Unit With Braze Plate Evaporator Without Optional Economizer
PACKAGE CHILLER
W/O ECONOMIZER
Representative Refrigerant Diagram - Packaged Unit With Braze Plate Evaporator With Optional Economizer
is supplied with refrigerant specialties kits. Field to wire in the control cabinet. Use water tight boxes at splice
directly into compressor terminal box terminal block: locations that may be exposed to weather. Individual
connections must be soldered and shrink wrapped.
• Compressor #1: (LSV-1) wire 740-1A (red) wires
An outer shrink wrap is also required and should be
into compressor #1 terminal box terminal block at
wrapped with electical tape to be made more water
TB1-2-9. Wire 740-1B (white) wires to TB1-2-10.
resistant. The expansion valve wiring cannot run in
• Compressor #2: (LSV-2) wire 740-2A (red) wires conduit with other wiring that is over 24 Volts AC.
into compressor #2 terminal box terminal block at
TB2-2-9. Wire 740-2B (white) wires to TB2-2-10. 6. A flow switch must be installed in the leaving chilled
water line per manufacturer’s instructions and wired to
2. Two evaporator water temperature sensors with 100
terminals 8 and 23 on terminal block M5 in the chiller
feet of cable coiled up and attached to the unit base
control panel. See Unit Field Wiring Diagrams - Figure 27
for extension to the evaporator and insertion in fittings
and Figure 28.
located on the side of the inlet and outlet nozzles.
7. Do not reduce the wire lengths of factory wiring, except
3. One suction line refrigerant temperature sensor per as specifically noted in item #5.
circuit with 100 feet of cable coiled up and attached to
the unit base for extension to the evaporator.
Piping Layout
4. One suction line pressure transducer per circuit with 100
Figure 33 shows the piping layout for one of the two refrigerant
feet of cable coiled up and attached to the unit base for
circuits for AWV units with a remote evaporator with and
extension to the evaporator.
without the optional economizer circuit. The outdoor unit, the
5. The electronic expansion valve has a 30 foot long cable evaporator, and a kit of refrigerant components are shipped
attached and can be used when the outdoor unit is less as separate pieces for field mounting, wiring, and piping. The
than 30 feet away. For lengths greater than 30 feet but suction shutoff valve is standard on remote evaporator units.
no more than 200 feet, cut the factory supplied 22 AWG All components between the “Field Connection Points” should
cable/wire as close to the M12 connector (connects to be located as close to the evaporator as possible.
the EXV Stepper Motor) as possible to make a splice
using 14 AWG Wire Gauge size, reference Figure 32. Note: Field insulation of the suction lines and the liquid line on
NOTE: 14 AWG will use Belden part number 83754 or circuits with economizers is required. The outdoor unit will have
equivalent. For distances greater than 200 feet, 12 AWG a refrigerant charge equal to that of a packaged unit pumped
wire is recommended (Belden part number 83804 or down into the condenser. Any additional charge of refrigerant
equivalent). and oil required by the field piping is supplied by the customer.
The location and size of the refrigerant connections are shown
The inner foil shield and the outer Braid Shield should
on dimensional drawings available from a Daikin Applied sales
be grounded as close as possible to the EXV module
representative.
Figure 32: Remote EXV Field Wiring
NOTE:
PIPING SHOWN FOR ONE SYSTEM OF UNIT.
UNIT HAS TWO INDEPENDANT SYSTEMS.
REMOTE CHILLER
WITH OPTIONAL ECONOMIZER
Table 5: Sizing Guidelines for Horizontal or Downflow Suction Lines and Liquid Lines
Recommended Horizontal or Downflow Suction Line Size Recommended Liquid Line Size
Nominal Nominal
Circuit Estimated Line Suction Line Circuit Estimated Line Liquid Line Size
Capacity TEL (ft) Line Material Size (Inches) Capacity TEL (ft) Line Material (Inches)
65 50 Copper 3 5/8 65 50 Copper 1 5/8
90 50 Copper 3 5/8 90 50 Copper 1 5/8
115 50 Copper 3 5/8 115 50 Copper 1 5/8
140 50 Copper 4 1/8 140 50 Copper 1 5/8
165 50 Copper 4 1/8 165 50 Copper 2 1/8
190 50 Copper 4 1/8 190 50 Copper 2 1/8
215 50 Copper 5 1/8 215 50 Copper 2 1/8
240 50 Copper 5 1/8 240 50 Copper 2 1/8
265 50 Copper 5 1/8 265 50 Copper 2 1/8
65 75 Copper 3 5/8 65 75 Copper 1 5/8
90 75 Copper 3 5/8 90 75 Copper 1 5/8
115 75 Copper 4 1/8 115 75 Copper 2 1/8
140 75 Copper 4 1/8 140 75 Copper 2 1/8
165 75 Copper 5 1/8 165 75 Copper 2 1/8
190 75 Copper 5 1/8 190 75 Copper 2 1/8
215 75 Copper 5 1/8 215 75 Copper 2 1/8
240 75 Copper 5 1/8 240 75 Copper 2 1/8
265 75 Copper 5 1/8 265 75 Copper 2 5/8
65 100 Copper 3 5/8 65 100 Copper 1 5/8
90 100 Copper 3 5/8 90 100 Copper 1 5/8
115 100 Copper 4 1/8 115 100 Copper 2 1/8
140 100 Copper 5 1/8 140 100 Copper 2 1/8
165 100 Copper 5 1/8 165 100 Copper 2 1/8
190 100 Copper 5 1/8 190 100 Copper 2 1/8
215 100 Copper 5 1/8 215 100 Copper 2 5/8
240 100 Copper 6 1/8 240 100 Copper 2 5/8
265 100 Copper 6 1/8 265 100 Copper 2 5/8
65 125 Copper 3 5/8 65 125 Copper 1 5/8
90 125 Copper 4 1/8 90 125 Copper 1 5/8
115 125 Copper 4 1/8 115 125 Copper 2 1/8
140 125 Copper 5 1/8 140 125 Copper 2 1/8
165 125 Copper 5 1/8 165 125 Copper 2 1/8
190 125 Copper 5 1/8 190 125 Copper 2 5/8
215 125 Copper 6 1/8 215 125 Copper 2 5/8
240 125 Copper 6 1/8 240 125 Copper 2 5/8
265 125 Copper 6 1/8 265 125 Copper 2 5/8
Table 6: Sizing Guidelines for Horizontal or Downflow Suction Lines and Liquid Lines
Recommended Horizontal or Downflow Suction Line Size Recommended Liquid Line Size
Nominal Nominal
Circuit Estimated Line Suction Line Circuit Estimated Line Liquid Line Size
Capacity TEL (ft) Line Material Size (Inches) Capacity TEL (ft) Line Material (Inches)
65 150 Copper 3 5/8 65 150 Copper 1 5/8
90 150 Copper 4 1/8 90 150 Copper 2 1/8
115 150 Copper 4 1/8 115 150 Copper 2 1/8
140 150 Copper 5 1/8 140 150 Copper 2 1/8
165 150 Copper 5 1/8 165 150 Copper 2 1/8
190 150 Copper 6 1/8 190 150 Copper 2 5/8
215 150 Copper 6 1/8 215 150 Copper 2 5/8
240 150 Copper 6 1/8 240 150 Copper 2 5/8
265 150 Copper 6 1/8 265 150 Copper 2 5/8
65 175 Copper 4 1/8 65 175 Copper 1 5/8
90 175 Copper 4 1/8 90 175 Copper 2 1/8
115 175 Copper 4 1/8 115 175 Copper 2 1/8
140 175 Copper 5 1/8 140 175 Copper 2 1/8
165 175 Copper 5 1/8 165 175 Copper 2 5/8
190 175 Copper 6 1/8 190 175 Copper 2 5/8
215 175 Copper 6 1/8 215 175 Copper 2 5/8
240 175 Copper 6 1/8 240 175 Copper 2 5/8
265 175 Copper 6 1/8 265 175 Copper 2 5/8
65 200 Copper 4 1/8 65 200 Copper 1 5/8
90 200 Copper 4 1/8 90 200 Copper 2 1/8
115 200 Copper 4 1/8 115 200 Copper 2 1/8
140 200 Copper 5 1/8 140 200 Copper 2 1/8
165 200 Copper 5 1/8 165 200 Copper 2 5/8
190 200 Copper 6 1/8 190 200 Copper 2 5/8
215 200 Copper 6 1/8 215 200 Copper 2 5/8
240 200 Copper 6 1/8 240 200 Copper 2 5/8
265 200 Copper 6 1/8 265 200 Copper 3 1/8
65 225 Copper 4 1/8 65 225 Copper 2 1/8
90 225 Copper 4 1/8 90 225 Copper 2 1/8
115 225 Copper 4 1/8 115 225 Copper 2 1/8
140 225 Copper 5 1/8 140 225 Copper 2 5/8
165 225 Copper 5 1/8 165 225 Copper 2 5/8
190 225 Copper 6 1/8 190 225 Copper 2 5/8
215 225 Copper 6 1/8 215 225 Copper 2 5/8
240 225 Copper 6 1/8 240 225 Copper 3 1/8
265 225 Copper 6 1/8 265 225 Copper 3 1/8
Table 7: Sizing Guidelines for Horizontal or Downflow Suction Lines and Liquid Lines
Recommended Horizontal or Downflow Suction Line Size Recommended Liquid Line Sizes
Nominal Nominal
Circuit Estimated Line Suction Line Circuit Estimated Line Liquid Line Size
Capacity TEL (ft) Line Material Size (Inches) Capacity TEL (ft) Line Material (Inches)
65 250 Copper 4 1/8 65 250 Copper 2 1/8
90 250 Copper 4 1/8 90 250 Copper 2 1/8
115 250 Copper 4 1/8 115 250 Copper 2 1/8
140 250 Copper 5 1/8 140 250 Copper 2 5/8
165 250 Copper 5 1/8 165 250 Copper 2 5/8
190 250 Copper 6 1/8 190 250 Copper 2 5/8
215 250 Copper 6 1/8 215 250 Copper 2 5/8
240 250 Copper 6 1/8 240 250 Copper 3 1/8
265 250 Copper 6 1/8 265 250 Copper 3 1/8
65 275 Copper 4 1/8 65 275 Copper 2 1/8
90 275 Copper 4 1/8 90 275 Copper 2 1/8
115 275 Copper 4 1/8 115 275 Copper 2 1/8
140 275 Copper 5 1/8 140 275 Copper 2 5/8
165 275 Copper 5 1/8 165 275 Copper 2 5/8
190 275 Copper 6 1/8 190 275 Copper 2 5/8
215 275 Copper 6 1/8 215 275 Copper 3 1/8
240 275 Copper 6 1/8 240 275 Copper 3 1/8
265 275 Copper 6 1/8 265 275 Copper 3 1/8
65 300 Copper 4 1/8 65 300 Copper 2 1/8
90 300 Copper 4 1/8 90 300 Copper 2 1/8
115 300 Copper 4 1/8 115 300 Copper 2 1/8
140 300 Copper 5 1/8 140 300 Copper 2 5/8
165 300 Copper 5 1/8 165 300 Copper 2 5/8
190 300 Copper 6 1/8 190 300 Copper 2 5/8
215 300 Copper 6 1/8 215 300 Copper 3 1/8
240 300 Copper 6 1/8 240 300 Copper 3 1/8
265 300 Copper 6 1/8 265 300 Copper 3 1/8
Table 8: Alternate Sizing Guidelines for Horizontal or Table 9: Sizing Guidelines for Upflow Lines
Downflow Suction Lines - Steel Recommended Upflow Suction Line Size
Recommended Horizontal or Downflow Suction Line Size
Nominal Circuit Suction Line Estimated Line
Nominal Circuit Estimated Line Suction Line Capacity Line Material Size (Inches) TEL (ft)
Capacity TEL (ft) Line Material Size (Inches)
65 Copper 3 5/8 50
240 100 Steel 6
90 Copper 3 5/8 50
265 100 Steel 6
115 Copper 3 5/8 50
215 125 Steel 6
140 Copper 4 1/8 50
240 125 Steel 6
165 Copper 4 1/8 50
265 125 Steel 6
190 Copper 5 1/8 50
190 150 Steel 6
215 Copper 5 1/8 50
215 150 Steel 6
240 Copper 5 1/8 50
240 150 Steel 6
265 Copper 5 1/8 50
265 150 Steel 6
65 Copper 3 5/8 75
190 175 Steel 6
90 Copper 3 5/8 75
215 175 Steel 6
115 Copper 3 5/8 75
240 175 Steel 6
140 Copper 4 1/8 75
265 175 Steel 6
165 Copper 4 1/8 75
190 200 Steel 6
190 Copper 5 1/8 75
215 200 Steel 6
215 Copper 5 1/8 75
240 200 Steel 6
240 Copper 5 1/8 75
265 200 Steel 6
265 Copper 5 1/8 75
190 225 Steel 6
215 225 Steel 6
240 225 Steel 6
265 225 Steel 6
190 250 Steel 6
215 250 Steel 6
240 250 Steel 6
265 250 Steel 6
190 275 Steel 6
215 275 Steel 6
240 275 Steel 6
265 275 Steel 6
190 300 Steel 6
215 300 Steel 6
240 300 Steel 6
265 300 Steel 6
NOTE: FOR STEEL LINES ONLY
For use in horizontal and down flow applications only where
the evaporator is at or below the chiller elevation.
Recommend schedule 40 steel pipe.
Carbon steel pipe shall be ASTM Standard A 53 Grade B,
Type E (electric resistance welded) or Type S (seamless); or
ASTM Standard A 106 Grade B (seamless). Standard A 53
Type F is not permitted.
Refrigeration piping design and fabrication should be in
accordance with the applicable sections of ASME B31.5 -
Refrigeration Piping and Heat Transfer Components for the
steel piping.
BLOCK-OFF
EVAPORATOR EV4027 WITH PLATES,
SPACERS, AND BOLTS
332532100 80 (M14 X 1.50 X 50MM LONG)
3.2
470
18.5
100
3.9 110
16 4.33
.63
2412 169
95.0 6.7 110
4.33
18
.7
ALL Ø0.25
COUPLINGS
303
11.9
455 EVAPORATOR 455
17.9 NAME PLATE 17.9 SHRADER FITTING 75 75
66 66 FOR REFRIGERANT 2.95 2.95
2.58 2.58 ASME/CRN PRESSURE (2)
1.625 IDS 1/4" NPTF NAME PLATE 1/4" NPTF
LIQUID FERRULE
PART # E44070016
FLANGE # E44060007
O RING # E44130152 INLET
OUTLET
1/2" NPTF
485 3000# HALF CPLG. 406 ASME/ CRN EVAPORATOR
NAME PLATE NAME PLATE
19.1 SENSOR WELL QTY 2 16.0
QTY 2
250 (SEE NOTE 9)
9.8
SUCTION O RING
# E44130201
168 C C
1/2" NPTF 120
10 6.63 PIPE QTY 2 463
4.7
.39 GROOVED 18.2
QTY 2 FEET MOUNTING
2123 270
83.6 10.6 528
18MM X 43MM 20.8
SLOTS
40 33 (QTY. 4)
60
1.57 1.3
2.36
60
2.36
60
2.4
SECTION C-C
572
22.5
138
5.43
64 16
100
2.5 .6
3.9
138
2360 195 5.43
92.9 7.7
12
.5
ALL Ø.25
COUPLINGS
DETAIL A
354
219 13.9
445 8.63 PIPE EVAPORATOR
17.5 GROOVED NAME PLATE 445 94 94
75 75 QTY 2 17.5 SHRADER FITTING 3.70 3.70
1/4" NPTF ASME/CRN FOR REFRIGERANT
3.0 3.0 NAME PLATE 1/4" NPTF PRESSURE (2)
60
2.4
SECTION C-C
4085 42
160.8 1.6 REF
3900 110
153.5 4.3
1950 BLOCK-OFF
76.8 WITH PLATES,
SPACERS, AND BOLTS
HEATER (M14 X 1.50 X 50MM LONG)
WIRES
EVAPORATOR EV5039
80
332532300 3.2
572 16 137.9
22.5 .63 5.43
100
3.9
137.9
5.43
64
2.5
3510 195
138.2 7.7
140 DETAIL A
1.625 IDS 5.5
LIQUID FERRULE SCHRADER FITTING
PART # E44070016 FOR REFRIGERANT
FLANGE # E44060007 219.2 PRESSURE (2)
EVAPORATOR
O RING # E44130152 635 8.63 PIPE NAME PLATE 354
25.0 GROOVED 635 13.9
75 75 QTY 2 25.0
ASME/CRN 94 94
2.95 2.95 1/4" NPTF NAME PLATE 3.70 3.70
1/4" NPTF
638
25.1
HEATER
1/2" NPTF 508 WIRES
ASME/ CRN EVAPORATOR
644 3000# HALF CPLG. 20.0
NAME PLATE NAME PLATE
25.4 QTY 2
SENSOR WELL
C C QTY 2 SUCTION
(SEE NOTE9) 120 O RING
1/2" NPTF 4.7 443
# E44136600
10 3283 QTY 2 262 17.4
.39 129.3 10.3 FEET MOUNTING
528
40 20.8
1.57
12
51 2X .5
2.01 51 ALL Ø.25
2.01 COUPLINGS
77 3300 150
3.0 129.9 5.9
HEATER WIRE 42
APPROX. LOCATION 1.6 REF
BLOCK-OFF WITH PLATES,
SPACERS, AND BOLTS
(M14 X 1.50 X 50MM LONG
100
3.9
2830 [235]
111.4 9.25 LIQUID AND SUCTION CAST HEAD
DETAILS ARE FOR REFERENCE ONLY
635
25.0
466 466 430
273 EVAPORATOR NAMEPLATE
18.3 10.7 PIPE 18.3 16.9
106 106 1/4" NPTF 362 GROOVED 362 106 106
4.2 4.2 ASME/CRN NAMEPLATE 14.3
QTY 2 14.3 QTY 2 4.16 4.16
1/2" NPTF
QTY 2
689 660 167
26.0 1/2" NPTF 6.57
27.1 3000# HALF CPLG
OUTLET QTY 2
357 INLET
14.1
Ø6.38 [162]
120 167
4.7 6.57
54 2123 189 SUCTION O RING
2.13 12 83.6 7.4 #E44136670
68
2X .5 SENSOR WELL
2.68 QTY 2
ALL Ø0.25
(18MM).71 X (43MM)1.69 (SEE NOTE 9)
COUPLINGS
SLOTS QTY 4
68
2.68 528 463
Ø2.125 IDS
LIQUID FERRULE 20.8 18.2
PART # E4470043 33
FLANGE # E44060009 1.3
O RING # E44130170
60
2.4
60
2.4
SECTION C-C
4145 42
163.2 REF 1.6 REF
BLOCK-OFF
95 3900 150 WITH PLATES,
3.7 153.5 5.9 SPACERS, AND BOLTS
HEATER (M14 X 1.50 X 50MM LONG)
WIRES
80 166.9
EVAPORATOR EV6639 14 6.57
3.2 .55
332532400 1950
76.8
664 166.9
26.1 6.57
99.8
3.9
162
6.38
INLET
20.1
OUTLET .8
688.9 1/2" NPTF 660 ASME/ CRN EVAPORATOR
NAME PLATE NAME PLATE
3000# HALF CPLG. 26.0
27.1 SENSOR WELL QTY 2
QTY 2
357 (SEE NOTE9)
14.1
C C
463 HEATER
1/2" NPTF 32.5 WIRES
QTY 2 120 18.2
1.3 MOUNTING FEET
4.7
10.5
3282 231 528
68 .41 2.125 IDS
LIQUID FERRULE 129.2 9.1 20.8
2.68
PART # E44070043
FLANGE # E44060009 SUCTION O RING
60 O RING # E44130170 # E44136670
68 2.36
2.68
DETAIL B
Dimensional Drawings
Figure 39: Reference Dimensional Drawing - 08 Fan to 14 Fan Configurations With Brazed Plate Evaporator
43.8
WATER
INLET / OUTLET
MINI CONTROL BOX
(ALL TURBOSCREW UNITS)
L1 / L2
L3 / L4 87.6
L5 / L6 (10, 12 & 14 FAN) DOES NOT INCLUDE
LIFTING LUGS
100.1
FIELD POWER ENTRY
AT BOTTOM OF BOX
Ø6.0 GROOVED
CONNECTION CG Y
37.21
13.00
CG Z
CG X
A (WATER INLET) 5.20 BASE
B (WATER OUTLET) RAIL WIDTH
TYP.
Z (BASE LENGTH)
2.60
TYP.
# OF L1 / L3 / L5 / M1 / M3 / M5 / M7 /
EVAP A B Z CG X CG Y CG Z
FANS L2 L4 L6 M2 M4 M6 M8
Figure 40: Reference Dimensional Drawing - 12 Fan and 14 Fan Configurations with Shell and Tube Evaporator
87.6
DOES NOT INCLUDE
LIFTING LUGS
100.1
WATER INLET
WATER CG Y
OUTLET
CG X
CG Z 5.2 BASE
B A FIELD POWER ENTRY FROM
BOTTOM FOR SMALL RAIL WIDTH
Z (BASE LENGTH) CONTROL BOX (SHOWN),
FROM SIDE FOR LARGE
CONTROL BOX,
M7 / M8 M5 / M6 M3 / M4 M1 / M2
2.60
D RH
(OPTIONAL
RH WATER D LH .750
CONN.) (STANDARD MOUNTING HOLE SIZE
TYP
LH WATER
CONN.)
2.60
L5 / L6 L3 / L4 L1 / L2
Figure 41: Reference Dimensional Drawing - 16 Fan - 30 Fan Configurations with Shell and Tube Evaporator
87.6
DOES NOT INCLUDE
LIFTING LUGS
100.1
WATER INLET
WATER CG Y
OUTLET
CG X
CG Z
5.2 BASE
B A FIELD POWER ENTRY FROM
BOTTOM FOR SMALL RAIL WIDTH
Z (BASE LENGTH) CONTROL BOX (SHOWN),
FROM SIDE FOR LARGE
CONTROL BOX,
M9 / M10 M7 / M8 M5 / M6 M3 / M4 M1 / M2
2.60
D RH
(OPTIONAL
RH WATER D LH .750 MOUNTING HOLE SIZE
CONN.) (STANDARD TYP
LH WATER
CONN.)
2.60
L7 / L8 L5 / L6 L3 / L4 L1 / L2
NOTE: Water connection sizes are given in Pressure Drop Data starting on page 39.
“L” refers to Lifting Eye Point locations. “M” refers to Mounting Point locations.
Table 12: Unit Dimensions by Configuration with Shell and Tube Evaporator
# OF L1 / L3 / L5 / L7 / M1 / M3 / M5 / M7 / M9 /
EVAP A B C D LH D RH Z CG X CG Y CG Z
FANS L2 L4 L6 L8 M2 M4 M6 M8 M10
12 EV 4027 148.4 95.0 17.0 31.9 55.7 258.1 23 121.3 199.6 15 80.3 135.3 200.5
EV 4027 169.7 95.0 17.0 31.9 55.7 296 N/A N/A
14 23 146.1 249.3 15 80.3 160.2 249.3
EV 5027 171.1 92.9 21.2 29.9 57.8 296
EV 4027 169.7 95.0 17.0 31.9 55.7 334
16 EV 5027 171.1 92.9 21.2 29.9 57.8 334 23 78 190 319.3 15 80.3 135.3 200.5 290.5
EV 5039 171.1 138.2 21.2 29.9 57.8 334
EV 4027 169.7 95.0 17.0 31.9 55.7 371.7
18 EV 5027 171.1 92.9 21.2 29.9 57.8 371.7 23 78 190 313 15 80.3 135.3 200.5 310
Isolator Information
R4
4.63
3.87
VM&C
VM&C
R4
1.63
.38
M10 M8 M6 M4 M2
NOTE: Flow rates and pressure drops reflect water only and do not
apply to glycol solutions.
20 20
PD PD
(ft) (ft)
10 10
0 0
0 100 200 300 400 500 600 0 200 400 600 800 1000
Flow Rate (gpm) Flow Rate (gpm)
20 30
20
PD
PD
(ft) (ft)
10
10
0
0 0 100 200 300 400 500 600 700
0 100 200 300 400 500 600 700
Flow Rate (gpm)
Flow Rate (gpm)
30
40
30
20
PD
PD (ft)
(ft)
20
10
10
0 0
0 100 200 300 400 500 600 700 800 0 200 400 600 800 1000 1200 1400
30 40
30
20
PD
PD (ft)
(ft) 20
10
10
0
0 100 200 300 400 500 600 700 800 0
0 100 200 300 400 500 600 700 800 900
Flow Rate (gpm) Flow Rate (gpm)
30
20
PD PD
(ft) (ft)
20
10
10
0 0
0 200 400 600 800 1000 0 200 400 600 800 1000 1200 1400
Flow Rate (gpm) Flow Rate (gpm)
50
40
PD 30
(ft)
20
10
0
0 200 400 600 800 1000 1200
Evaporator EV66391616/09
50
40
PD 30
(ft)
20
10
0
0 200 400 600 800 1000 1200 1400
40
30
PD
(ft)
20
10
0
0 200 400 600 800 1000 1200 1400 1600 1800
Controller Operation
Compressor Compressor
VFD 1 VFD 2
Modbus
Peripheral Bus
DC
Fan
DC
Fan
DC
Fan ... DC
Fan
Modbus
DC Fan Controller
NOTE: Graphic shows typical chiller controller arrangement; individual chiller configurations will be as ordered.
Table 15: Analog Outputs - Fan VFD DO1 Compressor Run Compressor Off Compressor
Command On
# Description Output Signal DO2 Liquid Line SV Solenoid Closed Solenoid Open
X5 Fan VFD #1 0-10 Vdc DO3 Liquid Injection SV Solenoid Closed Solenoid Open
X6 Fan VFD #2 0-10 Vdc DO4 100% VR SV Solenoid Closed Solenoid Open
DO5 75% VR SV Solenoid Closed Solenoid Open
Table 16: Digital Inputs DO6 50% VR SV Solenoid Closed Solenoid Open
# Description Signal Off Signal On X8 Economizer SV Solenoid Closed Solenoid Open
DI1 GFP Relay 1 Fault No Fault
DI2 Evaporator Flow Switch No Flow Flow EEXV Modules - Circuit #1 and #2
DI3 Mode Switch Cool mode Ice mode
DI4 Remote Switch Unit disable Unit enable Table 20: Digital Inputs
DI5 Unit Switch Unit disable Unit enable # Description Signal Off Signal On
DI6 Emergency Stop Unit off Unit enable DI1 Mechanical Low Pressure Switch Fault No Fault
X8 GFP Relay 2 Fault No Fault
Table 21: Digital Outputs
Table 17: Digital Outputs # Description Output OFF Output ON
# Description Output OFF Output ON DO1 Economizer SV Solenoid Closed Solenoid Open
Driver Description
A Evaporator EXV Circuit #1
B Evaporator EXV Circuit #2
Driver Description
A Economizer EXV Circuit #1
B Economizer EXV Circuit #2
Alarm/Limit Module
Table 26: Analog Inputs
RapidRestore® Module
Table 29: Digital Inputs
Set Points
The following parameters are remembered during power off (permanent memory), are factory set to the Default value, and can be
adjusted to any value in the Range column. Read and write access to these set points is determined by the Global HMI (Human
Machine Interface) Standard Specification.
Table 35: Cool LWT Set Point Ranges Table 37: Low Ambient Lockout
Evaporator Glycol Range Condenser Fan VFD Range
No 4.44 to 21.12°C (40 to 70°F) None 0 to 15°C (32 to 59°F)
Yes -3.89 to 21.12°C (25 to 70°F) 1st Fan VFD, All Fan VFD -28.89 to 15°C (-20 to 59°F)
NOTE: Unless Low Ambient Lockout is disabled.
Table 36: Evaporator Fluid Freeze
Evaporator Glycol Range Table 38: Low Evaporator Pressure Unload
No 1.1 to 6°C (34 to 42.8°F) Evaporator Glycol Range
Yes -28.89 to 6°C (-20 to 42.8°F) No 150 to 510 kPa (21.8 to 74 psi)
Yes 0 to 510 kPa (0 to 74 psi)
Table 40: Fan VFD Configuration = None Table 41: Fan VFD Configuration = 1st Fan VFD
Set Point Default Value Loaded Set Point Default Value Loaded
Fan Stage Up Deadband 0 4°C (7.2°F) Fan Stage Up Deadband 0 2.5°C (4.5°F)
Fan Stage Up Deadband 1 5°C (9°F) Fan Stage Up Deadband 1 2.5°C (4.5°F)
Fan Stage Up Deadband 2 5.5°C (9.9°F) Fan Stage Up Deadband 2 4°C (7.2°F)
Fan Stage Up Deadband 3 6°C (10.8°F) Fan Stage Up Deadband 3 5°C (9°F)
Fan Stage Up Deadband 4 6.5°C (11.7°F) Fan Stage Up Deadband 4 4°C (7.2°F)
Fan Stage Up Deadband 5 6.5°C (11.7°F) Fan Stage Up Deadband 5 4°C (7.2°F)
Fan Stage Down Deadband 1 10°C (18°F) Fan Stage Down Deadband 1 4°C (7.2°F)
Fan Stage Down Deadband 2 8°C (14.4°F) Fan Stage Down Deadband 2 3.5°C (6.3°F)
Fan Stage Down Deadband 3 5.5°C (9.9°F) Fan Stage Down Deadband 3 3°C (5.4°F)
Fan Stage Down Deadband 4 4°C (7.2°F) Fan Stage Down Deadband 4 2.5°C (4.5°F)
Fan Stage Down Deadband 5 4°C (7.2°F) Fan Stage Down Deadband 5 2.5°C (4.5°F)
Unit Functions
A pulldown rate is calculated by inverting the slope value and Table 43: Unit Mode Combinations
limiting to a minimum value of 0°C/min. Available Control
Mode BAS
Modes Source Unit Mode
Switch Request
Unit Set Point Set Point
Cool - - - Cool
Capacity Cool/Ice Local Off - Cool
The unit capacity is the total of the circuit target capacities Cool/Ice Local On - Ice
divided by the number of circuits. Cool/Ice Network - Cool Cool
Cool/Ice Network - Ice Ice
Total Power Ice - - Ice
An estimate of the total unit power is calculated by adding the NOTE: A “-” Indicates that the value is ignored.
power estimate for each circuit. All values are in units of kW.
Glycol Configuration
Unit Enable If the Available Modes set point is set to an option “w/Glycol,”
then Evaporator Glycol set point must be selected as Yes.
Enabling and disabling the chiller is accomplished using set
Glycol operation opens up the ranges for several set points to
points and inputs to the chiller. The Unit Switch, Remote Switch
allow lower values.
Input, and Unit Enable Set Point are all required to be On/
Enable for the unit to be enabled when the control source is
set to Local. The same is true if the control source is set to
Network, with the additional requirement that the BAS Enable
set point be Enable.
Table 42: Enable Combinations
Control Remote Unit BAS
Unit Unit
Source Switch Enable Enable
Switch State
Set Point Input Set Point Set Point
Off - - - - Disable
- - - Disable - Disable
- - Disable - - Disable
On Local Enable Enable - Enable
- Network - - Disable Disable
On Network Enable Enable Enable Enable
NOTE: A “-” indicates that the value is ignored.
All of the methods for disabling the chiller, discussed in this
section, will cause a normal shutdown of any running circuits.
When the controller is powered up, the Unit Enable Set Point
will be initialized to Disable if the Unit Enable Initial Set Point is
set to Disable. The chiller will remain disabled after powering
up until the Unit Enable Set Point is set to Enable.
Unit Control States T1 - Off to Auto. All of the following are required:
3
• Unit Mode = Ice and LWT target is reached
• Unit alarm requiring normal shutdown is active
• Low Ambient Lockout is active
Unit Status
Unit Status is displayed to indicate the general condition of the unit. The following table lists the text displayed for each unit status
and the conditions that enable each status. If more than one status is enabled at the same time, the highest numbered status
overrides the others and is displayed.
the unit will remain in the off state until the lockout has cleared.
This condition will clear when OAT rises to the lockout set point
plus 2.5°C (4.5°F).
RUN START
Lockout Only Operation 5
If OAT drops below the low ambient lockout set point and
any circuits are running, then those circuits will be allowed
to remain running and the unit will not enter the low ambient T1 - Off to Start - All of the following are required:
lockout condition. Circuits that are not running will enter a • Unit state = Auto
circuit level lockout condition when OAT drops below the
• Freeze protection started
lockout set point. This condition will clear at the circuit level
when OAT rises to the lockout set point plus 2.5°C (4.5°F). T2 - Start to Run - Requires the following to be true:
If the OAT is below the low ambient lockout set point, the OAT • Flow ok for time longer than evaporator recirculate time
sensor fault is not active, and no circuits are running, then low set point
ambient lockout is triggered. The unit will go directly into the T3 - Run to Off - Requires all of the following to be true:
off state and will remain in the off state until the lockout has
• Unit state = Off
cleared. This condition will clear when OAT rises to the lockout
set point plus 2.5°C (4.5°F). • Freeze protection not active
T4 - Start to Off. - Requires all of the following to be true:
Disabled Operation • Unit state = Off
When low ambient lockout is disabled, the unit will not enter • Freeze protection not active
the low ambient lockout condition or shut down any running T5 - Run to Start. - Requires the following to be true:
circuits, regardless of the OAT.
• Flow switch input is low for longer than the flow proof set
point
above is still used. When the evaporator is not in the run state,
the run hours of the pumps will be compared. The pump with Active
LWT
the least hours will be designated as the primary at this time. Max Reset
Target
LWT Target 0 4 20
The evaporator LWT Target varies based on settings and Reset Signal (mA)
inputs and is selected as follows:
• if sequence numbers are equal, it must have the most run • One circuit running at full capacity (see circuit details for
hours determination of full capacity)
• if run hours are equal, it must have the least starts • Stage Up Delay has completed
• if starts are equal, it must be the lowest numbered circuit • LWT Error > Stage Up Delta T set point
• Capacity Increase command is active
Load/Unload Sequence • Max Number Circuits Running set point = 2
This section defines which circuit is the next one to load or
unload if the logic does not call for simultaneous load or unload
of both circuits.
The next circuit to load must meet the following requirements:
Lowest capacity of the running circuits
• if capacities are equal, it must have the lowest sequence
number of the circuits that are running
• if the sequence numbers are equal, it must have the least
In Cool Mode, capacity of the circuits is controlled so that when As the signal varies from 4 mA up to 20 mA, the maximum unit
possible their capacities are balanced. Circuits will generally capacity changes from 100% to 0%.
maintain a capacity imbalance that does not exceed 15%.
If a capacity change has not occurred for at least one minute
Network Limit
and the difference in capacity between the two running circuits The maximum unit capacity can be limited by a network
is more than 15%, then the circuit capacities will be adjusted. command. This function is only enabled if the unit control
The circuit at the lower capacity will load and the circuit at the source is set to Network. The signal will be received through
higher capacity will unload simultaneously. the BAS interface on the unit controller.
If either circuit is running in manual capacity control or running This network limit command directly sets a maximum unit
with active capacity limiting events, then no load balancing capacity from 0% to 100%.
adjustments will be made.
RapidRestore®
The option allows the capability to restart more quickly and to
load faster than normal when power is lost and restored.
Enabling
Changing the RapidRestore® set point to Enable will require
the following to be true:
• RapidRestore® module is present at address 22
• DI1 on the RapidRestore® module has a signal
If any of the above are no longer true, the RapidRestore® set
point will be changed to Disable.
Circuit Functions
Feedback capacity is a representation of the actual capacity as F4ALVVR80 692.1 692.1 574.8 N/A
a percentage of full capacity based on feedback regarding the
actual speed of the compressor.
Compressors vary capacity via changes to the speed. The Pumpdown Target Value
actual compressor speed is read from the VFD. Feedback The pressure target for pumpdown when the circuit enters the
capacity for a compressor with a VFD is: pumpdown state is selected as follows:
Actual Compressor Speed x 100 ÷ Maximum Speed If Service Pumpdown set point = Disable
Then Pumpdown Target = Evaporator Pressure at
pumpdown start – 20 kPa with value limited to the range
Saturated Condenser Temperature Limit from 35 kPa to the Pumpdown Pressure Max set point
The maximum saturated condenser temperature calculation If Service Pumpdown set point = Enable
is based on the compressor operational envelope. This value
Then Pumpdown Target = 35 kPa
is used for triggering high condenser pressure alarms and as
a reference for the trigger values of the high pressure hold
and unload events. Chiller software is designed to calculate
a dynamic maximum saturated condenser temperature.
High saturated condenser hold and unload offset values are
A circuit is available to start if the following conditions are true: • Circuit is available to start per the previous section
• Adequate pressure in the evaporator and condenser (see
• Circuit switch input is on
No Pressure At Start Alarm)
• No manual reset circuit fault alarms are active
• Unit capacity control logic requires the circuit to start
• Circuit Mode set point is set to Enable
T2 – Preopen to Start
• BAS Circuit Mode set point is set to Auto
Evaporator EXV completes preopen operation.
• No cycle timers are active
• Oil Sump Check = Ready T3 – Start to Run
Compressor speed ≥ 19 Hz for at least 30 seconds
Oil Sump Check T4 – Run to Pumpdown - Any of the following are required:
Oil sump check is to make sure that oil in the sump is of
• Unit capacity control logic requires this circuit to stop
sufficient quality prior to starting the compressor.
• Unit state is pumpdown
Oil sump check is set to Ready when
• A pumpdown alarm occurs on the circuit
Discharge Temperature > Saturated Oil Temperature + 5°C
• Circuit switch input is off
Oil sump check is set to Not Ready when
Discharge Temperature < Saturated Oil Temperature + 4.5°C • Control Source = Network and BAS Circuit Mode = Off
T5 – Pumpdown to Off - Any of the following are required:
Circuit States • Evaporator Pressure drops below Pumpdown Target
There are five distinct states of control for the circuit as shown. Value
• Circuit state has been pump down for longer than the
Figure 62: Circuit State Transitions Pumpdown Time Limit set point
• Unit state is Off
T1 • Rapid stop alarm occurs on the circuit
POWER
ON
OFF PREOPEN T6 – Run to Off - Any of the following are required:
T9 • Unit state is Off
• Rapid stop alarm occurs on the circuit
T2
T7 – Start to Off - Any of the following are required:
• Unit state is Off
• Rapid stop alarm occurs on the circuit
T7 T8 T8 – Start to Pumpdown - Any of the following are required:
START
3 Off:OAT Low
Circuit is off & cannot start due to Cycle Timers
low ambient lockout
A minimum time must pass between starts of each compressor.
Off: Max Starts Circuit is off & cannot start due to When the compressor starts, a timer starts which will run for a
4
Per Hr exceeding 4 starts/hr time determined by the Start-Start Timer set point.
Circuit is off & cannot start due to
5 Off:BAS Disable BAS Circuit Mode input being set A minimum time must pass between the stop and start of each
to Off compressor. When the compressor stops, a timer starts which
will run for a time determined by the Stop-Start Timer set point.
Circuit is off & cannot start due to
Off:Keypad While either timer is running, the compressor cannot start. Both
6 Circuit Mode set point on HMI is
Disable cycle timers will be enforced even through cycling of power to
set to Disable
Off:Circuit the chiller. These timers may be cleared via the Clear Cycle
7 Circuit is off & circuit switch is off Timers set point.
Switch
Circuit is off & Oil Sump Check =
8 Off:Oil Heating
Not Ready
Starts Per Hour Limit
Circuit is off & cannot start due to In addition to the cycle timers, a limit of four starts per hour
9 Off:Alarm is enforced. A buffer of start times for the last four starts is
active circuit alarm
10 Off:Test Mode Circuit is in test mode maintained. If the current time is an hour or less after the first
timestamp in the buffer, the next start will be delayed.
11 EXV Preopen Circuit is in preopen state
12 Run:Pumpdown Circuit is in pumpdown state This limit is cleared if the Clear Cycle Timers set point is set to
Circuit is in run state & running Yes.
13 Run:Normal
normally
Circuit is in start or run state & Capacity Control
Run:Evap Press
14 cannot load due to low evaporator The compressor will vary capacity via changes to the motor
Low
pressure speed (frequency).
Circuit is in start or run state &
Run:Cond Press
15 cannot load due to high condenser Auto Capacity Control
High
pressure The normal speed change is 1 Hz for all compressor
Circuit is in start or run state & configurations.
Run:VFD
16 cannot load due to high VFD line
Current High Circuit State = Off - Speed command is 0 Hz.
current
Circuit is in start or run state & Circuit State = Preopen - Speed command is set to the
Run:VFD Temp minimum for the configuration.
17 cannot load due to high VFD
High
temperature Circuit State = Start - Immediately after starting, the
Circuit is in start or run state & compressor speed will be set to the minimum for the
Run:Motor
18 cannot load due to high motor configuration and held there while circuit state is Start.
Current High
current
Circuit State = Run - After the circuit enters the Run state,
Circuit is in start or run state & changes to the speed are performed based on load and unload
Run:High LWT cannot load due to the evaporator commands coming from the unit capacity control logic (see
19
Limit LWT exceeding the limit for unit capacity control section). The speed is constrained to a
allowing full capacity range from the minimum based on the configuration up to the
Compressor Maximum Speed set point.
When a capacity increase occurs, a time delay starts; and Table 49: VR Solenoid Valve Control Stages
when a capacity decrease occurs, a separate time delay starts.
50 75 100
While either of these delays is active, no normal capacity Stage Up Stage Down
Stage VR VR VR VR
changes will occur. The load and unload delay times are SV SV SV
Condition Condition
calculated values.
Pressure
0 1.6 Off Off Off n/a
Circuit State = Pumpdown - Speed command will drop 2 Hz Ratio > 2.10
every second until reaching the minimum for the configuration. Pressure Pressure
1 1.8 On Off Off
Ratio > 2.85 Ratio < 1.90
Manual Speed Control 2 2.4 Off On Off
Pressure Pressure
Ratio > 3.85 Ratio < 2.65
The speed of the compressor may be controlled manually.
Pressure
Manual speed control is enabled via a set point with choices 3 3.1 On On On n/a
Ratio < 3.65
of Auto or Manual. Another set point allows setting the
compressor speed. However, the resulting compressor speed When the circuit state becomes Pumpdown or Off, all VR
is still limited to the range from the minimum speed based on solenoids should be turned off.
configuration up to the Compressor Maximum Speed set point.
The compressor speed will be stepped up or down until it is
equal to the speed that corresponds to the manual speed set
Condenser Fan Control
point. Changes to the speed will be made as fast as allowed by Condenser fan control will vary in operation based on the Fan
the calculated load and unload delays. Speed control may be VFD Configuration set point.
set to Manual only when circuit state is Start or Run.
Capacity control shall revert back to automatic control if either: Table 50: Condenser Fan Control Configurations
• the circuit state changes from Start or Run to another Fan VFD Control Type Control
state Configuration Mechanism
• capacity control has been set to Manual for four hours None Staging only Contactors
1st Fan VFD Staging and speed Contactors and
Load and Unload Delay
control of 1st fan on VFD
LWT Error determines the delays for load and unload the circuit
commands.
All Fan VFD Staging and speed Integrated VFD on
control of all fans each motor
Table 48: Load and Unload Delay Conditions
LWT Error Delay Physical Fan Layout
LWT Error > Startup Delta Load command delay is 5 Fans are numbered as shown below (top view of chiller). Fan
T set point seconds numbers start on the left side of the circuit, closest to the
0.1°C ≤ LWT Error ≤ Load command delay will vary control box when facing the control box.
Startup Delta T set point from 5 seconds to 10 seconds Circuit #1 fans start at 101 and can run through 116 depending
– (Stage Down Delta T Unload command delay will on the number of fans on the circuit. Circuit #2 fans start at 201
set point) ≤ LWT Error ≤ vary from 3 seconds to 6 and can run through 214 depending on the number of fans on
-0.1°C seconds the circuit.
LWT Error < -(Stage Down Unload command delay is 3
Delta T set point) seconds Figure 63: Fan Numbering Diagram - Representative
Circuit 1 Circuit 2
VR Solenoid Valve Control Control
Box
101 103 105 107 109 111 113 115 201 203 205 207 209 211 213
End 102 104 106 108 110 112 114 116 202 204 206 208 210 212 214
There are three solenoid valves for changing volume ratio of
the compressor: NOTE: Number of fans vary by unit configuration
• 50 VR solenoid valve
• 75 VR solenoid valve
• 100 VR solenoid valve
The compressor should start with all three solenoid valves off.
After compressor has been running for at least 20 seconds, the
control logic will “stage” the solenoid valves. Table 49 shows
which VR solenoid valves are on at each stage as well as
stage up and stage down conditions. These staging conditions
must be active for 30 seconds to trigger each stage up or
down.
Condenser Fan Control State The target value is displayed on the controller screen and is
equal to the base target, but also constrained to a calculated
There are only two control states: Off and Condensing range defined by the Minimum Target value and Maximum
Temperature Control. Target value.
When the circuit state is Off or Preopen, condenser fan control
will be in the Off state. All fans will be off. Base Target
When circuit state is Start, Run, or Pumpdown, the condenser Base Target (°C) = 0.979264 x OAT + 10.7
fan control will be in the Condensing Temperature Control
state. Fan staging and speed will be controlled as needed to Minimum Target Value
drive the saturated condenser temperature to the target. Minimum Target value is designed to keep the compressor
in its operational envelope. This value is calculated by the
Saturated Condenser Temp Target controller based on the pressure difference, pressure ratio and
There are two purposes to have a variable condenser fan stage down deadband.
saturated temperature target: First 10 minutes after compressor start, the minimum target is
a. Maintain pressure difference and pressure ratio 38°C (100.4°F).
above low limit for compressor to run within After the first 10 minutes, the minimum target range is
operational envelope gradually decreased to the calculated value at a rate of 0.1°C/
b. Achieve best performance at various conditions sec.
Circuit 1
# Fans 4 6 8 10 12 14 16
1 - 101 101 101 101 101 101
2 - 102 102 102 102 102 102
Fan
3 - 103 103 103,105 103,105 103,105 103,105
Output
4 - 104,106 104 104,106 104,106 104,106 104,106,107,108
#
5 - 105 105,107 107,109 107,109,111 107,109,111,113 109,111,113,115
6 - - 106,108 108,110 108,110,112 108,110,112,114 110,112,114,116
Circuit 2
# Fans 4 6 8 10 12 14 16
1 201 201 201 201 201 201 -
2 202 202 202 202 202 202 -
Fan
3 203 203 203 203,205 203,205 203,205 -
Output
4 204 204,206 204 204,206 204,206 204,206 -
#
5 - 205 105,107 207,209 207,209,211 207,209,211,213 -
6 - - 106,108 208,210 208,210,212 208,210,212,214 -
Staging Concept
As long as the condenser saturated temperature is within the band defined by the active stage up deadband and active stage down
deadband, the fan stage will not change. When saturated condenser temperature is outside of the deadbands, error is accumulated
and will cause a change in the fan stage.
Error If this error accumulation is greater than 11°C, Fan stage up.
Saturated Condenser
Temperature Target
Error If this error accumulation is greater than 3.0°C Fan stage down.
Staging Up
When the saturated condenser temperature is above the Target + the active deadband, a Stage Up error is accumulated.
Stage Up Error Step = saturated condenser temperature – (target + Stage Up Deadband)
The Stage Up Error Step is added to Stage Up Accumulator once every five seconds, only if the saturated condenser temperature
is not falling. When the Stage Up Error Accumulator is greater than 11°C (19.8°F) fan stage is increased by 1. When a stage up
occurs or the saturated condenser temperature falls back within the Stage Up deadband the Stage Up Accumulator is reset to zero.
The first fan will turn on when condenser saturated Stage Up Compensation
temperature is above the target rather than using the error
In order to create a smoother transition when the fan stage
accumulator.
increases, the VFD compensates by slowing down initially. This
is accomplished by adding the new fan stage up deadband
Staging Down
to the VFD target. The higher target causes the VFD logic to
When the saturated condenser refrigerant temperature is decrease fan speed. Then, every 2 seconds, 0.1°C (0.18°F) is
below the Target – the active deadband, a Stage Down error is subtracted from the VFD target until it is equal to the saturated
accumulated. condenser temperature target set point.
Stage Down Error Step = (target - Stage Down deadband) -
saturated condenser temperature Speed Signal to VFD
The Stage Down Error Step is added to Stage Down The fan VFD is controlled using a 0-10 volt signal. When the
Accumulator once every 5 seconds. When the Stage Down fan should be off, the signal will be 0 Vdc. When the fan should
Error Accumulator is greater than 3°C (5.4°F), a fan stage is be running, the signal will vary based on the percent speed
removed. calculation.
When a stage down occurs or the saturated condenser Speed Signal = Percent Speed / 10
temperature rises back within the Stage Down deadband the
Stage Down Error Accumulator is reset to zero.
Fan Control - All Fans with VFD
Active Deadbands If Fan VFD Configuration is set to All Fan VFD, different control
Stage Up and Stage Down deadbands are determined by set logic will be used. All fan motors are DC fan motors which
points as shown in the following table: have integrated inverters and are controlled via modbus. This
configuration requires the DC Fan Controller.
Table 53: Stage Deadbands
System Architecture
Fan Stage Up Setting Stage Down Setting Architecture of the control system components involved in
stage control of the DC fan motors is shown below. Data flows in both
0 Fan Stage Up --- directions on the communication link as well as the Modbus
Deadband 0 connection.
1 Fan Stage Up Fan Stage Down
Deadband 1 Deadband 1 Figure 65: Controller Communication Architecture
2 Fan Stage Up Fan Stage Down
Deadband 2 Deadband 2
3 Fan Stage Up Fan Stage Down
Deadband 3 Deadband 3 Unit Controller DC Fan Controller
Situations may arise that require some action from the chiller, If the problem(s) causing the alarm have been corrected, the
or that should be logged for future reference. The alarm digital alarms will be cleared, disappear from the Active Alarm list
output will be operated based on active alarm scenarios as and be posted in the Alarm Log. If not corrected, the On will
shown in the table below. immediately change back to OFF and the unit will remain in the
alarm condition.
State Scenario
Off
No alarms preventing the chiller or an individual Description of Alarms
circuit from running Details for each alarm are listed in a table format as shown
One, and only one, circuit has an alarm preventing below. The table below explains each row in the tables.
Blinking
it from running
Alarm: Description of the alarm
Unit alarm preventing chiller from running or both
On Displayed
circuits have alarms preventing them from running Text displayed on HMI in the alarm lists
Text:
For the Blinking state, the output should cycle five seconds on Trigger: Conditions required to trigger the alarm
then five seconds off while the indicated scenario is active.
Actions that should be taken when the alarm
Action Taken:
Alarm Logging triggers
Method by which the alarm can be cleared
All alarms appear in the active alarm list while active. All alarms Reset:
and conditions required for doing so, if any
are added to the alarm log when triggered and when cleared.
Entries in the log representing the occurrence of an alarm will
be preceded by ‘+’ while entries representing the clearing of an Unit Alarms
alarm will be preceded by ‘-’.
Unit GFP Fault
When an alarm occurs, the alarm type, date, and time are
stored in the active alarm buffer corresponding to that alarm Alarm: Unit GFP Fault
(viewed on the Alarm Active screens), and also in the alarm Displayed Text: Unit Ground Fault
history buffer (viewed on the Alarm Log screens). The active Trigger: All of the following are true:
alarm buffers hold a record of all current alarms. • Ground Fault Protection Option
set point = Single Point
The alarm log can be exported to a formatted SD card in the
controller. A setting called “Alarm Log Export” will be used to • GFP Relay 1 input is off for 1
second
initiate this when set to Yes. The exported log will be saved in a
text file on the SD card with each line representing an entry in Action Taken: Rapid shutdown all circuits and lock
out unit from running
the log. Only what is in the actual alarm log will be saved to the
file when the export was initiated. Reset: Auto reset when GFP Relay 1 input is
on for 5 seconds
Signaling Alarms
The following actions will signal that an alarm has occurred:
Circuit 1 GFP Fault
Alarm: Circuit 1 GFP Fault
• The unit or circuit executes a rapid or pumpdown shutoff.
Displayed Text: C1 Ground Fault
• An alarm bell icon will be displayed in the upper right-
Trigger: All of the following are true:
hand corner of all controller screens, including the
• Ground Fault Protection Option
optional remote user interface panel’s screens.
set point = Multi Point
• An optional field supplied and wired remote alarm device • GFP Relay 1 input is off for 1 sec
will be activated.
Action Taken: Rapid shutdown all circuits and lockout
Clearing Alarms/Faults unit from running.
Reset: Auto reset when GFP Relay 1 input is
Active alarms can be cleared through the keypad/display or a on for 5 seconds
BAS network. Alarms are automatically cleared when controller
power is cycled. Alarms are cleared only if the conditions Circuit 2 GFP Fault
required to initiate the alarm no longer exist. All alarms and
groups of alarms can be cleared via the keypad or network Alarm: Circuit 2 GFP Fault
via LON using nviClearAlarms and via BACnet using the Displayed Text: C2 Ground Fault
ClearAlarms object. Trigger: All of the following are true:
• Ground Fault Protection Option
To use the keypad, follow the Alarm links to the Alarms screen, set point = Multi Point
which will show Active Alarms and Alarm Log. Select Active • GFP Relay 2 input is off for 1 sec
Alarm and press the wheel to view the Alarm List (list of current Action Taken: Rapid shutdown all circuits and lockout
active alarms). They are in order with the most recent on unit from running.
top. The second line on the screen shows Alm Cnt (number Reset: Auto reset when GFP Relay 2 input is
of alarms currently active) and the status of the alarm clear on for 5 seconds
function. An active password is not necessary to clear alarms.
CIRCUIT
START
OAT ≥ -8°C OAT< -8°C
First 2 occurrences for this
Evap Pressure < 0 kPa for 5 Evap Pressure < 0 kPa for
condition will shut down
seconds 20 seconds
circuit but do not trigger the
OR OR
alarm. Third occurrence in
Evap Pressure < -50kPa for Evap Pressure < -50kPa for
the day will trigger the alarm.
2 seconds 5 seconds
{
CIRCUIT
RUN
Evap Pressure < Low
Evap Pressure < 0 kPa for 5 Evap Pressure < -50kPa for Pressure Unload set point for
5 minutes seconds 2 seconds 100 seconds
CC Module Comm Failure Action Taken: Rapid shutdown of circuit and lock out from
running
Alarm: CC Module Comm Failure
Reset: This alarm can be cleared manually via the
Displayed Text: CCn Module Comm Fail keypad or BAS command if sensor input
Trigger: Communication with the module has failed. voltage is 400 mv to 4600 mv for at least 5
Specifically, this means the reliability value seconds.
reported for the module is anything other
than 0 for at least 3 seconds.
Action Taken: Rapid shutdown of circuit and lock out
from running Condenser Pressure Sensor Fault
Reset: This alarm can be cleared manually via the Alarm: Condenser Pressure Sensor Fault
keypad or BAS command after reliability Displayed Text: Cn CondPressSenFault
value reported for the module is 0 for at Trigger: Trigger any time sensor input voltage is
least 5 seconds. less than 400 mv or more than 4600 mv
and UC communication with CC module is
OK for at least 1 second.
Action Taken: Rapid shutdown of circuit and lock out
EEXV Module Comm Failure from running
Alarm: EEXV Module Comm Failure Reset: This alarm can be cleared manually via the
keypad or BAS command if sensor input
Displayed Text: EEXVn Mod Comm Fail
voltage is 400 mv to 4600 mv for at least 5
Trigger: Evaporator Expansion Valve Type is set as
seconds.
an ETS model number (see Table 31) and
communication with the module has failed.
Specifically, this means the reliability value
reported for the module is anything other Oil Pressure Sensor Fault
than 0 for at least 3 seconds.
Alarm: Oil Pressure Sensor Fault
Action Taken: Rapid shutdown of circuit and lock out
from running Displayed Text: Cn OilPressSenFault
Reset: This alarm can be cleared manually via the Trigger: Trigger any time sensor input voltage is
keypad or BAS command after reliability less than 400 mv or more than 4600 mv
value reported for the module is 0 for at and UC communication with CC module is
least 5 seconds. OK for at least 1 second.
Action Taken: Normal shutdown of circuit and lock out
from running
Reset: This alarm can be cleared manually via
Evaporator Pressure Sensor Fault the keypad or BAS command if sensor
Alarm: Evaporator Pressure Sensor Fault input voltage is 400 mv to 4600 mv for at
least 5 seconds.
Displayed Text: Cn EvapPressSenFault
Trigger: Trigger any time sensor input voltage is
less than 400 mv and UC communication Suction Temperature Sensor Fault
with CC module is OK for at least 1
second. Alarm: Suction Temperature Sensor Fault
Trigger when sensor input voltage is more Displayed Text: Cn SuctTempSenFault
than 4600 mv and UC communication with Trigger: Trigger if any of the following are true for
CC module is OK for at least 1 second. at least 1 second:
However, this trigger should only occur • Sensor input value < 340 Ω
after circuit state is Start or Run for at least
• Sensor input value > 300 kΩ
90 seconds.
• Sensor reliability reported by control
Trigger if the evaporator approach is less system ≠ ‘No Fault’
than 1.11°C for more than 30 seconds. This Action Taken: Normal shutdown of circuit and lock out
trigger should only be enabled after the from running
circuit state is start or run for 30 seconds.
Reset: This alarm can be cleared manually via
The purpose of this trigger condition is to
the keypad or BAS command if sensor
prevent operation if the sensor is reading
input value is 340 Ω to 300 kΩ and
high but not out of range.
sensor reliability = ‘No Fault’ for at least 5
seconds.
Events Trigger: This event will trigger when the unit mode =
Cool, compressor is running, and saturated
Situations may arise that require some action from the chiller condenser temperature > high saturated
or that should be logged for future reference, but aren’t severe condenser hold value for at least 5 seconds.
enough to track as alarms. These events are stored in a log Action Taken: Compressor will not be able to increase
separate from alarms but accessed through the alarm menu. Reset: This event is cleared when the saturated
This log shows the time and date of the latest occurrence, condenser temperature drops at least 2°C
the count of occurrences for the current day, and the count of below the high saturated condenser hold
occurrences for each of the previous seven days. value for at least 3 minutes. It is also cleared if
the circuit is no longer in the Run state or the
Unit Power Restore unit operating mode is changed to Ice.
Trigger: Unit controller is powered up.
Action Taken: None
Reset: N/A
High Condenser Pressure - Unload
Trigger: This event will trigger when the unit mode =
Cool, compressor is running, and saturated
Low Evaporator Pressure - Hold condenser temperature > high saturated
condenser unload value for at least one
Trigger: This event will trigger when the unit mode is
second.
Cool, the circuit state is Run, and evaporator
pressure drops below the low evaporator Action Taken: The compressor speed will decrease 1 Hz
pressure hold value for 5 seconds. every second.
Reset: This event is cleared when saturated
Low evaporator pressure hold value = Low condenser temperature < high saturated
Evaporator Pressure Unload set point + Low condenser unload value for at least 5
Evaporator Pressure Hold Offset set point seconds. It is also cleared if the compressor is
Action Taken: Circuit will not be able to increase in capacity. no longer in the Run state or the unit operating
Reset: This event is reset when the evaporator mode is changed to Ice.
pressure rises at least 14 kPa (2.03 psi)
above the low evaporator pressure hold value
for 3 seconds. It is also reset if the circuit is no
longer in the Run state or the unit operating
mode is changed to Ice.
Low Pressure Difference Or Ratio Shutdown High VFD Output Current - Unload
Trigger: This event will trigger on the first and second Trigger: This event will trigger when all of the following
occurrence of the below conditions within are true for at least 3 seconds.
2 hours. A third occurrence within a 2 hour • Unit mode is Cool
window triggers the alarm.
• Compressor is running
Trigger 1:
• VFD Output Current > Max Motor
Pressure ratio is less than 1.6 for longer than Current x 0.99
the Low Pressure Diff/Ratio Delay set point Action Taken: Compressor speed will be reduced at a rate
after circuit state transition to Run. Pressure equivalent to 1 Hz every 2 seconds.
ratio is calculated as shown with pressures in Reset: This event is cleared when VFD Output
kPa: Current < Max Motor Current x 0.99. It is also
Ratio = (Condenser Pressure + 101.325)/ reset if the compressor is not running or the
(Evaporator Pressure + 101.325) unit operating mode is changed to Ice.
Trigger 2:
Pressure difference is less than 180 kPa for
longer than the Low Pressure Diff/Ratio Delay High VFD Line Current Hold
set point after circuit state transition to Run.
Pressure difference is calculated as shown Trigger: This event will trigger when all of the following
with pressures in kPa: are true for at least for 5 seconds.
LCD Screen
The keypad/display consists of a 5-line by 22-character is displayed to the far right of the line to indicate it is a “jump”
display, three buttons (keys) and a “push and roll” navigation line and the entire line is highlighted when the cursor is on that
wheel. There is an Alarm Button, Menu (Home) Button, and line.
a Back Button. The wheel is used to navigate between lines
on a screen (page) and to increase and decrease changeable Navigating
values when editing. Pushing the wheel acts as an Enter
When power is applied to the control circuit, the controller
Button and will jump from a link to the next set of parameters.
screen will be active and display the Home screen, which can
also be accessed by pressing the Menu button. The navigating
Figure 71: Typical Screen wheel is the only navigating device necessary, although the
▲▼ View/Set Unit 3 Menu, Alarm, and Back buttons can provide shortcuts as
explained later.
Status/Settings >
Set Up > Passwords
Temperatures > There are four levels of access for the user interface:
Date/Time/Schedule > • No password
• Operator level - 5321
Three types of lines exist:
• Technician/Manager level - will be provided at startup
• Menu title, displayed in the first line as in Figure 71.
• Daikin Applied service technician level
• Link (also called Jump) having an arrow ( > ) in the right
of the line and used to link to the next menu. Enter passwords from the Main Menu:
• Parameters with a value or adjustable set point. • Enter Password links to the Entry screen, which is an
The first line visible on each display includes the menu title and editable screen. Pressing the wheel goes to the edit
the line number to which the cursor is currently “pointing”, in mode where the password can be entered. The first (*)
the above menu representation, “Temperatures” is highlighted. will be highlighted; rotate the wheel clockwise to the first
number and set it by pressing the wheel. Repeat for the
The leftmost position of the title line includes an “up” arrow ▲
remaining three numbers. The password will time out
to indicate there are lines (parameters) “above” the currently
after 10 minutes with no keypad activity, and is cancelled
displayed line; and/or a “down” arrow ▼ to indicate there are
if a new password is entered or the control powers down.
lines (parameters) “below” the currently displayed items or an
“up/down” arrow to indicate there are lines “above and below” • Not entering a password allows access to a limited
the currently displayed line. number of parameters.
Information presented at the controller is relative to the
Each line on a screen can contain status-only information or
password access level; the most extensive menus are
include changeable data fields (set points).
available to service technicians.
A line in a menu may also be a link to further menus. This
Entering an invalid password has the same effect as not
is often referred to as a jump line, meaning pushing the
entering a password.
navigation wheel will cause a “jump” to a new menu. An arrow
Navigation Mode
When the navigation wheel is turned clockwise, the cursor
moves to the next line (down) on the page. When the wheel is
turned counterclockwise the cursor moves to the previous line
(up) on the page. The faster the wheel is turned the faster the
cursor moves. Pushing the wheel acts as an “Enter” button.
When the Back button is pressed, the display reverts back to
the previously displayed page. If the Back button is repeatedly
pressed, the display continues to revert one page back along
the current navigation path until the “main menu” is reached.
When the Menu (Home) button is pressed the display reverts
to the “main page.”
When the Alarm button is depressed, the Alarm Lists menu is
displayed.
Edit Mode
The Edit Mode is entered by pressing the navigation wheel
while the cursor is pointing to a line containing an editable field.
Once in the Edit Mode, pressing the wheel again causes the
editable field to be highlighted. Turning the wheel clockwise
while the editable field is highlighted causes the value to be
increased. Turning the wheel counterclockwise while the
editable field is highlighted causes the value to be decreased.
The faster the wheel is turned the faster the value is increased
or decreased. Pressing the wheel again will cause the new
value to be saved and the keypad/display to leave the Edit
Mode and return to Navigation Mode.
Pre-startup
Startup and Shutdown
Do not turn the unit off using the “Override Stop” switch,
Inspect the chiller to ensure no components became loose or without first moving Q1 and Q2 to the “Stop” position, unless
damaged during shipping or installation, including leak test and it is an emergency, as this will prevent the unit from going
wiring check. Complete the pre-start checklist at the front of through a proper shutdown/pumpdown sequence, resulting in
this manual and return to Daikin Applied prior to startup date. possible equipment damage.
NOTICE
CAUTION
Daikin Applied service personnel or factory authorized
service agency must perform initial startup in order to activate The unit has a onetime pumpdown operation. When Q1
warranty. Return the “Screw Compressor Equipment Warranty and Q2 are in the “Pumpdown and Stop” position, the unit
Form” within 10 working days to Daikin Applied as instructed will pump down once and not run again until the Q1 and Q2
on the form to obtain full warranty benefits. switches are moved to the “Auto” position. If Q1 and Q2 are
in the “Auto” position and the load has been satisfied, the unit
CAUTION will go into onetime pumpdown and will remain off until the
Most relays and terminals in the unit control center are MicroTech® III control senses a call for cooling and starts the
powered when S1 is closed and the control circuit disconnect unit.
is on. Therefore, do not close S1 until ready for startup or the
unit may start unintentionally and possibly cause equipment CAUTION
damage. Water flow to the unit must not be interrupted before the
compressors pump down to avoid freeze-up in the evaporator.
Interruption will cause equipment damage.
Startup
1. Verify requirements from “Chilled Water Piping” on page CAUTION
14 are met. If all power to the unit is turned off, the compressor heaters
2. Verify chilled water flow rate and calibrate thermal will become inoperable. Once power is resumed to the unit,
dispersion flow switch - see instructions on page 84. the compressor and oil separator heaters must be energized
a minimum of 12 hours before attempting to start the unit.
3. Double check that the discharge shutoff valve and the
optional compressor suction butterfly valves are open. Failure to do so can damage the compressors due to
excessive accumulation of liquid in the compressor.
4. Check that the manual liquid line shutoff valves at the
outlet of the subcooler coils are open.
5. Check the leaving chilled water temperature set point Startup After Temporary Shutdown
on the MicroTech® III controller to be sure it is set at the
desired chilled water temperature. 1. Insure that the compressor and oil separator heaters
have been energized for at least 12 hours prior to
6. Start the auxiliary equipment for the installation by starting the unit.
turning on the time clock, and/or remote on/off switch,
and chilled water pump. 2. Start the chilled water pump.
7. Check to see that pumpdown switches Q1 and Q2 are in 3. With system switch Q0 in the “On” position, move
the “Pumpdown and Stop” (open) position. Throw the S1 pumpdown switches Q1 and Q2 to the “Auto” position.
switch to the “Auto” position. 4. Observe the unit operation until the system has
8. Under the “Control Mode” menu of the keypad, place the stabilized.
unit into the automatic Cool Mode.
9. Start the system by moving pumpdown switch Q1 to the Extended (Seasonal) Shutdown
“Auto” position.
1. Move the Q1 and Q2 switches to the Manual Pumpdown
10. Repeat step 7 for Q2. position.
2. After the compressors have pumped down, turn off the
Temporary Shutdown chilled water pump.
Move pumpdown switches Q1 and Q2 to the “Pumpdown and 3. Turn off all power to the unit and to the chilled water
Stop” position. After the compressors have pumped down, turn pump.
off the chilled water pump. 4. If fluid is left in the evaporator, confirm that the
evaporator heaters are operational.
CAUTION
5. Move the emergency stop switch S1 to the “Off” position.
6. Close the compressor discharge valve and the optional
compressor suction valve (if so equipped) as well as the Delta-T before the MicroTech® III controller will stage on
liquid line shutoff valves. cooling.
7. Tag all opened compressor disconnect switches to warn 9. Under the “Control Mode” menu of the keypad, place the
against startup before opening the compressor suction unit into the automatic Cool Mode.
valve and liquid line shutoff valves. 10. Start the system by moving pumpdown switches to the
8. If glycol is not used in the system, drain all water from “Auto” position.
the unit evaporator and chilled water piping if the unit is The following table gives glycol concentrations required for
to be shutdown during winter and temperatures below freeze protection.
-20°F can be expected. The evaporator is equipped
with heaters to help protect it down to -20°F. Chilled
water piping must be protected with field-installed Table 54: Freeze Protection Temperature
protection. Do not leave the vessels or piping open to the Percent Volume Glycol Concentration Required
atmosphere over the shutdown period.
For Freeze Protection For Burst Protection
9. Do not apply power to the evaporator heaters if the °F (°C)
Ethylene Propylene Ethylene Propylene
system is drained of fluids as this can cause the heaters
Glycol Glycol Glycol Glycol
to burn out.
20 (6.7) 16 18 11 12
10 (-12.2) 25 29 17 20
Startup After Extended (Seasonal) 0 (-17.8) 33 36 22 24
Shutdown -10 (-23.3) 39 42 26 28
1. With all electrical disconnects locked and tagged out, -20 (-28.9) 44 46 30 30
check all screw or lug-type electrical connections to be -30 (-34.4) 48 50 30 33
sure they are tight for good electrical contact. -40 (-40.0) 52 54 30 35
DANGER -50 (-45.6) 56 57 30 35
LOCK AND TAG OUT ALL POWER SOURCES WHEN -60 (-51.1) 60 60 30 35
CHECKING CONNECTIONS. ELECTRICAL SHOCK WILL
CAUSE SEVERE PERSONAL INJURY OR DEATH.
NOTE: These values are examples only and cannot be
2. Check the voltage of the unit power supply and see that appropriate to every situation. Generally, for an
it is within the ±10% tolerance that is allowed. Voltage extended margin of protection, select a temperature
unbalance between phases must be within ±2%. at least 10°F lower than the expected lowest ambient
temperature. Inhibitor levels should be adjusted for
3. See that all auxiliary control equipment is operative and solutions less than 25% glycol.
that an adequate cooling load is available for startup.
Glycol of less than 25% concentration is not
4. Check all compressor flange connections for tightness to recommended, unless inhibitors are adjusted,
avoid refrigerant loss. Always replace valve seal caps. because of the potential for bacterial growth and loss
of heat transfer efficiency.
5. Make sure system switch Q0 is in the “Stop” position and
pumpdown switches Q1 and Q2 are set to “Pumpdown
and Stop”. Throw the main power and control disconnect
switches to “On.” This will energize the crankcase
heaters. Wait a minimum of 12 hours before starting up
unit. Turn compressor circuit breakers to “Off” position
until ready to start unit.
6. Open the optional compressor suction butterfly valves,
the liquid line shutoff valves, and compressor discharge
valves.
7. Vent the air from the evaporator water side as well as
from the system piping. Open all water flow valves and
start the chilled water pump. Check all piping for leaks
and recheck for air in the system. Verify the correct flow
rate by taking the pressure drop across the evaporator
and compare to the graphs beginning on page 39.
8. Set the chilled water set point to the required
temperature. The system water temperature must be
greater than the total of the leaving water temperature
set point plus one-half the control band plus the startup
Flow Switch Installation and Calibration pipe diameters prior to the sensor and 3 to 5 pipe diameters
of straight pipe after the sensor. Flow switch is placed in outlet
A thermal dispersion flow switch uses heat to determine pipe to reflect flow leaving the barrel. If installation on the
flow and therefore must be calibrated during system startup. inlet pipe is necessary, contact Chiller Technical Response
A thermal dispersion flow switch can be an acceptable at [email protected] to review the jobsite
replacement for paddle type flow switches and differential details.
pressure switches but care must be taken regarding wiring.
The thermal dispersion flow switch supplied by Daikin Applied, Figure 75: Mount in Direction of Flow
shown in Figure 1, comes as a 2 part unit consisting of a flow
switch and an adapter labeled E40242 by the supplier.
probe does not become coated with lubricant. Torque the Step 2: Once steady state minimum desired operating flow is
adapter/sensor connection to 18.5 ft/lbs. obtained, perform the ‘Teach’ function on the flow switch. The
‘Teach’ function is initiated by holding down the minus ‘-’ button
Wiring on the face of the flow switch for 15 seconds. During this 15
second period, LEDs ‘0’ and ‘9’ will be lit green. Once the
Refer to wiring diagram in the unit control panel.
‘Teach’ function is completed, the outer LEDs will flash green
Either AC or DC is used to power the flow switch. The unit as shown in .
controller’s digital input is a DC signal which is supplied
through the switch output of the flow switch for flow indication. Figure 77: Automatic Teach of Set point
It is required that the AC and DC commons of power be
separated. Contact Chiller Technical Response for alternate
wiring scenarios.
Step 3: After the ‘Teach’ function is completed and the outer procedure is performed to toggle to unlocked.
LEDs flashed, the flow switch will indicate a new set point NOTE: 1. The LED window display on flow switch represents
based upon the current flow which should still be at the steady a velocity range of 50 cm/s. The window centers on
state minimum desired operating flow. Figure 78 shows a the set point (SP). For example, if the SP was set to
typical display for this condition. All LEDs to the left of the 200 cm/s, then the LED labeled ‘0’ would represent
SP LED are lit green. The SP LED is lit RED (or may toggle a velocity of 180 cm/s when lit and the LED labeled 9
amber) which indicates that the flow switch is OPEN. Typically, would represent a velocity of 230 cm/s when lit.
an increase in fluid flow is between 15% to 30% above the 2. Each LED represents 5 cm/s, or two presses of the
‘Teach’ function flow is required for the SP LED to turn AMBER ‘+’ or ‘-’ buttons.
and the flow switch to CLOSE indicating acceptable flow. 3. When power is initially applied to the flow switch,
all green LEDs light and go out step by step. During
Figure 78: Teach Adjustment Complete this time, the output is closed. The unit is in the
operating mode.
4. When making manual adjustments to the set point
(SP), if no button is pressed for 2 seconds, the unit
returns to the operating mode with the newly set
value.
Flow below display range: The SP LED will be lit red and
the leftmost LED will be flashing green. For example, if the SP
was set to 200 cm/s, the flashing labeled ‘0’ would indicate that
the flow was below 180 cm/s. This would be shown if no flow
through chiller or lowered than desired flow.
System Maintenance
General
Table 56: Oil Charge per Compressor
On initial startup and periodically during operation, it will
be necessary to perform certain routine service checks. Compressor Designation Oil Quantity (gallons)
Among these are checking the liquid line sight glasses, and 3120, 3122 3.43
the compressor oil level sight glass. In addition, check the
3AL, 3BL 4.7
MicroTech® III controller temperature and pressure readings
with gauges and thermometers to see that the unit has normal 4AL 6.6
condensing/suction pressure and superheat/subcooling
readings. Oil Filter Removal and Renewal
A Periodic Maintenance Log is located at the end of this Prior to this procedure, pump out the compressor. Isolate the
manual. It is suggested that the log be copied and a report be electrical supply to the control panels and compressor motor
completed on a regular basis. The log will serve as a useful terminal. Filter should be changed when pressure drop delta
tool for a service technician in the event service is required. goes above the linear line in Figure 82.
Initial startup date, vibration readings, compressor megger
readings and oil analysis information should be kept for Figure 82: Pressure Drop to Change Oil Filter
reference baseline data. 100
y = 0.3846x + 10.596
If the service technician has determined that the refrigerant 90
charge has been contaminated, the charge should be
80
recovered and tested for contaminates or noncondensables.
Appropriate actions should be taken based on testing and
Oil Pressure Difference = Condenser Pressure - Oil
70
Clean Air Act regulations. 60
Lubrication
The fan motor bearings are permanently lubricated. No further WARNING
lubrication is required. Excessive fan motor bearing noise is an After the compressor has been pumped down and isolated,
indication of a potential bearing failure. the oil contained inside the filter housing will remain hot
enough to cause burns for some time afterwards. Always
POE type oil is used for compressor lubrication. This type of
allow sufficient time for the oil to cool down so that it is cool
oil is extremely hygroscopic, which means it will quickly absorb
enough not to be a danger when drained off (less than 35°C is
moisture if exposed to air and form acids that can be harmful
recommended). Severe injury from burns can result.
to the chiller. Avoid prolonged exposure of refrigerant to the
atmosphere to prevent this problem.
Figure 83: Oil Filter Location (Including Cutaway View)
CAUTION
POE oil must be handled carefully using proper protective
equipment (gloves, eye protection, etc.). The oil must not
come into contact with certain polymers (e.g. PVC) as it may
absorb moisture from this material. Also, do not use oil or
refrigerant additives to the system.
It is important that only the manufacturer’s recommended oil be
used. Acceptable POE oil types are:
• CPI/Lubrizol Emkarate RL68H
• Exxon/Mobil EAL Arctic 68
• Hatcol 3693
The compressor oil heater is 250 watts and is on when the
compressor is off and off when the compressor is on.
Figure 84: Oil Filter Housing Cover Plate 4. Evacuate air and noncondensables before valving
refrigerant back into the compressor.
Electrical Terminals
DANGER
Electric equipment can cause electric shock which will cause
severe personal injury or death. Turn off, lock out and tag all
power before continuing with following service. Panels can
have more than one power source.
Cleaning Microchannel Aluminum Coils For routine quarterly cleaning, first remove surface debris and
then clean the coil with an approved coil cleaner (see approved
Maintenance consists primarily of the routine removal of dirt products list in Table 57). After cleaning the coils with the
and debris from the outside surface of the fins. approved cleaning agent, use the approved chloride remover
to remove soluble salts and revitalize the unit.
WARNING
Prior to cleaning the unit, turn off and lock out the main power Recommended Coil Cleaner
switch to the unit and close all access panels.
The following cleaning agents, assuming they are used in
Remove Surface Loaded Fibers accordance with the manufacturer’s directions on the container
for proper mixing and cleaning, have been approved for use on
Surface loaded fibers or dirt should be removed prior to water epoxy coated coils to remove mold, mildew, dust, soot, greasy
rinse to prevent further restriction of airflow. If unable to back residue, lint and other particulate:
wash the side of the coil opposite that of the coils entering air
side, then surface loaded fibers or dirt should be removed with
Table 57: Epoxy Coil Recommended Cleaning Agents
a vacuum cleaner. If a vacuum cleaner is not available, a soft
non-metallic bristle brush may be used. In either case, the tool Cleaning Agent Reseller Part Number
should be applied in the direction of the fins. Hydro-Balance Corp
Enviro-Coil P.O. Box 730
NOTE: Use of a water stream, such as a garden hose, H-EC01
against a surface loaded coil will drive the fibers and Concentrate Prosper, TX 75078
dirt into the coil. This will make cleaning efforts more 800-527-5166
difficult. Surface loaded fibers must be completely Enviro-Coil
Home Depot H-EC01
removed prior to using low velocity clean water rinse. Concentrate
Chlor*Rid Int’l, Inc.
Periodic Clean Water Rinse Chloride P.O. Box 908
Chlor*Rid DTS
A monthly clean water rinse is recommended for coils that are Remover Chandler, AZ 85244
applied in coastal or industrial environments to help to remove 800-422-3217
chlorides, dirt and debris. An elevated water temperature (not
to exceed 130ºF) will reduce surface tension, increasing the CHLOR*RID DTS™ should be used to remove soluble salts
ability to remove chlorides and dirt. Pressure washer pressure from the epoxy coated coil, but the directions must be followed
must not exceed 600 psig and the nozzle should remain at closely. This product is not intended for use as a degreaser.
least one foot from the coil to avoid damaging fin edges. Any grease or oil film should first be removed with the
approved cleaning agent.
High Velocity Water or Compressed Air 1. Remove Barrier - Soluble salts adhere themselves
High velocity water from a pressure washer or compressed air to the substrate. For the effective use of this product,
should only be used at a very low pressure to prevent fin and/ the product must be able to come in contact with the
or coil damages. The force of the water or air jet may bend the salts. These salts may be beneath any soils, grease or
fin edges and increase airside pressure drop. Reduced unit dirt; therefore, these barriers must be removed prior to
performance or nuisance unit shutdowns may occur. application of this product. As in all surface preparation,
the best work yields the best results.
No maintenance is ordinarily required except the routine
removal of dirt and debris from the outside surface of the 2. Apply CHLOR*RID DTS - Apply CHLOR*RID DTS
fins. Daikin recommends the use of non-caustic, non-acidic directly onto the substrate. Sufficient product must be
cleaners available at most air conditioning supply outlets. Flush applied uniformly across the substrate to thoroughly
the coil from the inside out. wet out surface with no areas missed. This may
be accomplished by use of a pump-up sprayer or
Cleaning Epoxy Coated Coils conventional spray gun. The method does not matter, as
long as the entire area to be cleaned is wetted. After the
The following additional cleaning procedures are substrate has been thoroughly wetted, the salts will be
recommended as part of the routine maintenance activities soluble and is now only necessary to rinse them off.
for epoxy coated coils. Documented routine cleaning of epoxy
coated coils is required to maintain warranty coverage. 3. Rinse - It is highly recommended that a hose be used
as a pressure washer will damage the fins. The water
Routine Quarterly Cleaning of Epoxy Coil used for the rinse is recommended to be of potable
quality, though a lesser quality of water may be used if a
Quarterly cleaning is essential to extend the life of an epoxy small amount of CHLOR*RID DTS is added. Check with
coated coil and is required to maintain warranty coverage. CHLOR*RID International, Inc. for recommendations on
Coil cleaning shall be part of the unit’s regularly scheduled lesser quality rinse water.
maintenance procedures. Failure to clean an epoxy coated coil
will void the warranty and may result in reduced efficiency and
durability in the environment.
Harsh Chemical and Acid Cleaners through the MicroTech® III controller. When in the auto mode,
the circuit with the fewest number of starts will be started first.
Harsh chemicals, household bleach or acid cleaners should
If all circuits are operating and a stage down in the number of
not be used to clean epoxy coated coils. These cleaners can
operating compressors is required, the circuit with the most
be very difficult to rinse out of the coil and can accelerate
operating hours will cycle off first. The operator can override
corrosion and attack the epoxy coating. If there is dirt below
the MicroTech® III controller, and manually select the lead
the surface of the coil, use the recommended coil cleaners as
circuit as circuit #1 or #2.
described above.
WARNING
Use caution when applying coil cleaners. They can contain
Pump Operation
potentially harmful chemicals. Wear breathing apparatus and It is highly recommended that the chiller unit control the chilled
protective clothing. Carefully follow the cleaner manufacturer’s water pump(s). The integral chiller control system has the
MSDS sheets. Thoroughly rinse all surfaces to remove any capability to selectively start pump A or B or automatically
cleaner residue. Do not damage the fins. alternate pump selection at each start and also has pump
standby operation capability.
Liquid Line Sight Glass Failure to have the chiller control the pumps may cause the
following problems:
Observe the refrigerant sight glasses weekly. A clear glass of
liquid indicates that there is adequate refrigerant charge in the 1. If any device, other than the chiller, should try to start the
system to provide proper feed through the expansion valve. chiller without first starting the pumps, the chiller will lock
out on the No Flow alarm and require a manual reset
Bubbling refrigerant in the sight glass, during stable run
to restart. This can be disruptive to the normal cooling
conditions, may indicate that there can be an EXV problem
process.
since the EXV regulates refrigerant flow. Refrigerant gas
flashing in the sight glass could also indicate an excessive 2. In areas where freeze-up is a concern, the chiller control
pressure drop in the liquid line, possibly due to a clogged filter- senses the chilled water temperature and turns on an
drier or a restriction elsewhere in the liquid line. immersion heater in the evaporator. It also signals the
chilled water pump to start, providing flow through the
An element inside the sight glass indicates the moisture
evaporator and additional protection against evaporator
condition corresponding to a given element color. If the sight
and outside pipe freeze-up. Other pump starting
glass does not indicate a dry condition after about 12 hours of
methods will not automatically provide this protection.
operation, an oil acid test is recommended.
Note: The owner/operator must be aware that when the
Do not use the sight glass on the EXV body for refrigerant water temperature falls below freezing temperatures it
charging. Its purpose is to view the position of the valve. is imperative NOT to stop the pump(s) as immediate
freeze-up can occur.
Lead-Lag This method of freeze protection is only effective as
A feature on all Daikin Pathfinder® air-cooled chillers is a long as the facility and the chiller have power. The only
system for alternating the sequence in which the compressors positive freeze protection during power failures is to
start to balance the number of starts and run hours. Lead- drain the evaporator and blow out each tube or add the
Lag of the refrigerant circuits is accomplished automatically appropriate concentration of glycol to the system.
Compressor VFD
Table 58: Compressor VFD Inspection Areas
Appendix
Definitions
Active Set Point OAT
The active set point is the setting in effect at any given Outside ambient air temperature
moment. This variation occurs on set points that can be altered Offset
during normal operation. Resetting the chilled water leaving
temperature set point by one of several methods, such as Offset is the difference between the actual value of a variable
return water temperature, is an example. (such as temperature or pressure) and the reading shown on
the controller as a result of the sensor signal.
Active Capacity Limit
Refrigerant Saturated Temperature
The active set point is the setting in effect at any given
moment. Any one of several external inputs can limit a Refrigerant saturated temperature is calculated from the
compressor’s capacity below its maximum value. pressure sensor readings for each circuit. The pressure is fitted
to an R-134a temperature/pressure curve to determine the
Deadband saturated temperature.
The deadband is a range of values surrounding a set point Soft Loading
such that a change in the variable occurring within the
deadband range causes no action from the controller. For Soft Loading is a configurable function used to ramp up the
example, if a temperature set point is 44°F and it has a unit capacity over a given time period, usually used to influence
deadband of ± 2°F, nothing will happen until the measured building electrical demand by gradually loading the unit.
temperature is less than 42°F or more than 46°F. SP
DIN Set point
Digital input, usually followed by a number designating the Suction Superheat (SSH)
number of the input.
Suction superheat is calculated for each circuit using the
Error following equation:
In the context of this manual, “Error” is the difference between Suction Superheat = Suction Temp – Evap Saturated Temp
the actual value of a variable and the target setting or set point.
Stage Up/Down Accumulator - Fans
Evaporator Approach
The accumulator can be thought of as a bank storing
The evaporator approach is calculated for each circuit. occurrences that indicate the need for an additional fan.
Evaporator Approach = LWT – Evap Saturated Temp Stage up/Stage down Delta-T
Evap Recirc Timer Staging is the act of starting or stopping a compressor or fan
A timing function, with a 30-second default, that holds off any when another is still operating. The Delta-T is the “deadband”
reading of chilled water for the duration of the timing setting. on either side of the set point in which no action is taken.
This delay allows the chilled water sensors (especially water Stage Up Delay
temperatures) to take a more accurate reading of the chilled
water system conditions. The time delay from the start of the first compressor to the start
of the second.
EXV
Startup Delta-T
Electronic expansion valve, used to control the flow of
refrigerant to the evaporator. Number of degrees above the LWT set point required to start
the first compressor.
Load Limit
Stop Delta-T
An external signal from the keypad, the BAS or a 4-20 mA
signal that limits the compressor loading to a designated Number of degrees below the LWT set point required for the
percent of full load. Frequently used to limit unit power input. last compressor to stop.
Load balance is a technique that equally distributes the total Volts, direct current
unit load among the running compressors on a unit or group of
units.
LWT
Leaving water temperature. The “water” is any fluid used in the
chiller circuit.
ms
Millisecond
Daikin Applied Americas Inc. dba Daikin Applied (“Company”) warrants to contractor, purchaser and any owner of the product
(collectively “Owner”) that Company, at it’s option, will repair or replace defective parts in the event any product manufactured by
Company, including products sold under the brand name Daikin and used in the United States or Canada, proves defective in material
or workmanship within twelve (12) months from initial startup or eighteen (18) months from the date shipped by Company, whichever
occurs first. Authorized replaced parts are warranted for the duration of the original warranty. All shipments of such parts will be
made FOB factory, freight prepaid and allowed. Company reserves the right to select carrier and method of shipment.
In addition, labor to repair or replace warranty parts is provided during Company normal working hours on products with rotary
screw compressors and centrifugal compressors. Warranty labor is not provided for any other products.
Company’s liability to Owner under this warranty shall not exceed the lesser of the cost of correcting defects in the products sold or the
original purchase price of the products.
PRODUCT STARTUP ON CENTRIFUGAL AND SCREW COMPRESSOR PRODUCTS IS MANDATORY and must be
performed by a Daikin Applied or a Company authorized service representative.
It is Owner’s responsibility to complete and return the Registration and Startup Forms accompanying the product to Company within
ten (10) days of original startup. If this is not done, the ship date and the startup date will be deemed the same for warranty period
determination, and this warranty shall expire twelve (12) months from that date.
EXCEPTIONS
1. If free warranty labor is available as set forth above, such free labor does not include diagnostic visits, inspections, travel time and
related expenses, or unusual access time or costs required by product location.
2. Refrigerants, fluids, oils and expendable items such as filters are not covered by this warranty.
3. This warranty shall not apply to products or parts which (a) have been opened, disassembled, repaired, or altered by anyone other
than Company or its authorized service representative; or (b) have been subjected to misuse, negligence, accidents, damage, or
abnormal use or service; or (c) have been operated, installed, or startup has been provided in a manner contrary to Company’s
printed instructions, or (d) were manufactured or furnished by others and which are not an integral part of a product manufactured
by Company; (e) have been exposed to contaminates, or corrosive agents, chemicals, or minerals, from the water supply source, or
(f) have not been fully paid for by Owner.
ASSISTANCE
To obtain assistance or information regarding this warranty, please contact your local sales representative or a Daikin Applied office.
SOLE REMEDY
THIS WARRANTY CONSTITUTES THE OWNER’S SOLE REMEDY. IT IS GIVEN IN LIEU OF ALL OTHER
WARRANTIES. THERE IS NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. IN NO EVENT AND UNDER NO CIRCUMSTANCE SHALL COMPANY BE LIABLE FOR INCIDENTAL,
INDIRECT, SPECIAL, CONTINGENT OR CONSEQUENTIAL DAMAGES, WHETHER THE THEORY BE BREACH OF
THIS OR ANY OTHER WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
No person (including any agent, sales representative, dealer or distributor) has the authority to expand the Company’s obligation
beyond the terms of this express warranty or to state that the performance of the product is other than that published by Company.
For additional consideration, Company will provide an extended warranty(ies) on certain products or components thereof. The terms
of the extended warranty(ies) are shown on a separate extended warranty statement.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.