SAT Procedure
SAT Procedure
3. Procedure
3a. PI test circuit is set up between L1 phase and Neutral.
3b. Set all O/C relays setting to 110% of the CT ratio.
3c. Primary current is injected between L1 & N phases by slowly raising the current value to 50% and 100% of the
rate primary current of the CT’s under test.NOTE/* Tester can test 50% , if the CT ratio are 4000A an above.
3d. L1 phase current , checked using Ammeter to confirm that the CT ratio is in order. Then the spill current is noted
and recorded. The spill current should not more than 50mA if the polarities are correct at 100% inject current.
3e. For primary current will reduce to required value amp , the over-current setting dial of the over-current relay
which has been set to 110% is slowly rotate anti-clockwise until the O/C relay operate and trip the circuit
breaker under test at desire setting.
3f. Repeat step (3c/3d.) for L2 & N , L3 & N phases.
3g. Press the ON button to inject current to the circuit and at the same time start the timer to take note of the tripping
time after the circuit breaker is trip.
3h. As the tripping time at 0.5sec max for incoming s or 0.3 sec is for outgoing as required.
the time delay can be set by adjusting the time delay setting dial ,
and reconfirm the time delay by repeating the above until the required time is recorded on the counter.