Water Cooled Centrifugal Chiller

Job Information Technical Data Sheet


Job Name MALL DEPOK
Date 4/18/2019 4:30:22 PM
Submitted By Shyntia ENDAH
Software Version HTS1.0.1
Country of Origin China
Unit Overview
Unit Name Capacity Cooling kW/tonR NPLV.IP Power Supply Starter Type
tonR kW/tonR kW/tonR
HTS 832.0 0.6053 0.5527 380 V / 50 Hz SS

Unit
Model HTS113MBE71F/E3312-EK-2/C3012-EK-2

Approval AHRI

Compressor Quantity Capacity Control Refrigerant Refrigerant Quantity

1 Inlet Guide Vanes R134a 1281 lb

Evaporator
EWT LWT Fluid Type Actual Fluid Flow Min Fluid Flow Fouling Factor

54.00 °F 44.00 °F Water 1991 gpm 739.6 gpm 0.000100 h·°F·ft ²/Btu

Condenser
EWT LWT Fluid Type Actual Fluid Flow Min Fluid Flow Fouling Factor

85.00 °F 95.00 °F Water 2348 gpm 705.9 gpm 0.000250 h·°F·ft ²/Btu

Unit Performance
Performance Points Rated with Constant Condenser EWT
Cooling Cooling
Evaporator Fluid Condenser Fluid
Point # % of Capacity Input COP kW/tonR RLA
Full tonR kW/kW kW/tonR A Flow EWT LWT PD Flow EWT LWT PD
Load gpm °F °F ft H2O gpm °F °F ft H2O
1 100.0 832.0 503.6 5.810 0.6053 871 1991 54.00 44.00 17.1 2348 85.00 95.00 26.0

2 90.0 748.8 444.5 5.925 0.5936 765 1991 53.00 44.00 17.2 2348 85.00 93.97 26.1

3 80.0 665.6 393.3 5.951 0.5910 677 1991 52.00 44.00 17.2 2348 85.00 92.97 26.1

4 70.0 582.4 348.8 5.873 0.5988 601 1991 51.00 44.00 17.2 2348 85.00 91.99 26.2

5 60.0 499.2 307.7 5.705 0.6165 533 1991 50.00 44.00 17.3 2348 85.00 91.01 26.2

6 50.0 416.0 268.0 5.460 0.6441 468 1991 49.00 44.00 17.3 2348 85.00 90.05 26.3

7 40.0 332.8 227.4 5.148 0.6831 404 1991 48.00 44.00 17.3 2348 85.00 89.08 26.3

8 30.0 249.6 183.8 4.775 0.7365 337 1991 47.00 44.00 17.3 2348 85.00 88.10 26.4

9 26.6 221.0 167.8 4.632 0.7592 312 1991 46.65 44.00 17.3 2348 85.00 87.76 26.4

10 0.0 - - - - - - - - - - - - -

Chiller unable to run at requested load point.

HTS1.0.1 Page 1 of 3
Water Cooled Centrifugal Chiller
Service Data
Service Points Rated with Constant Condenser EWT

Point # Superheat Subcooling Evaporator Fluid Condenser Fluid

ȴ°F ȴ°F Temperature Pressure Velocity Temperature Pressure Velocity


°F psig ft/s °F psig ft/s
1 1.0 8.7 41.4 36.5 7.1 98.1 120.2 8.6

2 1.0 8.0 41.7 36.7 7.1 96.7 117.3 8.6

3 1.0 7.3 41.9 37.0 7.1 95.3 114.5 8.6

4 1.0 6.5 42.2 37.2 7.1 93.9 111.9 8.6

5 1.0 5.8 42.4 37.4 7.1 92.6 109.3 8.6

6 1.0 5.0 42.6 37.7 7.1 91.3 106.9 8.6

7 1.0 4.1 42.9 37.9 7.1 90.1 104.5 8.6

8 1.0 3.3 43.1 38.1 7.1 88.8 102.1 8.6

9 1.0 2.9 43.2 38.2 7.1 88.4 101.3 8.6

10 - - - - - - - -

Chiller unable to run at requested load point.

Physical
Evaporator
Length Diameter Passes Tube Material Tube wall Thickness Design Pressure (Waterside)

12 ft 33 in 2 Cu 0.025 in 150 psig

Condenser
Length Diameter Passes Tube Material Tube wall Thickness Design Pressure (Waterside)

12 ft 30 in 2 Cu 0.025 in 150 psig

Electrical
Power RLA LRA OutputAmps Power Connection Power Factor MOCP

380 V / 50 Hz 871 A 4284 A - Single Point - 2142 A

Drive
Type Model Location Harmonic Distortion Enclosure Type

SS ASP952 Unit Mounted Standard IP22

Sound
Sound Pressure dB(A)

63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Overall 75% Load 50% Load 25% Load

69.0 67.0 69.0 72.0 76.0 79.0 79.0 74.0 84.5 82.0 82.0 83.0

Sound Pressure (dB) measured in accordance with ANSI/AHRI Standard 575-2008 ('A' weighted)

Options
Basic Unit

Oil Cooler Refrigerant Cooled

AHRI Certification

HTS1.0.1 Page 2 of 3
Water Cooled Centrifugal Chiller
Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the
AHRI Directory at www.ahridirectory.org.

Notes
1. Above RLA, MCA and MOCP values are per Chiller.
2. For variable water flow rate application change should be less than 30% per minute.

HTS1.0.1 Page 3 of 3