Ramsay Test Study Guide 2021
Ramsay Test Study Guide 2021
Electrical Symbols
Bearings
Ohms law
Power dissipated 300 ohms and 120 v equals how many watts?
I = V / R I = 120 v / 300 ohms I = 0.4 amps
watts = amps x volts watts = 0.4 x 120 watts = 48
How many main line contactors across line of ac reversing motor control? 2
Overload relay
What does an overload relay sense? Electrical overload or phase failure.
Overload protection relays prevent motor damage by monitoring the current in the motor circuit and breaking the
circuit when an electrical overload or a phase failure is detected. Since relays are much cheaper than motors, they
provide an affordable way of protecting motors.
Megohmmeter
The megohmmeter shows sudden drop in insulation resistance test means what for motor? Equipment flooding
Sometimes the drop in insulation resistance is sudden, as when equipment is flooded. Usually, however, it drops
gradually, giving plenty of warning, if checked periodically. Such checks permit planned reconditioning before
service failure. If there are no checks, a motor with poor insulation, for example, may not only be dangerous to
touch when voltage is applied, but also be subject to burn out. What was good insulation has become a
partial conductor.
Resistance
When checking resistance, do you remove power? yes
A resistance measurement must be performed with the power off. The way that a meter measures resistance is
that it actually puts a small current across the probes and measures the resulting voltage.
Load cell
Does load cell require analog input module? – Yes
Fluid clutch
What allows a motor to run continuously while the load starts and stops? Fluid clutch
Micrometer Interpretation:
Megohmmeter
The megohmmeter shows sudden drop in insulation resistance test means what for motor? Equipment flooding
Sometimes the drop in insulation resistance is sudden, as when equipment is flooded. Usually, however, it drops
gradually, giving plenty of warning, if checked periodically. Such checks permit planned reconditioning before
service failure. If there are no checks, a motor with poor insulation, for example, may not only be dangerous to
touch when voltage is applied, but also be subject to burn out. What was good insulation has become a
partial conductor.
The megohmmeter shows sudden drop in insulation resistance test means what for motor? Equipment flooding
3. First insert the black test lead into the COM jack.
4. Then insert the red lead into the VΩ jack.
When finished, remove the leads in reverse order: red first, then black.
5. Connect test leads across the component being tested.
Make sure that contact between the test leads and circuit is good.
6. Read the measurement on the display.
7. When finished, turn the multimeter OFF to prevent battery drain.
The first step in troubleshooting is to determine if the power for the output in question is present and to restore
that power if it is not. There is a further complication to troubleshooting most output modules, because they
typically contain a fuse to protect the output switching device. Faults in field wiring and devices can blow that fuse,
so its condition must be verified before proceeding. Many modules are equipped with a "fuse blown" indicator
that shows which channel or module has a blown fuse. These fuses may be accessible from the front of the
module, or the module may have to be removed or even disassembled in order to gain access to them.
Once power has been verified and the fuses checked the procedure for troubleshooting digital outputs is
somewhat the reverse of that for digital inputs.
SINGLE PHASING:
Three-phase motors must be connected to a nominal voltage to function properly. If for any reason any of the
phases that supply the motor are disconnected, the motor continues to operate with the remaining 2 phases. This
is called phase failure or single phasing.
If a three-phase motor is operating and loses one of the phases, the motor will continue to operate at a reduced
speed and experience vibrations. The current will also increase considerably in the remaining phases, causing an
internal heating of the motor components. If the motor is not disconnected quickly, it will break down as a result
of this increase in temperature.
This failure can be harmful even if it occurs when the engine is not in operation because, depending on the load,
sometimes the engine is able to start even when only two phases are connected.
Causes of a phase failure:
•Loss of one of the phases from the supply.
•One of the cables that supply the motor is damaged.
•Broken connection terminals due to vibrations or aging.
•Connection terminals that are not properly tightened.
•One of the fuses of the three-phase circuit opens.
•The starter contactor is damaged/rusty and leaves an open phase.
•Damaged relay contacts.
•Protections poorly configured.
Effects of a phase failure:
•The engine operates at a reduced speed.
•Considerable loss of the relative power of the motor.
•Because only 2 phases are providing the power, the current in the remaining phases increases considerably.
This means that the insulation in the motor windings is not able to withstand the increase in current and heat.
When the insulation is damaged, a short circuit is created in the winding that causes the motor to burn.
•It can cause generator overload.
•If the motor is off when the failure occurs, it may not start when its operation is required and if it does, it will
burn.
Thermocouple:
A Thermocouple is a sensor used to measure temperature. Thermocouples consist of two wire legs made from
different metals. The wires legs are welded together at one end, creating a junction. This junction is where the
temperature is measured. When the junction experiences a change in temperature, a voltage is created. The
voltage can then be interpreted using thermocouple reference tables to calculate the temperature.