10. Adjust the speed switch and speed window limits to the correct values according to the
output table on the configuration sheet.
11. Connect a frequency generator to the engine speed sensor 1 input, (X13-2, X13-3)
Adjust the frequency to the same as the frequency from the engine speed sensors at
nominal engine speed. The speed signal high level has to be min.15 V.
Doc ID: DAAB038320 Revision: a 3/9
12. Measure Vmax, XP3-12, it should now be 1,000V. If not, check the input frequency and
the actual speed settings, S701-705 and S711-715. If still not Ok, see calibrating
instructions for ESM-10, chapter 2.
13. Measure Vdisplay, XP3-14 and adjust the Vdisplay voltage to the correct value according to
the output table from the configuration sheet. This is to be done while the input
frequency is equal to the frequency from speed sensors at nominal engine speed, 100%.
14. Power OFF the ESM and disconnect the test adapter and the frequency generator
15. Put back the module cover and tighten the screws holding it.
16. The ESM is now ready to be installed.
17. After tuning an ESM-10 make sure that the “as tuned” setting values are stored
properly for later use.
If you by accident press the switch used for f/U calibration to many times so that the
value goes greater that 0.000V or 1.000V you have to start the calibration from the
beginning.
10. Press the S720 button with short pushes until the reading on the multimeter is 20,00mA.
The reading on the multimeter will increase for each push and the CPU3 LED will also
blink
11. When 20,00mA, (or 10,00V), is reached press S720 for a longer time until CPU3 LED
goes dark, (>3s)
12. Measure the output current for the TCA 2 output, X28-3, 4
13. Repeat points 5-10
14. Measure the output current, (or voltage), for TCB 1 output, X27-5, 6
15. Repeat points 5-10
16. Measure the output current for TCB 2 output, X28-5, 6
17. Repeat points 5-10
18. For exiting the calibration mode press the S720 button again until CPU3 LED goes dark,
(> 3s). NOTE! If not exiting the calibration mode the calibration data will not be stored
properly. (This point only apply to ESM-10 rev.3 and upwards)
19. Set switch S721 back to the correct position according to ESM setting table related to
the installation in question
20. Now the calibration for the turbo charger analogue conversion is ready
21. Power OFF the ESM and mount the module cover
Figure 3, ESM PCB layout with switches, trimmers and test connectors