Nuclear Cables
Nuclear Cables
NUCLEAR
GENERAL CABLE and ULTROL are trademarks of General Cable Technologies Corporation
Nuclear Cables Catalog
Table of Contents
Sections:
Introduction
Table of Contents
Sections: (cont’d)
4. Technical Information
Our exclusive Ultrol system provides proven reliability in a full line of cables recognized for use in Class 1E
nuclear rated environments — from 600 V single conductor switchboard and power cables to multi-conductor
instrumentation, control, power and coaxial/triaxial cables.
®
Ultrol SIS, Switchboard Wire, Class 1E Nuclear, 600V, 90ºC, VW-1, Class B, K & H, UL Type SIS and Type
SIS/XHHW-2 ― SPECS 100 & 125
• Conductor: 18 AWG thru 1000 kcmil tinned, annealed copper, Class B, Flexible Class K or Class H
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE) - Gray
• Options: Conductor stranding • Bare copper • Full-colored insulation • UL Listed SIS/XHHW-2 for sizes 14
AWG thru 4/0 AWG and XHHW-2 for kcmil sizes
• Industry & Quality Assurance Compliances: ICEA S-95-658 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC • UL 44 SIS/XHHW-2
®
Ultrol Heavy Wall, Single Conductor, Power Cable, Class 1E Nuclear, 600V, 90ºC, VW-1, UL Type
RHH/RHW-2 ― SPEC 150
• Conductor: 14 AWG thru 1000 kcmil tinned, annealed copper, Class B stranding
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE) - Black
• Options: Conductor stranding • Full-colored insulation • UL Listed RHH/RHW-2 for sizes 14 AWG thru 1000
kcmil • CT USE and SUNLIGHT RESISTANT for 1/0 AWG and larger
• Industry & Quality Assurance Compliances: ICEA S-95-658 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC • UL 44 RHH/RHW-2
®
Ultrol Dual Wall, Single Conductor, Power Cable, Class 1E Nuclear, 600V, 90ºC, VW-1, UL Type RHH/RHW-2
― SPEC 175
• Conductor: 14 AWG thru 1000 kcmil tinned, annealed copper, Class B stranding
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE) - Black
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • Full-colored insulation • UL Listed RHH or RHW-2 or USE for sizes 14
AWG thru 1000 kcmil • CT USE and SUNLIGHT RESISTANT for 1/0 AWG and larger
• Industry & Quality Assurance Compliances: ICEA S-95-658 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC • UL 44 RHH/RHW-2
Gerry Liskom • Market Manager, Nuclear Heidi Field • Product Specialist, Nuclear
[email protected] • 800.237.6419 x18712 [email protected] •800.237.6419 x18726
ULTROL®… Still ahead of its time after 35 years
Class 1E nuclear rated cables
®
Ultrol Instrumentation Cable, Multi-Conductor, Class 1E Nuclear, 600V, 90ºC, VW-1 ― SPEC 200
• Conductor: 18 AWG and 16 AWG tinned, annealed copper, Class B stranding
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE)
• Identification: Color coded per ICEA Method 1, Table E-1
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • 300 V & 1000 V • Overall galvanized steel or aluminum interlocked armor
sheath
• Industry & Quality Assurance Compliances: ICEA S-73-532 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • IEEE 1202 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC
®
Ultrol Instrumentation Cable, Multi-Conductor, Overall Shield, Class 1E Nuclear, 600V, 90ºC,
VW-1 ― SPEC 225
• Conductor: 18 AWG and 16 AWG tinned, annealed copper, Class B stranding
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE)
• Identification: Color coded per ICEA Method 1, Table E-1
• Overall Shield: Aluminum/polyester tape in contact with a stranded tinned copper drain wire
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • 300 V & 1000 V • Copper/mylar tape shield • Tinned copper braid shield •
Overall galvanized steel or aluminum interlocked armor sheath
• Industry & Quality Assurance Compliances: ICEA S-73-532 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • IEEE 1202 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC
®
Ultrol Instrumentation Cable, Individually Shielded Pairs or Triads, Overall Shield, Class 1E Nuclear, 600V,
90ºC, VW-1 ― SPEC 250
• Conductor: 18 AWG and 16 AWG tinned, annealed copper, Class B stranding
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE)
• Identification: Color-coded per ICEA Method 1; Pairs – black and white, Triads – black, white and red.
One conductor in each pair/triad is printed alpha-numerically for easy identification.
• Individually Shielded: Pairs or triads are 100% shielded with an aluminum/polyester tape in contact with a
stranded tinned copper drain wire
• Overall Shield: Aluminum/polyester tape in contact with a stranded tinned copper drain wire
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • 300 V & 1000 V • Copper/mylar tape shield with drain wire • Tinned copper
braid shield • Overall galvanized steel or aluminum interlocked armor sheath
• Industry & Quality Assurance Compliances: ICEA S-73-532 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • IEEE 1202 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC
Gerry Liskom • Market Manager, Nuclear Heidi Field • Product Specialist, Nuclear
[email protected] • 800.237.6419 x18712 [email protected] •800.237.6419 x18726
ULTROL®… Still ahead of its time after 35 years
Class 1E nuclear rated cables
®
Ultrol Control Cable, Multi-Conductor, Class 1E Nuclear, 600V, 90ºC, VW-1, UL Type TC ― SPEC 275
• Conductor: 14 AWG thru 10 AWG tinned, annealed copper, Class B stranding, 2 thru 37 conductors
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE)
• Identification: Color coded per ICEA Method 1, Table E-1
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • 1 kV & 2 kV • E-2 color code • Overall galvanized steel or aluminum
interlocked armor sheath
• Industry & Quality Assurance Compliances: ICEA S-73-532 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • IEEE 1202 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC • UL 1277
Type TC • UL 44 XHHW-2
®
Ultrol Control Cable, Multi-Conductor, Overall Shield, Class 1E Nuclear, 600V, 90ºC, VW-1, UL Type TC ―
SPEC 300
• Conductor: 14 AWG thru 10 AWG, tinned, annealed copper, Class B stranding - 2 thru 37 conductors
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE)
• Identification: Color coded per ICEA Method 1, Table E-1
• Overall Shield: Aluminum/polyester tape in contact with a stranded tinned copper drain wire
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • 1 kV & 2 kV • E-2 color code • Helical tinned copper tape shield •
Longitudinal corrugated tinned copper tape shield • Overall galvanized steel or aluminum interlocked armor
sheath
• Industry & Quality Assurance Compliances: ICEA S-73-532 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • IEEE 1202 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC • UL 1277
Type TC • UL 44 XHHW-2
®
Ultrol Power Cable, 3 or 4 Conductors with Ground, Class 1E Nuclear, 600V, 90ºC, VW-1, UL Type TC ―
SPEC 325
• Conductor: 14 AWG thru 750 kcmil tinned, annealed copper, Class B stranding
• Insulation: Flame-retardant, heat-, moisture- and radiation-resistant, thermoset Ultrol Cross-Linked
Polyethylene (FR-XLPE)
• Identification: Color coded per ICEA Method 4; black with printed numbers
• Grounding Conductor(s): Annealed tinned copper, Class B stranding, sized according to NEC
®
requirements
• Jacket: Heavy-duty Chlorosulphonated Polyethylene (CSPE) - Black
• Options: Conductor stranding • 1 kV & 2 kV • Full-colored insulation • Helical tinned copper tape shield •
Longitudinal corrugated tinned copper tape shield • Overall galvanized steel or aluminum interlocked armor
sheath
• Industry & Quality Assurance Compliances: ICEA S-95-658 • ICEA T-29-520 • IEEE 323-1974 • IEEE
383-1974 • IEEE 1202 • VW-1 • NRC 10CFR50 • ASME NQA-1 • ANSI N45.2 • NIAC • NUPIC • UL 1277
Type TC • UL 44 XHHW-2
Gerry Liskom • Market Manager, Nuclear Heidi Field • Product Specialist, Nuclear
[email protected] • 800.237.6419 x18712 [email protected] •800.237.6419 x18726
ULTROL®… Still ahead of its time after 35 years
Class 1E nuclear rated cables
SPEC 350 CS50060 – 50 Ohm Coax RG-174/U Equivalent SPEC 475 TCD95285 – 89 Ohm Coax RG-22B/U Equivalent
SPEC 375 CS50116 – 50 Ohm Coax RG-58C/U Equivalent SPEC 500 CS95146 – 95 Ohm Coax RG-62B/U Equivalent
SPEC 400 CS50285 – 50 Ohm Coax RG-213/U Equivalent SPEC 525 CD95146 – 95 Ohm Coax RG-71B/U Equivalent
SPEC 425 CS75146 – 75 Ohm Coax RG-59B/U Equivalent SPEC 550 TS752855 – 75 Ohm Triax RG-11A/U Equivalent
SPEC 450 CS75285 – 75 Ohm Coax RG-11A/U Equivalent
Industry & Quality Assurance Compliances: ICEA S-73-532 • IEEE 323-1974 • IEEE 383-1974 • VW-1 • NRC
10CFR50 • ASME NQA-1 • ANSI N45.2 •.NIAC • NUPIC • MIL-C-17 EQUIVALENT
General Cable’s Ultrol Class 1E product line reliability has been validated to perform its intended safety-
related function during Design Basis Events (DBE) by being environmentally qualified through simulated
Steam Line Break (SLB) and Loss-of-Coolant Accident (LOCA) environments. Compliance Standards and
Franklin Qualification Reports for the Ultrol product line are as follows:
Every Ultrol cable is manufactured in conformance with the documented General Cable Quality Assurance
program for Nuclear Facilities and Quality Control procedures, all under our ISO 9001:2008, ASME NQA-
1:1994 and ASME NQA-1:2008 (and 2009 Supplemental) commitment-to-quality organization. General
Cable’s facility has maintained its nuclear status through regular audits by industry committees such as the
Nuclear Procurement Issues Committee and several other quality assurance organizations.
Quality Assurance
• International Standards Organization – ISO • Nuclear Regulatory Commission – NRC 10
9001:2008 CFR 50 Appendix B
• American National Standards Institute – • Nuclear Procurement Issues Committee
ANSI N45.2 (NUPIC)
• American Society of Mechanical Engineers • Nuclear Industry Assessment Committee
– ASME NQA-1:1994 and ASME NQA- (NIAC)
1:2008 (and 2009 Supplemental)
GENERAL CABLE and ULTROL are trademarks of General Cable Technologies Corporation.
Gerry Liskom • Market Manager, Nuclear Heidi Field • Product Specialist, Nuclear
[email protected] • 800.237.6419 x18712 [email protected] •800.237.6419 x18726
Nuclear Cables Catalog
Table of Contents
Product Construction:
Product Construction:
ULTROL® SIS SWITCHBOARD WIRE, CLASS 1E NUCLEAR, 600 V, 90ºC, VW-1, FLEXIBLE CLASS K & H,
UL TYPE SIS AND TYPE SIS/XHHW-2
Min. Avg. Min. Avg.
Insulation Nom. Cable Copper Net
Cond. Thickness Diameter Weight Weight
Catalog Size Cond. lbs/ kg/ lbs/ kg/
Number (AWG) Strand Inches mm Inches mm 1000 ft. km 1000 ft. km
327130.08 18 16/.010 0.030 0.76 0.108 2.69 5 7 9 14
327140.08 16 26/.010 0.030 0.76 0.119 2.97 8 12 13 19
327150.08 14 41/.010 0.030 0.76 0.133 3.33 13 19 18 27
327160.08 12 65/.010 0.030 0.76 0.150 3.76 20 30 27 40
327170.08 10 105/.010 0.030 0.76 0.174 4.37 33 50 41 61
327180.08 8 133/.0111 0.045 1.14 0.257 6.45 52 77 70 105
327190.08 6 133/.0140 0.045 1.14 0.299 7.52 82 122 105 156
327200.08 4 133/.0177 0.045 1.14 0.353 8.89 132 196 160 239
327210.08 2 133/.0223 0.045 1.14 0.420 10.6 208 310 244 363
327220.08 1 259/.0180 0.055 1.40 0.476 12.0 266 396 312 465
327230.08 1/0 259/.0202 0.055 1.40 0.520 13.1 344 512 386 574
327240.08 2/0 259/.0227 0.055 1.40 0.571 14.4 422 628 481 715
327250.08 3/0 259/.0255 0.055 1.40 0.628 15.9 533 793 600 892
327260.08 4/0 259/.0286 0.055 1.40 0.714 18.1 670 997 746 1110
379310.08 250 427/.0242 0.065 1.65 0.761 19.2 795 1183 888 1321
379320.08 350 427/.0286 0.065 1.65 0.874 22.1 1110 1652 1221 1817
379330.08 500 427/.0342 0.065 1.65 1.034 26.2 1590 2366 1728 2572
379340.08 750 703/.0327 0.080 2.03 1.286 32.6 2410 3586 2611 3886
379350.08 1000 703/.0377 0.080 2.03 1.458 36.9 3205 4769 3441 5120
Dimensions and weights are subject to industry tolerance.
Product Construction:
ULTROL® HEAVY WALL, SINGLE CONDUCTOR, POWER CABLE, CLASS 1E NUCLEAR, 600 V, 90ºC, VW-1,
UL TYPE RHH/RHW-2
Min. Avg. Min. Avg.
Insulation Thickness Nom. Cable Copper Net
Cond. Diameter Weight Weight
Catalog Size Cond. lbs/ kg/ lbs/ kg/
Number (AWG) Strand Inches mm Inches mm 1000 ft. km 1000 ft. km
379380 14 7/.0242 0.045 1.14 0.163 4.14 13 19 22 33
379390 12 7/.0305 0.045 1.14 0.182 4.62 20 30 32 47
379400 10 7/.0385 0.045 1.14 0.205 5.21 32 48 46 68
379410 8 7/.0486 0.060 1.52 0.266 6.76 51 76 74 110
379420 6 7/.0612 0.060 1.52 0.303 7.70 81 121 109 162
384540 4 7/.0772 0.060 1.52 0.350 8.89 129 192 163 242
379440 2 7/.0974 0.060 1.52 0.409 10.4 205 305 247 368
379450 1 19/.0664 0.080 2.03 0.488 12.4 258 384 319 474
379460 1/0 19/.0745 0.080 2.03 0.527 13.4 326 485 393 585
379470 2/0 19/.0837 0.080 2.03 0.572 14.5 411 612 486 723
379480 3/0 19/.0940 0.080 2.03 0.622 15.8 518 771 601 894
379490 4/0 19/.1055 0.080 2.03 0.678 17.2 653 972 746 1110
379500 250 37/.0822 0.095 2.41 0.754 19.2 772 1149 889 1323
379510 350 37/.0973 0.095 2.41 0.857 21.8 1081 1609 1218 1813
379520 500 37/.1162 0.095 2.41 0.986 25.0 1544 2297 1707 2540
379530 750 61/.1109 0.110 2.79 1.199 30.5 2316 3446 2543 3783
379540 1000 61/.1280 0.110 2.79 1.349 34.3 3088 4595 3349 4983
Dimensions and weights are subject to industry tolerance.
Product Construction:
Options: Industry Compliances:
Conductor: Conductor stranding Class 1E Qualified in accordance with
14 AWG thru 1000 kcmil tinned, annealed Full-colored insulation IEEE 323-1974 and IEEE 383-1974
copper per ASTM B33; Class B stranding CT USE and SUNLIGHT RESISTANT ICEA S-95-658 (formerly ICEA S-66-
per ASTM B8 for 1/0 AWG and larger 524 & S-19-81)
UL 44 RHH/RHW-2
Insulation: Applications:
Flame-retardant, heat-, moisture- and Ultrol Power cable is a 600 V, insulated Flame Test Compliances:
radiation-resistant, thermoset Ultrol® Cross- dual wall, single conductor Class 1E rated IEEE 383 (70,000 BTU/hr)
Linked Polyethylene (FR-XLPE) - Black wire construction specifically designed ICEA T-29-520 (210,000 BTU/hr)
for applications in nuclear generating UL VW-1
Jacket: stations and where additional jacketing
Heavy-duty Chlorosulphonated protection is required. Other:
Polyethylene (CSPE) - Black For use in Class 1E low voltage power Quality assurance program in
and lighting functions where optimum accordance with NRC 10CFR50
Print: performance is required Appendix B
For 14 AWG thru 4/ 0 AWG: May be installed in trays, conduit, ducts, ANSI N45.2
GENERAL CABLE BRAND REX or direct buried. ASME NQA-1
BRAND (WC) ULTROL 1/C XXAWG NIAC
COPPER FR-XLPE (UL) TYPE Features: NUPIC
RHH/RHW-2 600V 90ºC VW-1 Rated at 90ºC wet or dry
NUCLEAR YEAR OF MFG Fully traceable Packaging:
Note: Sizes 1/ 0 AWG & larger include: Qualified for 40-year service life Material to be shipped on non-returnable
TRACEABILITY NUMBER & Radiation resistant (up to 200 megarads) wooden reels
SEQUENTIAL FOOTAGE MARK
Long-term thermal endurance and
For 250 kcmil thru 1000 kcmil: superior electricals
GENERAL CABLE BRAND REX
Excellent mechanical cut through
BRAND (WC) ULTROL 1/C XXXKCMIL properties
COPPER FR-XLPE (UL) TYPE
Long-term moisture and radiation
RHH/RHW-2 600V 90ºC VW-1
stability
NUCLEAR YEAR OF MFG
Free stripping for ease of termination
TRACEABILITY NUMBER
SEQUENTIAL FOOTAGE MARK Meets the cold bend test at -40°C
ULTROL® DUAL WALL, SINGLE CONDUCTOR, POWER CABLE, CLASS 1E NUCLEAR, 600 V, 90ºC, VW-1,
UL TYPE RHH/RHW-2
Min. Avg. Min. Avg.
Insulation Jacket Nom. Cable Copper Net
Cond. Thickness Thickness Diameter Weight Weight
Catalog Size Cond. lbs/ kg/ lbs/ kg/
Number (AWG) Strand Inches mm Inches mm Inches mm 1000 ft. km 1000 ft. km
379550 14 7/.0242 0.030 0.76 0.015 0.38 0.165 4.19 13 19 23 34
379560 12 7/.0305 0.030 0.76 0.015 0.38 0.184 4.67 20 30 32 48
397150 10 7/.0385 0.030 0.76 0.015 0.38 0.207 5.26 32 48 46 69
379580 8 7/.0486 0.045 1.14 0.015 0.38 0.268 6.81 51 76 75 112
379590 6 7/.0612 0.045 1.14 0.030 0.76 0.336 8.53 81 121 119 177
379600 4 7/.0772 0.045 1.14 0.030 0.76 0.383 9.73 129 192 175 260
379610 2 7/.0974 0.045 1.14 0.030 0.76 0.442 11.2 205 305 261 388
379620 1 19/.0664 0.055 1.40 0.045 1.14 0.530 13.5 258 384 340 506
379630 1/0 19/.0745 0.055 1.40 0.045 1.14 0.569 14.5 326 485 416 620
379640 2/0 19/.0837 0.055 1.40 0.045 1.14 0.614 15.6 411 612 511 760
379650 3/0 19/.0940 0.055 1.40 0.045 1.14 0.664 16.9 518 771 629 935
379660 4/0 19/.1055 0.055 1.40 0.045 1.14 0.720 18.3 653 972 776 1154
379670 250 37/.0822 0.065 1.65 0.065 1.65 0.829 21.1 772 1149 947 1410
379680 350 37/.0973 0.065 1.65 0.065 1.65 0.932 23.7 1081 1609 1284 1911
379690 500 37/.1162 0.065 1.65 0.065 1.65 1.061 27.0 1544 2297 1783 2653
378700 750 61/.1109 0.080 2.03 0.065 1.65 1.271 32.3 2316 3446 2631 3915
379710 1000 61/.1280 0.080 2.03 0.065 1.65 1.421 36.1 3088 4595 3448 5131
Dimensions and weights are subject to industry tolerance.
Product Construction:
377670 2/C Flat 16 7/.0192 0.025 0.64 0.045 1.14 0.210 x 5.33 x 16 24 54 80
0.320 8.13
Product Construction:
Product Construction:
378120 2 SPS 16 7/.0192 0.025 0.64 18 0.045 1.14 0.495 12.6 48 71 166 247
378130 3 SPS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.556 14.1 69 103 222 330
378140 4 SPS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.608 15.4 91 135 284 423
378150 5 SPS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.665 16.9 113 168 342 509
378160 7 SPS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.725 18.4 156 232 376 560
378170 9 SPS 16 7/.0192 0.025 0.64 18 0.080 2.03 0.887 22.5 199 296 517 769
378180 12 SPS 16 7/.0192 0.025 0.64 18 0.080 2.03 0.996 25.3 264 393 651 969
378190 19 SPS 16 7/.0192 0.025 0.64 18 0.080 2.03 1.164 29.6 414 616 882 1313
378200 2 STS 18 7/.0152 0.025 0.64 20 0.045 1.14 0.489 12.4 40 60 172 256
378210 3 STS 18 7/.0152 0.025 0.64 20 0.045 1.14 0.519 13.2 59 87 215 320
378220 4 STS 18 7/.0152 0.025 0.64 20 0.060 1.52 0.599 15.2 77 115 308 458
378230 5 STS 18 7/.0152 0.025 0.64 20 0.060 1.52 0.655 16.6 96 143 364 542
378240 7 STS 18 7/.0152 0.025 0.64 20 0.060 1.52 0.714 18.1 133 198 400 595
378250 9 STS 18 7/.0152 0.025 0.64 20 0.060 1.52 0.833 21.2 170 253 493 734
378260 12 STS 18 7/.0152 0.025 0.64 20 0.080 2.03 0.979 24.9 226 336 685 1019
378270 19 STS 18 7/.0152 0.025 0.64 20 0.080 2.03 1.145 29.1 356 530 910 1354
378280 2 STS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.554 14.1 64 96 223 332
378290 3 STS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.587 14.9 94 139 300 447
378300 4 STS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.642 16.3 124 185 389 579
378310 5 STS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.704 17.9 154 229 465 692
378320 7 STS 16 7/.0192 0.025 0.64 18 0.060 1.52 0.768 19.5 213 317 515 766
378330 9 STS 16 7/.0192 0.025 0.64 18 0.080 2.03 0.939 23.9 272 405 709 1055
378340 12 STS 16 7/.0192 0.025 0.64 18 0.080 2.03 1.055 26.8 361 537 892 1328
378350 19 STS 16 7/.0192 0.025 0.64 18 0.080 2.03 1.236 31.4 569 847 1208 1798
Insulated Conductor Diameter (Inches) 18 AWG (.10) and 16 AWG (.11).
Dimensions and weights are subject to industry tolerance.
Product Construction:
378370 2/C 14 7/.0242 0.030 0.76 0.045 1.14 0.359 9.12 26 38 82 121
378380 3/C 14 7/.0242 0.030 0.76 0.045 1.14 0.379 9.63 38 57 93 138
378390 4/C 14 7/.0242 0.030 0.76 0.045 1.14 0.414 10.5 51 76 116 173
378400 5/C 14 7/.0242 0.030 0.76 0.045 1.14 0.452 11.5 64 95 135 201
378410 7/C 14 7/.0242 0.030 0.76 0.045 1.14 0.492 12.5 90 134 190 283
378420 9/C 14 7/.0242 0.030 0.76 0.060 1.52 0.603 15.3 116 173 262 390
378430 12/C 14 7/.0242 0.030 0.76 0.060 1.52 0.675 17.2 155 231 322 479
378440 19/C 14 7/.0242 0.030 0.76 0.060 1.52 0.785 19.9 245 365 505 752
378450 25/C 14 7/.0242 0.030 0.76 0.080 2.03 0.951 24.2 321 478 630 938
378460 30/C 14 7/.0242 0.030 0.76 0.080 2.03 1.013 25.7 385 573 790 1176
378470 37/C 14 7/.0242 0.030 0.76 0.080 2.03 1.091 27.7 476 708 880 1310
378500 2/C Flat 12 7/.0305 0.030 0.76 0.045 1.14 0.242 x 6.15 x 41 60 95 141
0.394 10.01
378510 2/C 12 7/.0305 0.030 0.76 0.045 1.14 0.397 10.1 41 61 106 158
378520 3/C 12 7/.0305 0.030 0.76 0.045 1.14 0.420 10.7 61 91 123 183
378530 4/C 12 7/.0305 0.030 0.76 0.045 1.14 0.460 11.7 81 121 172 256
378540 5/C 12 7/.0305 0.030 0.76 0.045 1.14 0.503 12.8 102 152 205 305
378550 7/C 12 7/.0305 0.030 0.76 0.060 1.52 0.579 14.7 143 213 276 411
378560 9/C 12 7/.0305 0.030 0.76 0.060 1.52 0.671 17.1 184 274 360 536
362030 12/C 12 7/.0305 0.030 0.76 0.060 1.52 0.754 19.2 245 365 456 679
378580 19/C 12 7/.0305 0.030 0.76 0.080 2.03 0.923 23.4 389 579 705 1049
378590 25/C 12 7/.0305 0.030 0.76 0.080 2.03 1.067 27.1 512 762 875 1302
378600 30/C 12 7/.0305 0.030 0.76 0.080 2.03 1.138 28.9 613 912 1015 1511
378610 37/C 12 7/.0305 0.030 0.76 0.080 2.03 1.227 31.2 756 1125 1223 1820
378640 2/C Flat 10 7/.0385 0.030 0.76 0.045 1.14 0.265 x 6.73 x 64 96 132 196
0.440 11.18
378650 2/C 10 7/.0385 0.030 0.76 0.045 1.14 0.443 11.3 65 96 140 208
378660 3/C 10 7/.0385 0.030 0.76 0.045 1.14 0.470 11.9 97 144 170 253
378670 4/C 10 7/.0385 0.030 0.76 0.045 1.14 0.515 13.1 130 194 251 374
378680 5/C 10 7/.0385 0.030 0.76 0.060 1.52 0.595 15.1 162 241 309 460
378690 7/C 10 7/.0385 0.030 0.76 0.060 1.52 0.648 16.5 227 338 374 557
378700 9/C 10 7/.0385 0.030 0.76 0.060 1.52 0.754 19.2 292 435 523 778
378710 12/C 10 7/.0385 0.030 0.76 0.080 2.03 0.890 22.6 390 580 658 979
378720 19/C 10 7/.0385 0.030 0.76 0.080 2.03 1.038 26.4 614 918 976 1453
Insulated Conductor Diameter (Inches) 14 AWG (.14), 12 AWG (.16) and 10 AWG (.18).
Dimensions and weights are subject to industry tolerance.
Product Construction:
ULTROL® CONTROL CABLE, MULTI-CONDUCTOR, OVERALL SHIELD, CLASS 1E NUCLEAR, 600 V, 90ºC,
VW-1, UL TYPE TC
Min. Avg. Min. Avg.
Insulation Drain Jacket Nom. Cable Copper Net
Cond. Thickness Wire Thickness Diameter Weight Weight
Catalog No. of Size Cond. Size lbs/ kg/ lbs/ kg/
Number Cond. (AWG) Strand Inches mm (AWG) Inches mm Inches mm 1000 ft. km 1000 ft. km
363640 2/C 14 7/.0242 0.030 0.76 16 0.045 1.14 0.359 9.12 34 50 92 137
378760 3/C 14 7/.0242 0.030 0.76 16 0.045 1.14 0.379 9.63 47 69 103 153
378770 4/C 14 7/.0242 0.030 0.76 16 0.045 1.14 0.414 10.5 59 88 127 189
378780 5/C 14 7/.0242 0.030 0.76 16 0.045 1.14 0.512 13.0 72 108 146 217
378790 7/C 14 7/.0242 0.030 0.76 16 0.060 1.52 0.582 14.8 98 146 202 301
378800 9/C 14 7/.0242 0.030 0.76 16 0.060 1.52 0.663 16.8 124 185 274 408
378810 12/C 14 7/.0242 0.030 0.76 16 0.060 1.52 0.736 18.7 163 243 335 499
378820 19/C 14 7/.0242 0.030 0.76 16 0.080 2.03 0.888 22.6 251 374 519 772
378830 25/C 14 7/.0242 0.030 0.76 16 0.080 2.03 1.014 25.8 330 491 644 958
378840 30/C 14 7/.0242 0.030 0.76 16 0.080 2.03 1.076 27.3 394 586 806 1200
378850 37/C 14 7/.0242 0.030 0.76 16 0.080 2.03 1.154 29.3 484 720 994 1479
378860 2/C 12 7/.0305 0.030 0.76 14 0.045 1.14 0.397 10.0 54 80 122 182
378870 3/C 12 7/.0305 0.030 0.76 14 0.045 1.14 0.420 10.7 74 110 139 207
378880 4/C 12 7/.0305 0.030 0.76 14 0.045 1.14 0.460 11.7 94 140 188 280
378890 5/C 12 7/.0305 0.030 0.76 14 0.060 1.52 0.607 15.4 115 171 221 329
378900 7/C 12 7/.0305 0.030 0.76 14 0.060 1.52 0.653 16.6 156 232 292 435
378910 9/C 12 7/.0305 0.030 0.76 14 0.060 1.52 0.745 18.9 197 293 376 560
378920 12/C 12 7/.0305 0.030 0.76 14 0.060 1.52 0.828 21.0 258 384 472 702
378930 19/C 12 7/.0305 0.030 0.76 14 0.080 2.03 0.997 25.3 401 597 721 1073
378940 25/C 12 7/.0305 0.030 0.76 14 0.080 2.03 1.141 29.0 525 781 892 1328
378950 30/C 12 7/.0305 0.030 0.76 14 0.080 2.03 1.211 30.8 626 932 1032 1536
378960 37/C 12 7/.0305 0.030 0.76 14 0.080 2.03 1.301 33.1 769 1144 1240 1845
378970 2/C 10 7/.0385 0.030 0.76 12 0.045 1.14 0.443 11.3 85 127 165 246
378980 3/C 10 7/.0385 0.030 0.76 12 0.045 1.14 0.470 11.9 118 176 195 290
378990 4/C 10 7/.0385 0.030 0.76 12 0.045 1.14 0.515 13.1 150 223 276 411
379000 5/C 10 7/.0385 0.030 0.76 12 0.060 1.52 0.688 17.5 183 272 334 497
379010 7/C 10 7/.0385 0.030 0.76 12 0.060 1.52 0.740 18.8 248 369 401 597
379020 9/C 10 7/.0385 0.030 0.76 12 0.080 2.03 0.887 22.5 313 466 549 817
379030 12/C 10 7/.0385 0.030 0.76 12 0.080 2.03 0.982 24.9 411 612 684 1018
379040 19/C 10 7/.0385 0.030 0.76 12 0.080 2.03 1.130 28.7 638 950 1001 1490
Insulated Conductor Diameter (Inches) 14 AWG (.14), 12 AWG (.16) and 10 AWG (.18).
Dimensions and weights are subject to industry tolerance.
Product Construction:
ULTROL® POWER CABLE, 3 OR 4 CONDUCTORS WITH GROUND, CLASS 1E NUCLEAR, 600 V, 90ºC, VW-1,
UL TYPE TC
Min. Avg. Min. Avg.
Insulation Drain Jacket Nom. Cable Copper Net
Cond. Thickness Wire Thickness Diameter Weight Weight
Catalog No. of Size Cond. Size lbs/ kg/ lbs/ kg/
Number Cond. (AWG) Strand Inches mm (AWG) Inches mm Inches mm 1000 ft. km 1000 ft. km
379050 3/C 8 7/.0486 0.045 1.14 10 0.060 1.52 0.629 16.0 187 278 316 470
379060 4/C 8 7/.0486 0.045 1.14 10 0.060 1.52 0.690 17.5 238 354 391 582
379070 3/C 6 7/.0612 0.045 1.14 8 0.060 1.52 0.708 18.0 297 442 461 686
379080 4/C 6 7/.0612 0.045 1.14 8 0.060 1.52 0.779 19.8 379 564 573 853
379090 3/C 4 7/.0772 0.045 1.14 8 0.060 1.52 0.810 20.6 442 658 680 1012
379100 4/C 4 7/.0772 0.045 1.14 8 0.080 2.03 0.932 23.7 572 851 851 1267
379110 3/C 2 7/.0974 0.045 1.14 6 0.080 2.03 0.977 24.8 701 1043 988 1470
379120 4/C 2 7/.0974 0.045 1.14 6 0.080 2.03 1.075 27.3 908 1351 1246 1854
379130 3/C 1 19/.0664 0.055 1.14 6 0.080 2.03 1.115 28.3 861 1281 1242 1848
379140 4/C 1 19/.0664 0.055 1.14 6 0.080 2.03 1.225 31.1 1122 1670 1670 2485
379150 3/C 1/0 19/.0745 0.055 1.40 6 0.080 2.03 1.186 30.1 1081 1609 1446 2152
379160 4/C 1/0 19/.0745 0.055 1.40 6 0.080 2.03 1.309 33.3 1395 2076 1847 2749
379170 3/C 2/0 19/.0837 0.055 1.40 6 0.080 2.03 1.283 32.6 1323 1969 1749 2603
379180 4/C 2/0 19/.0837 0.055 1.40 6 0.080 2.03 1.418 36.0 1737 2585 2246 3343
379190 3/C 3/0 19/.0940 0.055 1.40 4 0.080 2.03 1.391 35.3 1694 2521 2163 3219
379200 4/C 3/0 19/.0940 0.055 1.40 4 0.080 2.03 1.538 39.1 2217 3299 2778 4134
379210 3/C 4/0 19/.1055 0.055 1.40 4 0.080 2.03 1.511 38.4 2102 3128 2638 3926
379220 4/C 4/0 19/.1055 0.055 1.40 4 0.110 2.79 1.734 44.0 2760 4107 3512 5227
379230 3/C 250 37/.0822 0.065 1.65 4 0.080 2.03 1.658 42.1 2460 3661 3194 4753
379240 4/C 250 37/.0822 0.065 1.65 4 0.110 2.79 1.898 48.2 3239 4820 4101 6103
379250 3/C 350 37/.0973 0.065 1.65 3 0.110 2.79 2.146 54.5 3437 5115 4320 6429
379260 4/C 350 37/.0973 0.065 1.65 3 0.110 2.79 1.940 49.3 4517 6722 5585 8312
379270 3/C 500 37/.1162 0.065 1.65 2 0.110 2.79 2.218 56.3 4866 7242 5903 8785
379280 4/C 500 37/.1162 0.065 1.65 2 0.110 2.79 2.458 62.4 6424 9560 7646 11379
379290 3/C 750 61/.1109 0.080 2.03 1 0.110 2.79 2.670 67.8 7249 10788 8831 13142
379300 4/C 750 61/.1109 0.080 2.03 1 0.140 3.56 3.025 76.8 9585 14264 11463 17059
Dimensions and weights are subject to industry tolerance.
Conductor:
26 AWG (7/34) bare copperweld 40% conductivity
O.D.: .019” nom.
Insulation:
Flame retardant, heat, moisture and radiation resistant, 1
thermoset Ultrol® Cross-linked Polyethylene 1 10 Frequency (MHz) 100 1000
Wall: .021” nom.
O.D.: .060” nom. Mechanical Data:
Bend Radius:
Shield: 0.8” (Training)
38 AWG tinned copper braid, 95% min. coverage. 1.2” (Pulling)
Cable Area: .0079 in2
Jacket: Braid Strength: 18.4 lbs
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene
Electrical Characteristics:
Wall: .011” nom.
Impedance: 50 ohms
O.D.: .100” ± .005”
Capacitance: 31.8 pF/ft
Velocity of Propagation: 64%
Print:
DC Loop Resistance: 110.99 ohms/1000 ft
GENERAL CABLE® BRAND REX BRAND (WC) CS50060
COAXIAL RG-174/U TYPE PLUS DAY/MONTH/YEAR Insulation Resistance: 25,000 megohms–1000ft
OF MANUFACTURE UNIQUE SERIAL NUMBER Maximum Operating Voltage: 1100 volts, RMS
SEQUENTIAL FOOTAGE MARK Dielectric Strength: 4500 volts, RMS
Conductor:
20 AWG (10/30) tinned copper
O.D.: .036” nom. 1
1 10 100 1000
Insulation:
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene 0.1
Wall: .041” nom. Frequency (MHz)
O.D.: .119” nom.
Mechanical Data:
Shield: Bend Radius:
36 AWG tinned copper braid, 95% min. coverage. 1.56” (Training)
2.34” (Pulling)
Jacket: Cable Area: .030 in2
Heavy-duty Chlorosulphonated Polyethylene (CSPE) – Black Braid strength: 36 lbs
Wall: .027” nom.
O.D.: .195” ± .005”
Electrical Characteristics:
Impedance: 50 ohms
Print:
Capacitance: 31.8 pF/ft
GENERAL CABLE® BRAND REX BRAND (WC) CS50116
COAXIAL RG-58C/U TYPE PLUS DAY/MONTH/YEAR Velocity of Propagation: 64%
OF MANUFACTURE UNIQUE SERIAL NUMBER DC Loop Resistance: 15.74 ohms/1000 ft
SEQUENTIAL FOOTAGE MARK Insulation Resistance: 26,000 megohms–1000ft
Maximum Operating Voltage: 1400 volts, RMS
Feature: Dielectric Strength: 5000 volts, RMS
Meets cold bend test at -40°C
Industry Compliances:
Cable Weight: Class 1E Qualified in accordance with IEEE 323-1974 and
27 lbs/1000 ft nom. IEEE 383-1974
ICEA S-73-532
Catalog Number:
Brand-Rex CS50116 Other:
General Cable 204220 Quality Assurance program in accordance with NRC
10CFR50 Appendix B
Options: ANSI 45.2
Armor – braid or interlocked armor ASME NQA-1
Flame retardant, heat, moisture and radiation resistant, NIAC
thermoset Ultrol® Cross-linked Polyethylene jacket NUPIC
Conductor:
12 AWG 7/.0284 tinned copper
O.D.: .085” nom. 1
1 10 100 1000
Insulation:
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene
0.1
Wall: .100” nom. Frequency (MHz)
O.D.: .285” nom.
Mechanical Data:
Shield: Bend Radius:
33 AWG tinned copper braid, 95% min. coverage 3.24” (Training)
4.86” (Pulling)
Jacket: Cable Area: .129 in2
Heavy-duty Chlorosulphonated Polyethylene (CSPE) – Black Braid strength: 160 lbs
Wall: .044” nom.
O.D.: .405” ± .005” Electrical Characteristics:
Impedance: 50 ohms
Print:
Capacitance: 31.8 pF/ft
GENERAL CABLE® BRAND REX BRAND (WC)
Velocity of Propagation: 64%
CS50285 COAXIAL RG-213/U TYPE PLUS
DAY/MONTH/YEAR OF MANUFACTURE UNIQUE DC Loop Resistance: 3.13 ohms/1000 ft
SERIAL NUMBER SEQUENTIAL FOOTAGE MARK Insulation Resistance: 26,000 megohms–1000ft
Maximum Operating Voltage: 3,700 volts, RMS
Feature: Dielectric Strength: 10,000 volts, RMS
Meets cold bend test at -40°C
Industry Compliances:
Cable Weight: Class 1E Qualified in accordance with IEEE 323-1974 and
113.5 lbs/1000 ft IEEE 383-1974
ICEA S-73-532
Catalog Number:
Brand-Rex: CS50285 Other:
General Cable: 204310 Quality Assurance program in accordance with NRC 10CFR50
Appendix B
Options: ANSI 45.2
Armor – braid or interlocked armor ASME NQA-1
Flame retardant, heat, moisture and radiation resistant, NIAC
thermoset Ultrol® Cross-linked Polyethylene jacket NUPIC
Product Construction:
Conductor:
24 AWG 16/36 tinned copper 1
O.D.: .023” nom. 1 10 100 1000
Insulation:
Flame Retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene 0.1
Frequency (MHz)
Wall: .062” nom.
O.D.: .148” nom.
Mechanical Data:
Bend Radius:
Shield:
34 AWG tinned copper braid, 95% min. coverage 1.94” (Training)
2.90” (Pulling)
Jacket: Cable Area: .046 in2
Heavy-duty Chlorosulphonated Polyethylene (CSPE) – Black Braid strength: 70 lbs
Wall: .033” nom.
O.D.: .242” ± .005” Electrical Characteristics:
Impedance: 75 ohms
Print: Capacitance: 21.2 pF/ft
GENERAL CABLE® BRAND REX BRAND (WC) CS75146 Velocity of Propagation: 64%
COAXIAL RG-59B/U TYPE PLUS DAY/MONTH/YEAR DC Loop Resistance: 31.04 ohms/1000 ft
OF MANUFACTURE UNIQUE SERIAL NUMBER Insulation Resistance: 40,000 megohms–1000ft
SEQUENTIAL FOOTAGE MARK Maximum Operating Voltage: 2,200 volts, RMS
Dielectric Strength: 7,000 volts, RMS
Feature:
Meets cold bend test at -40°C Industry Compliances:
Class 1E Qualified in accordance with IEEE 323-1974 and
Cable weight: IEEE 383-1974
38.2 lbs/1000 ft ICEA S-73-532
Conductor:
19 AWG (7/27) tinned copper
O.D.: .043” nom. 1
1 10 100 1000
Insulation:
Flame Retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene
Wall: .121” nom. 0.1
Frequency (MHz)
O.D.: .285” nom.
Mechanical Data:
Shield:
Bend Radius:
33 AWG tinned copper braid, 95% min. coverage
3.24” (Training)
Jacket: 4.86” (Pulling)
Heavy-duty Chlorosulphonated Polyethylene (CSPE) – Black Cable Area: .129 in2
Wall: .045” nom. Braid strength: 160 lbs
O.D.: .405” ± .007”
Electrical Characteristics:
Print: Impedance: 75 ohms
GENERAL CABLE® BRAND REX BRAND (WC) Capacitance: 21.2 pF/ft
CS75285 COAXIAL RG-11A/U TYPE PLUS Velocity of Propagation: 64%
DAY/MONTH/YEAR OF MANUFACTURE UNIQUE DC Loop Resistance: 7.35 ohms/1000 ft
SERIAL NUMBER SEQUENTIAL FOOTAGE MARK Insulation Resistance: 40,000 megohms–1000ft
Maximum Operating Voltage: 4,000 volts, RMS
Feature: Dielectric Strength: 10,000 volts, RMS
Meets cold bend test at -40°C
Industry Compliances:
Cable weight: Class 1E Qualified in accordance with IEEE 323-1974 and IEEE
95.2 lbs/1000 ft 383-1974
ICEA S-73-532
Catalog Number:
Brand-Rex: CS75285 Other:
General Cable: 204190 Quality Assurance program in accordance with NRC 10CFR50
Appendix B
Options: ANSI 45.2
Armor – braid or interlocked armor ASME NQA-1
Flame retardant, heat, moisture and radiation resistant, NIAC
thermoset Ultrol® Cross-linked Polyethylene jacket NUPIC
Catalog Number:
Brand-Rex: TCD95285
General Cable: 203250
Options:
Armor – braid or interlocked armor
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene jacket
Print:
GENERAL CABLE® BRAND REX BRAND (WC) TCD95285
TWIN COAXIAL RG-22B/U TYPE PLUS
DAY/MONTH/YEAR OF MANUFACTURE UNIQUE SERIAL
NUMBER SEQUENTIAL FOOTAGE MARK
Feature:
Meets cold bend test at -40°C
Cable weight:
124.7 lbs/1000 ft
Conductor: 10
28 AWG copper-covered steel
O.D.: .0126” nom.
Insulation:
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene
Wall: .064” nom. 1
O.D.: .140” nom. 1 10
Frequency (MHz)
100 1000
Shield:
Mechanical Data:
34 AWG tinned copper braid, 95% min. coverage
Bend Radius:
Jacket: 1.94” (Training)
Heavy-duty Chlorosulphonated Polyethylene (CSPE) – 2.90” (Pulling)
Black Cable Area: .046 in2
Wall: .037” nom. Braid strength: 70 lbs
O.D.: .242” ± .005”
Electrical Characteristics:
Print: Impedance: 95 ohms
GENERAL CABLE® BRAND REX BRAND (WC) Capacitance: 16.7 pF/ft
CS95146 COAXIAL RG-62B/U TYPE PLUS Velocity of Propagation: 64%
DAY/MONTH/YEAR OF MANUFACTURE UNIQUE DC Loop Resistance: 169.6 ohms/1000 ft
SERIAL NUMBER SEQUENTIAL FOOTAGE MARK Insulation Resistance: 52,000 megohms–1000ft
Maximum Operating Voltage: 2,000 volts, RMS
Feature: Dielectric Strength: 7,500 volts, RMS
Meets cold bend test at -40°C
Industry Compliances:
Cable Weight: Class 1E Qualified in accordance with IEEE 323-1974 and
38.8 lbs/1000 ft IEEE 383-1974
ICEA S-73-532
Catalog Number:
Brand-Rex: CS95146 Other:
General Cable: 204210 Quality Assurance program in accordance with NRC 10CFR50
Appendix B
Options: ANSI 45.2
Armor – braid or interlocked armor ASME NQA-1
Flame retardant, heat, moisture and radiation resistant, NIAC
thermoset Ultrol® Cross-linked Polyethylene jacket NUPIC
Conductor:
28 AWG copper-covered steel
O.D.: .0126” nom.
Insulation: 1
Flame retardant, heat, moisture and radiation resistant, 1 10 Frequency (MHz) 100 1000
thermoset Ultrol® Cross-linked Polyethylene
Wall: .064” nom. Mechanical Data:
O.D.: .140” nom. Bend Radius:
2.0” (Training)
Inner Shield: 3.0” (Pulling)
34 AWG tinned copper braid, 95% min. coverage Cable Area: .049 in2
Braid strength: 140 lbs
Inner Shield:
34 AWG tinned copper braid, 95% min. coverage
Electrical Characteristics:
Jacket: Impedance: 95 ohms
Heavy-duty Chlorosulphonated Polyethylene (CSPE) – Black Capacitance: 16.7 pF/ft
Wall: .026” nom. Velocity of Propagation: 64%
O.D.: .250” ± .005” DC Loop Resistance: 168.2 ohms/1000 ft
Insulation Resistance: 52,000 megohms–1000ft
Print: Maximum Operating Voltage: 2,000 volts, RMS
GENERAL CABLE® BRAND REX BRAND (WC) Dielectric Strength: 7,500 volts, RMS
CD95146 COAXIAL RG-71B/U TYPE PLUS
DAY/MONTH/YEAR OF MANUFACTURE UNIQUE Industry Compliances:
SERIAL NUMBER SEQUENTIAL FOOTAGE MARK Class 1E Qualified in accordance with IEEE 323-1974 and
IEEE 383-1974
Feature: ICEA S-73-532
Meets cold bend test at -40°C
Other:
Cable Weight: Quality Assurance program in accordance with NRC 10CFR50
53.4 lbs/1000 ft Appendix B
ANSI 45.2
Catalog Number: ASME NQA-1
Brand-Rex: CD95146 NIAC
General Cable: 204300 NUPIC
Options:
Armor – braid or interlocked armor
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene jacket
Conductor:
19 AWG (7/27) tinned copper
O.D.: .043” nom. 1
1 10 100 1000
Insulation:
Flame Retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene
Wall: .121” nom.—O.D.: .285” nom. 0.1
Frequency (MHz)
Inner Shield:
33 AWG tinned copper braid, 95% min. coverage Mechanical Data:
Bend Radius:
Intershield Insulation: 3.72” (Training)
Flame retardant, heat, moisture and radiation resistant, 5.58” (Pulling)
thermoset Ultrol® Cross-linked Polyethylene Cable Area: .181 in2
Wall: .025” nom.—O.D.: .365” nom. Braid strength: 160 lbs
Options:
Armor – braid or interlocked armor
Flame retardant, heat, moisture and radiation resistant,
thermoset Ultrol® Cross-linked Polyethylene jacket
Compliance Standards
• ANSI
• ICEA
• IEEE
Every Ultrol cable is manufactured in conformance with the documented General Cable Quality Assurance
program for Nuclear Facilities and Quality Control procedures, all under our ISO 9001:2008, ASME NQA-
1:1994 and ASME NQA-1:2008 (and 2009 Supplemental) commitment-to-quality organization. General
Cable’s facility has maintained its nuclear status through regular audits by industry committees such as the
Nuclear Procurement Issues Committee and several other quality assurance organizations.
Quality Assurance
Method 1 - Method 3 -
Table E1 Color Sequence Table E1 Color Sequence
CONDUCTOR BACKGROUND FIRST SECOND CONDUCTOR BACKGROUND FIRST SECOND CONDUCTOR CONDUCTOR PRINTING
NUMBER OR BASE TRACER TRACER NUMBER OR BASE TRACER TRACER NUMBER
COLOR COLOR COLOR COLOR COLOR COLOR
1 Black - - 20 Red Green - 1 “1-Black”
2 White - - 21 Orange Green - 2 “2-White”
3 Red - - 22 Black White Red 3 “3-Red”
4 Green - - 23 White Black Red 4 “4-Green”
5 Orange - - 24 Red Black White
6 Blue - - 25 Green Black White
7 White Black - 26 Orange Black White Method 3 -
8 Red Black - 27 Blue Black White Table E2 Color Sequence
9 Green Black - 28 Black Red Green
CONDUCTOR CONDUCTOR PRINTING
10 Orange Black - 29 White Red Green NUMBER
11 Blue Black - 30 Red Black Green
12 Black White - 31 Green Black Orange 1 “1-Black”
13 Red White - 32 Orange Black Green 2 “2-Red”
14 Green White - 33 Blue White Orange 3 “3-Blue”
15 Blue White - 34 Black White Orange 4 “4-Orange”
16 Black Red - 35 White Red Orange
17 White Red - 36 Orange White Blue
18 Orange Red - 37 White Red Blue Method 4 -
19 Blue Red - All Conductors Black
Pair cables are Black, White and numbered. Triad cables are Black, White, Red and numbered. CONDUCTOR CONDUCTOR PRINTING
NUMBER
Method 1 -
Table E2 Color Sequence 1 “1-One”
2 “2-Two”
CONDUCTOR BACKGROUND TRACER CONDUCTOR BACKGROUND TRACER
NUMBER OR BASE COLOR NUMBER OR BASE COLOR 3 “3-Three”
COLOR COLOR 4 “4-Four”
1 Black - 19 Orange Blue 5 “5-Five”
2 Red - 20 Yellow Blue
3 Blue - 21 Brown Blue
4 Orange - 22 Black Orange
5 Yellow - 23 Red Orange
6 Brown - 24 Blue Orange
7 Red Black 25 Yellow Orange
8 Blue Black 26 Brown Orange
9 Orange Black 27 Black Yellow
10 Yellow Black 28 Red Yellow
11 Brown Black 29 Blue Yellow
12 Black Red 30 Orange Yellow
13 Blue Red 31 Brown Yellow
14 Orange Red 32 Black Brown
15 Yellow Red 33 Red Brown
16 Brown Red 34 Blue Brown
17 Black Blue 35 Orange Brown
18 Red Blue 36 Yellow Brown
Pair cables are Black, Red and numbered. Triad cables are Black, Red, Blue and numbered. Colors
repeat after 36 conductors. There are no Green or White conductors or stripes.
Phone: 800-237-6419
ext. 18712 or 18726
www.generalcable.com
SPEC A125
January, 2011
Insulation Resistance:
Megohms—Kilofeet Megohms—Kilometer 0.3048
Megohms—Kilometer Megohms—Kilofeet 3.2808
Pounds/Square Inch Kilo Pascal* 6.895
Mechanical Kilo Pascal* Pounds/Square Inch 0.1432
Pounds (force) Newtons 4.448
* 1 Pascal = 1 newton/m2
Phone: 888-593-3355
www.generalcable.com
SPEC B025
February, 2011
Copper Conductor
ASTM CLASS B
CONCENTRIC COMPRESSED COMPACT
COND. SIZE STRANDING NOMINAL AREA NOMINAL WEIGHT NOMINAL O.D. NOMINAL O.D. NOMINAL O.D.
AWG/kcmil INCHES CIRCULAR MILS mm² LBS/1000 FT¹ kg/km INCHES mm INCHES mm INCHES mm
Phone: 888-593-3355
www.generalcable.com
SPEC B030
February, 2011
Copper Conductor
ASTM CLASS C
Phone: 888-593-3355
www.generalcable.com
SPEC B035
February, 2011
Copper Conductor
ASTM CLASS H
9 — — — — — — —
8 133/.0111 16,510 8.37 0.164 4.17 52 77
7 133/.0126 20,820 10.50 0.190 4.83 67 100
6 133/.0140 26,240 13.30 0.204 5.18 82 122
5 133/.0158 33,090 16.80 0.231 5.87 105 156
4 133/.0177 41,740 21.20 0.260 6.60 132 196
3 133/.0199 52,620 26.70 0.292 7.42 167 248
2 133/.0223 66,360 33.60 0.327 8.31 208 310
1 259/.0180 83,690 42.40 0.363 9.22 266 396
1/0 259/.0202 105,600 53.50 0.407 10.30 334 497
2/0 259/.0227 133,100 67.40 0.458 11.60 422 628
3/0 259/.0255 167,800 85 0.515 13.10 533 793
4/0 259/.0286 211,600 107 0.579 14.70 670 997
250 427/.0242 250,000 127 0.627 15.90 795 1183
262.6 — — — — — — —
300 427/.0265 300,000 152 0.702 17.80 953 1418
313.1 — — — — — — —
350 427/.0286 350,000 177 0.740 18.80 1110 1652
373.7 — — — — — — —
400 427/.0306 400,000 203 0.809 20.50 1270 1890
444.4 — — — — — — —
500 427/.0342 500,000 253 0.900 22.90 1590 2366
535.3 — — — — — — —
592 — — — — — — —
600 703/.0292 600,000 304 1.022 26.00 1920 2857
646.4 — — — — — — —
750 703/.0327 750,000 380 1.122 28.50 2410 3586
777.7 — — — — — — —
1000 703/.0377 1,000,000 507 1.294 32.90 3205 4769
1111 — — — — — — —
Dimensions and weights are nominal; subject to industry tolerances.
Phone: 888-593-3355
www.generalcable.com
SPEC B040
February, 2011
Copper Conductor
ASTM CLASS I
Phone: 888-593-3355
www.generalcable.com
SPEC B045
February, 2011
Copper Conductor
ASTM CLASS K
22 — — — — — — —
20 10/.010 1,020 0.52 0.036 0.91 3.2 4.8
18 16/.010 1,620 0.82 0.046 1.20 5 7.4
16 26/.010 2,580 1.31 0.057 1.40 7.97 12
14 41/.010 4,110 2.08 0.071 1.80 12.8 19
12 65/.010 6,530 3.31 0.088 2.20 20.3 30.2
10 105/.010 10,380 5.26 0.112 2.80 33.3 49.6
9 133/.010 13,090 6.63 0.150 3.80 42.4 63.1
8 168/.010 16,510 8.37 0.164 4 53.2 80.8
7 210/.010 20,820 10.50 0.175 4.40 66.8 99.4
6 266/.010 26,240 13.30 0.198 5.00 84.2 125
5 336/.010 33,090 16.80 0.261 6.60 106 158
4 420/.010 41,740 21.20 0.249 6.30 132 196
3 532/.010 52,620 26.70 0.298 7.60 169 251
2 665/.010 66,360 33.60 0.317 8.10 211 314
1 836/.010 83,690 42.40 0.356 9 266 396
1/0 1064/.010 105,600 53.50 0.401 10 338 503
2/0 1323/.010 133,100 67.40 0.501 13 425 632
3/0 1666/.010 167,800 85 0.562 14 535 796
4/0 2107/.010 211,600 107 0.627 15.93 676 1006
250 2499/.010 250,000 127 0.688 17 802 1193
262.6 2220/.010 222,000 112 0.680 17 824 1226
300 2989/.010 300,000 152 0.753 19 960 1428
313.1 3136/.010 313,600 159 0.750 19 969 1442
350 3458/.010 350,000 177 0.818 21 1120 1667
373.7 3737/.010 373,700 189 0.790 20 1210 1800
400 3990/.010 400,000 203 0.878 22 1290 1920
444.4 — — — — — — —
500 5054/.010 500,000 253 0.990 25 1635 2433
535.3 5320/.010 532,000 270 0.950 24 1641 2442
592 — — — — — — —
600 5985/.010 600,000 340 1.125 29 1950 2902
646.4 6466/.010 646,600 328 1.040 26 1987 2957
750 7448/.010 750,000 380 1.276 32 2427 3611
777.7 — — — — — — —
1000 9975/.010 1,000,000 507 1.498 38 3250 4769
1111 — — — — — — —
Dimensions and weights are nominal; subject to industry tolerances.
Phone: 888-593-3355
www.generalcable.com
SPEC D005
January, 2010
YES NO
Cradle both reel flanges between forks. Do not lift by top flange. Cable or reel
will be damaged.
Reels can be hoisted with a shaft Use a spreader bar to prevent bending
extended through both flanges. the reel flanges and mashing the cable.
Place spacers under the bottom flange Upended heavy reels will often arrive
and between reels to create a space to damaged. Refuse or receive subject to
insert the forks. inspection for hidden damage.
Lower reels from truck using hydraulic Never allow forks to touch cable surface
gate, hoist or fork lift. LOWER CAREFULLY. or reel wrap.
Phone: 888-593-3355
www.generalcable.com
SPEC D026
January, 2011
Phone: 800-237-6419
ext. 18712 or 18726
www.generalcable.com
SPEC D050
January, 2010
Phone: 888-593-3355
www.generalcable.com
SPEC E005
January, 2010
Pre-Installation Instructions
Pre-Installation
Overview Cable Inspection Cabling Handling
To ensure safety during cable installation Inspect every cable reel for damage Remove all nails and staples from
and reliability once the cable is installed, before accepting the shipment. Be the reel flanges before moving a reel,
you should confirm the following prior to particularly alert for cable damage if: and avoid all objects that could crush,
installation: gouge or impact the cable when
• A reel is laying flat on its side moving. NEVER use the cable as a
• T
he cable selected is proper for your • Several reels are stacked means to move a reel.
application
• Other freight is stacked on a reel When unreeling, observe recommended
• T
he cable has not been damaged in bending radii, use swivels to prevent
transit or storage • N
ails have been driven into reel flang- twisting and avoid overruns.
es to secure shipping blocks
Review all applicable state and national
codes to verify that the cable chosen is • A reel flange is damaged
appropriate for the job. Also, consult your • A
cable covering is removed, stained
local building authority. or damaged
Next, you must identify any existing • A
cable end seal is removed or
cable damage and prevent any further damaged
damage from occurring. This is done
• A
reel has been dropped
through proper cable inspection,
(hidden damage likely)
handling and storage.
Phone: 888-593-3355
www.generalcable.com
SPEC E025
January, 2011
Installation
Overview Installation Temperature Equipment
Most cables are subjected to more Low temperatures are a cause for The proper use of appropriate equipment
mechanical stress during installation than concern when installing cable. Cable is crucial to a successful cable installation.
they ever experience in actual operation. should not be installed when temperatures The equipment needed for most installa-
Needless to say, handling and pulling your are less than the cold bend temperature tions is detailed in the following checklist:
cable according to manufacturer’s recom- rating of the cable product plus 15°C (i.e.,
mendations is extremely important. minimum installation temperature = cold 0-1/5/10 kip dynamometer
bend temperature rating + 15°C). The cold basket grip pullers
There are six main considerations in any bend temperature rating is indicated on the cable cutter
cable installation: catalog Spec sheet. cable end seals
• Ambient temperature Prior to performing a low temperature cable pulling lubricant
(less than 10°F or -12˚C) cable installation, cable tray bend sheaves
• Equipment cable should be stored for a minimum of cable tray rollers
24 hours at a temperature of 55°F (13˚C) capstan-type puller
• Conduit fill
or higher.
diameter tape
• Mechanical fit in raceway Cable should be pulled more slowly and duct cleaning mandrels
• Physical limitations trained in place the same day it is removed electric safety blankets and clamps
from storage. Do not impact, drop, kink or extension cords and GFCI protection
• Knowledgeable installers bend cable sharply in low temperatures.
fish tape or string blower/vacuum
For more information, reference floodlights
IEEE 1185 Recommended Practices for gang rollers: with at least 4 ft.
Cable Installations in Generating Stations effective radius
and Industrial Facilities. gloves
guide-in flexible tubing (elephant trunks)
hand winches (come-a-long)
HI-POT tester
lint-free rags
make-up air blower & hose
manhole edge sheave
measuring tape
personal protection equipment (PPE)
plywood sheets
portable electric generator
pre-lubing devices
pulling rope
pump, diaphragm
radios or telephones
reel arbor
reel brakes
reel jacks
several wire rope slings of various
lengths
shackles/clevis
short ropes for temp tie-offs
swivels
warning flags, signs
Phone: 888-593-3355
www.generalcable.com
SPEC E050
January, 2010
Installation—Feed-In Setups
Reels on truck
Figure 1 Figure 2
Phone: 888-593-3355
www.generalcable.com
SPEC E050
January, 2010
Installation—Feed-In Setups
Single Sheave
Single sheaves should only be
used for GUIDING cables. Arrange
multiple blocks to maintain bending
radii whenever cable changes
direction or elevation.
Figure 3
Radius
Phone: 888-593-3355
www.generalcable.com
SPEC E075
January, 2010
NUMBER OF CONDUCTORS
AWG/kcmil 1 2 3 4 5 6
18 13 26 39 41 52 62
16 20 40 60 65 81 97
14 33 66 99 105 132 158
12 52 104 157 167 209 251
10 83 166 249 266 332 399
8 132 264 396 423 528 634
6 210 420 630 672 840 1008
4 334 668 1002 1069 1336 1603
2 531 1062 1593 1699 2124 2548
1 670 1339 2009 2142 2678 3214
1/0 845 1690 2534 2703 3379 4055
2/0 1065 2130 3194 3407 4259 5111
3/0 1342 2685 4027 4296 5370 6444
4/0 1693 3386 5078 5417 6771 8125
250 2000 4000 6000 6400 8000 9600
350 2800 5600 8400 8960 10000 10000
500 4000 8000 10000 10000 10000 10000
750 6000 10000 10000 10000 10000 10000
1000 8000 10000 10000 10000 10000 10000
The maximum allowable pulling tensions are for direct attachment to the conductor.
T = 0.008 x cmil x n, if n ≤ 3
T = 0.008 x cmil x n x 0.8, if n > 3
Phone: 888-593-3355
www.generalcable.com
SPEC E075
January, 2010
Number Of Conductors 18 16 14 12 10
2 26 40 66 104 166
3 39 60 99 157 249
4 41 65 105 167 266
5 52 81 132 209 332
6 62 97 158 251 399
7 73 113 184 293 465
8 83 129 210 334 531
9 93 145 237 376 598
10 104 161 263 418 664
12 124 194 316 502 797
14 145 226 368 585 930
15 156 242 395 627 996
16 166 258 421 669 1000
18 187 290 473 752 1000
19 197 306 500 794 1000
20 207 323 526 836 1000
22 228 355 549 919 1000
24 249 387 631 1000 1000
25 259 403 658 1000 1000
30 311 484 789 1000 1000
37 383 596 974 1000 1000
The maximum allowable pulling tensions are for multi conductor cables pulled into a raceway or cable tray using a basket grip or similar device secured directly to the cable jacket.
It is recommended that a combination of basket grips and pulling eyes be used whenever possible.
T = 0.008 x cmil x n, if n ≤ 3
T = 0.008 x cmil x n x 0.8, if n > 3
Phone: 888-593-3355
www.generalcable.com
SPEC E125
January, 2011
Overview
Sidewall bearing pressure (SWBP), or sidewall
loading, is the radial force exerted on a cable
being pulled around a conduit bend or sheave.
Excessive SWBP can crush a cable and is,
therefore, one of the most restrictive factors in
installations having bends and requiring high
pulling tensions. SWBP is reduced by increasing
the radius of bends. Tension
The maximum tension that can safely be applied
to the cable during installation can be calculated
using the maximum SWBP for the cable and the
radius of the bend it is traversing.
For example, a cable having a maximum SWBP
of 300 lb/ft that is being pulled around a bend
having a radius of 2 feet should have no more Sidewall Load
than 300 lbs/ft x 2 ft or 600 lbs tension applied
to it as the cable exits the bend.
Phone: 888-593-3355
www.generalcable.com
NUCLEAR
NUCLEAR