PROJECT TITLE: RIVERSIDE CITY ESTATE PHASDE 2

DOCUMENT TITLE: ELECTRICAL LOAD CALCULATION


DOCUMENT NUMBER: DOCX-1
SUMMARY
TOTAL CONNECTED TOTAL CONNECTED
APARTMENT NOS.
LOAD (KW) TRANSFORMER LOAD (KVA)
Ground floor 26.5296 24.84235294
First floor 29.376 7.9488
Water pump 0.00 0
TOTAL LOAD in kW 55.91 69.88
EQUIPMENT & ENTRANCE 60.00
PANEL AMPACITY (A) MCB 63A, with 500A Cu basbar
PUMPS
Description No's Wattage (kW)
Water pump 0 1.1 -
Storm 0 0.5 -
Pool pump 0 0.5 -
Fire pump 0 7.5 -
STP 0 5.5 -
Total Power for the Pump -
Simultaneous Factor(100%) 1
Load factor (100%) 1
Cos φ 0.85
Frequency 50
Voltage 230
Max.simultaneous absorbed power (kW) -
Max. simultaneous transformer load (kVA -
Sub-Panel Ampacity (A) -
Rated MCB -
LOAD CALCULATION -RIVERSIDE CITY ESTATE GROUND FLOOR
i. Lighting Loads
Luminaire Technical Specification No's Wattage Total

60 W 220V SPOT LIGHT CEILING 24 60 1440


46 W 220V PENDANT LIGHT CILING 3 46 138
PARKING LIGHT 2 36 72

WATER PROOF ROUND LED PANEL LIGHT 300X300MM 25 18 450


Lighting Loads Total in W 450.0
Simultaneous Factor 0.8
Load Factor 1
Cos φ 1
Frequency 50Hz
Voltage (V) 230
Max.simultaneous Load in (kW) 0.36
Max. Simultaneous Transformer load (kVA) 0.36
ii.Small Power =<1500W Estimated Loads.
Description No's Wattage Total
Power Socket 1P,230V,16A 15 1500 22,500.0
Power Socket 1P,230V,32A 3 3680 11,040.0
iii. Connected Loads - Estimation
Refrigirator 1 4000 4,000.0
Cooker Units- Gas and Electricity 1 1750 1,750.0
Water Heaters 0 2100 -
Washing Machine 0 1850 -
Cooker Units- Electricity Only 1 13500 13,500.0
Small Power Sockets Total Loads in (kW) 33,540.0
Total Connected Loads in (kW) 19,250.0
Simultaneous Factor 0.4
Load Factor (100%) 0.6
Cos φ 0.85
Voltage
Max.simultaneous absorbed power (kW) 12.7
Max. simultaneous transformer load (kVA) 14.9
Max.simultaneous absorbed power (kW) 13.5
Max. simultaneous transformer load (kVA) 24.8
Total Power in kW 26.5
Sub-Panel Ampacity (A) 98.04
Rated MCB 100.00
LOAD CALCULATION -RIVERSIDE CITY ESTATE FIRST FLOOR
i. Lighting Loads
Luminaire Technical Specification No's Wattage Total

60 W 220V SPOT LIGHT CEILING 54 60 3240


46 W 220V PENDANT LIGHT CILING 5 46 230
PARKING LIGHT 2 36 72

WATER PROOF ROUND LED PANEL LIGHT 300X300MM 27 18 486


Lighting Loads Total in W 486.0
Simultaneous Factor 0.8
Load Factor 1
Cos φ 1
Frequency 50Hz
Voltage (V) 230
Max.simultaneous Load in (kW) 0.39
Max. Simultaneous Transformer load (kVA) 0.39
ii.Small Power =<1500W Estimated Loads.
Description No's Wattage Total
Power Socket 1P,230V,16A 21 1500 31,500.0
Power Socket 1P,230V,32A 0 3680 -
iii. Connected Loads - Estimation
Refrigirator 0 4000 -
Cooker Units- Gas and Electricity 0 1750 -
Water Heaters 0 2100 -
Washing Machine 0 1850 -
Cooker Units- Electricity Only 0 13500 -
Small Power Sockets Total Loads in (kW) 31,500.0
Total Connected Loads in (kW) -
Simultaneous Factor 0.4
Load Factor (100%) 0.6
Cos φ 0.85
Voltage
Max.simultaneous absorbed power (kW) 7.6
Max. simultaneous transformer load (kVA) 8.9
Max.simultaneous absorbed power (kW) -
Max. simultaneous transformer load (kVA) 14.8
Total Power in kW 7.9
Sub-Panel Ampacity (A) 29.38
Rated MCB 32.00