MC Installation Guide Southwire
MC Installation Guide Southwire
APPLICATION GUIDE
PVC Jacketed
Feeder MC Cable
1
PURPOSE OF THIS GUIDE
This guide provides engineers and contractors with essential information on the basic applications, selection,
and installation of MC feeder cables including MEGA MC™ cable, Riser MC™ High Rise cable, and PVC Jacketed
Feeder MC cable. Southwire can provide additional support and/or consulting services for specific applications.
Electrical contractors have used smaller MC cables for branch circuits for many years. The industry is now
using more large MC feeder cable. These large cables offer the owners and contractor the same advantages as
found with the smaller MC cable branch circuits, and are now being used in most types of commercial construction,
including apartments, condominiums, hotels, stadiums and office buildings.
MC feeder cables provide a neat and orderly appearance, alternative to pipe and wire. This guide should address
most concerns about handling and installing these large MC feeder cables.
2
1
MC CABLE ADVANTAGE
Using Type MC cable, contractors can install multiple conductors with professional-looking, owner-satisfying
appearance in less time than it takes to hang empty conduit.
Feeder MC cables can include up to five conductors plus a ground wire in wire sizes up to 1000 kcmil in a tough,
flexible aluminum armor. MC cable puts an entire 600 volt feeder circuit into a single, rapid-installation assembly
that is NEC® compliant for high-rise buildings, assembly halls, and many hazardous locations.
MC CONDUIT
Requires “neat and workmanlike” installation YES YES
Required supports 6 Feet 10 Feet
(maximum length between supports)
Support with clamps and trapeze YES YES
Assembly tested YES NO
Unlimited number of bends YES 360˚ Maximum
Note: Beginning with the 2014 National Electrical Code (NEC), article 330.30(B) allows for listed MC Cables
(including Riser MCTM High Rise Cable) with ungrounded conductors 250kcmil and larger to be secured at intervals
not exceeding 10 feet in vertical installations. Prior to the 2014 NEC, this securing requirement was every 6 feet.
32
TABLE OF CONTENTS
SECTION 1. PRE-ORDER, PRE-INSTALLATION CHECK LIST
DETERMINING CONDUCTOR TYPES.................................................................................................................. 6
Copper conductors.................................................................................................................................6
8000 Series aluminum alloy conductors..................................................................................................7
NUMBER OF CONDUCTORS IN ASSEMBLY, AND CABLE LENGTH........................................................................7
PARALLEL CIRCUITS.........................................................................................................................................7
REFERENCE INFORMATION...............................................................................................................................8
NEC® Table 250.122 Minimum Size Equipment Grounding Conductors
for Grounding Raceway and Equipment....................................................................................................8
CABLES FOR DIRECT BURIAL OR CONCRETE ENCASED.....................................................................................8
CABLES FOR VERTICAL RUNS...........................................................................................................................8
MC CABLE FITTINGS.........................................................................................................................................8
MAXIMUM REEL SIZES.....................................................................................................................................9
CABLE SUPPORT SYSTEM.................................................................................................................................9
ROLLERS AND SHEAVES NEEDED FOR INSTALLATION.......................................................................................9
4
3
TERMINATING MC CABLES.............................................................................................................................18
Cable fittings.......................................................................................................................................18
Transitions and splicing........................................................................................................................18
Hardware manufacturers.......................................................................................................................19
REFERENCE INFORMATION............................................................................................................................19
Support in Vertical Raceways................................................................................................................19
NEC® 330.24 Bending Radius.............................................................................................................19
NEC® 330.30 Securing and Supporting................................................................................................19
54
SECTION 4. ANNEXES
ANNEX A. CALCULATING ROLLER SPACING AND CABLE PULLING TENSION.....................................................31
Roller spacing calculations ...................................................................................................................31
Pulling tension calculations ..................................................................................................................31
Maximum tension on conductors...........................................................................................................32
Pulling tension calculations..................................................................................................................32
Multiple conductors.............................................................................................................................33
Horizontal straight sections...................................................................................................................33
Inclined straight section........................................................................................................................33
Vertical sections...................................................................................................................................33
Tension in bends .................................................................................................................................33
Tension entering cable pull...................................................................................................................34
Feeding off reel horizontally .................................................................................................................34
Feeding off reel vertically .....................................................................................................................34
ANNEX B. CABLE SPECIFICATION
Type MC Feeder Cable .........................................................................................................................35
Part 1 - General.......................................................................................................................35
Part 2 - Product.......................................................................................................................36
Part 3 - Installation..................................................................................................................37
ANNEX C. PRODUCT DATA SHEETS
Armorlite® MC Cable with Alumaflex® Brand Triple E® THHN/THWN-2 Conductors......................................38
Armorlite® PVC Jacketed Feeder MC Cable with Alumaflex® Brand Triple E® THHN/THWN-2 Conductors.......42
Armorlite® Riser MC™ Cable with Alumaflex® Brand Triple E® THHN/THWN-2 Conductors...........................46
Armorlite® MC Cable with Alumaflex® Brand Triple E® XHHW-2 Conductors................................................48
Armorlite® PVC Jacketed MC Cable with Alumaflex® Brand Triple E® XHHW-2 Conductors............................50
Armorlite® Feeder MC Cable with Copper Conductors................................................................................52
Armorlite® PVC Jacketed MC Cable with Copper Conductors......................................................................55
Armorlite® Riser MC™ Cable with Copper THHN/THWN-2 Conductors........................................................58
6
5
SECTION 1. PRE-ORDER,
PRE-INSTALLATION CHECK LIST
Like conduit, MC cable installations must look neat and workmanlike for owner satisfaction, as well as
codecompliance. Plan for runs that lay either parallel or perpendicular to walls. Keep groups of cable evenly
spaced and parallel around bends. In the end, total labor for an attractive MC cable installation will be
significantly lower than an equivalent pipe-and-wire installation.
The following questions must be answered before installing MC feeder cable. This section will cover each of these
items in more detail.
Conductor sizes – Copper conductors are available in sizes 1 AWG through 750 kcmil.
Bare or insulated ground conductors – MC cable assemblies that use copper conductors sized 1/0 AWG
and larger will have bare copper ground conductors as standard construction. Cables that use copper
conductors 1 AWG or smaller have green insulated ground conductors as standard construction.
Insulated ground conductors or additional ground conductors can be supplied in any MC cable.
76
8000 SERIES ALUMINUM ALLOY CONDUCTORS
Southwire’s MC cable with aluminum alloy conductors uses Southwire’s patented Alumaflex® 8000
Series (AA8176) aluminum alloy. Insulation is either type XHHW-2 insulation, rated 90°C in wet* or dry
locations, or THHN/THWN insulation, rated 90ºC dry/75ºC wet. Triple-e® conductors have delivered
reliable power for many decades, and match copper for connectivity, torque retention and yield strength.
Number of insulated conductors – Standard MC cables are available with either three or four
insulated conductors. Custom cables are available.
Conductor sizes – Alumaflex® brand aluminum conductors are available in sizes 6 AWG through 1000 kcmil.
Bare or insulated ground conductors – MC cable assemblies with insulated aluminum conductors will
provide bare aluminum alloy grounding conductors as standard construction. MC cable with aluminum
conductors can also be supplied with copper equipment grounding conductor(s). Insulated grounding
conductors or additional ground conductors can be supplied in any MC cable. These constructions may
be subject to Southwire manufacturing lead time and minimum order quantities.
Terminating lugs for aluminum conductors – When converting a project from copper conductors to
aluminum conductors, the aluminum conductors’ overall size will be larger. When terminating at
panels and switch gear, it is important to make sure that the lugs are sized for the aluminum conductor.
Example:
When converting a project from 500 kcmil copper to 750 kcmil aluminum alloy, make sure that the
lugs are sized for the larger 750 kcmil conductor. Equipment must be UL listed with the larger lugs.
If time permits, before ordering switchgear, let the manufacturer know that you plan on using
aluminum alloy conductors.
First find out whether the installation is single-phase or three-phase. This will determine whether MC cables
will need three or four insulated conductors plus ground. Remember the equipment grounding conductor
usually will be bare. Insulated grounds are available.
When measuring the overall feeder length required for a particular run, calculate the total cable required,
then add in an additional make-up length. As rule of thumb, add twice the distance from floor to ceiling for
make-up lengths.
PARALLEL CIRCUITS
NOTE: This is very important!
Each MC cable in a parallel run must have the correct equipment grounding conductor included inside
the MC cable. The equipment grounding conductor must be sized to match the upstream over-current
protection device as provided in NEC® Table 250.122. Cables with undersized grounds will not meet
code and the installation will be rejected by the electrical inspector. See NEC® 250.122 Minimum Size
Equipment Conductors For Grounding Raceway and Equipment on page 9.
*Wet loacations require an overall PVC jacket per UL 1569 & NEC® 330
8
7
REFERENCE INFORMATION
NEC® TABLE 250.122 - MINIMUM SIZE EQUIPMENT GROUNDING
CONDUCTORS FOR GROUNDING RACEWAY AND EQUIPMENT
RATING OR SETTING OF AUTOMATIC OVERCURRENT DEVICE IN SIZE (AWG or kcmil)
CIRCUIT AHEAD OFEQUIPMENT, CONDUIT, ETC., MOT EXCEEDING
(AMPERES) COPPER ALUMINUM OR COPPER-CLAD ALUMINUM*
15 14 12
20 12 10
60 10 8
100 8 6
200 6 4
300 4 2
400 3 1
500 2 1/0
600 1 2/0
800 1/0 3/0
1000 2/0 4/0
1200 3/0 250
1600 4/0 350
2000 250 400
2500 350 600
3000 400 600
4000 500 750
5000 700 1200
6000 800 1200
Note: Where necessary to comply with 250.4 (A)(5) or (B)(4), the equipment grounding conductor shall be sized larger than
given in the table. *See installation restrictions in 250.120. Reprinted with permission from NFPA, 70-2017, the National Electrical Code®
Copyright 2016, National Fire Protection Association MA 02169. This reprinted material is not the official position of the NFPA on the
referenced subject which is represented solely by the standard in its entirety.
MC CABLE FITTINGS
MC cable must be installed using fittings that are UL listed for this product. Fittings that are only listed for Flexible Con-
duits are not permitted to be used on MC cables. Listed MC cable fittings provide a shoulder that protects conductors from
any sharp edges in the armor. Anti-short bushings are not required by the NEC® for MC cables. MC cable fittings are avail-
able for wet and dry locations, in hub sizes from 1 to 3 inches, and several armor diameter ranges. Section 2 gives more
detail on selection and use of MC cable fittings.
98
MAXIMUM REEL SIZE
Southwire can ship MC feeder cable on many different reel sizes. Large reels may require that the contractor have
appropriate handling equipment on the job site to move reels once they are delivered. It is also important to
consider the dimensions of doorways, elevators, etc. Southwire can provide information on reel sizes and weights
when the jobsite order is quoted.
The number of bends in an MC cable pull will be dictated by the need for a neat, workmanlike installation. Like
conduit, MC cable installations must look neat for owner satisfaction. Plan for runs that lie either parallel or
perpendicular to walls. All UL Listed Type MC cables, including MEGA MC™ cable, Riser MC™ High Rise cable, and PVC
Jacketed Feeder MC cable are subject to a minimum bend radius of seven times the OD of the finished cable (per NEC
330.24(B)).
Pre-plan the number and location of rollers, sheave wheels or radius roller assemblies, if they are required.
Rollers and sheave assemblies must be ordered in time to have them available for the actual installation.
All of these factors will be important in planning the actual cable pull as described in Section 2,
“Cable Rigging and Installation.”
CAUTION
To meet NEC requirements and to avoid cable damage, each bend must have a final installed radius
®
that is at least seven times the diameter of the MC cable being installed. Pulling radius may need to be greater.
10
9
SECTION 2. CABLE RIGGING
AND INSTALLATION
Remember, code compliance is not the same as owner satisfaction for either MC cable or conduit. MC cable
installations with parallel and perpendicular layouts can look just as good as conduit, with less effort.
In applications where the appearance of the MC cable is particularly important, supports installed closer
than the required 6-foot intervals may be recommended. The use of these additional supports will reduce
cable sag and provide a neater installation.
Supporting MC cable in vertical applications – Southwire’s UL Listed Riser MC™ High Rise cable is specifically designed
for use in vertical installations to eliminate the need for additional conductor supports, offsets, or junction boxes
that would otherwise be required per NEC® 300.19. Riser MC™ cable includes a polymeric binder jacket under
the armor and over the conductors that provides continuous support for the conductors throughout the entire
length of the cable. Per NEC® 330.30, MC cables in vertical applications shall be secured at intervals not
exceeding 10 feet for cables with ungrounded conductors sized 250kcmil and larger.
Standard MC cables are not designed to support the cable weight in long vertical installations. Long vertical runs of
standard MC cables must meet the same requirements used for supporting conductors in vertical raceways shown in
NEC® Table 300.19(A). In addition, NEC® Article 392 also requires MC cable to be secured in vertical cable tray
installations. For special riser-cable construction of MC cable, exceptions can be made to these vertical support
distance requirements in Table 300.19(A).
Using standard MC cable, you may be able to meet the support requirements of Table 300.19(A) by pulling horizontal
offsets in the cable at the required vertical distance. Be sure to verify that offsets will meet local inspection
requirements. Consult with the MC cable manufacturer for other alternatives for supporting large sized MC cable
in long vertical runs. See Support In Vertical Raceways page 19.
11
10
Channel struts and threaded rod — For trapeze installations, use channel struts supported by threaded
rods that are hung from anchors set in concrete or attached to building supports. To install the anchors:
• Drill a hole with the diameter of the anchor. Make the hole deeper than the length of the
anchor or screw.
• Clean the debris from the hole and drive the rod hanger into the hole.
• Thread the rod in the hanger and bolt the strut to the other end of the threaded rod.
• Follow manufacturer's recommendations to ensure hangers are secure.
MC cable using strut support systems MC cable using trapeze support system
Straps and cable clamps — A variety of straps, clamps, staples and hangers are available to secure specific
sizes of MC cable directly to the supporting surface. Before ordering clamps make sure that you have
selected the correct clamp size. Verify the overall dimensions of the MC feeder cable and compare them with the
published clamp sizes. Use any of these supports only for the MC cable size indicated on the hardware or
on the support packaging. In vertical applications, NEC® 330.30 allows MC cable to be secured at intervals
not exceeding 10 feet for cables with ungrounded conductors sized 250kcmil and larger.
MC cable secured every 6’ with straps and clamp MC cable secured every 6’ with straps and clamp
Cables containing four or fewer conductors smaller than 10 AWG must be secured within 12 inches of every
termination. (There are some exceptions in NEC® Article 330.30 Securing and Supporting on page 19.)
12
11
Basket type wire mesh – Basket type wire mesh cable supports — also called wire basket support
systems — are gaining acceptance as a dedicated support system. These basket trays are
lightweight and easy to install. They can be used for either vertical or horizontal installations.
When used as a support system, they are not classified as cable trays in the NEC® handbook.
A common misconception about basket type wire mesh supports is that these systems are classified as
a cable tray installation and must be installed and inspected per NEC® Article 392. MC cable installa-
tions using wire mesh support systems are not required to meet the requirements outlined in Article 392.
This is because wire mesh systems are considered an exposed installation. MC cable installed using a
wire basket support system is required to be secured to the basket system every 6 feet. If MC cable is
installed per Article 392, securing every 6 feet is no longer required.
See NEC® 330.30 Securing and Supporting on page 19.
NEMA Standards Publication VE 2-2001, Cable Tray Installation Guidelines, provides installation
instructions for wire mesh support systems as well as other types of cable tray systems.
Be sure that sheaves and rollers are mounted securely to withstand the required pulling forces. Sheave
wheels, pulleys and rollers must be maintained and lubricated to reduce friction.
13
12
Pulley sizes and count – No two pulls are alike. Some pulls require tuggers, and some can be done by hand.
The size and the number of pulleys needed depend on the size of the conductors and length of the pull.
Example:
When installing a 750 kcmil, three-conductor aluminum alloy MC feeder
cable, a radius roller may be required instead of an individual sheave wheel.
The overall diameter of the 750 kcmil three-conductor cable is approximately 2.674 inches. The minimum
bending radius for MC cable per NEC® Section 330.24 is seven times the cable’s overall diameter
(7 x 2.674 inches = 18.72 inches). The required diameter of an individual sheave wheel for this bending
radius is 2 x 18.72 = 37.44 inches. Most manufacturers do not make individual wheels larger than 36
inches, therefore a radius roller assembly that gives a bending radius of 38 inches or larger is required.
Sheave wheel sizes and types – When pulling cable around bends, large sheave diameters will reduce the
amount of sidewall pressure created at each bend. If you have a large bending radius you may not be able
to find a radius roller large enough to meet the required bending radius for this installation. Large cables
1 AWG – 750 kcmil may require the use of radius rollers, in which are multiple wheels mounted together
provide the required bend radius.
Individual sheaves should have a minimum inside radius of 1.25 inches. Sheave or radius rollers should
be located every 20 degrees of bend.
Roller spacing and mounting – Roller spacing varies with cable weight, cable tension and cable
construction. For heavy cables or long pulls, the equation in Annex A, “Calculating Roller Spacing and Cable
Pulling Tensions,” will help calculate roller spacing. To check the calculated value, use a length of cable to
determine maximum spacing under no tension. In general, position rollers so that cables do not drag across
surfaces, or rub against objects that can be damaged or that can damage the cable.
14
13
PREPARING MC CABLE FOR INSTALLATION
Prior to pulling MC cable, prepare the end by stripping the armor back to the insulated conductors for a length
of two to three feet.
Cutting and stripping MC cables – Take special care when cutting the armor on MC cable. Ensure that the cut
does not penetrate the conductors under the armor. Here are two common methods of cutting MC cable armor:
The three most common tools used for cutting MC cable are the rotary cutter, ring cut saw, and the hacksaw.
Size and type of the cable determines the cutting tool you choose.
Motorized ring cut saws deliver fast cutting for both lengthwise cuts and ring cuts. They handle cable
up to 5 inches in diameter.
15
14
(C) HACKSAW
Use a sharp hacksaw blade with at least 32 teeth per inch to cut any size of armored cable.
You will need a heavy-duty frame to hold the cable taut.
(1) Secure the cable in a vise or support.
(2) Cut two adjacent convolutions at approximately 60 degrees (illustration).
(3) Remove the cable from the vise.
(4) Grip the cable on each side of the cut, twist and slide off the armor.
Using hacksaw to cut two adjacent convolutions Removing mylar tape from conductors
CAUTION
Cutting MC cable armor may leave sharp edges. Always protect
your hands and arms with protective sleeves and work gloves.
PULLING MC CABLE
Assessing the pull – Begin planning an MC cable pull by assessing the difficulty of the pull. The vast
majority of MC cable pulls are less than 200 feet, with only a few bends. These installations generally require
no calculations of pulling tension and sidewall pressure. This section will give some general guidelines and
considerations for simple pulls. For more complex installations, refer to Annex A, "Calculating Roller Spacing
and Cable Pulling Tensions," in the back of this book.
General caution about bending radius and sidewall pressure – The robust construction of MC cable does not
mean that it is indestructible. To protect the cable while pulling, you must configure sheave wheels, pulleys
and rollers to prevent damage to the cable from bending or excessive sidewall pressure.
Bending radius for permanent training – Before the cable is pulled in, check the radius of each bend that
will be in the cable after installation. The minimum allowable bending radius for cable with interlocked armor
or corrugated continuous welded armor cable is seven times the overall diameter of the cable (per NEC®
330.24). Cables with smooth (non-corrugated) continuous welded armor require a minimum bend radius of
10 to 15 times the overall diameter of the cable. As long as you observe the limits on pulling tension and
sidewall pressure, there is no restriction on the number of bends in an MC cable installation.
16
15
Bending radius for cable under tension – When pulling MC feeder cable, the factor that limits pulling
tension is usually the pressure exerted on the cable sidewall when pulling around bends.
When MC cable is pulled around a bend, the pulling tension causes pressure on the sidewall
of the cable. Sharp bends concentrate the sidewall pressure in a small area, so larger radiuses
allow higher pulling tensions.
When pulling MC cable through a series of bends, pulling tension is cumulative. If the radiuses are
all equal, the first bend will see the least tension and create the least sidewall pressure. As the cable
goes through the last bend of a series, it is subjected to all the tension required to pull it through
the earlier bends. The result is that the last bend typically will have the most tension and the most
sidewall pressure.
To avoid cable damage, it’s important to make sure that the radiuses around all bends are large
enough to keep the pressure on the cable sidewall within recommended limits. A typical sidewall
bearing pressure limit for Type MC cable is 300 pounds of pulling tension per foot of bend radius.
By this rule of thumb, a 36-inch bend radius would limit the pulling tension to 900 pounds.
If there is any question about the sidewall pressure and pulling tension with MC feeder cables, please
refer to Annex A, “Calculating Roller Spacing and Cable Pulling Tensions.” These calculations will help
to determine whether your pull will be easy, difficult or impossible. If you have further questions, or
need additional help concerning your particular installation, please contact your Southwire Project Engineer.
17
16
Securing pull rope – To pull MC feeder cable into position, first secure the pull rope to the cable. The best way to
do this is by securing the pull rope to the conductor assembly and then tape the armor to the conductors.
For any MC cable installation method, all pulling forces should be exerted directly on the conductors.
Neverapply pulling forces directly to the armor or binder jacket. Always refer to the pulling equipment
and accessories manufactures’ instructions for proper installation and pulling information.
Securing pull rope to cable assembly Securing basket grip to conductor assembly
to avoid pulling conductors out of armor
Method 3: Using a wire-mesh grip or pulling eye This method provides greater strength than Method 2.
• Attach a pulling eye to the core conductors.
• Attach a grip over the armor to prevent it from sliding back.
• Expect some damage to the conductors under the grip. Remove the damaged conductor
ends after pulling.
Installation tip: Attach a pull-back cord to the pulling eye on the cable and pull the cord
through with the cable. Then use the pull-back cord to get rope back quickly to start next pull.
18
17
TERMINATING MC CABLES
Cable fittings – MC cable must be installed using fittings specifically designed and listed for this type of cable.
Be sure to order the proper fittings for the planned installation.
With Riser MC™ cable - Southwire’s Riser MC™ cable is UL Listed as Type MC and can be used with any NEC
compliant fittings, clamps, straps, hangers, etc provided that they are appropriately sized for the Riser MC™ cable
OD. When terminating Riser MC™ cable, the binder jacket should be removed flush with the end of the armor prior
to installing the fitting.
Transitions and splicing – In general, MC cable requires fewer splices when compared to conduit and wire
installations. Occasionally, you will need to splice or transition from one wiring method to another wiring
method, such as from a conduit system to a MC cable. This transition will require a junction box.
Hardware manufacturers – Here is a partial list of hardware manufacturers for MC cable. This list is not all-
inclusive, but is meant to help the installer find the hardware needed for a complete installation.
19
18
S T A N D A R D M E G A M C™ C A B L E S U P P O R T I N V E R T I C A L R A C E W A Y S * * *
SIZE OF WIRE ALUMINUM COPPER
(feet) (feet)
18 AWG through 8 AWG 100 100
*** The information contained in this table applies to standard MEGA MC™ cable constructions.
Southwire’s Riser MC™ cable construction is not subject to the requirements of this table because
the conductors are supported continuously throughout the entire length of the cable.
20
19
SECTION 3. APPLICATION
AND DESIGN GUIDE
There are a variety of applications that are suitable for MC cable installations. All MC cable installations
are required to meet both NEC® and UL requirements. When designing an installation using MC cable it is
important to define “neat and workmanlike” installations in the design specification.
• Wet Locations
• Direct burial
• Embedded in concrete
• Vertical installations
In addition, both jacketed and non-jacketed MC cable can be used in many UL fire-rated building assemblies.
Wet locations – The NEC® in 330.10(A) (11) allows MC cable to be used in wet locations when the insulated
conductors under the metallic covering and the overall jacket are listed for use in wet locations. Cable
manufacturers recommend a jacket over the armor and that the insulated conductors under the metallic
covering are listed for use in wet locations. The most commonly used conductors in MC cable are THHN/THWN
and XHHW. The jacket provides protection for the armor against the possible development of a corrosive cell
and limits the amount of water the conductors are subjected to under the armor.
Direct burial – Direct burial is a cost-effective approach for projects. Direct buried installations are considered
wet locations and require the conductors to be UL - listed for use in wet locations.
You can use jacketed MC cable as direct-buried underground services, feeders and branch circuits. Labeling
on the jacket of the cable must identify it as listed for direct burial. The label must read either “FOR DIRECT
BURIAL,” “DIRECT BURIAL,” “DIR BUR” or “DIR BURIAL.”
Concrete encased – The NEC® handbook states that jacketed MC cable identified for direct burial applications is suitable
for installation in concrete. Again, the jacket provides protection to the metal armor.
Vertical Installations – Southwire’s patented Riser MC™ High Rise cable is designed specifically for installation in vertical
applications without the need for offsets or junction boxes. Riser MC™ High Rise cable is UL Listed as Type MC cable
and may be used with any fittings, straps, clamps, hangers, etc that are NEC compliant with standard MC cable
installations. Additionally, Riser MC™ High Rise cable is subject to the same bend radius requirements as standard MC
cable – 7 times the cable OD.
21
20
When embedding MC cable in concrete, inform other trades about the installation, so they can take
appropriate care to protect the cable from damage. One way to inform other trades, when using reusable
concrete forms, is to spray paint the inside of the form along the path of the MC cable. When the form is
removed, the paint should adhere to the concrete, marking the location of the MC cable in the concrete.
NOTE: NEC® Article 390 for under floor raceways also covers Trench-Type Raceways Flush with Concrete
GROUNDING CONSIDERATIONS
NEC® Section 330.108 requires that Type MC cable
provide an adequate path for equipment grounding.
The method used to achieve adequate grounding depends NEC® 330.108 - WHERE TYPE MC CABLE IS
on the construction of the cable. Standard interlocked USED FOR EQUIPMENT GROUNDING; IT SHALL
armor construction requires an equipment grounding COMPLY WITH 250.118(10) AND 250.122
conductor in the cable. The conductor may be bare or
green insulated.
The equipment grounding conductor of Southwire Type MC cable can be configured either as a single
conductor or as multiple equal-sized conductors whose sum is equal to or larger than the required size.
In either case, the grounding capacity is sized in accordance with NEC® requirements (NEC® 250.122).
Other available MC cable constructions may also provide additional equipment grounding conductors that may
be used for isolated or redundant grounding.
Equipment grounding conductors for cables in parallel circuits – NEC® Section 250.122 requires that
parallel conductors have an equipment grounding conductor sized according to the rating or setting of the
overcurrent device.
22
21
When designing applications with paralleled Type MC cables, the equipment grounding conductor size should be
specified large enough to meet the requirements of NEC® 250.122. See NEC® Table 250.122 Minimum Size
Equipment Grounding Conductors for Grounding Racway and Equipment on page 9. Southwire has special
constructions available to meet these requirements for high ampacity paralleled circuits.
NOTE: An external equipment ground cannot be used for paralleled circuits using MC cables.
MC CABLE REPAIR
Proper working practices will minimize installation damage to MC cable. When cable damage does occur,
replacement is recommended. When replacing the cable is not an option, follow the suggestions below
for repair.
• Examine the cable to ensure the conductors under the armor have not been damaged
• It’s best to obtain approvals for repairs on MC cable before making the repair. Inform
the authority with jurisdiction and the owner’s representative of the need for repair.
• Obtain repair kits and materials from distributors who service industrial accounts.
• Follow the manufacturer’s instructions provided with the repair materials.
• Before the repair, protect the damaged cable against the ingress of water.
• Make the repair watertight. Use a shrinkable covering or electrical tape.
Always maintain or re-establish the electrical continuity and physical protection afforded by the armor prior to the
damage. To re-establish the electrical continuity of the armor, use bonding straps with constant tension springs.
Provide mechanical protection for the underlying conductors.
NEC® COMPLIANCE
NEC® uses permitted – NEC® Section 330.10 allows MC cable in indoor and outdoor applications including:
exposed or concealed services, feeders and branch circuits, power, lighting, control and signal circuits. When
properly jacketed and listed, MC cable can be used in wet or dry locations, direct buried, embedded in concrete,
installed in cable trays and raceways, and hung from a messenger as aerial cable. MC cable is also permitted in
many hazardous location applications.
The list of permitted uses in Section 330.10 is not all-inclusive. The code language is intended to provide
guidance on where and how the cable may be used. See NEC® 300.10 Uses Not Permitted page 28.
NEC® uses not permitted – Section 330.12 of the NEC® handbook specifies uses of Type MC cable that are not
permitted. As with permitted uses, this list is not all-inclusive. In particular, note that the introductory sentence
contains the phrase, “unless the metallic sheath is suitable for the conditions or is protected by material suitable
for the conditions.” This is the clause that allows jacketed MC cable to be used in direct burial, embedded in concrete,
and in corrosive environments. Type MC cable used in these applications will typically have a nonmetallic covering,
such as a PVC jacket, over the metallic armor. See NEC® 300.12 Uses Not Permitted page 28.
23
22
NEC® references for Type MC cable – The following NEC® references for Type MC cable are provided as a
convenience. These references cover uses related to all Type MC cable designs, including smooth and corrugated
sheaths and interlocked armor constructions. As with all electrical installations, the cable system must meet
complete NEC® requirements, and be installed in compliance with the relevant UL listing and following the
manufacturers instructions.
24
23
Special occupancies
• ARTICLE 501, Class I Locations (Hazardous Locations)
502.10(A) Class I, Division 1
502.10(B) Class I, Division 2
• ARTICLE 502, Class II Locations (Hazardous Locations)
502.10(A) Class II, Division 1
502.10(A) Class II, Division 2
• ARTICLE 503, Class III Locations (Hazardous Locations)
503.10(A) Class III, Division 1
503.10(A) Class III, Division 2
• ARTICLE 518, Places of Assembly
518.4, Wiring Methods
• ARTICLE 520, Theaters, Audience Areas of Motion Picture and Television Studios
and Similar Locations
520.5, Wiring Methods
• ARTICLE 550, Mobile Homes, Manufactured Homes and Mobile Home Parks
550.16(A) (2), Grounding
• ARTICLE 551, Recreational Vehicles and Recreational Vehicle Parks
551.47(A), Wiring Methods
551.55(C), Interior Equipment Grounding
• ARTICLE 552, Park Trailers
551.48(A), Wiring Methods
551.56(C) (1), Interior Equipment Grounding
Special occupancies
• ARTICLE 610, Cranes and Hoists
610.11, Wiring Methods
• ARTICLE 620, Elevators, Dumbwaiters, Escalators, Moving Walks, Wheelchair Lifts,
and Stairway Lifts
620.21, Wiring Methods
620.81, Metal Raceways Attached to Cars
• ARTICLE 645, Information Technology Equipment
645.5, Supply Circuits and Interconnecting Cables
• ARTICLE 668, Electrolytic Cells, Interconnecting Cables
668.30(C), Fixed and Portable Electrical Equipment – Wiring Methods
• ARTICLE 680, Swimming Pools, Fountains and Similar Installations
680. 21(A) (1) and (4), Motors - Wiring Methods
680. 23(F) (1), Underwater Luminaires (Lighting Fixures) – Branch Circuit Wiring
25
24
UL COMPLIANCE
UL standards and directories – NEC® 110.3(B) states,“Listed or labeled equipment shall be installed and
used in accordance with any instructions included in the listing or labeling.” Underwriters Laboratories
publishes a number of standards and directories that provide detailed information on the construction,
performance, application, ratings, and installation aspects of Type MC cable.
The UL standard for the construction and performance of Type MC cable is UL 1569. NEC® Section 330.112
requires the insulated conductors used in MC cable in sizes 14 AWG and larger are to be of a type listed
in Table 310.13 or of a type identified for use in Type MC cable. Predominantly, Type MC cable contains
thermoplastic Type THHN/THWN conductors manufactured to UL 83 or thermoset type XHHW conductors
manufactured to UL 44.
UL directories contain information about the products that they list, recognize and certify. Installers and
inspectors use the directories for information on specifying and installing products in accordance with their
listing. These directories are helpful tools for understanding the details of how products such as Type MC
cable are constructed and marked. The directories also provide information on special or optional ratings, and
on terminations. One of the directories covers UL approved methods for maintaining the fire-resistive rating
on walls, floors, and ceilings in fire-resistance rated construction, when cables must penetrate them. This
information is readily available at the UL website, www.ul.com.
UL general information for electrical equipment – The following information on Type MC cable is reprinted
from the UL General Information for Electrical Equipment Directory. This information is needed to fully
understand the applications that metal clad cable can be used. The UL product information should be
used with the NEC® to assure proper use of the product. Updated information can be found at the UL’s
website, www.ul.com.
PJAZ
Metal Clad Cable
GENERAL
This category covers Type MC metal-clad cable. It is rated for use up to 2000 V, and listed in sizes 18 AWG through
2000 kcmil for copper, 12 AWG through 2000 kcmil for aluminum, or copper-clad aluminum, and employs thermoset
or thermoplastic insulated conductors. It is intended for installation in accordance with Article 330 of ANSI/NFPA 70,
“National Electrical Code” (NEC®).
The cable consists of one or more insulated conductors; one or more grounding conductors (required for interlocked
armor, as needed for smooth or corrugated tube); one or more optional optical fiber members; and an overall metal sheath.
The metal sheath is an interlocked metal tape, a corrugated metal tube, or a smooth metal tube. The metal sheath of
single-conductor cable is nonferrous. A nonmetallic jacket may be provided under and/or over the metal sheath. Cable with
metal armor, rated 5,000 to 35,000 V is covered under Medium-Voltage Cable (PITY) and is marked “Type MV or MC.”
Cable with interlocked armor that has been determined to be suitable for use as a grounding means has interlocked
aluminum armor in direct contact with a single, full-sized, bare aluminum grounding/bonding conductor. This cable is marked
to indicate that the armor/grounding conductor combination is suitable for ground. The equipment grounding conductor
required
within all other cable with interlocked armor may be insulated or bare, may be sectioned, and is located in the cable core
but not in contact with the armor. Any additional grounding conductors of either design have green insulation. One insulated
grounding conductor may be unmarked, one other may have only a yellow stripe and the balance have surface markings that
indicate they are additional equipment grounding conductors or isolated grounding conductors.
The sheath of the smooth or corrugated tube Type MC cable or a combination of the sheath and a supplemental bare or
unstriped green insulated conductor is suitable for use as the ground path required for equipment grounding.
The supplemental grounding conductor may be sectioned. When sectioned, all sections are identical. Each additional green
insulated grounding conductor has either a yellow stripe or a surface marking or both to indicate that it is an additional
equipment or isolated grounding conductor. Additional grounding conductors, however marked, are not smaller than the
required grounding conductor.
26
25
UL product markings – Information regarding temperature rating, voltage rating, cable, and conductor type and
size is shown either on a marker tape under the armor or on the surface of a nonmetallic jacket, if used. The
following product marking information is taken for the 2005 UL PJAZ Information Guide for Metal-Clad Cable.
Another resource for understanding cable markings is the UL Wire and Cable Marking Guide. This information
is readily available at UL’s website, www.ul.com.
UL listing information – UL listing information can be found at www.ul.com. This website contains all the
information from the referenced directories, as well as other general information relating to UL’s products and
services. This information is found in the UL online certification directory. The company name or keyword
search is usually the easiest way to start.
PRODUCT MARKINGS
Information regarding temperature rating, voltage rating, cable and conductor Type and AWG size is shown either on a
marker tape under the armor or on the surface of a nonmetallic jacket, if used.
Copper-clad aluminum conductors are surface printed “AL (CU-CLAD)” or “Cu-clad Al.” Aluminum conductors are
surface printed “AL.”
Cable employing compact-stranded copper conductors is so identified directly following the conductor size, wherever it
appears (surface, tag, carton or reel), by “compact copper.” The abbreviations “CMPCT” and “CU” may be used for
compact and copper, respectively.
Tags, reels and cartons for products employing compact-stranded copper conductors have the marking: “Terminate with
connectors identified for use with compact-stranded copper conductors.”
For termination information, see Electrical Equipment for Use in Ordinary Locations (AALZ).
Cable suitable for use in cable trays, direct sunlight or direct burial application is so marked. Cable marked for direct burial
is also considered acceptable for encasement in concrete.
Cable marked “Oil Resistant I” or “Oil Res I” is suitable for exposure to mineral oil at 60°C. Cable suitable for exposure to
mineral oil at 75°C is marked “Oil Resistant II” or “Oil Res II.”
Cable with a nonmetallic outer jacket that complies with the Limited Smoke Test requirements specified in UL 1685,
“Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables,” and all unjacketed metal-
clad cable may be marked with the suffix “LS.”
Cable with an interlocked armor that is intended as a ground path is marked “armor is grounding path component,” and is
provided with installation instructions.
2005 UL PJAZ.GuideInfo
Metal-Clad Cable
27
26
MC cable feeders and fire-rated assemblies – Standard MC cables order do not carry 1-, 2-, and 3- Hour Fire ratings.
Some walls, floors and ceilings are required by local building codes to have fire-resistance ratings.
These ratings designate resistance to the spread of fire in hours: There are one-, two-, and three-hour ratings.
Required fire ratings may appear on construction drawings. Southwire Type MC cable is listed for use in UL
1-, 2-, and 3- Hour Through-Penetration Fire Stop Systems.
The installation of MC cables or other wiring methods must not reduce or negate the rating of fire-rated
assemblies and must prevent the passage of smoke, gases and flames from one area to another.
Type MC cables are well suited for installation in fire-rated walls floors and ceilings. The required fire-
resistance can be obtained by sealing the openings around cables using a UL-listed method – such as fire
caulking or pads – where the cables pass through a rated wall, floor or ceiling.
Fire-rated assemblies – Fire rated assemblies are included in the UL’s Fire Resistance Directories. These
assemblies, which include the wiring methods permitted, have been tested to determine their fire resistance
as an asssembly. It is important to remember that no deviation can be made from the components used in the
assembly or from the manner in which they are installed.
Penetration fire-stop systems include specially designed components such as blocks with inserts where cables
in cable trays pass through fire rated walls. These components are installed on the job. These systems must
be installed in accordance with all applicable building codes as well as the instructions provided by the
manufacturer and in the product listing.
Be certain cables are protected from physical damage where they pass through floors. This protection can be
provided by installation in protective conduit sleeves.
Fire Resistance Directory – UL’s Fire Resistance Directory covers construction detail necessary for constructing
fire rated walls, floors and ceilings under the category “Through Penetration Fire Stop Systems.” The
Fire Resistance Directory also covers UL-listed materials and methods for sealing walls, ceilings , or floors
penetrated by electrical cables, conduit, cable tray or other equipment.
Always consult the Fire Resistance Directory for the proper method of sealing openings. Openings that are not
sealed in accordance with the UL listed “Throught-Prevention Fire Stop Systems” are subject to rejection by
inspecting authorities.
NOTE: The listed through-penetration fire stop systems can be found at www.ul.com
28
27
REFERENCE INFORMATION
FPN: The “Uses Permitted” is not an all-inclusive list. The permitted uses specified by the NEC® are not all-inclusive, but
only provide guidance on where and how the cable may be used.
Type MC cable shall not be used where exposed to the following destructive corrosive conditions,
unless the metallic sheath is suitable for the conditions or is protected by material suitable for the
conditions:
(1) Where subject to physical damage
(2) Direct burial in the earth
(3) In concrete
FPN to (3): MC cable that is identified for direct burial applications is suitable for installation in concrete
(4) Where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or
of hydrochloric
Reprinted with permission from NFPA, 70-2017, the National Electrical Code Copyright 2016, National Fire Protection
Association MA 02169. This reprinted material is not the official position of the NFPA on the referenced subject which is
represented solely by the standard in its entirety.
29
28
N E C ® TA B L E 3 1 0 . 1 5 ( B ) ( 1 6 ) ( F O R M E R LY TA B L E 3 1 0 . 1 6 ) A L L O WA B L E A M PA C I T I E S O F I N S U L AT E D
C O N D U C T O R S R AT E D U P T O A N D I N C L U D I N G 2 0 0 0 V O LT S 6 0 ° C T H R O U G H 9 0 ° C ( 1 4 0 ° F T H R O U G H
1 9 4 ° ) , N O T M O R E T H A N T H R E E C UR R E N T- C A R R Y I N G C O N D U C T O R S I N R A C E WAY, C A B L E , O R
E A R T H ( D I R E C T LY B UR I E D ) , B A S E D O N A M B I E N T T E M P E R AT UR E O F 3 0 ° C ( 8 6 ° F ) *
TEMPERATURE RATING OF CONDUCTOR [SEE TABLE 310.14(A)]
SIZE 60˚C (140˚F) 75˚C (167˚F) 90˚C (194˚F) 60˚C (140˚F) 75˚C (167˚F) 90˚C (194˚F) SIZE
AWG OR TYPES TW, UF TYPES RHW, TYPES TBS, SA, SIS, FEP, TYPES TW, UF TYPES RHW, TYPES TBS, SA, SIS, FEP, AWG OR
kcmil THHW, THW, FEPB, MI, RHH, RHW-2, THHW, THW, FEPB, MI, RHH, RHW-2, kcmil
THWN, XHHW, THHN, THHW, THW-2, THWN, XHHW, THHN, THHW, THW-2,
USE, ZW THWN-2, USE-2, XHH, USE, ZW THWN-2, USE-2, XHH,
XHHW, XHHW-2, ZW-2 XHHW, XHHW-2, ZW-2
COPPER ALUMINUM OR COPPER
18** – – 14 – – – –
16** – – 18 – – – –
14** 15 20 25 – – – –
12** 20 25 30 15 20 25 12**
10** 30 35 40 25 30 35 10**
8 40 50 55 35 40 45 8
6 55 65 75 40 50 55 6
4 70 85 95 55 65 75 4
3 85 100 110 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 145 85 100 115 1
1/0 125 150 170 100 120 135 1/0
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0
4/0 195 230 260 150 180 205 4/0
250 215 255 290 170 205 230 250
300 240 285 320 195 230 260 300
350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500
600 350 420 475 285 340 385 600
700 385 460 520 315 375 425 700
750 400 475 535 320 385 435 750
800 410 490 555 330 395 445 800
900 435 520 585 355 425 480 900
1000 455 545 615 375 445 500 1000
1250 495 590 665 405 485 545 1250
1500 525 625 705 435 520 585 1500
1750 545 650 735 455 545 615 1750
2000 555 665 750 470 560 630 2000
Reprinted with permission from NFPA, 70-2017, THE National Electrical Code® Copyright 2016, National Fire Protection Assiciation MA 02169.
This reprinted material is not the official position of the NFPA on the referenced subject which is represented solely by the standard in its entirety.
* Refer to 310.15(B)(2) for the ampacity correction factors where the ambient temperature is other than 30°C (86ºF) Refer to 310.15(B)(3)(a) for more than three
current-carrying conductors.
**Refer to 240.4(D) for conductor overcurrent protection limitations.
29
N E C ® TA B L E 3 1 0 . 1 5 ( B ) ( 2 ) ( a ) A M B I E N T T E M P E R AT UR E
C O R R E C T I O N FA C T O R S B A S E D O N 3 0 ° C ( 8 6 ° F ) *
FOR AMBIENT TEMPERATURES OTHER THAN 30° C (86°), MULITPLY THE ALLOWABLE AMPACITIES
SHOWN ABOVE BY THE APPROPRIATE FACTOR SHOWN BELOW)
31
30
SECTION 4. ANNEXES
ANNEX A. CALCULATING ROLLER SPACING AND CABLE PULLING TENSION
The information contained in Annex A is applicable for all Southwire interlocked armor feeder MC cable
constructions including MEGA MC™ cable, Riser MC™ cable, and PVC Jacketed Feeder MC cable.
Roller spacing calculations – Roller spacing will vary with cable weight, cable tension and cable construction.
To estimate roller spacing, use the following equation.
Roller Spacing
The distance “s” may be conservative for armored cable because the equation assumes a perfectly flexible
cable. When possible, a length of cable should be used to determine maximum spacing under no tension as a
check for the calculated values.
Pulling tension calculations – Calculations of pulling tensions for MC cable are similar to those for pulling
cable in conduit, adjusting the coefficient of friction to reflect using rollers and sheaves. Calculations should
be made to indicate whether the pull looks “easy” or “impossible,” making the decision to pull an obvious
choice. When a “marginal” situation is encountered, the entire pull should be reviewed. This review may
include more rigorous calculations or trial pulls. A final decision should be made based on installation factors
known to the end user and installer.
Do not exceed the allowable tension stated by the manufacturer of the pulling eye or 10,000 pounds, which-
ever is less. Traditional conservative practices limit the allowable tension of a basket grip to 1,000 pounds.
Under specific conditions, this limit can be safely exceeded.
32
31
Maximum tension on conductors – The conductors of the cable are generally the only members that can bear the
pulling forces without damage. Do not use metallic shielding wires, tapes, braids or armor not designed for the
purpose in pulling tension calculations. It is important to remember that when pulling MC feeder cable, the limiting
factor is typically the sidewall bearing pressure.
The distance “s” may be conservative for armored cable because the equation assumes a perfectly flexible cable.
When possible, a length of cable should be used to determine maximum spacing under no tension as a check for
the calculated values.
Pulling tension calculations – Calculations of pulling tensions for MC cable are similar to those for pulling cable in
conduit, adjusting the coefficient of friction to reflect using rollers and sheaves. Calculations should be made to
indicate whether the pull looks “easy” or “impossible,” making the decision to pull an obvious choice. When a
“marginal” situation is encountered, the entire pull should be reviewed. This review may include more rigorous
calculations or trial pulls. A final decision should be made based on installation factors known to the end user and
installer.
Do not exceed the allowable tension stated by the manufacturer of the pulling eye or 10,000 pounds, whichever is
less. Traditional conservative practices limit the allowable tension of a basket grip to 1,000 pounds.Under specific
conditions, this limit can be safely exceeded.
32
Multiple conductors — Maximum pulling tension for multiple conductors in parallel, or multiplexed, and multiple
conductor cables.
Horizontal straight sections — The tension for a horizontal straight section of cable can be estimated with the
following equation.
The coefficient of friction (μ) equal to 0.15 accounts for the low rolling friction of well-maintained rollers.
Inclined straight section – Use the following equation for pulling up an inclined straight section.
– + μcos0
Tout = –WL(sin0 –) Tin pounds
Use the following equation for pulling down an inclined straight section.
– + μcos0
Tout = –WL(sin0 –) Tin pounds
Vertical sections – When pulling straight up or down, the equation for inclined pulls simplifies to the following
equations.
Pulling straight up
Tout = –WL + Tin pounds
Tension in bends – If the sheaves are well maintained, they will not have the multiplying effect on tension
that bends in conduit have. The sheaves will turn with the cable, allowing the coefficient of friction to be
34
33
assumed zero. This results in the commonly used approximation for conduit bend equation
becoming equal to one. Even though these bends produce no multiplying effect, for heavier
cables it is essential to include the force required to bend the cable around the sheave. A 200-pound
per bend adder should be used for a three-conductor 500 kcmil copper conductor armored cable. If the
sheaves are not well maintained, the bend will have a multiplying effect. The tension in the pull must
then be calculated using the same equations used for installations in conduit.
Tension entering cable pull – Because the tension entering the cable pull is rarely zero, it is critical that
the tension required to remove the cable from the reel be used to calculate the total tension for the
installation.
Many times, it is difficult to know the location of the reel of cable until the cable is being installed.
The following equations are used to approximate the tension entering the cable pull and can be used to
determine how critical the reel position will be for pull.
Feeding off reel horizontally – When the cable reel can be elevated so that the cable can be pulled
directly into the pull, the following equation should be used to approximate the tension required to
remove the cable from the reel.
Feeding off reel vertically – When the cable reel must be positioned directly below the pull the following
equation should be used to approximate the tension required to pull the cable up into the first roller.
T = 25W pound
The tension now can be approximated for pulling the cable from a horizontal position when the reel is
placed directly under the first roller. To estimate the tension entering the pull when the reel must be
placed away from and below the first roller or sheave, use the equation for feeding off the reel vertically
where the height (L) is the vertical distance between the reel and the first roller. To allow for bending
forces as the cable comes off the reel, the minimum tension added should be 25 W.
35
34
ANNEX B. CABLE SPECIFICATIONS
26 05 19 WIRE AND CABLE TYPE MC FEEDER CABLE
PART 1 – GENERAL
1.1 SECTION INCLUDES
A. Feeder and Services: Type MC Cable for use as services and feeders.
B. General Applications: Type MC Cable may also be used in the following general applications
per based on the National Electrical Code® (NEC®):
1. For services, feeders and branch circuits
2. For power and lighting
3. Indoors
4. Exposed or concealed
5. In cable tray where identified for such use
6. In a raceway
7. In dry locations and embedded in plaster or against other masonry
8. Jacketed MC Cable may be used in wet locations, either direct burial, in underground
conduit, or overhead.
1.2 SUBMITTALS
A. Product Data: Submit manufacturer’s product data that materials comply with specified
requirements and are suitable for intended application.
B. Installation Instructions: Manufacture’s installation instructions shall be included in submittal.
Industry guides may supplement the manufacturer’s instructions.
C. Manufacturer: Type MC Cables for circuits, feeders and services shall be supplied from a
single manufacturer.
1.3 REQUIREMENTS
A. Underwriters Laboratories: Type MC Cable shall meet the following Underwriters Laboratories
(UL) standards.
1. UL 1569 Standard for Metal-Clad Cables
2. UL Standard 83 for Thermoplastic-Insulated Wires and Cables or UL Standard 44 for
Thermoset-Insulated Wires and Cables
3. UL Standard 1479 Standard for Fire Tests of Through-Penetration Firestops.
4. UL Classified 1, 2, and 3 Hour Through-Penetration Firestop Systems.
B. National Electrical Code® : Type MC Cable shall meet the following NEC® requirements.
1. NEC® Articles 230, 300, 330
2. NEC® Class I Div. 2, Class Ii, Div. 2 & Class Iii Div. 1 Hazardous Locations.
C. Federal Specification: Type MC Cable shall meet Federal Specification A-A59544.
D. Flame Test: Type MC Cable shall pass IEEE 1202 (70,000 BTU/hr) Vertical Cable Tray
Flame Test.
36
35
PART 2 – PRODUCTS
2.1 MANUFACTURER
A. Southwire Company, LLC, One Southwire Drive, Carrollton, Georgia, 30119.
Website: www.southwire.com.
37
36
PART 3 – INSTALLATION
3.4 INSTALLATION
A. Neat and Workmanlike Installation: MC Cable shall be installed parallel or perpendicular to
walls. No diagonal runs shall be permitted. Additional supports shall be used when the cable
is exposed. (The use of a basket type wire mesh support system or similar system should
be used when the cable is exposed.)
B. Manufacturers Instructions: Type MC Cable shall be installed per the manufacturers written
installation instructions. Industry guides may supplement the manufacturer’s instructions.
C. Field Support: Manufacturer shall provide, when requested, field engineering support for
MC Cable installation.
D. Manufacturer: Type MC Cables for circuits, feeders and services shall be supplied from
a single manufacturer.
E. Fittings: Type MC Cable fittings supplied by cable manufacturer shall be used for all feeder
cable. The fittings shall be UL-listed for use with metal-clad cable, Type MC cable, employing
interlocking aluminum tape.
F. Securing and Supporting: MC Cable shall be secured and supported as specified per
NEC® 330.30 for horizontal and vertical installations.
G. Minimum Bending Radius: Bends in MC Cable shall be made so that the cable will not be
damaged. The radius of the curve of the inner edge of any bend should not be less than
seven times the cable diameter.
H. Firestop Systems: MC Cable shall be installed per the cable manufacturer’s Through-
Penetration Firestop Systems listing by Underwriter Laboratory.
1. Copper: Copper conductors shall be compressed class B stranded or equivalent.
2. Insulation: The conductors shall be constructed with XHHW-2 or THHN/THWN insulation
rated for 90°C dry, 90°C wet and rated for 600 volts.
I. Equipment Grounding Conductor
1. Aluminum: A bare compact aluminum grounding conductor shall be cabled with aluminum
phase conductors.
2. Copper: A bare or green insulated grounding conductor shall be cabled with copper phase.
3.3 AMPACITY
A. The ampacity of Type MC Cable shall be determined in accordance with Article 310.15 of the
National Electrical Code®. The installation should not exceed the ratings of the terminations
and equipment.
38
37
ARMORLITE® MC CABLE
WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
1/0 AWG through 900 kcmil Alumaflex® Brand THHN/THWN-2 Insulated Singles with
8000 series Triple E® Aluminum Alloy. Bare Alumaflex® Brand Aluminum Alloy Grounding
Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor.
®
Southwire Armorlite® MC Cable meets or exceeds these requirements:
Conductors
TRIPLE E® 8000 SERIES ALUMINUM
• UL 83
• UL 1569
• UL 1685
Lightweight Aluminum
• Federal Specification A-A59544 (formerly J-C-30B)
Interlocked Armor
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
600 Volt • IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
• NFPA 70 (National Electrical Code), Article 330
Insulated Singles
Rated THHN/THWN-2 • REACH/RoHS-2 (Chemical Limit) Compliant
• Listed for use in UL 1, 2, and 3 Hour Through-Penetration Fire Stop Systems
Bare Alumaflex®
Brand Aluminum Alloy CONSTRUCTION
Grounding Conductor
Southwire Armorlite® MC Cable is constructed with TypeTHHN/THWN-2 conductors rated
90˚ C dry, and a bare equipment grounding conductor. Conductors are Alumaflex®
Brand AA-8000 series aluminum alloy compact stranded. A binder tape is wrapped over
the conductors. Aluminum interlocking armor is applied over the assembly. Conductors
also available in High Voltage Colors.
39
38
ARMORLITE® MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
1/0-3 AL THHN 4 ALUMINUM
55-87-59-99 602 1.190
(BLACK/RED/WHITE) (BARE)
1/0-4 AL THHN 4 ALUMINUM 60-52-87-99 758 1.304
(BLACK/RED/BLUE/WHITE) (BARE)
40
39
ARMORLITE® MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
750-3 AL THHN 1/0 ALUMINUM
55-72-31-99 3118 2.63
(BLACK/RED/WHITE) (BARE)
750-3 AL THHN 3/0 ALUMINUM
55-48-49-99 3177 2.63
(BLACK/RED/WHITE) (BARE)
750-3 AL THHN 750 ALUMINUM
56-35-99-99 3777 2.891
(BLACK/RED/WHITE) (BARE)
750-4 AL THHN 3/0 ALUMINUM
60-71-01-99 4089 2.9
(BLACK/RED/BLUE/WHITE) (BARE)
41
40
ARMORLITE® MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
600-4 AL THHN 400 ALUMINUM
55-24-83-99 3684 2.94
(BROWN/ORANGE/YELLOW/GRAY) (BARE)
FEATURES
COLOR CODING,
STANDARD PRODUCTS
Color sequence for 277V/480Y High Voltage Color systems and other special colors are available subject
to economic order quantity.
42
41
ARMORLITE® PVC JACKETED
FEEDER MC CABLE
WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
1/0 AWG through 900 kcmil Alumaflex® Brand THHN/THWN-2 Insulated Singles with 8000
series Triple E® Aluminum Alloy. Bare Alumaflex® Brand Aluminum Alloy Grounding Con-
ductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor. Overall PVC Jacket.
APPLICATIONS
Lightweight Aluminum Southwire Armorlite® PVC Jacketed MC Feeder Cable meets or exceeds the
following requirements:
Interlocked Armor with
overall PVC Jacket • UL 83
• UL 1569
600 Volt
• UL 1685
Insulated Singles • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
Rated THHN/THWN-2 • Federal Specification A-A59544 (formerly J-C-30B)
Bare Alumaflex® • Jacketed & Non Jacketed will both pass " UL Test" & "FT4/IEEE 1202"(70,000 Btu/hr)
Vertical Cable Tray Flame Test
Brand Aluminum Alloy
Grounding Conductor • NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2, and 3 Hour Through-Penetration Fire Stop Systems
Flame Retardant
• REACH/RoHS-2 (Chemical Limit) Compliant
Sunlight Resistant
PVC Jacket
CONSTRUCTION
Southwire Armorlite® PVC Jacketed MC Feeder Cable is constructed with Alumaflex® Brand
Triple e® THHN/THWN-2 conductors rated 90°C wet or dry, and a bare aluminum grounding
conductor for sizes 1/0 AWG and larger. The conductors are cabled together and a binder
tape is wrapped around the assembly. Aluminum interlocking armor is applied over the
assembly. A black flame retardant sunlight resistant PVC jacket is applied over the armor.
The jacket is available in other colors upon request, subject to economic order quantities.
43
42
ARMORLITE® PVC JACKETED FEEDER MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
44
43
ARMORLITE® PVC JACKETED FEEDER MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
45
44
ARMORLITE® PVC JACKETED FEEDER MC CABLE WITH ALUMAFLEX®
BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
FEATURES
46
45
ARMORLITE® RISER MC™ HIGH RISE CABLE
WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
1/0 AWG through 900 kcmil Alumaflex® Brand THHN/THWN-2 Insulated Singles with
8000 series Triple E® Aluminum Alloy. Bare Alumaflex® Brand Aluminum Alloy Grounding
Conductor. UL Listed. 600 Volts. Binder Jacket for Continuous Conductor Support.
Lightweight Aluminum Interlocked Armor.
• Places of Assembly per NEC® 518.4 and theaters per NEC® 520.5
High Voltage Low Voltage
Colors Colors • Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per
NEC® 645.5(D) & 645.5(D)(2)
MADE WITH
®
STANDARDS & REFERENCES
Conductors
TRIPLE E® 8000 SERIES ALUMINUM
Southwire Armorlite® Riser MC™ High Rise Cable meets or exceeds the requirements of:
• UL 83
Bare Alumaflex® • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Fire Stop Systems
Brand Aluminum Alloy • REACH/RoHS-2 (Chemical Limit) Compliant
Grounding Conductor
CONSTRUCTION
Southwire Armorlite® Riser MC™ High Rise Cable is constructed with Type THHN/THWN-2
conductors and a bare equipment grounding conductor. Conductors are Alumaflex® Brand
8000 series aluminum alloy compact stranded. A binder tape is wrapped over the conduc-
tors and an integral polymeric binder jacket is applied under armor for continuous conduc-
tor support. Aluminum interlocking armor is applied snuggly over the assembly.
An optional overall PVC Jacket can be applied over the armor.
47
46
ARMORLITE® RISER MC™ HIGH RISE CABLE WITH ALUMAFLEX® BRAND TRIPLE E® THHN/THWN-2 CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
1-4 AL 4 ALUMINUM
59-75-42-99 970 1.615
(BLACK/WHITE/RED/BLUE) (BARE)
1/0-4 AL 4 ALUMINUM 58-34-62-99 1165 1.820
(BROWN/ORANGE/YELLOW/GRAY) (GREEN)
2/0-3 AL 4 ALUMINUM
58-37-66-99 1070 1.695
(BLACK/WHITE/RED) (GREEN)
2/0-4 AL 4 ALUMINUM
59-62-79-99 1245 1.770
(BLACK/WHITE/RED/BLUE) (BARE)
3/0-3 AL 4 ALUMINUM
58-39-13-99 1230 1.865
(BLACK/WHITE/RED) (GREEN)
3/0-4 AL 4 ALUMINUM
59-33-49-99 1505 2.035
(BLACK/WHITE/RED/BLUE) (BARE)
4/0-3 AL 2 ALUMINUM
58-39-17-99 1445 1.945
(BLACK/WHITE/RED) (GREEN)
4/0-4 AL 1 ALUMINUM
58-18-69-01 1805 2.160
(BROWN/ORANGE/YELLOW/GRAY) (GREEN)
250-3 AL 1 ALUMINUM
58-06-37-99 1650 1.995
(BROWN/ORANGE/YELLOW) (BARE)
250-4 AL 1 ALUMINUM
56-52-12-99 1995 2.160
(BROWN/ORANGE/YELLOW/GRAY) (BARE)
350-4 AL 1/0 ALUMINUM
56-11-35-99 2540 2.445
(BLACK/WHITE/RED/BLUE) (BARE)
400-4 AL 3/0 ALUMINUM
58-06-34-99 2845 2.500
(BROWN/ORANGE/YELLOW/GRAY) (BARE)
500-4 AL 3/0 ALUMINUM
56-49-42-99 3340 2.685
(BROWN/ORANGE/YELLOW/GRAY) (GREEN)
600-4 AL 3/0 ALUMINUM
58-65-44-99 4035 3.070
(BLACK/WHITE/RED/BLUE) (GREEN)
FEATURES
48
47
ARMORLITE® MC CABLE
WITH ALUMAFLEX® BRAND TRIPLE E® XHHW-2 CONDUCTORS
1/0 AWG through 900 kcmil Alumaflex® Brand XHHW-2 Insulated Singles with 8000 series
Triple E® Aluminum Alloy. Bare Alumaflex® Brand Aluminum Alloy Grounding Conductor.
UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor.
Southwire Armorlite® MC Cable is constructed with Type XHHW-2 conductors rated 90˚C
wet or dry, and a bare equipment grounding conductor. Conductors are Alumaflex® Brand
AA-8000 series aluminum alloy compact stranded. A binder tape is wrapped over the con-
ductors. Aluminum interlocking armor is applied over the assembly. A PVC Jacket is applied
over the armor.
49
48
ARMORLITE® MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® XHHW-2 CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
6-3 STRANDED XHHW 6 STRANDED
55-96-94-99 305 .884
(BLACK/BLACK-WHITE/BLACK-RED) (BARE)
FEATURES
COLOR CODING
50
49
ARMORLITE® PVC JACKETED MC CABLE
WITH ALUMAFLEX® BRAND TRIPLE E® XHHW-2 CONDUCTORS
6 AWG through 900 kcmil XHHW-2 Insulated Singles with 8000 Series Triple E®
Aluminum Alloy. Bare Alumaflex® Brand Aluminum Alloy Grounding Conductor. UL Listed.
600 Volts. Lightweight Aluminum Interlocked Armor with Overall PVC Jacket.
• Direct burial applications, installation in concrete and where exposed to cinder fills,
strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
• Branch, feeder and service power distribution in commercial, industrial, institutional,
and multi-residential buildings.
• Power, lighting, control and signal circuits
• Fished or embedded in plaster
• Concealed or exposed installations
• Places of Assembly per NEC® 518.4 and theaters per NEC® 520.5
• Installation in cable tray and approved raceways
• Under raised floors for information technology equipment conductors and cables per
NEC® 645.5(D) & 645.5(D)(2)
• Class I Div. 2, Class II Div. 2, & Class III Div. 1 Hazardous Locations
MADE WITH
®
STANDARDS & REFERENCES
Conductors
TRIPLE E® 8000 SERIES ALUMINUM
Southwire Armorlite® PVC Jacketed MC Cable meets or exceeds the requirements:
• UL 44
• UL 1569
Lightweight Aluminum
Interlocked Armor • UL 1685
• UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
600 Volt
• ICEA S-95-658 (NEMA WC70)
Cross-linked • Federal Specification A-A59544 (formerly J-C-30B)
Polyethylene (XLP) • IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
Insulated Singles
Rated XHHW-2 • NFPA 70 (National Electrical Code), Article 330
• Listed for use in UL 1, 2, and 3 Hour Through-Penetration Fire Stop Systems
Bare Alumaflex® • REACH/RoHS-2 (Chemical Limit) Compliant
Brand Aluminum Alloy
Grounding Conductor
CONSTRUCTION
51
50
ARMORLITE® PVC JACKETED MC CABLE WITH ALUMAFLEX® BRAND TRIPLE E® XHHW-2 CONDUCTORS
FEATURES
COLOR CODING,
STANDARD PRODUCTS
52
51
ARMORLITE® FEEDER MC CABLE
WITH COPPER CONDUCTORS
1 AWG through 750 kcmil Copper THHN/THWN-2 Insulated Singles. Copper Grounding
Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.
600 Volt • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Fire Stop Systems
• REACH/RoHS-2 (Chemical Limit) Compliant
THHN/THWN-2 CONSTRUCTION
Insulated Singles
Southwire Armorlite® MC Cable is constructed with soft-drawn copper, Type THHN/THWN-2
Bare Copper Grounding conductors rated 90°C dry, and a bare copper grounding conductor for sizes 1/0 AWG and
Conductor larger. The conductors are cabled together and a binder tape bearing the print legend is
wrapped around the assembly. Aluminum interlocking armor is applied over the assembly.
Sizes 1 AWG through Also available in steel. Conductors are black with phase identification.
750 kcmil
Colors available upon request with economic order quantity.
53
52
ARMORLITE® FEEDER MC CABLE WITH COPPER CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
1-3 STRANDED 6 STRANDED
89-03-47-99 1139 1.203
(PHASE ID: BLACK/WHITE/ PHASE ID: RED) (GREEN)
1-4 STRANDED
6 STRANDED 89-03-55-99 1460 1.351
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(GREEN)
PHASE ID: BLUE)
1/0-3 STRANDED 6 STRANDED
89-03-48-99 1347 1.245
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
1/0-4 STRANDED
6 STRANDED 89-03-56-99 1737 1.362
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
2/0-3 STRANDED 6 STRANDED
89-03-49-99 1633 1.339
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
2/0-4 STRANDED
6 STRANDED 89-03-57-99 2190 1.571
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
3/0-3 STRANDED 4 STRANDED
89-03-94-99 2040 1.449
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
3/0-4 STRANDED
4 STRANDED 89-03-95-99 2720 1.694
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
3/0-4 STRANDED
3 STRANDED 56-10-32-99 2757 1.716
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
4/0-3 STRANDED 4 STRANDED
89-03-51-99 2562 1.665
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
4/0-3 STRANDED
4 STRANDED 56-10-33-99 2638 1.67
(PHASE ID: BLACK/WHITE/
(BARE)
PHASE ID: RED)
4/0-4 STRANDED 4 STRANDED
89-03-59-99 3313 1.824
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/ (BARE)
PHASE ID: BLUE)
4/0-4 STRANDED
2 STRANDED 56-10-34-99 3396 1.857
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
250-3 STRANDED 4 STRANDED
89-03-52-99 2991 1.817
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
350-4 STRANDED
3 STRANDED 89-03-61-99 5261 2.242
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
350-3 STRANDED 3/0 STRANDED
56-41-92-99 4435 2.242
(PHASE ID: BLACK/WHITE/ PHASE ID: RED) (BARE)
54
53
ARMORLITE® FEEDER MC CABLE WITH COPPER CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
500-4 STRANDED
2 STRANDED 89-03-62-99 7305 2.557
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
500-3 STRANDED
1/0 STRANDED 56-41-98-99 5715 2.318
(PHASE ID: BLACK/WHITE/
(BARE)
PHASE ID: RED)
500-4 STRANDED
1/0 STRANDED 56-42-02-99 7426 2.554
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
500-3 STRANDED
250 STRANDED 56-13-75-99 6201 2.553
(PHASE ID: BLACK/WHITE/PHASE ID: RED)
(BARE)
500-4 STRANDED
250 STRANDED 56-41-96-99 7921 2.818
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
600-4 STRANDED
2 STRANDED 55-20-88-99 8685 2.794
(PHASE ID: BLACK/WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
750-3 STRANDED 4/0 STRANDED
55-51-47-99 8572 2.754
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
750-4 STRANDED
1/0 STRANDED 55-04-53-99 10,779 3.040
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
FEATURES
COLOR CODING,
STANDARD PRODUCTS
Color sequence for 277V/480Y High Voltage Color systems and other special colors are available subject to economic
order quantity.
55
54
ARMORLITE® PVC JACKETED MC CABLE
WITH COPPER CONDUCTORS
1 AWG through 750 kcmil Copper THHN/THWN-2 Insulated Power Feeder Conductors.
Bare Copper Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight
Aluminum Interlocked Armor with Overall PVC Jacket.
APPLICATIONS
56
55
ARMORLITE® PVC JACKETED MC CABLE WITH COPPER CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
1-3 STRANDED 6 STRANDED
55-42-93-99 1255 1.303
(PHASE ID: BLACK/WHITE/ PHASE ID: RED) (GREEN)
1-4 STRANDED
6 STRANDED 55-56-69-99 1588 1.451
(PHASE ID: BLACK/ WHITE/ PHASE ID:
(GREEN)
RED/ PHASE ID: BLUE)
1/0-3 STRANDED 6 STRANDED
55-42-86-99 1466 1.342
(PHASE ID: BLACK/WHITE/PHASE ID: RED) (BARE)
1/0-4 STRANDED
6 STRANDED 55-42-90-99 1867 1.462
(PHASE ID: BLACK/ WHITE/ PHASE ID: RED/
(BARE)
PHASE ID: BLUE)
57
56
ARMORLITE® PVC JACKETED MC CABLE WITH COPPER CONDUCTORS
FEATURES
COLOR CODING,
STANDARD PRODUCTS
Color sequence for 277V/480Y High Voltage Color systems and other special colors are available subject to economic
order quantity.
58
57
ARMORLITE® RISER MC™ HIGH RISE CABLE
WITH COPPER THHN/THWN-2 CONDUCTORS
1/0 AWG through 750 kcmil Copper THHN/THWN-2 Insulated Singles. Bare Copper
Grounding Conductor. UL Listed. 600 Volts. Lightweight Aluminum Interlocked Armor.
Southwire Armorlite® Riser MC™ High Rise Cable meets or exceeds the requirements of:
• UL 83
• UL 1569
• UL 1685
• ICEA S-95-658 (NEMA WC70)
600 Volt • Listed for use in UL 1, 2, and 3 Hour Through-Penetration Fire Stop Systems
• REACH/RoHS-2 (Chemical Limit) Compliant
THHN Insulated Singles
CONSTRUCTION
Bare Copper
Grounding Conductor Southwire Armorlite® Riser MC™ High Rise Cable is constructed with Type THHN/THWN-2
conductors and a bare equipment grounding conductor. A binder tape is wrapped over the
conductors and an integral polymeric binder jacket is applied under armor for continuous
conductor support. Aluminum interlocking armor is applied snuggly over the assembly. An
optional overall PVC Jacket can be applied over the armor.
59
58
ARMORLITE® RISER MC™ HIGH RISE CABLE WITH COPPER THHN/THWN-2 CONDUCTORS
CONDUCTOR SIZE AND COLORS GROUNDING SIZE AND COLOR STOCK NUMBER WEIGHT OVERALL DIAMETER
(lbs/1000 ft) (INCHES)
1-3 CU THHN 1 COPPER 58-77-07-99 1653 1.693
(BLACK/RED/WHITE) (BARE)
* Available with oversize grounding conductors and other constructions upon request.
** For allowable ampacities, refer to NEC 310.15
FEATURES
60
59
N E C ® TA B L E 3 1 0 . 1 5 ( B ) ( 1 6 ) A L L O WA B L E
A M PA C I T I E S F O R 6 0 0 V C O N D U C T O R S
Table is reprinted from NFPA 70-2017, the National Electric Code, © 2016
National Fire Protection Association, Quincy, Massachusetts 02269. This
reprinted material is not the complete and official position of the National
Fire Protection Association on the referenced subject, which is represented
only by the standard in its entirety.
61
60
MC CABLE CONNECTOR SIZE
TIGHTENING TORQUE
FOR SLOTTED HEAD SCREWS
Socket Size Across Flats Tightening Torque
inch (mm) pund-inches (N-m)
1/8 (3.2) 45 (5.1)
5/32 (4.0) 100 (11.3)
3/16 (4.8) ¹20 (13.6)
7/32 (5.6) 150 (16.9)
1/4 (6.4) 200 (22.6)
5/16 (7.9) 275 (31.1)
3/8 (9.5) 375 (42.4)
1/2 (12.7) 500 (56.5)
9/16 (14.3) 600 (67.8)
62
61
SOUTHWIRE MC CABLE PRODUCTS
Southwire can provide many armored products that may be needed for your project. The Southwire catalog
provides a complete list of MC cable products in feeder and branch circuit sizes. Southwire also offers a variety of
flexible metal conduit, liquidtight, non-metallic and other specialty products.
CUSTOM ARMORING
If your installation requires a special conductor assembly, Southwire can provide pricing for these special
cables. Minimum runs will be required for these specials. Please contact your Southwire Sales Office for
further details.
This publication is a collection of items of general information related to the subject of MC Feeder Cables. It is not intended to be nor
should it be used as authority for design, construction, use or installation. The design, construction, use and installation of Metal Clad
cables and flexible conduit should only be undertaken by competent professionals in light of currently accepted design and engineering
practices.
While great care has been employed to ensure that the applications, tables, standards and references and other information contained herein
are free of errors, absolutely no warranties, either expressed or implied, are made as to the accuracy or completeness of any such tables and
form ulas contained herein.
THOSE PREPARING AND/OR CONTRIBUTING TO THE PUBLICATION SPECIFICALLY DISCLAIM ANY WARRANTY OF ANY KIND, EITHER
EXPRESSED OR IMPLIED. THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY
SPECIFICALLY DISCLAIMED BY SOUTHWIRE AND ALL OTHER PARTIES INVOLVED IN THE CREATION, PRODUCTION, OR DELIVERY OF
THIS PUBLICATION.
Neither Southwire nor anyone else who has been involved in the creation, production or delivery of this publication shall be liable for any direct,
indirect, consequential, or incidental damages arising out of the use, the results of the use, or inability to use such publication, even if Southwire
has been advised of the possibility of such damages or claim. Some states do not allow the exclusion or limitation for consequential incidental
damages, so the above limitation may not apply to you.
63
62
©2017 Southwire Company, LLC. All Rights Reserved.
National Electrical Code® and NEC® are registered
trademarks of National Fire Protection Association.
64