Version 7.2.

PVsyst - Simulation report


Grid-Connected System

Project: Deuselino
Variant: New simulation variant
No 3D scene defined, no shadings
System power: 2503 kWp
Colinas do Tocantins - Brazil

Author
Project: Deuselino
Variant: New simulation variant

PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4

Project summary
Geographical Site Situation Project settings
Colinas do Tocantins Latitude -8.07 °S Albedo 0.20
Brazil Longitude -48.50 °W
Altitude 222 m
Time zone UTC-3

Meteo data
Colinas do Tocantins
Meteonorm 8.0 (2009-2017), Sat=100% - Synthetic

System summary
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation Near Shadings User's needs


Fixed plane No Shadings Unlimited load (grid)
Tilt/Azimuth 11 / 0 °

System information
PV Array Inverters
Nb. of modules 3654 units Nb. of units 8 units
Pnom total 2503 kWp Pnom total 2000 kWac
Pnom ratio 1.251

Results summary
Produced Energy 4243 MWh/year Specific production 1695 kWh/kWp/year Perf. Ratio PR 86.95 %

Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Special graphs 6

26/07/24 PVsyst Licensed to Page 2/6


Project: Deuselino
Variant: New simulation variant

PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4

General parameters
Grid-Connected System No 3D scene defined, no shadings

PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 11 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon No Shadings Unlimited load (grid)

PV Array Characteristics
PV module Inverter
Manufacturer Trina Solar Manufacturer Huawei Technologies
Model TSM-685NEG21C.20 Model SUN2000-250KTL-H1
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 685 Wp Unit Nom. Power 250 kWac
Number of PV modules 3654 units Number of inverters 8 unit
Nominal (STC) 2503 kWp Total power 2000 kWac
Modules 126 Strings x 29 In series Operating voltage 500-1500 V
At operating cond. (50°C) Max. power (=>30°C) 275 kWac
Pmpp 2321 kWp Pnom ratio (DC:AC) 1.25
U mpp 1056 V
I mpp 2197 A

Total PV power Total inverter power


Nominal (STC) 2503 kWp Total power 2000 kWac
Total 3654 modules Nb. of inverters 8 units
Module area 11351 m² Pnom ratio 1.25
Cell area 10635 m²

Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 7.8 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module mismatch losses Strings Mismatch loss


Loss Fraction 2.0 % at MPP Loss Fraction 0.1 %

IAM loss factor


Incidence effect (IAM): User defined profile

0° 50° 60° 65° 70° 75° 80° 85° 90°


1.000 1.000 1.000 0.998 0.990 0.975 0.932 0.749 0.000

26/07/24 PVsyst Licensed to Page 3/6


Project: Deuselino
Variant: New simulation variant

PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4

Main results
System Production
Produced Energy 4243 MWh/year Specific production 1695 kWh/kWp/year
Performance Ratio PR 86.95 %

Normalized productions (per installed kWp) Performance Ratio PR

Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² MWh MWh ratio
January 153.2 82.35 28.33 144.8 144.2 324.1 319.5 0.881
February 141.8 72.56 28.27 137.0 136.5 305.1 300.7 0.877
March 157.6 79.03 28.55 158.3 157.9 350.9 345.9 0.873
April 151.8 65.26 28.57 158.6 158.2 351.3 346.2 0.872
May 159.1 59.73 30.17 172.4 172.0 380.5 375.0 0.869
June 164.1 47.79 30.41 183.1 182.7 403.2 397.4 0.867
July 172.5 49.58 31.35 191.3 190.9 418.2 412.1 0.861
August 197.9 49.74 32.70 212.9 212.5 459.4 452.6 0.849
September 175.7 74.06 31.82 179.2 178.7 391.3 385.5 0.859
October 149.5 86.37 30.48 147.0 146.3 326.8 322.0 0.875
November 137.4 80.56 29.07 130.9 130.3 293.1 288.8 0.881
December 142.1 88.48 29.07 133.9 133.3 301.5 297.2 0.887
Year 1902.7 835.52 29.91 1949.5 1943.7 4305.3 4242.9 0.870

Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

26/07/24 PVsyst Licensed to Page 4/6


Project: Deuselino
Variant: New simulation variant

PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4

Loss diagram
1903 kWh/m² Global horizontal irradiation
+2.5% Global incident in coll. plane

-0.30% IAM factor on global

1944 kWh/m² * 11351 m² coll. Effective irradiation on collectors

efficiency at STC = 22.05% PV conversion

4864 MWh Array nominal energy (at STC effic.)


+0.21% PV loss due to irradiance level

-9.39% PV loss due to temperature

+0.75% Module quality loss

-2.10% Mismatch loss, modules and strings

-1.08% Ohmic wiring loss


4309 MWh Array virtual energy at MPP
-1.44% Inverter Loss during operation (efficiency)
-0.10% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
0.00% Night consumption
4243 MWh Available Energy at Inverter Output
4243 MWh Energy injected into grid

26/07/24 PVsyst Licensed to Page 5/6


Project: Deuselino
Variant: New simulation variant

PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4

Special graphs
Daily Input/Output diagram

System Output Power Distribution

26/07/24 PVsyst Licensed to Page 6/6