Project: Deuselino
Variant: New simulation variant
No 3D scene defined, no shadings
System power: 2503 kWp
Colinas do Tocantins - Brazil
Author
Project: Deuselino
Variant: New simulation variant
PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4
Project summary
Geographical Site Situation Project settings
Colinas do Tocantins Latitude -8.07 °S Albedo 0.20
Brazil Longitude -48.50 °W
Altitude 222 m
Time zone UTC-3
Meteo data
Colinas do Tocantins
Meteonorm 8.0 (2009-2017), Sat=100% - Synthetic
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PV Array Inverters
Nb. of modules 3654 units Nb. of units 8 units
Pnom total 2503 kWp Pnom total 2000 kWac
Pnom ratio 1.251
Results summary
Produced Energy 4243 MWh/year Specific production 1695 kWh/kWp/year Perf. Ratio PR 86.95 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
Special graphs 6
PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 11 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Trina Solar Manufacturer Huawei Technologies
Model TSM-685NEG21C.20 Model SUN2000-250KTL-H1
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 685 Wp Unit Nom. Power 250 kWac
Number of PV modules 3654 units Number of inverters 8 unit
Nominal (STC) 2503 kWp Total power 2000 kWac
Modules 126 Strings x 29 In series Operating voltage 500-1500 V
At operating cond. (50°C) Max. power (=>30°C) 275 kWac
Pmpp 2321 kWp Pnom ratio (DC:AC) 1.25
U mpp 1056 V
I mpp 2197 A
Array losses
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 7.8 mΩ Loss Fraction -0.8 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4
Main results
System Production
Produced Energy 4243 MWh/year Specific production 1695 kWh/kWp/year
Performance Ratio PR 86.95 %
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4
Loss diagram
1903 kWh/m² Global horizontal irradiation
+2.5% Global incident in coll. plane
PVsyst V7.2.4
VC0, Simulation date:
26/07/24 18:35
with v7.2.4
Special graphs
Daily Input/Output diagram