Apparrent Power
Apparrent Power
Power in an electric circuit is the rate of flow of energy past a given point of the
circuit. In alternating current circuits, energy storage elements such as
inductance and capacitance may result in periodic reversals of the direction of
energy flow. The portion of power that, averaged over a complete cycle of the
AC waveform, results in net transfer of energy in one direction is known as real
power. The portion of power due to stored energy, which returns to the source
in each cycle, is known as reactive power.
Contents
1 Real, reactive, and apparent power Usually hidden from the unaided eye, the
2 Power factor blinking of (non-incandescent) lighting
3 Reactive power powered by AC mains is revealed in this
4 Unbalanced polyphase systems motion-blurred long exposure of city
lights. Light is emitted twice each cycle.
5 Basic calculations using real numbers
6 Multiple frequency systems
7 References
8 See also
If the load is purely reactive, then the voltage and current are 90° degrees out of phase.
For half of each cycle, the product of voltage and current is positive, but on the other
half of the cycle, the product is negative, indicating that on average, exactly as much
energy flows toward the load as flows back. There is no net energy flow over one
cycle. In this case, only reactive energy flows—there is no net transfer of energy to the The apparent power is the vector
load. sum of real and reactive power.
Real power (P)
Reactive power (Q)
Practical loads have resistance, inductance, and capacitance, so both real and reactive
Complex power (S)
power will flow to real loads. Power engineers measure apparent power as the vector Apparent Power (|S|)
sum of real and reactive power. Apparent power is the product of the root-mean-
square voltage and current.
Engineers care about apparent power, because even though the current associated with reactive power does no work at the
load, it heats the wires, wasting energy. Conductors, transformers and generators must be sized to carry the total current, not
just the current that does useful work.
Another consequence is that adding the apparent power for two loads will not accurately give the total apparent power
unless they have the same displacement between current and voltage (the same power factor).
If a capacitor and an inductor are placed in parallel, then the currents flowing through the inductor and the capacitor tend to
cancel out rather than adding. Conventionally, capacitors are considered to generate reactive power and inductors to
consume it. This is the fundamental mechanism for controlling the power factor in electric power transmission; capacitors
(or inductors) are inserted in a circuit to partially cancel reactive power 'consumed' by the load.
Engineers use the following terms to describe energy flow in a system (and assign each of them a different unit to
differentiate between them):
Reactive power does not transfer energy, so it is represented as the imaginary axis of the vector diagram. Real power moves
energy, so it is the real axis.
The unit for all forms of power is the watt (symbol: W), but this unit is generally reserved for real power. Apparent power is
conventionally expressed in volt-amperes (VA) since it is the product of rms voltage and rms current. The unit for reactive
power is expressed as VAr, which stands for volt-amperes reactive. Since reactive power transfers no net energy to the load,
it is sometimes called "wattless" power. It does, however, serve an important function in electrical grids and its lack has
been cited as a significant factor in the Northeast Blackout of 2003.[1]
Understanding the relationship between these three quantities lies at the heart of understanding power engineering. The
mathematical relationship among them can be represented by vectors or expressed using complex numbers,
(where j is the imaginary unit).
Power factor
Main article: Power factor
The ratio between real power and apparent power in a circuit is called the power factor. It's a practical measure of the
efficiency of a power distribution system. For two systems transmitting the same amount of real power, the system with the
lower power factor will have higher circulating currents due to energy that returns to the source from energy storage in the
load. These higher currents produce higher losses and reduce overall transmission efficiency. A lower power factor circuit
will have a higher apparent power and higher losses for the same amount of real power.
The power factor is one when the voltage and current are in phase. It is zero when the current leads or lags the voltage by 90
degrees. Power factors are usually stated as "leading" or "lagging" to show the sign of the phase angle, where leading
indicates a negative sign.
Purely capacitive circuits cause reactive power with the current waveform leading the voltage wave by 90 degrees, while
purely inductive circuits cause reactive power with the current waveform lagging the voltage waveform by 90 degrees. The
result of this is that capacitive and inductive circuit elements tend to cancel each other out.
Where the waveforms are purely sinusoidal, the power factor is the cosine of the phase angle ( ) between the current and
voltage sinusoid waveforms. Equipment data sheets and nameplates often will abbreviate power factor as "cos " for this
reason.
Example: The real power is 700 W and the phase angle between voltage and current is 45.6°. The power factor is
cos(45.6°) = 0.700. The apparent power is then: 700 W / cos(45.6°) = 1000 VA. [2]
Reactive power
In power transmission and distribution, significant effort is made to control the reactive power. This is typically done
automatically by switching inductors or capacitor banks in and out, by adjusting generator excitation, and by other means.
Electricity retailers may use electricity meters which measure reactive power to financially penalize customers with low
power factor loads. This is particularly relevant to customers operating highly inductive loads such as motors at water
pumping stations.
that is, the quotient of the sums of the real powers for each phase over the magnitude of the sum of the complex powers for
each phase.
The 1920 committee found no consensus and the topic continued to dominate discussions. In 1930 another committee
formed and once again failed to resolve the question. The transcripts of their discussions are the lengthiest and most
controversial ever published by the AIEE (Emanuel, 1993). Further resolution of this debate did not come until the late
1990s.
For a perfect capacitor or inductor there is no net power transfer, so all power is reactive. Therefore for a perfect capacitor
or inductor:
If X is defined as being positive for an inductor and negative for a capacitor then we can remove the modulus signs from Q
and X and get.
For real power it would at first appear that we would have to calculate loads of product terms and average all of them.
However if we look at one of these product terms in more detail we come to a very interesting result.
however the time average of a function of the form cos( t+k) is zero provided that is nonzero. Therefore the only product
terms that have a nonzero average are those where the frequency of voltage and current match. In other words it is possible
to calculate real (average) power by simply treating each frequency separately and adding up the answers.
Furthermore, if we assume the voltage of the mains supply is a single frequency (which it usually is), this shows that
harmonic currents are a bad thing. They will increase the rms current (since there will be non-zero terms added) and
therefore apparent power, but they will have no effect on the real power transferred. Hence, harmonic currents will reduce
the power factor.
Harmonic currents can be reduced by a filter placed at the input of the device. Typically this will consist of either just a
capacitor (relying on parasitic resistance and inductance in the supply) or a capacitor-inductor network. An active power
factor correction circuit at the input would generally reduce the harmonic currents further and maintain the power factor
closer to unity.
References
1. ^ "August 14, 2003 Outage - Sequence of Events". FERC. 2003-09-12. http://www.ferc.gov/industries/electric/indus-
act/blackout/09-12-03-blackout-sum.pdf. Retrieved 2008-02-18.
2. ^ "AC power calculation". http://74.125.77.132/search?q=cache:LOdT-
N4UkNUJ:encon.fke.utm.my/courses/see1023/AC_CircuitAnaysis2.ppt. 091123 encon.fke.utm.my (google cache)
See also
War of Currents
Electric power transmission
Transformer
Mains electricity
Retrieved from "http://en.wikipedia.org/wiki/AC_power"
Categories: Electric power