Ic Harmonized Wire Coding
H 05 V V F 3 G 0.75
Types
Harmonized ................................................................. H
Other standard ............................................................. A
Voltage Rating*
300/300V ..................................................................... 03
300/500V ..................................................................... 05
450/750V ..................................................................... 07
Metallic Coverings
Copper screen as braid over the assembled cores .......
C4
Construction Detail
(Constructional Components)
Flat, separate cable ...................................................... H
Flat, non-separate cable ............................................... H2
Conductor Material
Copper ......................................................................... (no symbol)
Aluminum .................................................................... -A
Conductor Construction
(Construction Forms)
Fine wire-flexible cable—Flexible conductor of a
flexible cable or cord ................................................... -F
Fine wire-stationary install—Flexible conductor of
flexible cable or fixed installations ............................... -K
Cross-Sectional Size of
Conductors in mm2
Nominal cross-section of conductor in mm2................ (number)
*The rated voltage in an alternating current system, is expressed by the combination of two values Uo/U, expressed in volts, where: Rev. 4-19
a) “Uo” is the r.m.s value between any insulated conductor and “earth” (metal covering of the cable or the surrounding medium);
b) “U” is the r.m.s. value between any two phase conductors of a multicore cable or of a system of a single core cables.
In an alternating current system, the rated voltage of a cable should be at least equal to the nominal voltage of the system for which it is intended. This condition applies to the values of both Uo and U.
Source: EN 50525–1 Section 4
UK
U.S.A. 10 Kelvin Drive • Knowlhill, Milton Keynes
P.O. Box 115, Oskaloosa, IA 52577 Buckinghamshire MK5 8NH
® United States/Canada, Puerto Rico, Virgin Islands UK, Ireland, Germany, Switzerland, Austria
Toll-Free Phone: (800) 662-2290 • Toll-Free Fax: (800) 645-5360 Freephone: 00800 5566 5566 • Freefax: 00800 5655 5655
®
International International
Phone: (641) 673-5000 • Fax: (641) 673-5100 Phone: +44 (0)1908 295300 • Fax: +44 (0)1908 295301
E-mail: [email protected] E-mail: [email protected]
© DiskArt™ 1988
© DiskArt™ 1988