Installer's Guide: Warning
Installer's Guide: Warning
Installer’s Guide
Convertible Variable Speed – Air Handlers 3.5 - 5 Ton
4TEE3F39A1000A, 4TEE3F48A1000A,
4TEE3F48B1000A, 4TEE3F64A1000A
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service informa-
tion pack upon completion of work.
NOTE: The 4TEE3F48B air handler should NOT be CONTENTS
installed in the horizontal left or down flow
configuration unless the outdoor unit has an AHRI General Information .............................................. 1
rating with 18-GJ23D1 in the AHRI Directory. System Installation Limitations & Recommendations ...................... 1
ratings listed without 18-GJ23D1 are for horizontal
Two Piece Cabinet Disassembly ........................ 3
right and upflow configurations only. The
manufacturer recommends installing only approved, Unit Installation ...................................................... 4
matched indoor and outdoor systems.
Vertical Upflow ....................................................................... 4
Vertical Downflow ................................................................... 4
A. GENERAL INFORMATION Horizontal Left ........................................................................ 7
▲! WARNING Horizontal Right ..................................................................... 8
THIS INFORMATION IS FOR USE BY INDIVIDUALS Refrigerant Piping ................................................. 8
HAVING ADEQUATE BACKGROUNDS OF ELECTRICAL
AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO Condensate Drain Piping ...................................... 9
REPAIR A CENTRAL AIR CONDITIONING PRODUCT Electrical - Wiring ................................................. 10
MAY RESULT IN PERSONAL INJURY AND/OR PROP-
ERTY DAMAGE. THE MANUFACTURER OR SELLER Airflow Adjustment ............................................... 10
CANNOT BE RESPONSIBLE FOR THE INTERPRETA-
Hook Up Diagrams ............................................... 12
TION OF THIS INFORMATION, NOR CAN IT ASSUME
ANY LIABILITY IN CONNECTION WITH ITS USE. Outline Drawings ................................................. 15
Checkout Procedures .......................................... 18
▲
! CAUTION
To prevent shortening its service life, the air handler NOTE: Version française sur la page 17.
should not be used during the finishing phases of con-
struction. The low return air temperatures can lead to ponents are in the unit. Any missing parts should be re-
the formation of condensate. Condensate in the pres- ported to your supplier at once, and replaced with au-
ence of chlorides and fluorides from paint, varnish, thorized parts only.
stains, adhesives, cleaning compounds, and cement
creates a corrosive condition which may cause rapid ! CAUTION
deterioration of the cabinet and internal components. Cardboard packing material must be removed from in-
These instructions do not cover all variations in sys- side the blower assembly before starting the unit.
tems or provide for every possible contingency. Should Failure to do so may cause indoor blower motor failure.
further information be desired or particular problems INSTALLATION LIMITATIONS & RECOMMENDATIONS
arise which are not covered sufficiently by this manual,
The general location of the air handler is normally se-
contact your local distributor or the manufacturer as
lected by the architect, contractor and/or home owner
listed on the air handler nameplate.
for the most effective application and satisfaction.
These Air Handlers are shipped from the factory in the
upflow or horizontal right configuration and are fully NOTE: Condensation may occur on the surface of the
convertible to downflow or horizontal left. Refer to Sec- air handler when installed in an unconditioned loca-
tion. When units are installed in unconditioned spaces,
tion C beginning on page 3 for additional information.
verify that all electrical and refrigerant line penetrations
INSPECTION on the air handler are sealed completely.
Check carefully for any shipping damage. This must be
reported to and claims made against the transportation
company immediately. Check to be sure all major com-
Installer’s Guide
AIR HANDLER SUB-BASE REAR
FLANGE
JOISTS JOIST
ONE INCH DUCT SPACERS
HEADER
B
FRONT OF
UNIT
A
UNIT
SUBBASE
APPROX. 3/4" FLANGES ON FIELD
FABRICATED DUCT OR PLENUM FLOOR
HEADER
JOIST
JOISTS
MODEL NO. A B
HEADER HEADER
TAYBASE100 23-3/4 14-13/16
TAYBASE101 21-3/4 14-13/16 MIN. SPACING TO
These air handlers are suitable for installation in a 6. When the air handler with supplementary heater is
closet, alcove or utility room with free, non-ducted, air to be installed in the downflow position on combus-
return, using the area space as a return air plenum. tible flooring an accessory sub-base (TAYBASE100
With ducted supply air, if the minimum clearances to for 4TEE3F39-64) must be used. See Figure 1.
combustible materials and service access are observed, 7. If supplementary heat is to be added, power supply
the above installations are suitable. must be sufficient to carry the load. In addition,
This area may also be used for other purposes, includ- minimum air flow settings, unit and duct clearances
ing an electric hot water heater - but in no case shall to combustible material must be maintained as
a fossil fuel device be installed and/or operated in stated on the air handler rating nameplate.
the same closet, alcove or utility room. ▲
! CAUTION
In addition, these air handlers are suitable for installa-
For air handlers not equipped with a factory installed
tion in an attic, garage or crawl space with ducted sup- electric heater, a field installed heater is available from
ply and return air. American Standard Inc. Only heaters built by American
This equipment has been evaluated in accordance with Standard Inc. are approved for use in the air handler.
the Code of Federal Regulations, Chapter XX, Part 3280 These heaters have been designed and tested in accor-
or the equivalent. “SUITABLE FOR MOBILE HOME dance with UL standards to provide safe and reliable
USE” operation. A list of approved heaters is provided on the
For proper installation the following items must be con- air handler rating nameplate. Heaters that are not fac-
sidered: tory approved could cause damage and are not cov-
ered under equipment warranty.
1. If adequate power is available and correct according
to nameplate specifications.
NOTE: If air handler is used WITHOUT a supplementary
2. Insulate all ducts, particularly if unit is located out- electric heater, a sheetmetal plate is required to cover
side of the conditioned space. the open hole in the airflow system (See Figure 2). In
3. Pursuant to Florida Building Code 13-610.2.A.2.1, addition, ensure that the cabinet is sealed air tight
this unit meets the criteria for a factory sealed where the field wires enter the unit.
air handler.
4. To ensure maximum efficiency and system perfor-
mance, the existing supply and return duct system
IF AIRHANDLER IS USED WITHOUT A FACTORY FURNISHED
static pressures must not exceed the total available SUPPLEMENTARY HEATER, A PLATE IS REQUIRED TO COVER
static pressure of the air handler. Reference ACCA THE OPEN HOLE IN THE AIR FLOW SYSTEM
Manual D, Manual S and Manual RS along with the 17"
air handler Product Data and Service Facts for addi-
tional information.
5. It is recommended that the outline drawing be stud- 1" 1/4" HOLES (4)
4"
6"
ied and dimensions properly noted and checked
against selected installation site. By noting in ad- ACCESSORY BAY99X123
vance which knockouts are to be used, proper clear- 3/8"
ance allowances can be made for installation and Figure 2 From Dwg. 21B140413
possible future service.
18-GE12D1-8 3
Installer’s Guide
C. UNIT INSTALLATION
UPFLOW
a. For maximum efficiency, the horizontal drip
tray should be removed. See Figures 5, 6 and 7.
Tray removal requires that the coil be removed
by sliding the coil out on the coil channel sup-
ports. There is a coil support tab at the top of the
coil connected to the case must be removed first.
Remove 1 inch insulation strip covering the lip of
the drip tray. The tray is detached by removing
the two screws at the drain pan. Remove the two
screws holding the two brackets at the top of the
coil. Remove drip tray by gently breaking the
seal between the drip tray and drain pan.
b. Remove the factory installed baffle assembly
from the apex of the coil by using a 5/16"
nutdriver to remove the screw. Replace this
baffle with the factory supplied narrow coil baffle
using the screws removed previously. See Figure Figure 5 Drip Pan Foam Removal
8. Reinstall coil assembly.
▲
! CAUTION
When installing the narrow coil baffle, make sure to
align the baffle up with the holes so NOT to puncture
the coil tubing.
c. Position unit on Pedestal or other suitable foun-
dation. If Pedestal is not used, a frame strong
enough to support the total weight must be pro-
vided. Provide a minimum height of 14 inches for
proper unrestricted airflow.
d. If a return air duct is connected to the air han-
dler, it must be the same dimensions as shown in
the outline drawing on page 14.
e. Pedestal and unit should be isolated from the
foundation using a suitable isolating material.
f. Openings where field wiring enters the Figure 6 Horitzontal Drip Pan Removal
cabinet must be completely sealed. Location
of power entry is shown on the Outline Drawing.
Use 2.5" clear stickers provided to seal all unused
electrical knockouts. See Figure 13.
g. After ductwork connections are made, seal air-
tight and per Local codes.
DOWNFLOW
a. For maximum efficiency, the horizontal drip
tray should be removed. See the Downflow Kit
Installer's Guide 18-GJ23D1-1 for complete in-
structions.
b. If a return duct is connected to the air handler, it
must be the same dimensions as the return
opening shown in the outline drawing on page
15.
4 18-GE12D1-8
Installer’s Guide
c. Openings where field wiring enters the For Maximum Efficiency on
cabinet must be completely sealed. Loca- Horizontal Left,
tion of power entry is shown in the outline Upflow and Downflow
drawing. Use 2.5" clear stickers provided to Remove Replace
seal all unused electrical knockouts. See and with
Figure 13. Discard Narrow
d. After ductwork connections are made, seal air- Baffle
tight and per Local codes.
Figure 8
DISCARD
DOWNFLOW BAFFLE KIT DRIP TRAY
SCREWS TO
REMOVE COIL
7/8" GASKET
X
7/8" GASKET
X
1/2" GASKET SCREWS TO
INSIDE SURFACE REMOVE COIL
OF BAFFLE
SECT. X-X
(TYP. BOTH SIDES)
WATER
BLOW-OFF WATER
BAFFLES DIVERTER
BAFFLES Figure 9
ATTACH WITH (5-ton only)
2 SCREWS
EACH SIDE
FILL WITH SEALANT
18-GE12D1-8 5
Installer’s Guide
Figure 10 FOR DOWNFLOW OR HORIZONTAL LEFT APPLICATIONS:
WHEN INSERTING COIL, TILT COIL FORWARD TO ALLOW
DRAINPAN TO CLEAR TABS ON COIL CHANNEL SUPPORTS.
Figure 11
Figure 12
6 18-GE12D1-8
Installer’s Guide
Rail
t
hee
kerS
c
Sti
kout
c
no
calK
i
ctr
Ele
Figure 13
HORIZONTAL LEFT
a. For maximum efficiency and Customer ease of
filter maintenance, it is recommended that a
properly sized remote filter and grille be in-
stalled for horizontal applications. Airflow should Figure 14
not exceed the face velocity of the filter being
used. The factory installed filter should If the unit is not suspended it must be supported
then be removed from the unit. as mentioned above and isolated carefully to pre-
b. To convert the unit to horizontal left, front ac- vent sound transmission. Vibration isolators (pur-
cess, slide the coil out on the coil channel sup- chased locally) must be placed under the unit.
ports and rotate the complete coil 180 degrees. f. It is always recommended that an auxiliary drain
c. Remove the factory installed baffle assembly pan be installed under a horizontal air handler
from the apex of the coil by using a 5/16" (See Condensate Piping) to prevent possible dam-
nutdriver to remove the hex head screw. There age to ceilings.
is a coil support tab at the top of the coil con- g. Isolate the auxiliary drain pan from the unit or
nected to the case must be removed first. Re- from the structure.
place this baffle with the factory supplied narrow h. Connect the auxiliary drain line to a separate
coil baffle using the screws removed previously. drain line (no trap is needed in this line) and ter-
See Figure 9. minate according to national and local codes.
d. The coil is then inserted back into the cabinet on i. If a return duct is connected to the air handler, it
the opposite side coil channel supports. The unit must be the same dimensions as the return
is now horizontal left with front access. Do not opening shown in the outline drawing on page
reattach coil support tab. 14.
e. If the unit is suspended, it must be supported j. Openings where field wiring enters the
from the bottom near both ends as well as the cabinet must be completely sealed. Location
middle to prevent sagging. The service access of power entry is shown on the outline drawing.
must remain unobstructed. If the unit is sup- Use 2.5" clear stickers provided to seal all unused
ported along the length of the front and back electrical knockouts. See Figure 13.
with rails, the air handler only needs to be sus- k. After ductwork connections are made, seal air-
pended at both ends. See Figure 14. tight and per Local codes.
18-GE12D1-8 7
Installer’s Guide
HORIZONTAL RIGHT
a. For maximum efficiency and Customer ease of
filter maintenance, it is recommended that a
properly sized remote filter grille be installed
for horizontal applications. Airflow should not ex-
ceed the face velocity of the filter being used.
The factory installed filter should then be
removed from the unit.
b. Unit is shipped from the factory in the upflow or
horizontal right configuration. Unit conversion is
not required.
c. If the unit is suspended, it must be supported
from the bottom near both ends as well as the
middle to prevent sagging. The service access
must remain unobstructed. If the unit is sup- Figure 15 Flange Attachment
ported along the length of the front and back, the
air handler only needs to be suspended at both E. REFRIGERANT PIPING
ends. See Figure 14.
d. If the unit is not suspended it must be isolated IMPORTANT:
Refrigerant piping must be routed to maintain service
carefully to prevent sound transmission. Vibra-
access to blower compartment and provide easy re-
tion isolators (purchased locally) must be placed moval of filter access panel and filter.
under the unit.
e. It is always recommended that an auxiliary drain NOTE: Penetration around the Refrigerant lines must
pan be installed under a horizontal air handler be sealed and Electrical inlets need to be sealed at
(See Condensate Drain Piping) to prevent pos- both the low and the high voltage.
sible damage to ceilings.
f. Isolate the auxiliary drain pan from the unit or 1. Refrigerant connections are made outside the cabi-
from the structure. net.
g. If a return duct is connected to the air handler, it 2. Installation of refrigerant lines is covered in the in-
must be the same dimensions as the return stallation instructions packaged with the outdoor
opening shown in the outline drawing on page unit. Evacuation, leak testing and brazing proce-
14. dures are included in those instructions. Read those
h. If a return duct is connected to the air handler, it instructions before starting installation of refriger-
must be the same dimensions as the return ant lines.
opening shown in the outline drawings.
NOTE: TXV Equipped is Non-Bleed, and may require a
i. Openings where field wiring enters the cabi-
start kit on the outdoor unit.
net must be completely sealed. Location of
power entry is shown on the outline drawing.
Use 2.5" clear stickers provided to seal all unused BRAZE SHIELD
Figure 16
electrical knockouts. See Figure 13.
j. After ductwork connections are made, seal air-
tight and per Local codes.
D. DUCT CONNECTIONS
The supply and return air ducts should be connected to
the unit with flame retardant duct connectors.
Convertible duct flanges are provided on the discharge
opening to provide a “flush fit” for 3/4" or 1-1/2" duct
board applications, see the Outline drawing on page 16
for sizes of the duct connections. After the duct is se-
cured, seal around the supply duct to prevent air leak-
age.
NOTE: If the convertible duct flanges are not used, they
must be removed and discarded for proper airflow.
8 18-GE12D1-8
Installer’s Guide
F. BRAZING TO EVAPORATOR SECTION For proper drainage of condensate, the following steps
NOTE: A brazing shield is provided in the information should be followed:
pack accompanying this unit. This shield fits over the 1. The primary drain line must be trapped with a
refrigerant fittings while brazing. Wet the shield before minimum of 2" water seal as shown in Figures 17 &
brazing. See Figure 16. 18. Do not use preformed 3/4" PVC running
traps.
IMPORTANT:
The use of Field fabricated or manufactured traps
Do NOT unseal refrigerant tubing until ready to cut and
fit refrigerant lines. as shown in Figures 18 & 19 is acceptable. The
manufactured trap shown in Figure 18 allows for a
1. Remove both sealing caps from indoor coil. float switch option to be added.
2. Field supplied tubing should be cut squared-off, en- Refer to the manufacturers data and instructions
suring the tube is still round and free of burrs at for details.
the connecting end. Clean the tubing to prevent 2. The trap must be located within 4 feet of the air
contaminants from entering the system. handler drain outlet connection.
3. Run refrigerant tubing into the stub sockets of in- 3. It is recommended that a clean-out tee or cross be
door unit coil. Refrigerant line openings must be installed in the primary drain line for future main-
completely sealed. tenance (See Figure 18 & 19).
4. Braze and evacuate according to indoor and outdoor
installation instructions. Manufactured traps
5. Seal around refrigerant lines.
PAINTED AREAS OF UNIT MUST BE SHIELDED
DURING BRAZING
Figure 17
2" MIN.
Close as possible
Trap must be within 4'
3/4" NPT Secondary
of air handler condensate
drain connection.
Figure 19
drain connection
4. Do not use reducing fittings in the condensate drain
lines.
5. Slope the drain lines downward a minimum of 1/4"
3/4" NPT Primary
per foot.
drain connection
6. Insulate the primary drain to prevent sweating
where pipe temperature could meet or fall below
dewpoint temperatures.
7. Provide means for drainage to prevent winter
freeze-up of condensate line.
18-GE12D1-8 9
Installer’s Guide
8. Do not connect the drain line to a closed drain sys- I.CONTROL WIRING
tem. 1. Connect wiring between indoor unit, outdoor unit
9. Use Teflon® tape on the air handler drain line con- and Comfort Control. The use of color-coded low-
nections! Do Not Use pipe joint compound or PVC/ voltage wires is recommended.
CPVC cement! 2. A low voltage terminal board is provided for control
It is always recommended that an auxiliary drain pan wiring, and is located on the left side of the cross
be installed under a horizontally installed air handler. brace in the center of the unit.
3. If the low voltage wiring diagram is not listed in
Connect the auxiliary drain line to a separate drain line this installer’s guide for the particular application,
(no trap is needed in this line) and terminate according refer to the wiring diagram located on the control
to local codes. box cover of the outdoor unit or in the outdoor
NOTE: DO NOT use a torch or flame near the plastic unit’s service facts.
drain pan coupling.
IMPORTANT:
When supplementary heaters are installed, inspect to
NOTE: DO NOT tighten the drain pipe excessively. Sup- insure that all packaging material has been removed.
port the condensate piping and traps outside the unit
to prevent strain on the drain coupling.
J. AIRFLOW ADJUSTMENT
H. ELECTRICAL — POWER WIRING ▲
! CAUTION
1. These Air Handlers are shipped from the factory Disconnect power to the air handler before changing
wired for 230 volts. The units may be wired for 208 dip switch positions.
volts. Follow instructions on unit wiring diagram lo- Failure to follow this procedure may result in equip-
cated on blower housing and in the Service Facts ment damage.
document included with the unit. Blower speed changes are made on the ECM Fan Con-
2. The selection of wire and fuse sizes should be made trol mounted on the control box. The ECM Fan Control
according to the Minimum Branch Circuit Ampacity controls the variable speed motor.
and the Maximum Overcurrent Device listed on the There is a bank of 8 dip switches (See Figure 20). The
unit nameplate. dip switches work in pairs to match the airflow for the
▲
! WARNING outdoor unit size (tons), cooling airflow adjustment, Fan
off-delay options, and heating airflow adjustment. The
TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL switches appear as shown in Figure 21.
SHOCK OR CONTACT WITH MOVING PARTS, LOCK
If the airflow needs to be increased or decreased, see
UNIT DISCONNECT SWITCH IN OPEN POSITION BE-
the Airflow Label on the air handler or the Blower Per-
FORE SERVICING UNIT.
formance Table in the Service Facts. Information on
3. Field wiring diagrams for electric heaters and unit changing the speed of the blower motor for your specific
accessories are shipped with the accessory. outdoor model size is in the Blower Performance Table.
4. Wiring must conform to National and Local codes.
If an electric heater is not installed, connections are
made through the 7/8" knockout into the air handler
junction box to the two power leads and ground wire
connections which are located near the discharge of the
blower.
NOTE: If air handler is used with or without a heater,
the electrical entry hole as well as any other cabinet
penetrations must be sealed air-tight.
10 18-GE12D1-8
Installer’s Guide
Be sure to set the airflow for the correct tonnage. The FAN-OFF period is set on the ECM Fan Control
Refer to blower housing for correct setting. board by dip switches #5 and #6. The blower off-delay
Switches 1 - 4 Cooling Airflow settings are as follows:
Switches 5 - 6 Fan Off Delay Options COOLING OFF - DELAY OPTIONS
Switches 7 - 8 Auxiliary Heat
NOMINAL
SWITCH SETTINGS SELECTION
ECM FAN CONTROL AIRFLOW
CFM
SELECTION DIP Figure 20
5 - OFF 6 - OFF NONE SAME
LIGHT SWITCHES
5 - ON 6 - OFF 1.5 MINUTES 100% *
From Dwg. 800796a NOTE: Direct drive motors have bearings which are
permanently lubricated and under normal use lubrica-
If the optional humidistat is used, remove R-BK jumper tion is not recommended.
from the low voltage terminal board (not shown) and in-
100% if necessary
stall the humidistat between R and BK. (Jumper R to O
for cooling-only/non-heat pump systems with a humidis-
80%
tat.)
FAN OPERATION (CFM)
as required
Figure 21 COOLING HEATING FAN OFF AUXILIARY
1 7.5 3
AIRFLOW DELAY HEAT SPEEDS
minute minutes minutes
COMPRESSOR OPERATION ON OFF
K. CHECKOUT PROCEDURE
1. Check the Air Handler installation in accordance
with the instructions on page 16.
2. “Operational Procedure” for the system installation
DIP SWITCHES (AS SHIPPED) can be found in the outdoor unit installer guide and will
be compatible with this Air Handler.
18-GE12D1-8 11
Installer’s Guide
4TEE3F39, 48, 64 AIR HANDLERS WITH SINGLE STAGE COOLING, 2 STAGE HEAT
COMFORT CONTROL COOLING
2-STAGE HEAT/ VARIABLE SPEED O.D. SECTION
1-STAGE COOL AIR HANDLER (SINGLE SPEED)
NOTES:
NOTES:
12 18-GE12D1-8
Installer’s Guide
4TEE3F AIR HANDLERS WITH 2 STEP COOLING
STEP
Air Handler
See Note B
Notes:
1. Be sure power supply agrees with equipment nameplate.
2. Power wiring and grounding of equipment must comply with local codes.
3. Low voltage wiring to be No. 18 AWG minimum conductor.
4. If outdoor thermostat (ODT) is not used, connect W2 to W3.
5. Be sure the jumper between “R” and “BK” is cut or removed
(See Note B below).
6. With “O” and “Y/Y2” energized, indoor fan is at 80% airflow.
7. With “O”, “Y/Y2” and “BK” energized, indoor fan is at 100% airflow.
8. When heaters are used, discard power leads with polarized plug PM-A and
connect 1-PF to mating plug in the heater control box as shown.
REQUIRED WIRING
Notes:
1. ODT-B must be set lower than ODT-A.
2. If ODT-B is not used, connect A Jumper wire from W3 to W2. If ODT-A is
not used, connect a jumper wire from W2 to W1.
3. If electric heat does not have 3rd contactor (CH), connect a jumper wire
from W3 to W2. If electric heat does not have 2nd contactor (BH), connect a
jumper wire from W2 to W1.
4. X2 must be connected to variable speed air handler terminal W3, as
shown, for proper indoor air flow during the defrost cycle.
5. Connect only if used with applicable indoor thermostat.
6. When heaters are used, discard power leads with polarized plug PM-A and
connect 1-PF to mating plug in the heater control box as shown.
REQUIRED WIRING
18-GE12D1-8 13
Installer’s Guide
4TEE3F48 AIR HANDLERS WITH 2 STAGE COOLING, 2 STAGE HEAT
VARIABLE SPEED 2 STAGE
COMFORT CONTROL AIR HANDLER AIR CONDITIONER
NOTES:
NOTES:
14 18-GE12D1-8
Installer’s Guide
OUTLINE DRAWING FOR 4TEE3F39, 48, 64
18-GE12D1-8 15
Installer’s Guide
4TEE3F39, 48, 64 AIR HANDLERS DIMENSIONAL DATA
21.0" W
4TEE3F39A, 48A, 48B & 60A
Are two piece cabinets
Model No. H W
4TEE3F39A1000A
4TEE3F48A1000A
57.90 23.50
4TEE3F48B1000A
4TEE3F64A1000A
16 18-GE12D1-8
Installer’s Guide
18-GE12D1-8 17
CHECKOUT PROCEDURES
After installation has been completed, it is recommended that the Air Handler be checked against the following
checklist.
1. Make sure power is “OFF” at power disconnect 6. Make sure secondary drain pan is installed ..... [ ]
switch ........................................................................ [ ] 7. Check power supply for correct requirements per
2. Check all field wiring for tight connections. See that unit nameplate ......................................................... [ ]
grounding of unit is in accord with code ................. [ ] 8. Check filters for proper size. Inform owner of
3. Make sure unit suspension (if used) is secure and proper procedure for removal and reinstallation .... [ ]
that there are no tools or loose debris in, around or on 9. Energize the system and carefully observe its op-
top of the unit ........................................................... [ ] eration; make any necessary adjustment ............... [ ]
4. Check all duct outlets; they must be open and unre- 10. Instruct owner, engineer (if possible) on proper
stricted ...................................................................... [ ] operating procedure and leave Use and Care Manual
5. Check drain lines and be sure all joints are tight with owner ................................................................ [ ]
.................................................................................. [ ]
Trane
6200 Troup Highway
Tyler, TX 75707
www.trane.com 06/10
For more information contact Since the manufacturer has a policy of continuous product and product data improvement, it reserves the
your local dealer (distributor) right to change design and specifications without notice.