03-Chapter-Mine Climate
03-Chapter-Mine Climate
the point and the pressure loss between the vessel and the point of
CHAPTER I I I measurement because of flow.
The static pressure indicated above is positive since it is higher
MINE CLIMATE than the atmospheric pressure. If the vessel were evacuated, ins-
tead of being pressurized, to a pressure lower than the atmospheric,
the static pressure in the vessel will be negative.
The S. I . unit of pressure is Pa (pascal=N m- ) which equals 2
3.1 PHYSICAL PROPERTIES OF MINE AIR kg m- s- in basic units. Water gauges are commonly used for
1 1
Mine air is essentially a mixture of permanent gases like oxygen measurement of ventilation pressure in mines and the readings are
and nitrogen, with some water-vapour. At the prevalent tem- generally obtained in mm w.g., 1 mm w.g. being equal to g
peratures and pressures in the mines it behaves as an ideal gas. The (=9.8) Pa.
percentages of cxygen and nitrogen in mine air rarely vary much Pressure is sometimes expressed in terms of head which is the
from the usual, but the moisture content changes substantially height of a column of fluid exerting the pressure at its bottom. If
depending on physical conditions. we consider a column of air of density p and height h, the pressure
P at its bottom is equal to its weight over unit area.
3.2 PRESSURE P = P hg,
Pressure of a fluid on a surface with which it is in contact is the
normal force exerted by the fluid per unit area of the surface. orh = P/pg (3.1)
Pressure can be expressed in absolute measure when it gives the
difference in the pressure of the fluid and that of complete vacuum. K 3.3 BAROMETRIC PRESSURE
Often pressure is expressed with reference to the local atomspheric Barometric pressure or atmospheric pressure of air at any point
pressure as datum in which case it is called the gauge pressure. is the weight of the column of atmospheric air per unit area over
Gauge pressure is in fact the difference between the absolute that point. Thus, it varies with the elevation of the point and the
pressure and the atmospheric pressure. meteorological conditions. Barometric pressure at different depths
Pressure can again be divided into (a) static pressure and or elevations can be determined from the following relation after
(b) velocity pressure the sum of the two being called the total Laplace. 82
T = mean temperature of the air column between amount of tb,is change depends on the relative diameter of the cis-
the altitudes h and h in K.
x 2 tern. If A is the internal cross-sectional area of the tube and A ,
x t
e = mean vapour pressure of the air column in kPa, that of the cistern (excluding the outer cross-sectional area of the
4> = latitude of the station in rad, tail of ihe tube), then a rise of 1 mm in the tube will cause a fall of
K => barometric constant = 18 400 m, A /A mm in the cistern so that the total rise in the barometer rea-
x 2
a = coefficient of expansion of air = 0 003 665 ding will be (A +A )/A mm. Or, in other words, for a barometric
x 2 2
and are equal to 0.00/ 64 and 0.000 007 respectively. The above A ) mm. To avoid computation after reading, the scale in such a
2
relationship can be simplified with a reasonable degree of accuracy barometer is graduated in units of AJ(A +A ) standard units so
X t
compatible with mining calculations to that it gives the barometric reading directly. The value of A J (A -\-'. x
barometer. This essentially consists of a trough of mercury, over where c = temperature correction in kPa,
T
mercury in the cistern can not be adjusted. So, when the level of gi can be measured or calculated from the relation
mercury in the tube changes due to variation of barometric pressure gi = go (\2 64 cos 2<f>+0.000 007 cos* 2<f>)
there is a change in the level of mercury in the cistern also. The - 3.086 x H M A (3.6).
ll
MINE ENVIRONMENT A N D VENTILATION
156 M I N E C L I M A T E
157
where <f> is the latitude in rad and h, the altitude of the place above The error due to creep depends on the amount of change of press! ure
mean sea level in metres. and the time allowed before taking the reading. For accurate re ad-
ing, sufficient time commensurate with the pressure change sho uld
Example 3.1 be allowed before taking a reading with an aneroid.
A Fortin barometer installed at a mine reads 99.72 kPa. (b) Set. Sometimes a major change in temperature or press ;ure
Calculate the atmospheric pressure at the mine, if the mine is located may cause a permanent set in the distortion of the chamber 1 hhus
at an altitude of 330m from the mean sea level at 0.337 rad necessitating frequent checking of the instrument against a stanc lard
control instrument, particularly when working over a large xz inge
(19°-20') N latitude. The thermometer on the barometer records
of temperature and pressure.
a temperature of 294.15 K.
Correction for temperature from equation 3.4 (c) Variation of Temperature. This can affect the reading of the
aneroid substantially if the change in temperature is la Lrge.
99.72 (0.000 1818-0.000 0184) (294.15-273.15) Normally, aneroids are suitably compensated for temperatun ; by
1+0.000 1818 (294.15-273.15) -0.34 kPa. incorporating a bimetallic link in its design or by leaving a cei -tain
volume of gas inside the collapsible chamber, but even with tem-
Value of g from equation 3.6 perature-compensated aneroids, it has been, found that a varici ition
= 9.806 65 {1-0.002 64 x cos (2x0.337) of temperature of 14 K can cause an error of 66.6 Pa. ..This < jrror
+0.000 007 x cos (2 x 0.337)} - 3.086 x 10- x 330
2 6
again varies with pressure. Thus, it is necessary to correct the 1 >aro-
= 9.785 45 m s- . 2 meter reading in accordance with the calibration of the instru ment
Correction for gravity=(99.72 -0.34) (9.785 45 -9.806 65)/9.806 65 at known temperatures.
= -0.22 kPa.
Paulin Aneroid and Askania Statoscope. Both of these (the 1 latter
So, corrected barometer reading or the atmospheric pressure
covering a small range of pressure) try to avoid the error di je to
=99.72-(0.34+0.22)=99.l6 kPa.
creep. Mere, the distortion of the diaphragm is brought ba< |;k to
3.3.3 Aneroid Barometers
Mercury barometers have an accuracy of ± 0.025 mm Hg or POINTER
the weight of the shaft air-column approximately at the rate of ture from 7\o T coupled with an irreversible adiabatic expansion
9
1.1 kPa per 100m depth and its potential energy is converted to at constant temperature T fromP to P , P -P
v 2 z 2 being the shaft
a
heat energy. Provided no work is done by the air descending the pressure drop.
shaft, (i.e. the flow is frictionless and non-accelerative) and no heat Taking g=9.81 m s-* and C =1005 J kg- K - in equation 3.8,
p 1 1
or moisture is lost or gained by the air, the compression of air in it is seen that the *-ise in the dry-bulb temperature of air due to auto-
the downcast shaft will be reversible adiabatic following the compression is 0.976 K per 100m depth.
relation The wet-bulb temperature of air also rises with depth, though
at a lesser rate depending on the surface dry-bulb and wet-bulb
temperatures. For prevalent summer conditions in India the wet-
bulb temperature may rise at the rate of 0.3 to 0.25 K for every
100m depth. The above rates of rise in air temperature hold when
where T = temperature in K, there is no addition of moisture in the shaft, but with the evaporation
y = C / C . = 1.404 for dry air (y varies slightly with the
p r of moisture in the shaft, the rate of increase in the dry-bulb tem-
moisture content of air, but for mining purposes it perature with depth falls sharply. In such cases the adiabatic index.
can be taken as equal to 1.4), y in equation 3.7 may be replaced by a variable polytropic index n.
V = specific volume (volume of unit mass of air), In dry shafts n approaches y, but in wet shafts n can be equal to 1
P = barometric pressure and subscripts 1 and 2 indicate (isothermal compression) or even less than 1 because of evaporation
the state of air at the shaft-top and -bottom of water in the downcast shaft which lowers the dry-bulb tem-
respectively. perature. Observations at a very wet Indian mine (Chinakuri No.
The rise in temperature due to auto-compression at any depth 1 and 2 pits) give a value of n=0.905 in November and 0.709 in
April in the downcast shaft. This is because there is a fall in the
can be determined from equation 3.7 by finding the barometric
dry-bulb temperature of the air as it descends from the surface to
pressures at the shaft-top and at that depth (the latter can be found
the pit-bottom owing to excessive evaporation, even though the
from equation 3.2) or from specific volumes (or densities, since shaft is fairly deep (611m).
density P = -^-) at the two points. Under similar assumptions, the In the upcast shaft however, n has a higher value of 1.25,
rise in temperature due to auto-compression can also be obtained by since the upcast air is almost saturated with water so that its
equating the potential energy with enthalpy change (see the general temperature is not affected by evaporative cooling. For similar
energy balance equation 4.1. Under the assumptions made dQ=0 reasons, the polytropic index is lower in summer, when the air,
as no heat is transferred, dW=0 as no work is done and dKE=0 being at a higher temperature, is able to evaporate more moisture
as the flow is non-accelerative so that dH— —dPE) in the shaft.
hg=AH=C AT p (3.8) It must be remembered that in wet downcast shafts, though
there may be only a very small rise (there may even be a fall in very
where = rise in temperature in K, wet shafts) in the dry-bulb temperature, there is indeed a substantial
&H = change in enthalpy, J kg- 1
amount of latent heat added to the mine air. The rate of rise in
h = depth of shaft in m wet-bulb temperature remains the same irrespective of the amount
and C = specific heat of air in J kg- K- .
p 1 1
of moisture added in the shaft, unless of course there is heat transfer
The rise of temperature with depth by auto-compression as given from the strata in addition to heating due to auto-compression.
by tquations 3.7 and 3.8 does not change when there is friction in
MINE C L I M A T E
162 MINE E N V I R O N M E N T A N D VENTILATION
163
In old rock formations like those of the Kolar Gold Field the gold mining districts. The geothermic gradient at any place is thus
geothennal gradient is flat so that the rise in rock temperature with the rate of rise in temperature above this temperature.
depth almost equals the rise in air temperature due to auto-com- Table 3.1 gives the geothermic gradient in some mining districts
of the world, although a range varying from I K / l l m to 1K/I40m
pression, so that the heat transfer from the strata in the downcast
has been recorded.
shaft is insignificant compared to the heat of auto-compression.
But in the coal fields where the geothermal gradient is steep, there
may be substantial heat transfer from the strata as the depth in- Table 3.1 : Geothermic Gradient in Various Mining
creases. This will cause a steeper rise in the wet-bulb temperature Districts of the World
so that intolerable wet-bulb temperatures may be obtained at the
downcast shaft-bottom at relatively shallower depths compared to Mining district Geothermic gradient
the Kolar Gold Field.
Similar to the heating of air due to auto-compression in the Lancashire coalfields, U.K. lK/34m
downcast shaft, adiabatic expansion and consequent cooling take Hollinger and Mclntyre, Canada IK/122.4 m
place as the upcast air ascends to the surface. However, since most
mine workings are concentrated at the bottom levels, the cooling Witwatersrand, S. Africa 1K/100.8 m
through adiabatic expansion compensates for only a small fraction
of the heat gained by adiabatic compression. On the Witwaters- Kolar Gold Field I K 91 1 m
rand Gold Field this compensation was about 16.7% at a depth Indian coalfields lK/38.4m
of 1829m and only 11.1 % at a depth of 2743m.
3.5.3 Heat from Rock Geothermic gradient is determined by observing the virgin-rock
Heat flows out of the hot core of the earth at almost a constant temperature at various depths in a mine. For obtaining accurate
rate of 0.05 W m~* over most of the earth's surface. As a result, virgin-rock temperatures, readings should be taken at the bottom
the rock temperature is found to rise as we go deeper down the of boreholes where the temperature of the rock is not affected by
earth's crust. The rate of increase of temperature with depth is ventilating air-currents. The depth of the borehole required for
called the geothermic gradient. The geothermic or geothennal gra- accuracy depends on the time for which the rock face has been
dient varies from place to place and is dependent on the physical exposed. On the Witwatersrand Gold Field it has been found that
properties of the rock such as thermal conductivity, specific heat the minimum depth of boreholes required for accuracy is 9m. It
and density which govern the rate of heat transfer in the rock. The can be reduced to 6m in case of freshly exposed rock surfaces, but
geothermic gradient is steeper, or the rise in temperature with depth for good results, a hole of 15-30m depth is recommended. The
faster for rocks of lower thermal conductivity such as coal-measure United States Bureau of Mines,* on the other hand, observes that
3
rocks than for rocks of higher thermal conductivity. Other minor the virgin-rock temperature can be measured approximately
factors which affect the geothermic gradient are the age of the accurately by inserting a 250mm long psychrometric thermometer
rock and the presence of dykes, sulphide ore bodies etc. nearby. mounted in a groove on a 19mm diameter wooden rod into
The surface air temperature at any place varies during the a 1.5-1.8m deep drillhole at a rapidly advancing face. An allowance
course of the year, but the ground temperature at a depth of about of one hour after the drilling is made for the dissipation of the heat
15m from the surface remains constant throughout the year. This of drilling in the rock. Ten minutes are sufficient for the thermo-
temperature is usually the average annual temperature at the surface meter to pick up the rock temperature and the fall of temperature
and hence varies from place to place depending on the climate. It on withdrawal of the thermometer from the hole is very slow so that
is 301.5 K on the Kolar Gold Field but only 277.6 K in the Canadian a quick reading gives the rock temperature with a reasonable
164 MINE E N V I R O N M E N T A N D V E N T I L A T I O N MINE C L I M A T E 165
accuracy. The rate of cooling of the thermometer can be further thermocouple or thermister head is embedded in a short metallic
reduced by covering the bulb of the thermometer with a heat insula- cylinder which is inserted into a borehole in the rock with the help
ting material such as rubber. The accuracy is, however, much ham- of a mounting rod or tube. Digital quartz thermometers which
pered if cooled air circulates at the face at a high velocity. Similar give a digital indication of the temperature down to 0.001 K can
results have been obtained at North Staffordshire Colliery, U.K., 64
also be used for rock temperature measurement. They utilize the
where 1.2m long and 44mm diameter blastholes in coal were change in resonant frequency of quartz crystal with temperature
sufficient to record the virgin-rock temperature satisfactorily pro- and give a linear temperature characteristic They are not affected
vided the rate of advance of the heading was maintained at 0.9m by noise and cable resistance. /
day- . It was found that at a depth of 0.9m, the strata temperature
1
In virgin areas deep prospecting boreholes are commonly used
was not affected by the air temperature over a period ranging from for the measurement of the virgin-rock temperatures at regular
2 to 17 hours of exposure, as long as the difference between the depth intervals with the help of suitable temperature probes.
strata temperature and the air temperature did not exceed 10 K. Heat Transfer from the Rock to the Mine Air. This is mainly
The measurement of temperature in this case was done with a sensi- through direct heat transfer from the exposed rock surface to the
tive thermocouple. air. Wh^n the rock surface is dry, the heat transfer is mainly through
The South African practice is more accurate and uses a finely
43
convection and raises the sensible heat of the air, but when the rock
graduated maximum thermometer inserted in a groove on a 32mm surface is wet a substantial amount of water evaporates into the
diameter wooden rod (Fig. 3.3). The thermometer is chilled in an air thus leading to both sensible and latent heat transfer.
ice box before inserting in the hole which should be 38mm in dia- In very wet mines where a lot of water may flow out of the strata,
meter. The bulb and the portion of the stem where the thermometer a substantial amount of strata heat is transferred to the air through
is to be held by fingers are covered by rubber sleeves in order to the strata water flowing along the airways to the pit-bottom sumps.
insulate them against sudden rise of temperature. The borehole The strata water oozes out almost at the virgin-rock temperature
should be properly cleaned. A dry hole is preferred to a wet hole. and by the time it reaches the sumps, it may attain a temperature
The thermometer is inserted at the bottom of the hole by screwing equal to or slightly higher than the return air temperature so that
in the required number of extension rods to the one holding the the heat transfer through strata water equals C ( r , - 7 1 (where
p w
thermometer and pushing it inside the hole. It is left inside the hole C =specific heat of water, T =virgin-rock temperature and
pw v
for at least 48 hours (sometimes even for four days) before it is 7=temperature of water entering the sump) per unit mass of water
taken out, chilled and read. flowing out.
Direct heat transfer from the rock to the mine air is governed
ll-mmOEE* RECESS FC*
^WOOOtN ROD THERMOME1ER RECESS J RUBBER MHO rMOMll
by the rate of heat transfer within the rock mass and the heat
/ I .' / COUfUNO transfer from the rock wall of the excavation to the mine air. The
7TI—nr»T^ / ^TT- rate of sensible heat transfer from the rock wall to the air is a linear
function of the difference between the temperature of the rock wall
l?7«M» »| and the mean air temperature as well as the coefficient of heat
transfer
Fig. 3.3 Wooden rod for inserting maximum thermometer in boreholes for q=«(T -T )
s a (3.9)
measurements of virgin-rock temperature.
where q = rate of heat transfer, i.e. the amount of heat flow
Copper-constantan thermocouples connected to microvoltiueters per unit area per unit time,
or thermisters connected to a suitable bridge circuit can be usea a = coefficient of heat transfer and T and T are teh
t a
instead of thermometers for rock temperature measurement. The rock-wall and air temperatures respectively.
166 MINE ENVIRONMENT A N D VENTILATION MINE C L I M A T E 167
The coefficient of heat transfer or the thermal emmisivity is a The trierma I diffusivity of a rock is given by the relation
complex function of the properties of the rock surface, the mois-
ture content, temperature and ve ocity of air as well as the size of i - ~ (3.12)
the airway.
Quasi-emoirical relations based on Reynolds' analogy ha-e where d = thermal diffusivity of the rock,
been developed for predicting values of a for turbulent, flow in k — thermal conductivity of the rock,
pipes and the:-: can be used for mine airways for accurate estima-
tion of a. One ?uch relation due *o Colburn is as follows : 87
C — specific heat of the rock
A — area,
G = mass velocity = v P , a
t = time,
P mi average density of air,
a
Table 3.2 : Thermal Conductivity and Thermal trance will be given by the equation
Diffusivity of Rocks s
i ; -T =(T,-TJ4(x,y)
a (3.13)
Thermal conductivity. Thermal diffusivity, where (x, y) is a function of x and v,
Rock (kJ m- s- K- ) x 1CH
1 1 1 (m* s- x 10- )
1 7
kt roc
x =••-•• — , and y — —.—
Granite 18.84-27.21 9.0-13.0 C r* p k 7
and Jones. It will be seen from the figures that with increase of
65
development, the volume of air circulating in the drive was much
time, T falls at first rapidly and then slowly so that after the lapse
t
smaller (only 2.3m s- producing an air velocity of only 0.15 m s )
8 1 J
T,-T -<J,-T*.
L Q"° > C r ( 3 1 7 )
c = coefficient of mass transfer,
e (T ) = saturation vapour pressure at T which can now be
t t
This equation has been found by Hitchcock and Jones to 66
considered as an overall surface temperature for
satisfactorily predict air temperatures along an experimental dry both dry and wet portions of the rock
airway. Equation 3.17 shows that as the distance increases, the
temperature of air rises rapidly in the beginning and then slowly and e = vapour pressure of air.
until T approaches T, when L tends to infinity. Again it is seen
L At commonly prevalent temperatures in mines (290-310 K) e'(T ) t
that the greater the value of Q, the less is the value of T , which sug- L can be given by the approximate relation
gests that circulation of a large quantity of air through an airway e'{T.)'=aT* +bTt + c (3.19)
of a certain length helps in keeping the air temperature down.
where a, b and c are constants having values of 0.002 133,
Hitchcock and Jones found that the temperature at a point in x —1.121 64 and 147.83 respectively with T in K and e'in kPa.
t
drive fell to 300.9 K after two years of development, the virgin-rock e is given by the relation
temperature being 302.9 K ; but after only 6 days of completion of
e « 461.9 x 10-* m' T kPa (3.20)
the drive and establishment of through ventilation in it, the tem-
perature fell to 297.4 K. This is because of the fact that during where m'm absolute humidity in g m- . 4
MINE C L I M A T E
MINE E N V I R O N M E N T A N D VENTILATION
173
172
the ratio P„JB can be taken equal to unity in which case equation
The coefficient of mass transfer is a similar function of. flow para- 3.23 reduces to
meters as the coefficient of heat transfer.
The Stanton number in equation 3.10
Nu
S t= -Re-* ' C3.21) In terms of the heat transfer coefficient,
a D
where Nu = Nusselt number = —^—,
D = airway diameter
-%)fefe)[(-^)(^)r «
The variation in the dry-bulb temperature along the airway can
and Re = Reynolds number of flow
now be obtained from equation 3.15 which can be rewritten as
v D P. poc {T,-T) dL = P C QaT a p (3.26)
Similarly the rise in the absolute humidity of air along the air-
A similar group to the one on the right hand side of equation way can be written as
3.21 i.e. Shl(Re. Sc) can be used to correlate the mass transfer f P • [e'(T )-e]
m t dL = Q dm'x 10-* (3.27)
coefficient. or,/ p < [a T* + bT,+c-461.9X
w 10-* m'T]dL = Qdm'x 10-"
Similar to the Colburn heat transfer equation 3.10 we can write (3.28)
for mass transfer substituting the values of e' (T,) and e from equations 3.19 and
3.20 respectively.
The solution of the above differential equations needs the esti-
mation of T, at different times. This can be done by adopting the
S H . Sci = L (3.22) standard solution given by equation 3.13 provided a notional value
of T is adopted taking into account both sensible and latent heat
a
P*m = logarithmic mean partial air pressure Starfield" developed the following approximate relation based on
(B-e)-(B~e') Duhamel's theorem for taking into account the cooling history of
the airway which can be solved numerically :
B = atmospheric pressure,
e' = saturated vapour pressure at the temperature of
+1 £ fa T m \[ + {x,y) _i-
H + {x y) \)
t M
the evaporating film of water, / = 0 \
e = vapour pressure of air flowing
where the subscript n denotes the value of a variable at a time n it
and D = mass diffusivity of water-vapour into air
m
after the opening of the airway, 8t being a given interval of time.
- 0.092 m ' h - at 298 K.
1
For the same moment of time equation 3.29 can be written as T -T '
s S = T- T (3.35)
T = T -Lall
a n \aT\ bTi +c-46l.9xl0-«m;7v/| (3.31) An equation similar to 3.26 can be written as
Thus T for any moment of time (say, the present) can be built
a pec [(T,-T) (l-/JHT;-T)f ] w dL=P a C Q dT
p (3.36)
up from equations 3.30 and 3.31 at the start of the airway where
L = 0, if the air temperature and humidity at the time of commis- T, in the above equation can be obtained from equation 3.13 which
sioning of the airway is known. can be written as
For variations along the airway let us denote the value of the T=T+<f>(x,y)(T -T) ¥ (3.37)
variables at a distance 6X from the start of the airway by an
asterisk, e.g. T *. Assuming the variations to be nonlinear, the
m Combining equations 3.36 and 3.37, we have
following equations can be written for the values of T * and m * : n
dT pa* (x,
r..-r. + j«(jg- igl) + (3.32, dL P C, f
a [ ( r '- r ) ^ ( r - r ) ] (3 ' 38>
where ?'=rate of addition of heat from other sources over the is an imponderable, difficult to estimate from visual observation
length dL. of the roadway. It is best determined experimentally from heat
transfer studies in actual roadways.
Somewhat simpler relations have been suggested by Ramsden
for heat and mass transfer along wet roadways from which dry- Heat Transfer in an Advancing Stope. A stope differs in shape
bulb temperature and mixing ratio gradients along the roadway from an ordinary airway and keeps on advancing into virgin rock.
The rate of heat transfer in it depends on the rate of stope advance
can be predicted. A wet roadway has been considered to have a
and time apart from the shape and size of stope and the rock and
portion of its surface dry with a surface temperature T, and the
air characteristics. However, with a given rate of face advance,
remaining portion wet having a surface temperature T' which are t
a 'recurring state' will be reached in the stope, characterized
approximately related to the dry- and wet-bulb temperatures of
by a cyclic repetition of thermal gradient around the stope
air (T and T' respectively) by the relation
176 MINE E N V I R O N M E N T A N D VENTILATION
MINE C L I M A T E
177
after each blast, a certain time after the start of the stope in (ii) T -*-T (xl)the virgin-rock temperature as x->-oc and
v
rates of face advance and plotted it in Fig. 3.8 against two dimen-
sionless parameters L / y/d~t and h d.t so that q (/) can be cal- 2 F
HANGING WALL
culated from ( 0 obtained from equation 3.45.
Heat transfer from hanging wall which is similar to that from
foot wall is a two-dimensional problem and hence more difficult
to solve even on a computer. A simplified approach has been given
FOOT WALL
by Starfield who divides the stope width / to N sections each of
_ J length L so that JV=-^-and considers heat transfer from each sec-
Fig. 3.6 Heat transfer model of an advancing stope. Li
tion to be independent of the other.
The total flow of heat q (/) from a unit length of face over the
F
In the recurring stage the total heat transfer from the hanging
cycle time t is given by the relation wall over a period /, q (t) is given by the relation
H
0
where q (Nt) can be estimated from equation 3.45 by subs-
nax
1.0 i
0-9
\ f Cu)" u erfcCi
0.8
for h iqher vo ues o f i
1.(28 1
• \ fCu>" u
"*?
0-7
\
0-3
•
\
•
02
O'l
i i . .i
2.0 3-0 4-0 5-0 6-0
1.0
u = h
rock.
The total heat transferred per unit length of face over the cycle
time / is thus given by
(3.49)
MINE C L I M A T E
181
equation ;
0.11 (1+0.05 W) (T-T) ^ . k * ? £ (3.59)
m of face length,
W = stoping width, m,
average monthly face advance, m,
Is - stope span (average distance from centre gully
to stope face,
p = density of rock, kg m - 3
(3.60)
182
MINE E N V I R O N M E N T A N D VENTILATION MINE CLIMATE 183
f
When doing hard work, however, the heat produced by the ther hand, a haulage engine pulling tubs on level ground converts
body is much more than that produced by basal metabolism and^~ B of its power input to heat, a part of it being put into the air at
sometimes it may be as much as ten times the latter. The heat- the engine and the rest as frictional heat in the haulage road. It
engine efficiency of the human body, i.e. the ratio of the work done is a good practice to dispose of heat from large hoists, pumps or
by the man in a certain time to the amount Of heat produced by haulage engines directly to the return air by ventilating the engine
him in excess of that due to basal metabolism in that time is found rooms by a separate split of air-current. The frictional heat in
to be only 20%. Assuming the above heat-engine efficiency of the haulage roads can be prevented from getting at the face by installing
human body the heat produced by an average man doing moderate haulages in the return, a fact worth considering in deep mines.
work of 45 W is of the order of 310 W or about 165-170 W m - of 2
This becomes all the more important for locomotive haulage where
body surface. Wyndham gives the following typical metabolic heat all the heat is added to the air in the haulage road.
rates for different rates of work : Diesel locomotives, being much less efficient than electric
locomotives of either trolley-wire or battery type, produce more
Nature of work Light work Moderate work Hard work
heat for the same power. It must be borne in mind that the heat
(e.g. winch (e.g. sweeping, (e.g. tramming,. ;
JJproduced by diesel locomotives is equal to the heat content of the
driving) fitting) shovelling) V
fuel consumed. The heat content of normal diesel fuel is about
Metabolic heat 44 MJ kg- . A diesel locomotive consumes about 0.26 kg of fuel
1
rate, W m - of 2
per kWh so that the heat generated is 2.93 kW per kW of locomo-
body surface 90 180 270
tive power. However, since the locomotive does not work all the
time, the average heat generated by a diesel locomotive is of the
3.5.5 Heat Produced by Machinery order of 1 kW per kW of rated engine power.
This can be a large source of heat particularly in highly Almost all the work done by a fan is converted to heat except
mechanized mines. Most of the power input to electric- or I.C for the part used for increasing the kinetic energy of air as the air
185
undergoes adiabatic compression. The same is the case with com-
pressors. There is an increase in the air temperature of 0.826 K T, and T are temperatures in K of the compressed-air pipe
2
for every kPa pressure developed by the fan. That is the reason at the shaft-top and shaft-bottom respectively,
why it is better to locate booster fans on the return and to install / = latent heat of evaporation of water in J kg- 1
exhaust fans rather than forcing fans as main mine ventilators at and h = depth of shaft in m and m and m are moisture
x %
Compressed-air machinery add no heat to the mine air. Comsi the top and bottom of the shaft respectively.
pressed-air machines like rock drills which do frictional work add Example 3.2
heat to the rock face equivalent to the work done, but this is fully
compensated by the expansive cooling of the exhaust air. A fan ventilating a heading through a duct of 600mm diameter
circulates 4 m s- of air at the face. Calculate the heat added to
s 1
Assuming the air velocity at the drill inlet and exhaust to be
the air by the fan, if the input power of the fan is equal to 2.9 kW.
the same and neglecting the work of feed thrust on the drill, the
general energy balance equation (4.1) yields Cross-sectional area of the duct = — (0.6) =0.283m .
2 £
On the other hand compressed-air in pipes does add a certain and the density of air is assumed to be equal to 1.2 kg m- . 5
amount of heat to the mine air. Compressed-air is often generated Energy input to the fan converted to heat
at fairly high temperatures if proper after-cooling arrangement is = 2900-479 = 2421 J
not there. This hot compressed-air further gains heat due to auto- 3.5.6 Heat from Lights
compression in the pipe range in the shaft. As the compressed-air
goes down the shaft, it gives up heat to the ventilating air as a result This becomes significant i f carbide lamps are used. Cooke ' 4
of which some of the moisture in the compressed-air condensi estimates that a carbide lamp consuming 156g of carbide per shift
thus generating heat. The overall heat addition to the mine produces 96.5 J of heat per second although according to Jeppe,**
from compressed-air rs thus given by the relation, its power may be as high as 204.7 W when the lamp burns at full
brightness. A candle produces 25-35 J, an electric cap lamp (two-
cell type), 2.6 J and an ordinary electric bulb, 40 J every second
i=M{c;(T -Tj+-^m -mj+k)
l l
depnding of course on the current and voltage.
where q = heat lost by compressed-air in W, 3.5.7 Heat due to Oxidation
M = mass flow rate of compressed-air in kg s- , 1
I Cll
heat added to the air can be traced to this source. Neglecting the Table 3.3 : Distribution of Heat from Various Sources in a Mine
amount of oxygen consumed by men and flame lamps, i.e. assuming
all the oxygen consumed in a mine to be utilized in the oxidation Source Heat produced Heat produced
of coal, Haldane states that a fall of 0.1 in the percentage of oxygen in MW in % of tola]
in the air between the intake and return airways produces enough
heat to raise the air temperature by 7K. Auto-compression 2.42 21
It may be noted here that in coal mines desorption of methane Human beings 1.58 14
from coal produces a certain degree of cooling by extracting Carbide lamps 0.90 7
835-1025 kJ of heat per m of methane desorbed.
s
Power 1.32 12
Heat due to oxidation is not usually appreciable in metal mines Rock and other sources
where a small quantity of heat may be produced by the oxidation (by difference) 5.34 46
of timber. But in some mines producing sulphidic ores, spontaneous
heating of the sulphides may add a considerable amount of heat to Total 11.56 100
the air. Heat due to oxidation of coal is 8.79 MJ m- of O absorbed 3 a
account of the movement of strata in coal mines is only 1 % of the A downcast shaft is 300m deep. The barometer reads 102 kPa
total heat added to the air, although theoretically it should be of at the shaft-top. The surface air temperature being 295 K, cal-
culate the air temperature at the bottom of the shaft assuming
the order of 9% in consideration of the rock masses involved. This
the temperature of the air to be affected by auto-compression
is believed to be due to most of the heat being dissipated in the only.
broken rock mass itself.
The relative importance of the various sources of heat in a metal As a rough estimate, the rise in the temperature of air due to
mine is evident from the following example. A section of a mine auto-compression
on the Witwatersrand ' had 4500 men, each with a carbide lamp.
4 = 0.96x3=2.88 K.
The number of electrical units consumed were 822 000 kWh per Therefore, the mean temperature of the air column
month and the quantity of ventilating air was 151m's- . The depth 1
=295+1.44= 296.44 K
to the top of the section was 1524m and the total heat taken up by
Let B=barometric pressure at the shaft-bottom.
the air as calculated from the air temperature was 11.56 MW. The
distribution of heat was as given in Table 3.3. .". 300 =67.4x296.44 (log £ - l o g 102)
or B =105.6 kPa.
13
MINE CLIMAT?.: 189
MINE E N V I R O N M E N T A N D VENTILATION
188
3.6.1 Vapour Pressure
Now let T =temperature ai the shaft-bottom in K. This is the partial pressure of water-vapour present in a certain
(l.4-l)/l 4 volume of air or space. When a gas or mixture of gases such as air
is confined in a given space in a container it exerts a certain pressure
on the walls of the container. When another gas or water-vapour is
- 297.99K. allowed to diffuse into it and occupy the same space, the pressure
on the container walls is the sum of the partial pressures (the pres-
Using the relation given in equation 3.8, the rise in temperature sure exerted by the individual gas if it occupies the container alone)
= 300X9.8 U 2 9 3 K
of the component gases.
1005 Since at a certain temperature and atmospheric conditions the
barometric pressure does not change, addition of water-vapour
Therefore, r=295+2.93=297.93K. to dry air reduces its partial pressure and hence its density. Again,
water-vapour has a lower density than dry air. Hence the overall
3.6 MOISTURE CONTENT OF MINE AIR density of air is reduced by the addition of water-vapour. The
Mine air always contains some amount of moisture. There is a vapour pressure is the maximum when the air is saturated at a
maximum quantity of moisture which can be contained in any certain temperature. It should be noted that the saturation vapour
space of gas, air or even vacuum at a certain temperature. When presswe varies with temperature only and is independent of the
the air at a particular temperature contains the maximum amount presence of other gases and vapours. The saturated vapour pres-
of water-vapour it can hold, it (or rather the space) is called satu- sure of air for various temperatures have been experimentally
rated and can pick up no more water-vapour at that temperature. determined and are given in Table 3.4. Empirical relations
fl2
On the other hand, i f the air can still pick up some more water- (equations 3.19 and 3.41) have been fitted to these data and can
vapour at the prevailing temperature, it is called unsaturated. The be used for the calculation of saturation vapour pressure.
capacity of air for containing water-vapour increases with tem-
perature and hence if saturated air is heated up without adding any 3.6.2 Saturation Deficit
extra moisture to it, it becomes unsaturated. Conversely, if un- This is the difference between the saturation vapour pressure
saturated air is cooled, its degree of saturation increases until it is at the temperature of observation and the actual vapour pressure
fully saturated at a certain temperature. If the cooling proceeds and is measured in any pressure unit.
beyond this temperature, the air gives up water-vapour which con-
denses into mist or dew. This temperature at which the air attains 3.6.3 Relative Humidity
saturation is called the dew point. This is the ratio of actual vapour pressure to the saturation
Saturated air at a certain temperature holds a fixed amount of vapour pressure at the temperature of observation (dry-bulb tem-
moisture. This quantity remains the same i f the temperature is perature) expressed as a percentage. For temperatures prevalent
raised without further addition of moisture. I f on the other hand in mines, this can be taken equal to the saturation ratio which is
moisture is added as the temperature rises, the air picks up more the ratio of the mass of moisture per unit mass of dry air to the
moisture until it gets saturated at the higher temperature. mass of moisture required to saturate the air at the temperature
Moisture content of air can be expressed in the following terms: of observation.
(a) vapour pressure, (b) saturation deficit, (c) relative humidity, (d)
d€w point, (e) specific humidity, ( f ) mixing ratio and (g) absolute
humidity. Each of the above units except the relative humidity Saturation ratio = ^ — ) / (Xv) = Jjf^e' ( 3 6 4 )
vapour at the prevailing temperature, it is called unsaturated. The (equations 3.19 and 3.41) have been fitted to these data and can
capacity of air for containing water-vapour increases with tem- be used for the calculation of saturation vapour pressure.
perature and hence if saturated air is heated up without adding any
extra moisture to it, it becomes unsaturated. Conversely, if un- 3.6.2 Saturation Deficit
saturated air is cooled, its degree of saturation increases until it is This is the difference between the saturation vapour pressure
fully saturated at a certain temperature. If the cooling proceeds at the temperature of observation and the actual vapour pressure
beyond this temperature, the air gives up water-vapour which con- and is measured in any pressure unit.
denses into mist or dew. This temperature at which the air attains
saturation is called the dew point. 3.6.3 Relative Humidity
Saturated air at a certain temperature holds a fixed amount of This is the ratio of actual vapour pressure to the saturation
moisture. This quantity remains the same i f the temperature is vapour pressure at the temperature of observation (dry-bulb tem-
raised without further addition of moisture. I f on the other hand perature) expressed as a percentage. For temperatures prevalent
moisture is added as the temperature rises, the air picks up more in mines, this can be taken equal to the saturation ratio which is
moisture until it gets saturated at the higher temperature. the ratio of the mass of moisture per unit mass of dry air to the
Moisture content of air can be expressed in tht following terms: mass of moisture required to saturate the air at the temperature
(a) vapour pressure, (b) saturation deficit, (c) relative humidity, (d) of observation.
dew point, (e) specific humidity, ( f ) mixing ratio and (g) absolute
humidity. Each of the above units except the relative humidity c, . / 622e \ 622e' \
specifies. the moisture content completely, the relative humidity Saturate ratio = ( — ^ = (3 .64)
alone requiring the temperature to be given in addition.
(see later)
0.8 0.9
0.6 0.7
0.4 0.5
0.3 0.640 0.645
Temperature 0.1 0.2 0.635
0.0 0.626 0.631 0.689 0.693
in K 0.617 0.622 0.679 0.684 0.745
0.613 0.669 0.674 0.734 0.739
0.605 0.609 0.664 0.729 0.799
273 0.659 0.719 0.724 0.788 0.794
0.650 0.655 0.714 0.782 0.857
274 0.708 0.771 0.777 0.845 0.851
0.698 0.703 0.766 0.839
275 0.755 0.761 0.828 0.833
0.750 0.816 0.822 0.913 0.919
276 0.810 0.906
0.805 0.894 0.900 0.978 0.985
111 0.888 0.971
0.875 0.881 0.958 0.965 1.048 1.055
0.869 0.945 0.951 1.034 1.041 1.129
0.863 0.938 1.026 1.121 If!
278 0.932 1.019 1.114 Z
0.925 1.013 1.099 1.106 1.199 1.208 <
279 0.999 1.006 1.091 1.191
0.992 1.077 1.084 1.175 1.183
280 1.069 1.167 Z
1.062 1.160 1.283 1.291 z
281 1.144 1.152 1.274
282 1.136
1.249 1.257 1.266
1.362 1.371 1.380 m
1.474
1.224 1.232 1.240
1.335 1.344 1.353
1.455 1.464 -
283 1.216 1.318 1.326
1.426 1.436 1.445
1.553 1 563 1.573 >
1.300 1.309 1.417 1.543 1.679 Z
284 1.408 1.523 1.533 1.657 1.668 0
1.389 1.398 1.513 1.646 <»
285 1.503 1.625 1.636
1.483 1.493 1.615 1.790 r
286 1.604 1.767 1.779
1.584 1.594 1.756 1.908
287 1.733 1.744 1.884 1.896
1.723 1.860 1.872 2.020 2.032
1.701 1.712 1.848 2.007
1.690 1.825 1.836 1.982 . 1-995 2.151 2.164
288 ' 1.813 1.969 2.137
\.802 1.945 1.957 2.1U 2.124 2.289 2.304
289 1.932 2.098 2.275
1.920 2.072 2.085 2.246 2.261
290 2.059 2.233
2.045 2.205 2.219
291 2.191
292 2.178
4-
Table 3.4 (Contd.)—Pressure of Aqueous Vapour over Water in kPa
Temperature
in K 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 9
293 2.318 2.332 2.347 2.361 2.376 2.391 2.406 2.421 2.436 2.451
294 2.466 2.481 2.496 2.512 2.527 2.543 2.558 2.574 2.590 2.606
295 2.621 2.637 2.653 2.670 2.686 2.703 2.719 2.736 2.752 2.769
296 2.786 2.803 2.820 2.837 2.854 2.872 2.889 2.906 2.924 2.941
297 2.959 2.977 2.995 3.013 3.031 3.050 3.068 3.086 3.105 3.123
298 3.142 3.161 3.180 3.199 3.218 3.237 3.257 3.276 3.295 3.315
299 3.335 3.354 3.374 3.394 3.414 3.435 3.455 3.476 3.496 3.517
300 3.538 3.558 3.579 3.600 3.622 3.643 3.664 3.686 3.707 3.729
301 3.751 3.773 3.795 3.817 3.839 3.862 3.884 3.907 3.930 3.953
302 3.976 3.999 4.022 4.045 4.068 4.091 4.115 4.139 4.163 4.187
303 4.211 4.235 4.260 4.285 4.309 4.334 4.359 4.384 4.409 4.434
304 4.460 4.485 4.510 4.536 4.562 4.588 4.614 4.641 4.667 4.693
305 4.720 4.747 4.774 4.801 4.828 4.855 4.883 4.910 4.938 4.966
306 4.994 5.022 5.050 5.079 5.107 5.136 5.165 5.194 5.223 5.252
307 5.282 5.311 5.340 5.370 5.400 5.430 5.461 5.491 5.522 5.553
308 5.584 5.614 5.645 5.676 5.708 5.740 5.771 5.803 5.835 5.867
309 5.900 5.933 5.965 5.998 6.031 6.064 6.097 6.130 6.164 6.198
310 6.232 6.266 6.300 6.335 6.369 6.404 6.439 6.474 6.509 6.544
311 6.580 6.615 6.651 6.687 6 723 6.760 6.797 6.834 6.871 6.908
312 6.945 6.982 7.020 7.057 7.095 7.133 7.172 7.210 7.249 7.288
MINE C L I M A T E
179
MINE ENVIRONMENT A N D VENTILATION
192
\fl rt ffi 1 M — r-l r* >n oo oo
X O n 5> I - Os f£ o O- —
O '— ^ ^ ^ Cs TT; O O —• OO
r-' oo oo oo <T> OS O — — Ci r-l
- r- « i n
«.-> O T OO oo tt m
ON "* 3v V) — •—•
t » eo oo oo a> j! O 6 - N N
v-i oo O r » m O H l£ 0> OO p i
O —• m © r - r-. oo H oo r - o>
\ O •* 0~ t*j oo i»i o> * O '*
r- oo' 00 ON I > ^ © © — fS fS
e ^ io io * l~- Os It © (N 00 Os
NO r~ O m «N _ m r~ i»i — r-»
« ^ 03 m oo ^ oc " t O «
r-' r~ oo oo o< O d - r-i rsi
u
> <t ^ N o o- os — m m oo r~
o M >0 - r- so oo — r~ m so
IA * w cc r ) i s oo rt o; 1
r—' r-' oo" oo' o> os ©' o —' ~- r i
r3
>
3
5 »T r4 oo m —
os oo — oo op m
_ N -C - 9> o
V
OO W - VO ^ t— <s r - oo m
3 ^ oo in r- N ON' © d —' —' «S*
cr i— t— oo oo os
<
r-
»-i O * I*I
T T m r » —« oo
o o «3\>
r. 2
1^ N * T
' t oo N r - ON O 3.0
r - r - oo' oo Os
i
C Os m- m m O ~*
—. <s m © oo oo Fig. 3.8 q {t)\q
f max (f) vs Lly/Zi ( a f t e r Starfield).
o \ — vo r-t r-_
U CO <S vO —
r » oo oo os and that over unit time,
<7f(0 +2<7w(0 +9* (Q
(3.50)
sD OO OO Os Os m 3- 00 N o q = ;
so so oo r* op r- Os C-) rN
n h - 'O O O m «— r - f >
r-' r - oo oo os CN o©
In cut-and-fill method of stoping filling follows face advance.
The fill face will release a certain amount of sensible and latent
heat. For computing this the fill face can be assumed to be at the
q !- SO SO *T <N same surface temperature as the last section of the hanging wall.
d r j n * oo J
e*\ «ni O The heat transferred from the last section of the hanging
I oo oo ^
s
The heat transfer from unit area per unit time tfio
saturation ratio ( (B—e')e ") // e \
' ' relative humk
Q HN= YW K
where B = barometric pressure, e=vapour pressure and
e' = saturation vapour pressure.
The surface temperature of the hanging wall T, can now be deter" Since e and e' are too small in comparison with B, B—e and
mined from the relation B—e' can be considered to be equal and hence saturation ratio
can be taken equal to relative humidity.
Taking the same surface temperature for the fill face, the sensible
heat transfer from the fill face over the period t will be given by 3.6.4 Dew Point
For any vapour pressure e, a temperature T can be found d
so that the total sensible heat transfer per unit length of stope face
the dew-point temperature.
per unit time
q T ^ q (t)+ZlH0)+<I*
F (0+g«,(0 (3.55) 3.6.5 Specific Humidity
The specific humidity is defined as the mass of water-vapour
present in a unit mass of air (mass of air includes that of dry air as
Let this cause a rise in the dry-bulb temperature of the air of A X
well as of moisture). The specific humidity is related to vapour
Then q =C T p P Q &T
a (3.56) pressure by the relation
where Q = air-flow rate along the stope.
At the end of the unit length of face the dry-bulb air temperature s - 6 2 2 B = h m ( 3 6 6 )
now becomes T +AT. This air temperature can now be used for
0
where 5" *• specific humidity in g kg- . 1
calculating the heat transfer from the next unit length of the face
It is assumed that water-vapour has a density equal to 0.622
and the process continued till the dry-bulb air temperature at the
times that of air at the same temperature and pressure.
return end of the stope face is obtained.
The change in the absolute humidity and hence in the wet-bulb
3.6.6 Mixing Ratio
temperature along the face can be similarly obtained by solving the
equation This is a quantity similar to the above and is defined as the mass
W* (e'(T,)-e} = Q A m x 10-* (3.57) of water-vapour per unit mass of dry air,
where Am' = change in the absolute humidity of the air, for
or, m = 622 ~ - (3.67)
each unit length of face.
The above methods of computing heat addition in wet roadways
where m — mixing ratio in g kg- . 1
and stopes in mines are highly complicated and need substantial
amount of digital computation. Simplified empirical relations
3.6.7 Absolute Humidity
have been developed in South African gold mines for estimation
of heat transfer in roadways, stopes and development ends. This unit is less commonly Used nowadays. It is defined as the
Ramsden developed the following relation for wet airways :
188
mass of water-vapour per unit volume of air and is given by the
/ » \ 0 . « 7 / „ \_0.147/ £ \8
relation
10 e9
,,-5.5 (/. 0.255)<r,-7}(iL)
7 + (_) k^)^
m " 46L9T ( 3 6 8 )
MINE C L I M A T E 195
194 MINE E N V I R O N M E N T A N D V E N T I L A T I O N
and wet-bulb temperatures rise (the latter at a slower rate) and its
where m = absolute humidity in g m- , 3 relative humidity falls, but the dew point of the air remains cons-
T = temperature in K tant. If water is evaporated into unsaturated air its dry-bulb
and e = vapour pressure in kPa. temperature falls by evaporative cooling, the wet-bulb temperature
remains constant and the dew point rises until it reaches the wet-
3.6.8 Measurement of Humidity bulb temperature at the point of saturation. At such a point the
There are several methods for the measurement of humidity. dry-bulb temperature is equal to the wet-bulb temperature.
They are listed below in order of their use. The vapour pressure can be calculated from the dry- and wet-
(1) Thermodynamic method (the psychrometer). bulb temperatures using the following relations:
(2) Methods using hygroscopic substances (the hair hygro-
meter etc.)
(l)e=e'-0.00125 {T-T) (*+ ^""Iffi^) (3.69)
for an air velocity of 0-0.5 m s- 1
= 4.19kJ kg- K - . 1 1
g
.-. dry air-flow rate «= =9.22 kg s- . Q g 6 g 1
From the psychrometric chart determine the change in the mois- 165.92
ture content of air evaporatively cooled to saturation from 304 K and — r= = 18 kJ kg- of dry air 1
d.b. (dry-bulb) and 297 K w.b. (wet-bulb). Also show that 'evapora- for a water-flow rate of 4 kg tr . 1
tive cooling' is actually a process of heating. .'. Resultant enthalpy of cooled air
Referring to Fig. 3.9, air at 304/297 K on being evaporatively =53.21-9=44,21 kJ kg- of dry air for 1
cooled, will proceed along the wet-bulb line until it meets the a water-flow rate of 2 kg s- 1
100% relative humidity line when it will be saturated at 297 K. and = 53.21 - 1 8 = 35.21 kJ kg- of dry air for 1
At 304/297 K moisture content of air = 15.75 g kg- of dry air. 1 a water-flow rate of 4 kg tr . 1
At 297 K saturated, moisture content^ 18.75 g kg- of dry air. 1 The moisture content of air remains unchanged on cooling in
.'. Change in moisture content a shell-and-tube-type heat exchanger until it gets saturated at the
= 18.75-15.75=3 g kg- of dry air.
1
dew point after which the air will give up some condensed water
and follow the 100% relative humidity line on further cooling. It
Enthalpy at 304/297 K=71.6 kJ kg- of dry air. 1
must be noted here that in contrast to this, moisture content of
Enthalpy at 297 K saturated=72.0. kJ kg- of dry air. 1
air increases due to evaporation of water when the cooling is done
This clearly suggests that there is an addition of heat in spray-type coolers and the air follows the wet-bulb temperature
=0.4 kJ kg- of dry air.
1
line until it is saturated at the wet-bulb temperature when it follows
MINE E N V I R O N M E N T A N D VENTILATION MINE C L I M A T E 199
198
the 100% relative humidity line on further cooling. If cooling pro- For this mixing ratio and a dry-bulb temperature of 299 K the
wet-bulb temperature^297.5 K (from psychrometric chart).
ceeds to a sufficiently low temperature the ultimate state point is
When the proportion of the two mixing air-streams is reversed,
the same no matter what the method of cooling is (compare the
275x6 + 307x2
paths ACD and AGD for cooling of air from A to D in Fig. 3.10).
the weighted average dry-bulb temperature = g
Mixing ratio of air at 302/292 K
=9.5 g kg- of dry air.
1
= -283 K
For this mixing ratio and an enthalpy of 44.21 kJ kg- of dry air 1
The weighted average mixing ratio = (23.5 x 2+4.5 x6)/8
the air has a dry-bulb temperature of 293.5 K and a wet-bulb tem- =9.25 g kg- of dry air. Since this is higher than the maximum
1
perature of 289 K (from psychrometric chart), but for an enthalpy possible mixing ratio of 7 g kg- of dry air at 283 K, some water will
1
of 35.21 kJ kg- of dry air, the air gets cooled beyond the dew point.
1
condense out of the mixed air which will be saturated at 283 K.
From the intersection of the enthalpy line (35.21 kJ kg- of dry air) 1
3.6.10 Instruments for Measuring Relative Humidity of Mine Air
and 100% relative humidity line, the temperature of cooled air is
read as 285.5 K saturated. The Fixed or Non-ventilated Hygrometer. This is fixed at a sui-
table place in the mine so as to be well ventilated by the
mine air-current. It consists of two thermometers mounted side
Example 3.6
by side, the bulb of one being exposed to the air and that of the
Air at 307/302 K mixes with air at 275 K saturated in the pro- other covered with a thin gauze of muslin, the lower end of which
portion of 6 :2 by mass on dry air basis. Find the temperature and is dipped in a container filled with water. Distilled water or rain
humidity of the mixed air. What will be the temperature and humi- water (not mine water) should be used in the container as impurities
dity of the mixed air if the mass ratio of the two streams of air in water affect its rate of evaporation. The surface of the muslin
were reversed? should be clean and the muslin should be changed from time to
When the two air-streams mix, heat will be given up by the hotter time. Care should be taken to wipe all dirt and moisture from the
stream of air and taken up by the cooler stream until their dry-bulb surface of the dry bulb. When taking readings underground, the
temperatures become equal. This will be the dry-bulb temperature, lamp should not be held too close to the hygrometer. It should
of the mixed air. There will be no change in the total moisture preferably be held on the leeward side of the hygrometer so that the
content or enthalpy until and unless the mixture is cooled beyond heat given out by it does not affect the thermometers. This instru-
the dew point when condensed water will separate out of the mixed ment reads the dry-and wet-bulb temperatures from which the humi-
air thus reducing its moisture content and enthalpy (that removed dity can be obtained by referring to psychrometric tables or
by the condensed water). The mixed air will then be saturated at the charts.
weighted average dry-bulb temperature. Whirling Hygrometer or Sling Psychrometer. A defect of the
The weighted average dry-bulb temperature of the two streams fixed hygrometer is that unless it is placed in an air-current with a
of air velocity of 3 m s- or more, the moisture evaporated from the wet
1
. 307x6+275x2 m bulb surrounds both the dry and wet bulbs, thus affecting the read-
= 299 K ings slightly. Besides, the evaporative cooling of the wet bulb may
when they mix in proportion of 6:2. This will be the dry-bulb also affect the dry-bulb temperature with low air velocity. That is
temperature of the mixed air. why the whirling hygrometer is commonly used in mines for better
Mixing ratio of air at 307/302 K accuracy. This (Fig. 3.11) consists of a dry- and a wet-bulb thermo-
=23.5 g kg- of dry air
1
meter as in a fixed hygrometer and is provided with a handle for
and at 275 K saturated = 4.5 g kg- of dry air.
1
whirling it at a rate of 20 rad s- (—200 r.p.m.) which produces a
1
Resultant mixing ratio of the mixed air relative air velocity of 3 m s-1
F i g . M l Whirling ,gron«.«.. h
T — temperature of air in K
and Ro = universal gas constant= 8314.4 J kmol- K- . 1 1
Assmann Psychrometer. This is an aspiration psychrometer Taking air to have the composition by volume as given in Table
with the bulbs of the thermometers ventilated by a fan operated 1.1, and molecular masses of O , C0 , N and Ar (including other
z 2 2
by a clock-type spring. The bulbs of the thermometers are covered rare gases) as 32,44, 28 and 40 respectively the molecular mass of air.
with metal sleeves whose outer surfaces are bright chromium-plated = 2 32+0.03x44+78.09 x 28+0.93 x 40
0 9 5 x
287.1 7" 461.9 T raise the temperature (internal energy) of the air. But the specific
heat at constant pressure C is comparatively more since in this
p
J L 2 ™ ± ) 10. kg case the heat has not only to raise the temperature, but also to do
V 287.1 T ) 6 work for the expansion of the air. For ideal gases C —C =R p t ai
Since this is the mass of 1 m* of moist air, the density of moist air but for real gases C —C >R since there is not only external work
p r a
(3.78)
I J--0.378 e \ 10 kg m-
3
of expansion but also internal work done to overcome intermole-
cular cohesion when the air expands at constant pressure. For
> ""V"l87TT"y
air C is roughly equal to 1005 J kg- K - while C is roughly equal
p 1 1 r
to 712 J kg- K- . 1 1
Example 3.7
Specific heat varies with temperature and can be given by the
Calculate the density of air at a barometric pressure of 101.325 following simple relations for the range of temperatures commonly
kPa and dry- and wet-bulb temperatures of 299 and 296 K res- met with in mines.
pectively. (a) C,„=995.68+0.029 T J kg- K - (3.80)
1 1
From equation 3.72 vapour pressure e m 2.6 kPa. (b) C = 1553.7+0.645 T+35 169/r J kg- K
p (3.81) 1 J
Differentiating the above equation, we get and C corresponding to the average temperature (273.15+7")/2 K
pr
dH = dU+PdV+VdP (3.83) (more correctly the value of C (T— 213.\) in equation 3.87 should
p
Combining equations 3.83 and 3.84, we have where C = specific heat of water in liquid form
pw
equals the amount of heat added to the air. Generally however, fair accuracy is achieved by using equations
Enthalpy is a function of the state of the air and hence a change 3.87 or 3.89 with the following values of /, C^, C and C for pf pw
in enthalpy is dependent on the initial and final states and not on the range of temperatures commonly met with in mines :
the process of change. For an ideal gas change in enthalpy is given / = 2.5x10* J kg- , 1
dH = C dT
p (3.86) C = 1860 J kg- K - ,
pt 1 1
zero and the enthalpy at any particular state is given by the sum of Enthalpies of moist air as calculated on the above basis are plotted
the sensible heat of dry air, the latent heat of water-vapour and the in Fig. 3.9.
sensible heat of water-vapour. Let us first consider unsaturated In case of supersaturated air where there is some water existing
air. If 1 kg of dry air contains, say m g of water vapour at T K, the in liquid form in saturated air, the enthalpy will be given by the
relation
enthalpy will be given by the relation
//=C (7'-273.15)+0.001 m C ; (r-273.15)+0.001 ml kJkg-*
po p
//=C (r-273.15)+0.00'l m' C (T-273.15)+0.001 ml
pa m
where = specific heat of dry air, kJ kg- K - , 1 1 where m' = amount of water-vapour in the saturated air in
C = specific heat of water-vapour, kJ kg- K - ,
pr 1 1 g kg- of dry air 1
and / = latent heat of evaporation of water, kJ kg- . 1 and m" = amount of liquified water-vapour in g kg- of dry 1
3.10 EFFECT OF HEAT AND HUMIDITY Table 3.5 : Rise in Body Temperature with Wet-bulb Temperature
ON THE MINER
It has been said earlier that the human body produces a lot of waste
heat by the process of metabolism which has to be dissipated into Wet-bulb temperature Rise in body temperature
the surrounding mine air. inK in K
The major part of the heat produced by the body is dissipated
from the surface of the skin by radiation, convection and evapora- * Up to 302.15 0.11-0.66
tion of sweat, though a very small part is dissipated from the lung 302.65 - 304.85 . 0.33-0.77
through exhaled air. The heat transfer from the inner parts of the
body to the skin is through the blood circulatory system, although 305.35-307.65 0.66-1.55
conduction accounts for a minor part. Above 307.65 1.44-1.90
When the temperature of the atmosphere is 298 K or less, the
normal blood .circulation of the body along with conduction is
sufficient to transfer the heat from the inner parts of the body to Various authorities have given different tolerable limits of wet-
the surface of the skin.. The heat transfer from the skin to the bulb temperature. Haldane puts it at 304.3 K for partially accli-
43
ambient air at these temperatures is mainly by convection and radia- matized men at rest in still, saturated air. With a high dry-bulb
tion. But above 298 K, the heat transfer to the skin has to be faster. temperature, however, this value could be somewhat more. Caplan
Here, the vaso-motor control comes into operation, dilating the reported that with the prevalent high dry-bulb temperatures in the
size of blood vessels and thus ensuring larger blood circulation to y -^Kolar Gold Field of the order of 316-322 K, cases of heat stroke
the skin. As the temperature rises above 302 K, the sweat glands ~y "*rvere frequent at wet-bulb temperatures of 307.5-308.5 K but were
start functioning and now the heat transfer from the skin is rare below a wet-bulb temperature of 305.5 K. A study in South
mainly by the evaporation of sweat. Africa revealed that the probable risk of heat stroke rose sharply
When the dry-bulb temperature of the mine air exceeds the body when the wet-bulb temperature exceeded 305.15 K, but was low
temperature (310.05 K) the body can give away heat to the surround- when the wet-bulb temperature was between 300.15 K and 304.15 K.
ing atmosphere by the evaporation of sweat only. Fatal heat stroke risks were negligible below 302.5 K w.b. and non-
fatal heat stroke risks were negligible below 300.15 K .
3.10.1 Effect of High Wet-bulb Temperature
' The rate of evaporation of sweat depends on the moisture con- 3.10.2 Acclimatization
tent of the ambient air and the air velocity. Though the relative
Acclimatization plays an important role in the human tolerance
humidity of air is specified by the difference in the dry-bulb and
of high wet-bulb temperatures. The first physiological response
wet-bulb temperatures, it is the wet-bulb temperature, that greatly
^ f the human body to very hot and humid atmosphere is the dila-
influences the rate of evaporative cooling of the human body.At £
-%on of the blood vessels i n the skin, but the volume of the fluid in
high wet-bulb temperatures the rate of cooling gets reduced. As
the blood circulatory system does not immediately increase as a
a result, the body temperature rises as shown in Table 3.5.
result of which the heart-rate shoots up to 160-180 beats min- . 1
The rise in the temperature of the body varies from person to
After two to three days of acclimatization, however, the circulatory
person and depends on the degree of acclimatization. A moderate
volume builds up and consequently the heart-rate falls to 120 beats
rise in the body temperature of the order of 1.4 K is not harmful,
min- . In addition sweating begins earlier and the rate of sweating
1
but when the body temperature rises above 312 K and/or the heart increases.
rate exceeds 140 beats min- heat intolerance, that may ultimately
1
A system of acclimatization has been satisfactorily adopted in
lead to heat stroke, appears.
South African gold mines where the worker is made to work at a
208 M , N E ENVIRONMENT AND VENTILATION
M I N E C L I M A T E
209
controlled rate for four hours a day in a chamber with a saturated becomes hot, dry and gritty ; the pulse becomes fast and irregular
air temperature of 305.15 K. and an air velocity of 0.5 m s- . The 1 and the respiration, stertorous. At 314.25 K unconsciousness occurs
work rate is gradually increased to a maximum (rate of oxygen con- and the skin turns blue due to cyanosis. If no measures are taken
sumption = 1.41 min- ) on the last day over a period of eight days.
1
to reduce the temperature, death occurs due to asphyxia at
316.5 K.
This system has been claimed to satisfactorily acclimatize Bantu
miners for the following combinations of work and wet-bulb People having constipation and alcoholics are more prone to
temperature : heat stroke. People in febrile conditions having an initial body
(a) Light work (0.65 1 min- oxygen consumption) at 307.15 K.
1
temperature above the normal develop very high temperatures
under heat stroke conditions. It has been observed in South African
(b) Moderate work (0.95 1 min- oxygen consumption) at
1
mines that workers with low body weight who normally have low
305.15 K work capacity fall an easier prey to heat stroke. Gross overweight
(c) Hard work (1.45 1 min- oxygen consumption) at 304.15 K .
1 with low work capacity also makes the worker prone to heat stroke.
Worse wet-bulb temperatures can be tolerated by these acclimatized Older men (over 45 years of age) are more liable to heat stroke than
workers at reduced work rate, higher air velocity of 1-1.5 m s- 1
younger men.
or with the use of a micro-climate cooling system. The patient suffering from heat stroke should be stripped naked
It must, however, be noted here that the capacity for acclima- and laid down. Cold water should be poured over the body accom-
tization varies from person to person and some persons never really panied by vigorous fanning. The hair should be cropped short and
get acclimatized. Besides acclimatization is a temporary pheno- ice bag applied to the head until temperature comes down to 312 K
menon and the effect is lost if the worker is taken out of the hot and when the body should be covered by a thin blanket. Utmost
humid conditions for about a month or so. caution is necessary for a day or two as the symptoms of heat stroke
3.10.3 Effect of Air Velocity are likely to relapse.
Higher air velocity aids evaporative cooling, by removing the
saturated air from the immediate vicinity of the body surface. 3.10.5 Changes in Cardio-vascular System
However it has been seen that though an increase in air velocity Under hot and humid conditions, more blood is supplied to
up to 1 m s markedly affects the comfort condition, the effect is
_1 the skin and hence the cardiac rate and output increase so much that
less felt above this velocity and is negligible beyond a velocity of beyond the critical temperature cardiac failure may result. This
3 m V . On the other hand, velocities greater than 2 m s- are un-
1 1 leads to decreased blood pressure which causes less blood circula-
comfortable as they raise dust. High velocities of the order of 3m s- 1 tion. As a result, heat exhaustion symptomized by fatigue, nausea,
or more, when coupled with a high dry-bulb temperature of the giddiness and headache occurs leading under more severe condi-
order of 322 K and a low relative humidity, cause burning sensation tions to vomiting and blurred vision. The ultimate stage is heat
and a rise of body temperature by too rapid evaporation of sweaty a .fl, collapse which results in unconsciousness. In severe cases of
and may ultimately result in heat stroke. collap&e, the skin becomes cold and clammy and the pulse cannot
be felt. It is however less severe than heat stroke though the condi-
3.10.4 Heat Stroke tions producing it are the same.
' Heat stroke results from the breakdown of the temperature
regulating mechanism of the body when the body temperature 3.10.6 Changes in Water and Chloride Metabolism
shoots up. In the early stages, it is characterized by mental excite- There is a great loss of water from the body when there
ment followed by restlessness, intolerance and delirium. Vomiting is excessive sweating. At 307 K a resting man may sweat at the
:- • »uaial ftympjonii^ Muscular cramps and loss of body fluid occur rate of 120 cm per hour though when doing hard work the sweat
8
warntnre rises above 313 K, the skin irate may increase to 850 cm h- . Beyond this however, the sweat
8 1
MINE CLIMATE
^ w o r k w E f f l c i e n c y a t V a r , o u s W e t , u i b T c m p e r a t ; ; ;
r
output decreases due to fatigue of the sweat glands. Hal-
dane states that there have been cases where a man produces as
much as 2.94 kg of sweat per hour when doing hard work in a very Wet-bulb temperature in K Working efficiency (%)
hot atmosphere, though the average sweating rate of acclimatized
men varies between 0.45 and 0.7 kg h- . The loss of sweat is usually
1
306.8 75
made up by drinking water, but the maximum a man can drink at 308.2 50
hot temperatures is estimated at 700 cm h- . Drinking in excess
3 1
of this may result in vomiting and the water may not be able to get 310.1 • 25
into the body and the circulatory system owing to the lack of suffi-
cient blood supply to the alimentary canal. Excessive loss of water F'g- 3.12 gives the working •
causes dehydration of the body characterized by sunken eyes and go.d mines a, various wet b u f f Z Z Z l ''" °
S «
U t h A f r i c a
inelastic skin, high body temperature and may lead to the failure output a. 300..5K b e ^ ' » m g e - i s of work
of blood circulation.
Man has enough sodium chloride reserve in the body (28g in
blood and 57g in the tissues) and this is normally replenished by
the usual daily intake of 14 to 24g. The loss of sodium chloride
in 100 cm of sweat amounts to 0.5g only. Hence an occasional
3
i thermometer
8
of heat lost per cm* of the surface of the bulb
in cooling from 311 to 308 K is usually written
on the kata thermometer. This factor divided
by the time taken for the cooling gives the rate
O I * *
n e a t ^
o s sthermometer.
T o m t n c
the heat loss from the surface of the bulb due to radiation and
convection and hence is of little importance, particularly under Table 3.7 : Variation of Work Output with Wet-Kata Reading
hot and humid conditions where most of the heat loss from the
human body is through evaporation. All the same Hill advocates Wet-kata reading, Rest time in Relative work
a dry-kata reading of not less than 250 W m - for good working 8
W m-» min h - 1 output (%)
conditions. 778.7 7.3 100
The wet-kata reading is obtained by covering the bulb of the 611.3 6.7 94
kata thermometer by a wet muslin. The idea is to make it resemble 540.1 9.0 91
the human body which loses heat by radiation, convection as well 452.2 10.0 82
as evaporation. The wet-kata cooling power is related to the wet- 376.8 11.1 81
bulb temperature and the air velocity by the following relations.
268.0 22.4 59
K = (14.65+35.59 v ) (309.65-7") 1/s (3.91)
for air velocities < 1 m s- 1 Orenstein and Ireland also give the lower limit of wet-kata
and K = (4.19+46.05 v ' ) (309.65—7") 1 8 (3.92) cooling power for comfortable working condition as 628 W m- . * 1
for air velocities > l m s J However, the kata cooling power is not always consistent. The
where K = kata cooling power of air or the heat loss kata factor varies with temperature. A variation of 10% occurs
if the air temperature changes from 2 8 3 to 3 0 3 K . Moreover, with
in W m - \
low air velocities and large differences between dry- and wet-bulb
214 MINE ENVIRONMENT A N D VENTILATION MINE C L I M A T E
215
temperatures, the wet-kata cooling power has a considerably low
value. This is due to the fact that in an unventilated or poorly
ventilated wet-bulb thermometer (which the kata is in a way) the
moisture evaporated surrounds the bulb and hence the thermo-
meter gives a higher reading for the wet-bulb temperature than the
true value. Because of this higher estimation of the wet-bulb tem-
perature by the kata thermometer, the cooling power shown by.it
is less. This is illustrated by the following example. At a wet-bulb
temperature of 306.5 K and an air velocity of 0.51 m s- the kata
1
readings were 159, 130 and 71 W m-* for differences between dry-
and wet-bulb temperatures of 0, 5.56 and 16.67 K respectively
whereas for the same wet-bulb temperature and with an air velocity
of 5.1 m s- the kata readings for all dry-bulb temperatures re-
1
Effective temperature, K 80
cr
For men acclimatized in tropical conditions, the upper limit rises § 20
to 300 K which can also be taken as the upper limit for mine
L _ L _ l _ -i-A . J -
workers. 294 296 298 1 1 I \ J J .J ±
30? 304 306 308
Carrier gives the following working efficiency for industrial 310
EFFEC TIVE 'TEMPERATURE, K
workers at different effective temperatures :
R'' W O r k i n « ' «™y
m « « m ^ . u ( . f , c r Wyndhan,,
r e
temp., K. to variable work output and physical fitness of different men. Be-
temp;, K. sides, the calculation is complicated and involves the measurement
308 50 of several factors. It is perhaps because of this reason that P SR 4
various effective temperatures. 4^the human body surface to the surrounding air under any environ-
mental condition defined by dry-bulb temperature, wet-bulb
3.11.3 Predicted Four-hour Sweat Rate (P SR) 4 temperature, velocity of air, radiant temperature, atmospheric
A physiological index of comfort in a certain environment called pressure and the skin temperature. The following empirical rela-
the 'predicted four-hour sweat rate' was developed by the Medical tions were developed from extensive studies for different modes of
Research Council of Great Britain on the basis of large-scale tests heat transfer :
in London and Singapore between 1947 and 1953. The predicted
four-hour sweat rate can be read from nomograms prepared by the R = 17x 10-« (0.5 7V+154.1)» (T,-T ) R (3.93)
Council from the various variables affecting the index : dry-bulb C = 8,3 (B/10 1.3)°-» v°« (T,-T.) (3.94)
;1 «
2ia MINE ENVIRONMENT A N D VENTILATION MINE CLIMATE
219
i 1
and E = '-Li— (5/101.3)°- v - (e' -e)
8 0 6 t (3.95)
\
Ml -
B = barometric pressure in kPa,
T = radiant temperature, K,
\
r , -
Z 20!
o
V\
The specific cooling power of the air = /?-f-C+£" (3.96) >
S i«o
charts will give a good estimate of the cooling power of air. The As surface air enters a mine through a downcast shaft, its
chart also provides the design comfort environment (dry-bulb a temperature rises due to auto-compression. Strata heat may also
wet-bulb temperatures and air velocity) for any work rate for the add to the air temperature in deep mines. The latter will, however,
purpose .of the calculation of cooling load when air cooling becomes vary from season to season depending on the surface air temperature.
necessary. As the air travels from the downcast shaft-bottom to the working
For example, for hard work (metabolic rate of 270 W m- at 2 face, its temperature will further rise due to heat added from the
a place with a prevalent air speed of 0.5 m s-\e tolerable wet-bulb rock. While the rate of temperature rise will be somewhat slower
temperature will be 300.5 K (the dry-bulb temperature being in the intake airway, it will be higher across the workings which on
302.5 K). If, however, the air speed could be raised to 2.5 m s- ,- 1 advancing continuously expose virgin-rock faces to the air-current.
the tolerable wet-bulb limit will rise to 305 K. The air, however, rarely acquires the virgin-rock temperature (v.r.t.)
15
220 MINE ENVIRONMENT A N D VENTILATION MINE C L I M A T E
221
at the face except in relatively shallow and poorly ventilated mines.
If the temperature of air is less than the v.r.t as it leaves the wor-
kings, there will be a further rise in its temperature in the return
up to the upcast shaft-bottom (assumed to be at the same elevation
as the downcast shaft-bottom) though at a very slow rate owing to
the small difference in the rock and air iemperatures. However,
in bidirectional system of ventilation, there may actually be a fall
in the air temperature along the return owing to leakage of cooler
air from the intake. As the air rises in the upcast shaft, there is a
fall in its temperature due to auto-expansion, but it has a tempera-
ture still higher than that of the atmosphere except in very shallow
mines where the rock temperature may be lower than the surface
air temperature so that there is heat transfer from the air to the
rock.
The above is the case in dry mines. But in wet mines (most
mines are wet), there may be very slight rise in the dry-bulb tem-
perature of the air (in fact there may be a fall in extremely wet shafts)
at the downcast shaft-bottom. But the wet-bulb temperature rises
substantially increasing the relative humidity of the air. Strata heat
addition in the intake raises the dry-bulb temperature, but lowers
the relative humidity so that the air is capable of picking up more
moisture if the intake roadway is wet. In relatively dry faces there
is a rise in saturation deficit owing to rapid addition of strata heat.
In the return airway however, addition of moisture may decrease this heat is given up in the upcast shaft so that the total
the dry-bulb temperature while raising the wet-bulb temperature heat removed from the mine=93.7 (89.60-52.35)x 10- =3.49 3
so that the air is nearly saturated as the upcast shaft-bottom. Auto- MW.
expansion in the upcast shaft cools the air often below the dew There is an addition of 93.7 (14 — ll)=281.1g of moisture per
point causing water to condense in the upcast shaft. In deep and second in the downcast shaft, while total addition of moisture up
wet mines, the condensed water literally pours down the upcast to the upcast shaft-bottom is 93.7 (26.8-11)= 1480.5 gs- . Of 1
shaft. this 93.7 (26.8—24)=262.4 gs- condenses in the upcast shaft and
1
Fig. 3.17 illustrates the air temperature variation in a deep and is carried back into the mine. It is significant to observe that the
highly wet coal mine in India (Chinakuri No. 1 & 2 pits) while ventilating air acts as a water pump in the mine, removing in the
Fig. 3.18 illustrates the annual variation of the upcast and downcast above case 93.7 ( 2 4 - l l ) x 3 6 0 0 x 10-«=4.385 t ( o r m ) of water
8
pit-bottom temperatures at the same mine. in an hour. The quantity would be higher with higher air-flow
Fig. 3.17 also gives the variation in the enthalpy and moisture rates.
content of the air as it traverses the mine. With an intake of The methods of improving the cooling power of mine
80 m s as measured at the downcast shaft-bottom (specific volume
8 _1
air include (a) increasing the quantity of ventilating air,
=0.854 m' kg- of dry air) the dry air-flow rate is 93.7 kg tr . The
1 1 (b) circulating drier air and (c) cooling or refrigeration
heat added to the air between the downcast shaft-top and upcast of the circulating air (including the use of devaporized
shaft-bottom is 93.7 (99.65-52.35)x 10- =4.43 MW. A part of
3 compressed-air).
222 M I N E E N V I R O N M E N T A N D V E N T I L A T I O N
"T
301 -
J0> -
so* -
SOS -
JO* -
w
*J0J
«
-
= J0I -
wJOO -
B
*>2tt -
to
2*1 -
l»» -
0*»-»U(.i ItM»tB«TU»t
296 -
WCT-»UI» UMPlKATtme
2*1 -
2*1 -
UI6.
1975 re*.
1976
Fig. 3.18 Annual variation of temperatures at d.c. and u.c. shaft-bottoms
at Chinakuri No. 1 and 2 pits (1975-76).
^ t ^ K F E P * * *
1 ( 3 9 7 )
= QP\
Q = quantity of air flowing, m s- , 3 1
of dry air
and H, = enthalpy of in-flowing air, kJ kg- of dry air. 1
stroke by two-third and a considerable reduction in the rates of water from behind the lining and thus prevent moisture evaporating
accident and sickness. into the mine air. Covering up of water drains goes a long way in
However, the increase in volume has its limitations. In very minimizing evaporation of moisture into the mine air.
hot and humid mines where an increased air velocity produces little
bodily comfort, an extra volume of air will be of no help. Moreover 3.12.3 Refrigeration
mine airways should be large enough to take the extra quantity of Refrigeration of mine air is necessary when its temperature
air without causing excessive frictional pressure loss and excessive becomes excessive so that no further increase in the quantity
air velocity. High pressure loss increases the power cost of ventila- of air would improve environmental conditions. Refrigeration
tion and high air velocity raises dust in the roadways. Hence both plants are usually designed to produce tolerable environmental
of these are undesirable. conditions throughout the year at the working places in the mine.
We have seen earlier that the wet-bulb temperature of air Normally, the air is cooled and dehumidified so that it is saturated
entering a downcast shaft rises steadily with depth. At a certain at 275 to 278 K. It is then conducted to the working faces as such
depth therefore the wet-bulb temperature may reach a level which or after mixing with a stream of uncooled air so as to obtain the
will lead to the face wet-bulb temperature exceeding the tolerable desired face temperatures. Hence a refrigeration plant should be
limit. In such cases ventilation alone will not be sufficient to alleviate designed to have a capacity, sufficient for cooling the farthest face
the face environmental conditions. under the worst surface-temperature conditions as may occur in
the summer. The refrigerators installed on the Witwatersrand
3.12.2 Drying of Mine Air have usually a heat extracting capacity of 3.7 MW per 100 m s- 3 1
It has already been said that a fairly high dry-bulb temperature of air entering the mine. They cool the surface air at 292.5 K dry-
can be tolerable if the relative humidity or the wet-bulb temperature bulb and 289.5 K wet-bulb temperatures to 274.8 K saturated.
is low. That is why in deep and hot mines where the air temperature The first refrigerator installed in India at Oorgaum mine cooled air
is high, maintaining the air dry helps a great deal in improving the from 296 K wet-bulb to 277.5 K. saturated, the refrigerator capacity
working conditions. There is no economical process of drying the being approximately 5.58 MW per 100 m s- of air (the actual
3 1
air as such except by refrigeration. Drying of mine air by passing amount of heat extracted was 3.95 MW from 71.4 m s- of air
3 1
it over dessicants like calcium chloride, magnesium chloride or flowing through the mine).
silica gel becomes very costly and the advantage gained by drying Calculation of Cooling Load of a Refrigerator. The cooling load
is greatly compensated by the heat produced by absorption which of a refrigeration plant for any part of the mine is calculated so as
raises the temperature of air. However, care can be taken to see to provide comfortable environmental conditions (300.5 K w.b.
that the air does not pick up moisture in the mine and hence is and 302.5 K d.b.) assumed earlier for ventilation requirement cal-
maintained dry. This is done by adopting dry mining. Although culations. Heat-flow into the mine air from different sources has
dry mining is harmful from the point of view of dust hazard, it is been discussed earlier. On the basis of this study an estimate of
worthwhile to find out suitable dry dust-collecting means rather the total heat (both sensible and latent) added to' the mine air in
than to use water for dust suppression in very hot mines. However, this part q is made. The required cooling load q is then given by
c
if the strata ooze out water, it is very difficult to control the humidity the heat balance equation
of the mine air. Spraying of fuel oil over the surface of airways has f.-f+Q^m-IWkW (3-98)
been found to considerably reduce evaporation from the surface. .. The heat content of the air flowing into the mine varies from
Experiments with a roadway-surface sprayed with fuel oil and then season to season and the cooling load should be calculated for the
with water showed that it took the water one whole shift to evapo- maximum heat content of the in-flowing air (occuring in the sum-
rate whereas ordinarily it would have evaporated in 10 to 15 minutes. mer). However, it is necessary to determine the cooling load for
Sometimes it may be economical to line the major airways with
226 MINE ENVIRONMENT AND VENTILATION
MINE CLIMATE
( R = H i ~ #1 kJkg-
c (?.I0O)
1
3.5
= _ kgs-'perRt
H i H x (3.102)
The theoretical compressor volume (piston displacement) is
obtained by multiplying the mass of the refrigerant circulated by
the specific volume of the refrigerant which can be obtained from
the pressure-enthalpy (Mollier) diagram of the refrigerant (see Fig.
3.20 for such a diagram for Freon 12). Hence theoretical piston
displacement
= „ 1 „ • r.m'kW- 1 (3.103)
(3.105)
Heat removed through condenser which is theoretically equi-
valent to the heat absorbed in the evaporator plus the work
of compression
IT 11
=
Compressor. —TT-F o rkW perlarge-capacity
most kW cooling ofmine
loadrefrigeration(3.106)
plants,
reciprocatingHt compressors
— Hx or centrifugal compressors are generally
— —
MINE C L I M A T E 231
230 MINE E N V I R O N M E N T A N D V E N T I L A T I O N
to 370 rad s- or 3500 r.p.m.) and are usually air or water cooled.
1
condensers is given by the relation
Centrifugal compressors of single to eight stages have been used.
They have higher speed than reciprocating compressors That is
why they are more compact. There are no rubbing parts like valves, M " ° 4.1868 ( 7 W , ) k g S -' <- >3 ,07
piston rings, etc. and hence the efficiency is maintained over the where q = the rate of heat removal in kW
whole life of the plant and also the gas is delivered in a steady stream
which does not come in contact with contaminating lubri- =
ff—7p x cooling load, (3.108)
cating oil. 3 "1
Refrigerant. A good refrigerant should have a large latent T is the temperature of water at the condenser outlet and T
T LT
heat of evaporation and should evaporate and condense as near that at the condenser inlet in K.
atmospheric temperature and pressure as possible. Ammonia and The surface area of heat transfer, from which the number and
fluorinated hydrocarbons like Freon 11, 12 etc. are suitable size of tubes (in case of shell-and-tube type condenser) can be
refrigerants. Although carbon dioxide can reduce compressor size calculated, is given by the relation
because of its low specific volume, it is not suitable for use at mines, q = ocA &T kW m (3.109)
because of its low critical temperature (304.5 K) and toxicity. where A = the surface area of heat transfer in m , 2
Ammonia has the largest latent heat of evaporation and is LT = the log mean temperature difference in K
m
cheap, but is toxic and corrosive for brass and copper. However,
= _A7*i —A7*, AT^-Ar,
leakage of ammonia can be easily detected by smell and corrosion
MATVAn) 2.3 logL&TJATI) l * I I U J
can be avoided by selecting suitable material for construction of the
refrigerator. That is why it is commonly used in surface refrigera- A7\d AT = difference of temperature between water and
2
tion plants. On the other hand, Freon is a non-toxic refrigerant refrigerant at the inlet and outlet of the con-
and is therefore commonly us*ed in underground air-cooling plants denser respectively,
even though it is costlier than ammonia. Freon 11 (trichloro- and a = the overall heat transfer coefficient in
monofiuoro-methane) is generally used in centrifugal compressors kJ m- s- K- . 2 1 1
while Freon 12 (dichloro-difluoro-methane), in reciprocating com- a is usually calculated from test data on the type of condenser
pressors. as well as the water-refrigerant system.
Condensers and Evaporators. Condensers are generally of the a A can, however, be estimated from the relation
shell-and-tube type. Evaporative condensers, where the hot
i l + 1 + r + 1
refrigerant vapour passes through finned tubes on which water is (3.111)
sprayed by circulating pumps and there are fans to blow air over a A «, A lm ocf A( kA m aQ A„
the condenser tubes, are generally restricted to smaller plants not
exceeding 350 kW (100 Rt) in capacity. Such condensers do not where a, = heat-transfer coefficient at the inner surface of the
need any further cooling of condenser water. But for larger plants, • u < ^- a 21.4(r -206.48)v o» m ir
tube (convective) at. • — LJS.—
Do.i
the heated water from the condenser has to be cooled either in spray
ponds or cooling towers. Wm K J J (3,112)
Evaporators are similar to shell-and-tube type condensers in
construction. Their design should be such as to allow the boiling
232 MINE E N V I R O N M E N T A N D VENTILATION MINE CLIMATE
233
adopted only in small units such as spot coolers. In the indirect = M (H-H )-0.00l
a o MC (m -w )(r -273.15)kW
a pw / 0 w
to a fairly low temperature (near about the freezing point of water) T and T
ci co = temperature of cooling liquid at the inlet and
because brine has a lower freezing point, and hence is less likely to outlet of the cooling coil respectively, K ,
freeze in the pipelines. Calcium chloride and sodium chloride
MINE C L I M A T E 235
234 MINE E N V I R O N M E N T A N D VENTILATION
the mine. Fig. 3.21 gives some installations of this type.
/Y, and H = enthalpy of air entering the cooling chamber
0
Occasionally a horizontal spray chamber may be used with
and leaving it, kJ kg- of dry air, 1
induced draft.
m,- and /?;„ = mixing ratio of air entering and leaving the
cooling chamber, g kg- of dry air, 1
COOLING' CONCRETE
t of the chamber and C = specific heat of water.pw
TOWER '/ SP-L INING
Hence q = M C (T -TJ
wi pw W0 \
The limitations of the second law of thermodynamics that the A very suitable system is the divided installation (of tlv refri-
water cannot leave the tower at a temperature lower than the wet- gerator and the cooler) which incorporates the advantages of both
bulb temperature of the entering air and the wet-bulb temperature surface and underground plants.
of the air leaving the tower cannot exceed the temperature of water The first surface refrigeration plant was installed at the Morro
entering the tower should always hold in designing these cooling Velho Mine, Brazil in 1920. In 1929, the same mine installed the
towers. Equation 3.117 used for coolers can also be used for first underground refrigeration plant. The first mine air-condi-
cooling towers, though the heat transfer in this case is in the opposite tioning plant in India was installed in 1936 at the Oorgaum Mine,
direction (i.e. from water to air). Kolar Gold Fields. The surface refrigeration plants at mines today
Cooling towers are usually designed to cool condenser water are mostly of the ammonia type although at the Robinson Deep
by 7 to 9 K. Air velocities in cooling towers vary between 2.5 to Mine, South Africa there is a Carrene plant on the surface.
7.5 m s- , the higher velocities giving greater retention time for
1
Champion Reef Mine, K.G.F., India. A typical ammonia plant
the droplets of water, but velocities greater than 9 m s- are 1
installed on the Gifford Shaft at this mine is illustrated in Fig. 3.22.
undesirable as they tend to carry away a large amount of water The plant has a capacity of 3.7 MW (1060 Rt) cooling 70.82m s- 3 1
plants (centrally located) and spot coolers. It is very essential for compressed gas then passes through the oil separator which extracts
economy to maintain a high positional efficiency of the refrigeration any oil picked up from the compressor cylinder. The oil-free gas
plant. Obviously spot coolers which are located at the face have — n o w cooled to liquifaction in the condenser by circulating cold
the maximum positional efficiency as they supply the cooled air "rtater by three 22-kW pumps each having a capacity of 6.06
directly to the face, but they meet with the difficulty of disposing of m min- . The cooling water extracts the heat of compression of the
3 1
the heat extracted from air at the face. This heat can best be
disposed of if a direct return airway (not ventilating any other
district) is available nearby. Otherwise the heat extracted from one
face may be carried to another face or even recirculated to the refri-
geration plant in which case the effect of cooling at the face will
be reduced. Spot coolers are used generally for cooling remote
development headings, engine houses etc. They are semi-portable
and have small capacity. Reciprocating compressors are commonly
used. Both direct and indirect cooling (usua'ly with water as
a cooling medium) are used depending on the size. The quantity
air-flow through the spot cooler should not exceed half the quantitjjf
passing through the airway in order to prevent recirculation of air
through the cooler.
Surface refrigeration plants are of relatively large capacity
running into megawatts. For deep mines, however, their positional
efficiency falls where it may be more profitable to have central
underground refrigeration plants. Undeiground refrigeration plants
are generally of smaller capacities and face the problem of suitably 'g 3.22 Schematic diagram of the surface air-conditioning plant at
disposing of the heat extracted from the air. Champion Reef mine, K . G . F .
238 MINE ENVIRONMENT A N D VENTILATION
MINE C L I M A T E 239
gas as well as the latent heat of evaporation of ammonia. The liquid propeller fan of 2400mm diameter. The brine, after cooling the air
ammonia is then fed through the float regulator to the evaporator. gets warm and has to be cooled again by the vaporization of liquified
The float regulator so adjusts the flow that a constant level of liquid ammonia in the evaporator.
ammonia is maintained in the evaporator. The compressor in its An underground refrigeration plant has also been installed at
backward stroke causes a partial vacuum in the cylinder, as a result this mine. This was necessary because the south section workings
of which a part of the liquid ammonia in the evaporator is vapo- had 329.8 K d.b. and 306.5 K w.b. temperatures in spite of the
rized and drawn into the cylinder to be compressed again. After surface cooling plant. The plant is situated at a depth of 2318m
the extraction of heat from ammonia the cooling water gets warm from the surface and has a capacity of cooling 9.44 m s- at 305.9 K
3 1
and is cooled again in a spray pond. The condenser and evaporator d.b. and 293.2 K w.b. to 276.5 K saturated. The plant consists of
are of the shell-and-tube type. a three-cylinder compressor with Freon 12 (dichloro-difluoro-
A weak calcium chloride brine solution (sp. gr. 1.22) is methane, CCI F ) as refrigerant. The condensing water is cooled by
2 2
circulated through the evaporator by three brine circulation pumps spraying it in an upcast shaft. Fig. 3.23 gives the layout of the
each having a capacity of 4.9 m min- . The brine on leaving the
3 1 plant.
evaporator gets cooled and the cold brine is then circulated through Robinson Deep Mine, S. Africa. The principle of operation of the
the cooler which consists of a large coil of 38mm bore steel pipes. Carrene plant on Turf shaft at the Robinson Deep Mine, S. Africa is
Air to be cooled is blown over the cooler pipes by a 2-stage similar except that here centrifugal compressors are used to com-
press the refrigerant, Carrene No. 2 (trichloro-fluoro-methane,
CFCI ). It has been found that for the same capacity, centrifugal
3
35-8 k g <f'
U P - C A S T AIR
m min- against a head of 41.2m. The cooling water pumps are
3 1
80 LEVEL
200mm centrifugal ones driven by 56 kW motors running at
303.9 K
154 rad s- (1470 r.p.m.) and delivering 9 m min- against a
1 3 1
AIR 321.2 K/300.5K
CONDITIONING \ head of 26m. There are two fans circulating the air. Each of the
PLANT
WATER CONDENSED fans is driven by a 75 kW motor running at 76 rad s- 1
F R O M AIR
(725 r.p.m.).
, 1 FAN
Surface Plants vs Underground Plants. Surface plants have the
*za.
advantages of (a) simplicity, (b) convenience of operation and ins-
21.4 kQ S~' V£>. 30Q. 3 K / 2 9 0 - 5 K _
3 0 7 . 3 K/ 2 9 3 - 9 K —
TO OSBORNE S H A F T
pection, (c) safety, (d) cheapness (as they use cheap refrigerants like
ammonia) and (e) ease in the disposal of waste heat into the air.
Fig. 3.23. Schematic diagram of the underground air-cooling plant at Besides, surface refrigeration plants aid in producing a large natural
Champion Reef mine, K . G . F . ventilating pressure because of the large difference in the downcast
MINE CLIMATE 241
240 MINE E N V I R O N M E N T A N D VENTILATION
laterally over 1000m away from the bottom of the downcast shaft
and upcast air temperatures so much so that in deep mines, mecha- (where the underground refrigeration plants are usually situated),
nical ventilation may become unnecessary after the installation of the positional efficiency becomes unsatisfactorily low. In such cases
surface air-conditioning plants. the plant has to be located nearer the face.
On the other hand, underground refrigerators may slightly Underground refrigeration plants have the following disadvan-
reduce the natural ventilating pressure. The main disadvantage of tages: (a) They have to use non-toxic refrigerants like Freon which
surface refrigerators is their low positional efficiency which is costs four times more than ammonia, commonly used in surface
defined as the ratio of the effective cooling units produced at the plants. Also, it is difficult to prevent the leakage of refrigerant and
working face, i.e. the difference in the heat content of the face air Freon, being odourless, is less likely to be detected if leaking in a large
before and after the installation of the refrigerator to trie total quantity. Moreover the non-toxic refrigerants are less commonly
cooling units produced by the refrigerator. Positional efficiency of available, (b) The problem of dissipating the heat extracted from
surface plants increases with time, since the rock through which the air is difficult and heavy pumping expenses might have to be
the cooled air is carried to the face gets progressively cooled. How- incurred. Sometimes if suitable underground positions for spray
ever, the rate of increase of positional efficiency decreases with time cooling of water are not available, the water may have to be pumped
so much so that after a certain time the increase in positional to the surface for cooling thus involving a high cost of pumping.
efficiency can be considered as negligible. The positional efficiency Besides, spray cooling of water in upcast shafts or airways increases
in surface plants usually varies from 35% upwards, a lower posi- the humidity of the upcast air which then becomes unsuitable for
tional efficiency being considered unsatisfactory. In very hot and ventilating upper levels. Also, the condenser water gets fouled by
deep mines, particularly where the working faces are far off from picking up dust from the air and may lead to the corrosion of pipes,
the shaft, cool air from the surface refrigeration plants picks up (c) In dry and dusty mines, dust deposits on the surface of the tubes
much heat before it reaches the working place. It may be noted here in the cooler thus reducing the efficiency of heat transfer and neces-
that in deep shafts auto-compression alone can use up a major part sitating frequent cleaning for ensuring good operation, (d) There
of the cooling produced by the surface cooling plant. The problem is difficulty in suitably locating an underground excavation and
will be more acute if the mine is wet. Under such conditions an such excavations are costly, (e) Supervision of plant is difficult.
underground plant will have a higher positional efficiency by being
nearer the face. (f) In mines susceptible to rock burst, the excavation housing the
refrigerator may be subjected to high stresses set up by the differen-
Besides, surface plants pose some difficulties in feeding the tial cooling of the surrounding rock thus resulting in rock bursts.
cooled air into the mine. The commonest way is to feed a quantity (g) Underground plants are usually of small capacity (up to 1.75
of cooled air, slightly less than the quantity circulating through the MW) and hence a single plant may not be able to serve the whole
mine into the downcast shaft at a depth of 30m or more from the mine, (h) In case of a breakdown of the refrigeration plant under-
shaft collar so that a small quantity of unconditioned surface air ground, the working condition soon becomes unbearable whereas
always enters the mine at the top of the intake shaft. Alternatively, with a surface plant the downcast shaft serves in extracting heat
the cooled air can be fed at the top of the downcast shaft from the intake air for a considerable period. The sides of the shaft
which should then be covered with a suitable leakproof air-lock. get substantially cooled by the cool air from the surface refrigera-
Whereas the former method needs a close control of the quantity tion plant over the years. The extent of cooling is the maximum near
of cooled air fed into the mine and incurs some loss of cooling by the top of the shaft and decreases as the depth increases. When the
dilution with unconditioned air, the latter needs an air-lock which plant stops, the sides of the shaft absorb heat from the air for a time
is very inconvenient in a hoisting shaft. Besides, it is difficult to which is usually sufficient for the plant to be put back in operation.
prevent leakage of cooled air through the air-lock. Divided Installation. Here the major part of the refrigeration
Unaerground refrigeration plants have high positional efficiency plant excepting the cooler unit is located at the surface so that the
if suitably sited. It has been found in deep mines that if a face is
MINE C L I M A T E 243
242 MINE ENVIRONMENT A N D VENTILATION
metalliferous mines, as surface refrigeration plants have much lower
heat extracted from the air can be easily disposed of to the positional efficiency in coal mines. This is because of the following
atmosphere. But the cooler is located underground. The cooling reasons : (a) For the same depth, the heat produced in coal mines
medium (brine or water) from the evaporator is carried in insulated is more because of the higher strata temperature (geothermic
pipes to the cooler underground and returns through another range gradient in coal measure strata is usually steeper as is evident from
of pipes, thus forming a closed circuit. The pumping cost in this Table 3.1) and larger surface area of rock exposed even though the
case is low as the two columns of down-going and up-coming , thermal diffusivity and hence the rate of heat transfer i n coal
"measure strata is less, (b) Coal mines are usually more wet and
cooling medium almost balance each other and the power required
hence a large quantity of moisture is evaporated into the cooled
for pumping is for overcoming pipe friction only. A divided-instal-
air thus increasing its relative humidity, (c) A lot of heat is produced
lation plant has high positional efficiency, faces no difficulty in
in coal mines by the oxidization of coal. Because of these reasons
disposing of extracted heat and obviates the need of surface air-
it is better to have an underground cooling plant in a coal
locks, but its main disadvantage is the high cost of high-pressure
mine, preferably with the cooler unit (the heat exchanger
insulated pipelines required for conducting the coolant underground. between coolant or cooling medium and air) as near the face as
Besides it is difficult to adopt such a system for very deep mines possible.
owing to the very high pressures the ranges would be subjected to.
A typical example of divided installation is offerred at the Leslie- Spot Coolers. For ventilating hot faces, small-capacity spot
geois Colliery, Belgium, where the virgin-rock temperature at the coolers are becoming popular both in coal and metal mines. These
bottom horizon (at a depth of 1010m) is 318 K. A surface are semi-portable and have a cooling capacity generally varying
from 50-200 kW (15-55 Rt). There are two types of spot coolers :
ammonia plant of 2.42 MW capacity cools 200 m min- of water
3 1
•>(a) where the direct evaporation of the refrigerant cools the air
to 274.25 K. The chilled water is taken down the shaft through
' (generally confined to the smaller ones), and (b) where an interme-
insulated pipes. To avoid the passage of high-pressure chilled water
diate coolant such as water is used. The units usually consist of
through the heat exchangers underground the water is passed
reciprocating compressors driven by electric or compressed-air
through a Pelton turbine whereby its pressure is reduced. The
motors. Cooling of the compressed refrigerant is done in air-cooled
Pelton turbine drives a pump which pumps the warm water to ihe condensers. A typical direct-evaporation unit consisting of a V-8
surface. The pressure lost \r the turbine, pump and water pipes is compressor driven by a 25 kW motor along with a condenser and
made up by an electric motor of 180 kW. The chilled water from oil separator measures 1700mm in length, 750mm in width and
the turbine goes to a reservoir from where ii is distributed to coolers 1450mm in height. The cooled refrigerant passes through an evapo-
located near the face. rator fitted inside the ducting of a forcing fan supplying air to the
At Butte mine. Montana, U.S.A. the summer suiface tempera- face. The evaporator has a cooling surface of 40 m approximately
2
tures are 305.4 K s.b. and 28? 6 K w.b. with a dew point of 277.6 K which is capable of transferring 46 kJ m- h- K - to the air flowing
2 1 1
which means that the air is very dry. The cooling medium is water. at the rate of 2.67 m s- . The pressure required fcr the air-flow
3 1
It is cooled by spraying it in «s surface cooling to «er .hrough which > is 735 Pa. The spot coolers, though having the advantage of cooling
is circulated a current of air. The air is precoolec hy passing it over the face, leave the rest of the mine hot. However, a useful gain
the cooled water pipes. The cool water al . "' 4 K »: taken down the associated with spot coolers is that cool air helps in condensing
shaft which is 1220m deep, in insulated piy.es a.-r> is used to cool moisture on dust particles thus helping in dust supression at the
the air there. The cooling achieved undo-.'.' u» • < from 302.6 K face. Table 3.9 lists a few spot coolers.
w.b. to 294.3 K w.b. In winter the surface temperature is very low • Other methods of mine air-cooling include the use of devapo-
which makes cooling unnecessary, fiiis i> a typical example of rized compressed-air, ice or liquid air as well as regenerative
evaporative cooling of air which is sulfide: Hy -jry. cooling.
Air-conditioning in Deep Coal Mines. Air-conditioning in deep
and hot coal mines coses a slightly more difficult problem than in
244 MINE ENVIRONMENT AND VENTILATION MINE CLIMATE 245
Table 3.9 : Spot Coolers Compressed-air, when it expands by doing work, as for instance in
an air motor, cools down and any moisture present in it may freeze
Cooling to ice depending on the degree of expansion. This restricts the de-
Country Make capacity, Remarks sign of air motors to low expansion types where full work can r, t
kW be derived out of the compressed-air. Morever, aqueous vapou-
WK 1205 128 Compact, portable and in compressed-air carries the latent heat of evaporation into the
East Germany
mine. This heat is given up to the air when water-vapour condenses
(GDR) suitable for coal mines
West Germany KR 150 181 »!
'during the use of compressed-air for doing work and this neutra-
lizes to a large extent the expansive cooling produced by the
-do- KR 200 233 •1
49 compressed-air. It has been found that the temperature of expanded
USSR. WK 42 '1
exhaust air with saturated compressed-air is about 11.1 K higher
U.S.S.R. KP Sch.-l 73 .,
,,
than that with devaporized compressed-air. It is for these reasons
U.K. J. E. Hall 16
that devaporized compressed-air is far superior to ordinary com-
India Voltas 33 TR 115 Semi-portable, suitable
pressed-air in improving the cooling power of mine air.
0 for metal mines only.
Voltas 100 TR 350 Stationary, suitable Devaporization is done by overcompressing the air by about
-do-
for metal mines only. 50% over the normal working pressure of 500-650 kPa and then
passing it through a heat exchange system where the overcom-
pressed air is cooled by a current of cool devaporized compressed-
3.12.4 Regenerative Cooling air. The cooled overcompressed-air is now employed to run an air
This is only in the theoretical stage of development and has yet ^motor. In doing so it expands to the normal working pressure and
to be adopted in practice. If a certain gas of high density and low %- also cools to 273 K. At this temperature, all the moisture in the
specific heat such as carbon dioxide is circulated in a closed circuit compressed-air is liquified and removed from it. The dry and coo!
down the upcast shaft and up again through the downcast shaft, compressed-air is now circulated through the heat exchanger t<-
then the heat developed due to auto-compression of carbon dioxide cool the overcompressed-air.
will be dissipated into the upcast air while the cooling due to auto- The devaporized compressed-air is now sent down the mine
expansion will cool the downcast air. This not only produces cool- where it is used to run air motors, drills etc. at the face. The exhaust
ing of the downcast air but also increases the natural ventilation. air from these machines gets substantially cooled by expansion.
This, coupled with the dryness of the air helps in keeping down the
3.12.5 Devaporized Compressed-air temperature and humidity at the face.
Ordinarily, compressed-air when escaping from a pipe does This system, inspite of its limited capacity for cooling the mine
practically no work and hence does not produce any cooling. How- air as a whole, produces good cooling at the face where it is most
ever, compressed-air is saturated at its usual supply pressure of required. The extra power required in devaporizing the compressed-
500 kPa. Its degree of saturation is reduced to 20% on expansion ^ air is only 10% in case of reciprocating compressors and 12.5% in
to free air so that it reduces the overall relative humidity and the case of centrifugal compressors. However, the main disavantage of
wet-bulb temperature when mixed with the main air-current. A the devaporized compressed-air plant is its comparatively high
9% addition of compressed-air usually reduces the w.b. temperature cost and low efficiency of performance.
of the main air-stream by 1 K. This practice however is very
uneconomical. 3.12.6 Ice and Liquid Air
Wet compressed-air reduces the efficiency of drills etc. by Cooling of mine air at the face by the use of ice or liquid air
washing away the lubricant. It also causes rusting in the pipe ranges. becomes very costly.
246 MINE ENVIRONMENT AND VENTILATIONI
MINE CLIMATE 247
The comparative cost of cooling mine air by variour, methods
273.15+300.2 35 169
is given by Dobson as follows :4 8 = 1553.7+0.645
2 / ( 273.15+300.2)/2 1
( )
Table 3.10 : Comparative Cost of Various Methods of Cooling = 1861.3 J kg- K- . 1 1
{ )
/ (latent heat of vaporization) at 273.15 K=2.5004x 10 J kg- . 9 1
Method of cooling Cost in P MJ- 1
Therefore enthalpy of air at 300.2 K d.b. and 295.8 K w.b.
(
Additional ventilation* Hy=C (r -273.15)+0.001m C (r -273.15)+0.001/w /
l 1 1 l
Dehumidified compressed-air + 0.38-0.76 Amount of liquified vapour m =m —m =9.34 g kg- of dry air.
s 1 2 1
Ammonia plant at K G . F * 0.26 C (specific heat of dry air) over the range 273.15 to 277.4 K
Carrene plant at Turf shaft* 0.36 POi
Underground or surface
- 995.68 + 0.029 ^ ( 2 7 3 - 1 5 + ™ > ^ =1003.7 J k g - K - .
2 1 1
refrigeration plant (average) + 0.57
+ Estimated by Peele ' C (specific heat of water-vapour) over the range 273.15 to 277.4 K
P*t
* Estimated by Mclntyre
35 169
Example 3.8 = 1553.7+0.645 (273.15+277.4)/2 + ( :
=46.75- 88.2
=4123.4 kJ s- — 4.12 MW 1 (1180 Rt). (see equation 3.103).
Enthalpy of refrigerant after compression (assumed isentropic)
Example 3.9 ^ H = 592.9 kJ kg- .
t 1
3.1 The following are the readings of a barometer and thermo- 3.8 Using the psychrometric chart find the percentage of error
meter at the base camp and the face of a mine located on a hill-top. that may be introduced by'not taking into account the dry-bulb
Calculate the elevation of the mine face above the base camp. temperature in calculating the heat extraction capacity of a refri-
Neglect moisture content of air. geration plant for. cooling air from 291 K. w.b. to 277 K saturated.
Barometer reading, kPa Thermometer reading, K. The likely range of variation of the dry-bulb temperature is upto
Base camp 100.1 305 321 K.
Mine face 98.3 298
3.9 A hygrometer reads 303 K d.b./293 K w.b. Find the effective
3.2 How much heat is added to the mine air by (a) a 300 kW
temperature if the air velocity is 1 m s- . What air velocity would
1
underground pump pumping 6m of water per minute through a
3
ensure an effective temperature of 294 K. ?
height of 150m ; (b) a diesel truck running on level ground and
consuming 9.5 kg of fuel per hour on the average, the calorific value
of fuel being 42.6 MJ kg- ; (c) a 46 kW direct-driven surface for-
1
3.10 Calculate the enthalpy of air at 307 K d.b./302 K w.b. tem-
peratures at a barometric pressure of 101.33 kPa where the vapour
cing fan circulating 60 m s- of air through the mine at a static
3 1
pressure is 3.7 kPa. Assume specific heat of air = 1005 J kg- K - 1 J
pressure of 900 Pa. Assume 6m diameter shafts.
specific heat of water-vapour=I860 J kg- K - and latent heat of
1 1
308 K d.b./302 K w.b. temperatures every second. The barometer 3.12 The following measurements were made on a cooling plant.
reads 101.33 kPa. Calculate the duty of the cooling plant (evaporator heat exchange),
the condenser heat exchange and the compressor power input.
3.5 Find the mass of dry air in 5.1 m of moist air at 310 K d.b./
8
Evaporator water flow-rate = 28.7 kg s- 1
bulb temperature? What would be the amount of heat extracted Condenser water temperature
if the air were cooled further to 278 K saturated? What would inlet = 310.1 K.
be the mass of water-vapour condensed in the process? delivery = 315.3 K