0% found this document useful (0 votes)
139 views16 pages

Simulation of Sheath Voltage, Losses and Loss Factor of High Voltage Underground Cable Using MATLAB/Simulink

In this paper, 22 equations for high voltage cable sheaths are simulated in one model. The model outputs are represented by cable sheath voltages, circulating currents, losses and factors, eddy currents, losses, and factors in both tides laying states (trefoil and flat) when grounding the sheaths from a single point, two points, or cross-link. These values depend on the cable manufacturing's specific factors. The other factors affecting these values are specific to the laying and operation: the load current, the length of the cable to be laid out, the spacing between the cables, and the power frequency. This research aims to reduce or eliminate the losses of the cable sheath. These two types of currents cause losses that may sometimes equal the losses of the conductor of the cable carrying the load current. Which reduces the capacity of the cable and reduces the heat dissipation of the cable into the soil and damages it. Electricians are at risk of electrocution due to the high voltages of the sheaths when there is no current in the sheaths. Therefore, these currents and voltages must be eliminated by making a new model that studies the effect of all these factors on them. For complete access to the paper, please click on this link: https://ijpeds.iaescore.com/index.php/IJPEDS/article/view/21737
Copyright
© Attribution ShareAlike (BY-SA)
We take content rights seriously. If you suspect this is your content, claim it here.
0% found this document useful (0 votes)
139 views16 pages

Simulation of Sheath Voltage, Losses and Loss Factor of High Voltage Underground Cable Using MATLAB/Simulink

In this paper, 22 equations for high voltage cable sheaths are simulated in one model. The model outputs are represented by cable sheath voltages, circulating currents, losses and factors, eddy currents, losses, and factors in both tides laying states (trefoil and flat) when grounding the sheaths from a single point, two points, or cross-link. These values depend on the cable manufacturing's specific factors. The other factors affecting these values are specific to the laying and operation: the load current, the length of the cable to be laid out, the spacing between the cables, and the power frequency. This research aims to reduce or eliminate the losses of the cable sheath. These two types of currents cause losses that may sometimes equal the losses of the conductor of the cable carrying the load current. Which reduces the capacity of the cable and reduces the heat dissipation of the cable into the soil and damages it. Electricians are at risk of electrocution due to the high voltages of the sheaths when there is no current in the sheaths. Therefore, these currents and voltages must be eliminated by making a new model that studies the effect of all these factors on them. For complete access to the paper, please click on this link: https://ijpeds.iaescore.com/index.php/IJPEDS/article/view/21737
Copyright
© Attribution ShareAlike (BY-SA)
We take content rights seriously. If you suspect this is your content, claim it here.
You are on page 1/ 16

International Journal of Power Electronics and Drive Systems (IJPEDS)

Vol. 13, No. 1, March 2022, pp. 200~215


ISSN: 2088-8694, DOI: 10.11591/ijpeds.v13.i1.pp200-215  200

Simulation of sheath voltage, losses and loss factor of high


voltage underground cable using MATLAB/Simulink

Mahmood Natiq Abed1, Osamah Abdulsalam Suhry2, Mohammed Ahmed Ibrahim3


1
Ninavah Electricity Distribution Directorate, General Directorate of North Distribution Electricity, Ministry of Electricity, Mosul, Iraq
2
General Directorate of North Distribution Electricity, Ministry of Electricity, Mosul, Iraq
3
Department of Power Technical Engineering, Northern Technical University, Mosul, Iraq

Article Info ABSTRACT


Article history: In this paper, 22 equations for high voltage cable sheaths are simulated in
one model. The model outputs are represented by cable sheath voltages,
Received Jul 2, 2021 circulating currents, losses and factors, eddy currents, losses, and factors in
Revised Jan 15, 2022 both tides laying states (trefoil and flat) when grounding the sheaths from a
Accepted Jan 24, 2022 single point, two points, or cross-link. These values depend on the cable
manufacturing's specific factors. The other factors affecting these values are
specific to the laying and operation: the load current, the length of the cable
Keywords: to be laid out, the spacing between the cables, and the power frequency. This
research aims to reduce or eliminate the losses of the cable sheath. These
Circulating losses two types of currents cause losses that may sometimes equal the losses of the
Cross link conductor of the cable carrying the load current. Which reduces the capacity
Eddy losses of the cable and reduces the heat dissipation of the cable into the soil and
Sheath voltage damages it. Electricians are at risk of electrocution due to the high voltages
Single point of the sheaths when there is no current in the sheaths. Therefore, these
Two points currents and voltages must be eliminated by making a new model that
studies the effect of all these factors on them.
This is an open access article under the CC BY-SA license.

Corresponding Author:
Mohammed Ahmed Ibrahim
Department of Power Technical Engineering, Technical College of Engineering, Northern Technical
University, Mosul, Iraq
Email: [email protected]

1. INTRODUCTION
The danger of electric shock and fault currents is reduced with electric shock and fault currents
reduced with electric shock, and fault currents reduced with insulating material for high voltage underground
cables compared to the overhead transmission lines [1], [2]. Single-core cables have a high current capacity,
so they are more likely to be used for high power transmission than three core cables [3], [4]. The cable
insulation material is covered with metal tape or wires (sheath) to return fault and capacitive current, reduce
the mechanical effects on the main conductor and prevent the electric field effect outside this sheath [5]. An
induced voltage is generated at the metal sheath due to the passage of load current that magnetic product flux,
which penetrates this sheath as explained in (one end bonding). A current flow between the ground and the
sheath when it is grounded at (both ends); its value depends mainly on the sheath voltage and its impedance,
causing so-called circulating losses [6]. Overheating the soil surrounding the cable due to conductor and
circulating sheath currents may cause the soil surrounding the cable due to conductor and circulating sheath
currents may cause the insulation's thermal breakdown [7]. The factors affecting circulating currents are
discussed, and several methods of connecting cable sheaths are presented to reduce the risk of the sheath
(voltages and losses) [8]−[13]. Therefore, the sheath current value must be reduced on the metallic sheath to
prevent its negative effects, and the metallic sheath must be grounded to reduce the sheath current effect.

Journal homepage: http://ijpeds.iaescore.com


Int J Pow Elec & Dri Syst ISSN: 2088-8694  201

Single-point bonding, solid bonding, and cross bonding are used to ground metallic sheath of high voltage
underground cable [14], [15]. Sheath voltages and currents can be found by modeling their formulation to
determine the required precaution before installing these underground cables. However, these equations'
difficulty because of multiple factors affecting their values made their simulation difficult [16].
The standard equation is utilized to determine sheath resistance, sheath losses with multiple cables
arrangements, and conductor's resistivity [17]. Sheath and conductor losses with two ends bonding are
determined theoretically in [13]. In thermal analysis, volumetric heat source, the volumetric heat source in
thermal analysis, is found by implementing losses determination in sinewave currents of underground cables
in [18]. Several factors like radiuses and distances between cables and phase current alterations are used to
determine sheath voltage [19]−[21].

2. LITERATURE SURVEY
Boyde [10], studied how to reduce and eliminate the eddy current by connecting a current
transformer at the load side, where the metallic cable is connected at the primary part of the transformer.
Then, it should be grounded from this side and the source side (two-point bonding). Next, the secondary part
of the current transformer is connected to a voltage transformer. This connection aims to make the voltage
transformer convert a voltage equal to the induced sheath voltage and opposite to it at an angle of 180
degrees to avoid passing away of any circulating current in the metal cover. Ma et al. [12], used a
compensating inductance coil, where one end is connected to the end of the sheath and the other end to the
ground. As a result, an induced electromotive force is generated, opposite in the direction of the remaining
voltage in the sheath. This generated voltage is due to the induction of the magnetic flux resulting from the
load current. This coil is used in case of cross-bonding because the three parts of cable sheaths are not equal.
From practical experience, all of these methods cause a high cost. In addition, the fault current in long-
distance cables will lead to weakening all the joints that pass through on its way back. In this research, a new
model was made to compare the cables layout methods. In addition, a comparison between the sheath
bonding methods is covered in this paper by studying the effect of (load current, cable length, frequency,
distances between the cables) on these methods. Hence the lowest values for the currents and voltages of the
sheaths are obtained, and consequently the best performance.

3. THE INDUCED SHEATH VOLTAGE OF SINGLE-CORE UNDERGROUND CABLES


Arrangements, construction, and length of cables must be considered when determining, and the
length of cables must be considered when determining the sheath, and the length of cables must be
considered when determining sheath-induced voltage [4], [22], [23]. Its value can be measured at the free
point with respect to earth with earthing the other point, as explained in Figure 1. Each sheath per phase in
the trefoil arrangement caries the voltage in (1).

Figure 1. One-point sheath bonding

𝐼𝑐𝑠1=0 , 𝑈𝑠1 = 𝑈𝑠2 = 𝑈𝑠3 𝑗𝜔𝑀𝐼1 (1)

Us1,2,3 : induced voltages in sheaths V/m


The equal spacing between the phases of power cables causes similar sheath induced voltages.
Where M is the mutual inductance and depends on the spacing between axes of any adjacent cables (S) and
the mean radius of the circle formed by the sheath conductor as,

𝑆
𝑀1,2 = 𝑀2,3 = 𝑀1,3 = 𝑀 = 2 ∗ 10−7 ln ( ) H𝑚−1 (2)
𝑟𝑠ℎ

either the spacing in the flat formation arrangement is different because of the outer cables as,
Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
202  ISSN: 2088-8694

𝐼
𝑈𝑠2 = − 3 [√3(𝑋 + 𝑋𝑚 ) + 𝑗(𝑋 − 𝑋𝑚 )]
2
𝑈𝑠3 = 𝑗𝜔𝑀𝐼3 } (3)
𝐼3
𝑈𝑠1 = − [−√3(𝑋 + 𝑋𝑚 ) + 𝑗(𝑋 − 𝑋𝑚 )]
2

I1,2,3: load three phase currents


𝐻
𝑀𝑚 = 2 ∗ 10−7 ∗ ln 2 = 1.389 ∗ 10−7
𝑚

𝛺
𝑋 = 𝜔 ∗ 𝑀, 𝑇ℎ𝑒 𝑟𝑒𝑎𝑐𝑡𝑎𝑛𝑐𝑒 𝑝𝑒𝑟 𝑢𝑛𝑖𝑡 𝑙𝑒𝑛𝑔𝑡ℎ 𝑜𝑓 𝑠ℎ𝑒𝑎𝑡ℎ
𝑚

𝑋𝑚 = 𝜔 ∗ 𝑀𝑚 , Mutual reactance per unit length of cable between the sheath of an outer cable and the
𝛺
conductors of the other two, when cables are in flat formation . It is clear from (3), the middle cable has
𝑚
equal spacing from the outer two cables, and its sheath voltage is similar to those of trefoil formation
arrangement.

4. SHEATH LOSSES OF SINGLE-CORE UNDERGROUND CABLES


Sheath losses are current-dependent and can be divided into two categories according to the type
of bonding [4], [24], [25]. Sheath circulating losses appear due to the sheath bonding from both ends as a
result of passing a current between the sheath and the ground. Eddy losses occur regardless of bonding type
(one point, two points, or cross bonding).

4.1. Sheath circulating losses


Two points bonding causes the flowing of sheath circulating currents, leading to circulating losses,
as explained in Figure 2. The voltages above and the impedance represented by the sheath resistance and
sheath reactance define the circulating current in trefoil and flat arrangement. The sheath impedance of three-
phase cables in the trefoil arrangement is the same because of the equal spacing. Based on this, circulating
sheath current per phase of the three cables can be written as (4).

Figure 2. Two-point sheath bonding

−𝑗𝜔𝑀
𝐼𝑐𝑠1 = 𝐼𝑐𝑠2 = 𝐼𝑐𝑠3 = 𝐼1 (4)
𝑅𝑠 +𝑗𝜔𝑀

From (4), the sheath circulating loss and factor are explained:
𝜔2 𝑀2
𝑊𝑐𝑠 = |𝐼𝑐𝑠 |2 𝑅𝑠 = |𝐼|2 𝑅𝑠 ( ) W𝑚−1 (5)
𝑅𝑠 2 +𝜔2 𝑀2

𝑅𝑠 𝜔2 𝑀2
𝛿𝑐𝑠 = ( ) (6)
𝑅 𝑅𝑠 2 +𝜔2 𝑀2

Where the factor in (6) is the ratio of sheath circulating loss to the conductor load loss in Wm−1 . However,
this is not true in the flat arrangement at two-point sheath bonding where the sheath circulating equations are
more complicated than trefoil one because the different spacing between the cables results in unequal sheath
voltages, impedances, and currents. These currents of this arrangement can be calculated from (7)-(9).

𝐼2 𝑄2 √3𝑅𝑠 𝑃 𝑅𝑠 𝑄 √3𝑃2
𝐼𝑐𝑠1 = [( + )+𝑗( − )] (7)
2 𝑅𝑠 2 +𝑄 2 𝑅𝑠 2 +𝑃2 𝑅𝑠 2 +𝑄2 𝑅𝑠 2 +𝑃2
𝑄2 𝑅𝑠 𝑄
𝐼𝑐𝑠2 = −𝐼2 ( +𝑗 ) (8)
𝑅𝑠 2 +𝑄2 𝑅𝑠 2 +𝑄2

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  203

𝑄2 𝑅𝑠 𝑄
𝐼𝑐𝑠2 = −𝐼2 ( +𝑗 ) (9)
𝑅𝑠 2 +𝑄2 𝑅𝑠 2 +𝑄2

The sheath losses per meter for each phase and the loss factor are written in (10)-(12):

𝑊𝑐𝑠1 = 𝐼𝑐𝑠1 2 𝑅𝑠 𝑊𝑐𝑠2 = 𝐼𝑐𝑠2 2 𝑅𝑠 𝑊𝑐𝑠3 = 𝐼𝑐𝑠3 2 𝑅𝑠 (10)


𝐼𝑐𝑠2 2 𝑅𝑠 𝑅𝑠 𝑄2
𝛿𝑐𝑠3 = = ( ) (11)
𝐼2𝑅 𝑅 𝑅𝑠 2 +𝑄2

𝐼𝑐𝑠3 2 𝑅𝑠 𝑅𝑠 𝑄2 3𝑃2 2𝑄𝑅𝑠 𝑃𝑋𝑚


𝛿𝑐𝑠1 = = [ + + ] (12)
𝐼2𝑅 𝑅 4(𝑅𝑠 2 +𝑄2 ) 4(𝑅𝑠 2 +𝑃2 ) √3(𝑅𝑠 2 +𝑄2 )(𝑅𝑠 2 +𝑃2 )

𝐼𝑐𝑠1,2,3 𝑠ℎ𝑒𝑎𝑡ℎ 𝑐𝑖𝑟𝑐𝑢𝑙𝑎𝑡𝑖𝑛𝑔 𝑐𝑢𝑟𝑟𝑒𝑛𝑡𝑠

𝑃 = 𝑋 + 𝑋𝑚
𝑋𝑚
𝑄= 𝑋−
3

𝛺
𝑅𝑠 : 𝑠ℎ𝑒𝑎𝑡ℎ 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑎𝑡 𝑚𝑎𝑥𝑖𝑚𝑢𝑚 𝑜𝑝𝑒𝑟𝑎𝑡𝑖𝑛𝑔 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒
𝑚
𝛺
𝑅: 𝑚𝑎𝑖𝑛 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 𝑟𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒
𝑚

Three-phase arrangement with sheaths cross-bonded for long-run length and spacing of cables can
be allowed by eliminating exaggerated sheath voltage and circulating current using cross-bonding methods.
Current-carrying capacity is improved after increasing cables spacing with this method because of each
cable's thermal independence. The induced voltage is canceled by dividing the cable run into three parts
(sections) and cross-connecting the sheaths, as explained in the Figure 3.
In the first part, the sheath end of the first cable is cut and connected to the sheath beginning of the
second cable in the middle part. It was connecting the second cable's sheath end-point with the third cable's
beginning sheath point in the last section to make the directional summation of induced voltages in all parts
equal to zero without flowing any circulating current except the eddy currents. This method is most likely to
be employed in very high voltage cables because its expansiveness [4], [23]−[25].

Figure 3. Sheath cross bonding

4.2. Sheath eddy losses


Whether single or three cores, different bonding methods and cable types will not prevent eddy
current losses from occurring. In solid bonding (two ends) for sheaths of single-core cable, the circulating
current losses are enormous compared to these losses, and therefore, they can be neglected if the cable
conductor layers have small segments. The flowing eddy current is due to the different voltages on the sides
of the sheath. The density of the non-uniform current in the cable conductors makes (ep) on the outer surface
of the sheath lower than on the inner one because of their convergence from each other. This indicates that
the divergent cables eliminate this type of currents [4], [22], [23]. The sheath eddy current and loss factor
will be calculated by (13) and (14).

3𝐼 2 𝜔2 𝑟𝑠ℎ 2
𝐼𝑆𝐸 = √ ( ) ∗ 10−14 (13)
𝑅𝑠 2 𝑆

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
204  ISSN: 2088-8694

3𝜔2 𝑟𝑠ℎ 2
𝛿𝑆𝐸 = ( ) ∗ 10−14 (14)
𝑅𝑠 𝑅 𝑆

Where:
δSE : Eddy loss factor of the sheath
ISE: Sheath eddy-current in A
Nevertheless, in the flat arrangement, their values calculated by (15) to (16).

3𝜔2 𝑟𝑠ℎ 2
𝛿𝑆𝐸1 = 𝛿𝑆𝐸3 = ( ) ∗ 10−14 (16) (15)
2𝑅𝑠 𝑅 𝑆

3𝐼 2 𝜔2 𝑟𝑠ℎ 2
𝐼𝑆𝐸1 = 𝐼𝑆𝐸3 = √ ( ) ∗ 10−14 (16)
2𝑅𝑠 2 𝑆

6𝜔2 𝑟𝑠ℎ 2
𝛿𝑆𝐸2 = ( ) ∗ 10−14 (17)
𝑅𝑠 𝑅 𝑆

6𝐼 2 𝜔2 𝑟𝑠ℎ 2
𝐼𝑆𝐸2 = √ ( ) ∗ 10−14 (18)
𝑅𝑠 2 𝑆

Where:
δSE1 , δSE3 , Eddy loss factor of the sheath in two outer cables
δSE2 , Eddy loss factor of the sheath in middle cable
ISE1, ISE3: Sheath eddy-current in two outer cables in A
ISE2: Sheath eddy-current in middle cable in A
In the sheath cross-banded case, the eddy loss factor and currents calculated by (19) and (20).

𝑅𝑠 (𝛽1 𝑡𝑠 )4
𝛿𝑆𝐸 = [𝑔𝑠 𝛶° (1 + 𝛥1 + 𝛥2) + ( )] (19)
𝑅 12∗1012

1
(𝛽1 𝑡𝑠 )4 2
𝐼𝑆𝐸 = 𝐼 [𝑔𝑠 𝛶° (1 + 𝛥1 + 𝛥2) + ( )] (20)
12∗1012

𝑡 1.74
𝑔𝑠 = 1 + ( 𝑠 ) (𝛽1 𝐷𝑠 10−3 − 1.6) (21)
𝐷𝑠

4𝜋𝜔
𝛽1 = √ 7 (22)
10 𝜌 𝑠

𝜌𝑠 : The electrical resistivity of sheath material at operating temperature (Ω.m)


D.S.: The external diameter of the cable sheath (mm)
𝑡𝑠 : The thickness of sheath (mm)
Δ1 and Δ2 are factors whose values depend on the types of cable layouts formation.
𝑔𝑠 and β1 are factors whose values depend on the cable parameters.
For (m ≤ 0.1, Δ1 and Δ2 can be neglected)
Where: (m) is a factor that depends on power frequency and metallic sheath resistance.
These values can be calculated from [4], [23], [24].

5. SIMULATION AND RESULTS


The (1) to (23) have been simulated by the method of mathematics simulation. All equations include
dependent and non-dependent variables. The independent variables were utilized as variable inputs to show
the effect on all equation's outputs. Figure 4 illustrates all of these inputs with their sub-inputs values. The
Figures 5-19 represent simulation parts of the sheath voltages, currents, and loss factors in one modeling for
two layout formations (trefoil and flat).

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  205

Figure 4. The input and their branches

Figure 5. Sheath voltage Us1, Us2, Us3 for trefoil arrangement single point earthing

Figure 6. Circulation (currents, losses and loss factor) simulation circuit equations of trefoil arrangement of
two-point earthling

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
206  ISSN: 2088-8694

Figure 7. Eddy (currents, losses, and loss factor) simulation circuit equations of trefoil arrangement

Figure 8. (x0, m, gs, G1) parameters for trefoil arrangement

Figure 9. Eddy (currents, losses, and loss factor) simulation circuit equations of trefoil cross bonding
arrangement earthing

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  207

Figure 10. Sheath voltage Us1, Us3 for flat arrangement single point earthing

Figure 11. Circulation currents simulation circuit equations of the flat arrangement of two points earthing

Figure 12. Circulation (losses and loss factor) simulation circuit equations of the flat arrangement of two-
point earthing

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
208  ISSN: 2088-8694

Figure 13. Eddy (currents, losses and loss factor) simulation circuit equations of flat arrangement

Figure 14. (x0, G1) parameters for center cable flat arrangement

Figure 15. (x0, G1, G2) parameters for leading cable flat arrangement

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  209

Figure 16. (x0, G1, G2) parameters for lagging cable flat arrangement

Figure 17. Eddy (currents, losses, and loss factor) simulation circuit equations for the center cable of flat
cross bonding arrangement

Figure 18. Eddy (currents, losses, and loss factor) simulation circuit equations for outer cable leading phase
of flat cross bonding arrangement

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
210  ISSN: 2088-8694

Figure 19. Eddy (currents, losses and loss factor) simulation circuit equations for outer cable lagging phase of
flat cross bonding arrangement

Parameters of input values for 1*400 mm2, 19/33 kv underground single core cable in Table 1 are
taken from [26]. When the value of the load current changes within the range (200-500), the cable sheathes'
voltages will change at the trefoil and flat arrangements as in Figure 20 in the case of the sheaths being
grounded from one end only. The sheathes of the three-phase for the trefoil, and the mid-phase one in the flat
arrangement will increase within the range (108.56-304) V, while the limits for those of the outer phases of
the flat arrangement are (169.8-475.4) V.
The circulating currents results when the sheaths are grounded at both ends are shown in Figure 21.
The circulating currents in the trefoil and the center one of the flat arrangements have equal values within the
range (17.22-48) A while the currents of the external cables increased within the range (26.8-75) A and
(27.25-78-26) A. The results show the difference in the rate of increase of sheath currents at low and high
load currents concerning cable sheaths for flat and trefoil arrangement. This is because the difference in
distances between the power cables in a flat one causes a difference (increase) in the reactance value on the
outer cable sheaths, thus an apparent increase in the sheath voltage circulating currents.

Table 1. Parameters of underground cable 1*400 mm2 19/33 kv


Cable parameters Parameters values
𝑑𝑐 22.6 mm
𝐴𝑠 35 mm2
𝑟𝑠ℎ 21.287 mm
S 50.5 mm
𝑅𝑑𝑐20 𝑓𝑜𝑟 𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑜𝑟 0.047 Ω/k
𝜌𝑠20 1.7241ˣ10−8 𝛺. 𝑚
𝛼𝑐 𝑜𝑟 𝑠 20 3.93ˣ10−3

Figure 20. Sheath voltages with load current Figure 21. Eddy currents with load current

The increase in the sheath circulating currents increases the sheath circulating losses and factors, as
shown in Figure 22 and within the range in Table 2. Figures 23 to 26 in addition to the Table 3 of information

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  211

for currents and their losses indicate that eddy currents decrease as the resultant magnetic flux which induces
the sheath voltage is more uniform on that sheath. This talk crystallizes its result in the external cables of flat
layout formation compared to those of the middle cable and the three cables of trefoil arrangement where
they carry the lowest sheath eddy currents and then cause the smallest losses.

Figure 22. Circulating losses with load current

Table 2. Sheath circulating currents, their losses and loss factors in trefoil and flat cables arrangements with
two-point bindings when the load current changes (200-500)
Sheath circulating currents, their losses and loss Values
Load currents (200-550) A
Circulating currents for trefoil and center cable in flat layout formation (17.22-48) A
Circulating current for the outer first cable in flat layout formation (26.8-75) A
Circulating currents for center cable in flat layout formation (12.64-34.75) A
Circulating current for the outer third cable in flat layout formation (27.25-78-26) A
Circulating losses for trefoil layout formation (1.86-14.6) KW
Circulating losses for the outer first cable in flat layout formation (4.521-35.44) KW
Circulating losses for center cable in flat layout formation (1-7.6) KW
Circulating losses for the outer third cable in flat layout formation (4.91-38.47) KW
Circulating factor for trefoil and layout formation 0.081
Circulating factor for the outer first cable in flat layout formation 0.2
Circulating factor center cable in flat layout formation 0.044
Circulating factor for the outer third cable in flat layout formation 0.214

Figure 23. Eddy currents with load current Figure 24. Eddy losses

Figure 25. Eddy currents cross-bonding Figure 26. Eddy losses cross-bonding

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
212  ISSN: 2088-8694

Table 3. Sheath eddy currents, their losses and loss factors in trefoil and flat cables arrangements with single,
two points
Sheath eddy currents, their losses and loss factors values
I load (200-550) A
Trefoil Sheath eddy currents (7.3-20.08) A
Flat Sheath eddy current for center cable (10.33-28.4) A
Flat Sheath eddy current for outer cables (5.164-14.2) A
Trefoil Sheath eddy losses (335.023-2534) W
Flat Sheath eddy losses for center cable (670.046-5067) W
Flat Sheath eddy losses for outer cables (167.51-1270) W
Trefoil Sheath eddy factor 0.015
Flat Sheath eddy factor for center cable 0.03
Flat Sheath eddy factor for outer cables 0.007
Trefoil Sheath eddy currents (cross-bonding) (7.42-20.4) A
Flat Sheath eddy current for center cable (cross-bonding) (10.32-28.37) A
Flat Sheath eddy current for first cable (cross-bonding) (5.41-15) A
Flat Sheath eddy current for third cable (cross-bonding) (5-13.7) A
Trefoil Sheath eddy losses (cross-bonding) (346.09-2617.3) W
Flat Sheath eddy losses for center cable (cross-bonding) (668.4-5055) W
Flat Sheath eddy losses for first cable (cross-bonding) (184.12-1392) W
Flat Sheath eddy losses for third cable (cross-bonding) (156-1180) W
Trefoil Sheath eddy loss factor (cross-bonding) 0.0151
Flat Sheath eddy loss factor for center cable (cross-bonding) 0.029
Flat Sheath eddy loss factor for first cable (cross-bonding) 0.008
Flat Sheath eddy loss factor for third cable (cross-bonding) 0.0068

The case of changing the length of cables with a constant load current at 400 A. The effect of
changing the cable's length on the values of both sheath voltages, circulating and eddy losses are evident in
Figures 27 (a)-(d), as its increasing increases the mentioned outputs while the currents causing these losses
remain unchanged. The external cables' position in the flat layout formation results in the highest levels of
circulating and the lowest eddy losses.

(a) (b)

(c) (d)

Figure 27. Voltages and losses with cable's length: (a) sheath voltages with length, (b) sheath circulation
losses with length, (c) sheath eddy losses with length and (d) eddy losses cross-bonding

Cables spacing effect with constant load current at 400 A and length = 10000 m. The cables' spacing
is considered an independent variable in a logarithmic function, causing an increasing of sheath voltages,
circulating currents, losses, and their factors with decreasing the eddy currents, their losses and factors

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  213

exponentially as explained in Figures 28 (a)-(h). Frequency effect at (50-60) range with constant load current
at 400 A, S=50.5 mm and length = 10000 m. All outputs will increase linearly with this range as explained in
Figures 29 (a)-(c), their ranges and those of the load current and length effect are smaller than the cables
spacing effect.

(a) (b)

(c) (d)

(e) (f)

(g) (h)

Figure 28. Voltages, currents, losses and factors with cable's spacing: (a) sheath voltages with spacing,
(b) circulating currents with spacing, (c) circulating losses with spacing, (d) circulating loss factor with
spacing, (e) eddy currents with spacing, (f) eddy losses with spacing, (g) eddy currents cross-bonding with
spacing and (h) eddy losses cross-bonding with spacing

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)
214  ISSN: 2088-8694

(a) (b)

(c)

Figure 29. Voltages and currents with frequency: (a) sheath voltages with frequency (b) sheath circulating
currents with frequency, and (c) sheath eddy currents with frequency

6. CONCLUSION
In (1) to (22) were simulated using the MATLAB program in this paper. The elements in the Math
Operation List were used to solve these equations. These equations' outputs are mainly related to the cables'
trefoil and flat arrangements when their sheaths are connected to the ground from one point, two points, or
cross-connected. Keep attention to load current, cable length, spacing, and power frequency values before
proceeding with any laying method. When the cable’s sheath is connected from two points, the load on the
cable should be reduced to less than the permissible limit when connected from one point because its
capacity will be minor. Otherwise, the cable will be broken down. The eddy current losses can be ignored
because it is minimal compared to the circulating current losses. It is not recommended to set the phase far
apart from each other because this leads to an increase in the sheath voltage and the circulating currents
exponentially. The sheath voltage can go up to 900 volts if one end is connected and the currents can arrive
to 160 amps if two ends are connected. This is very risky on the cable condition and the safety of the
electricians at maintenance. It is better to work at a frequency of 50 Hz. Finally, the best way to reduce the
sheath voltages without any circulating current will be determined, in addition, a second path to return the
fault current without weakening the cable connection points caused by all of the above methods. This process
can be done by cutting the sheaths of the long cables at every joint. First, all the points at the beginning of
every section are connected to the external insulated conductor. Then the cable is grounded from the two
ends to guarantee passing the fault current through the external cable without causing damage to the joints.
The total voltage of the sheath divided by the number of sections equals the sheath voltage of each section.
Thus, if any sheath fault happens, the circulating current will flow in the defective section.

REFERENCES
[1] J. R. R. Ruiz, A. Garcia, X. A. Morera, “Circulating sheath currents in flat formation underground power lines,” RE&PQJ,
vol. 1, no. 5, pp. 61-65, March 2007, doi: 10.24084/repqj05.217.
[2] B. Akbal, “Determination of the sheath current of high voltage underground cable line by using statistical methods,” International
Journal of Engineering Science and Computing, vol. 6, no. 3, pp 2188-2192, March 2016, doi: 10.4010/2016.529.
[3] C. K. Jung, J. B. Lee, J. W. Kang, X. Wang, and Yong-Hua Song, “Characteristics and reduction of sheath circulating currents in
underground power cable systems,” Int. J. of Emerg. Elect. Pow. Sys., vol. 1, no. 1, pp 1-17, 2004, doi: 10.2202/1553-779X.1008.
[4] O. E. Gouda and A. Farag, “Bonding methods of underground cables,” Cairo University, pp. 1-148, October 2015, doi:
10.13140/RG.2.1.2305.3527.
[5] M. Abdel-Salam, H. Anis, A. El-Morshedy, and R. Radwan, High Voltage Engineering Theory and Practice, New York: Marcel
Dekker, 2000.
[6] “IEEE Guide for the Application of Sheath-Bonding Methods for Single-Conductor Cables and the Calculation of Induced
Voltages and Currents in Cable Sheaths,” in ANSI/IEEE Std 575-1988, vol., no., pp. 0_1-, 1987, doi:
10.1109/IEEESTD.1987.122985.
[7] O. E. Gouda, A. Z. El Dein, and G. M. Amer, “Effect of the Formation of the Dry Zone Around Underground Power Cables on
Their Ratings,” in IEEE Transactions on Power Delivery, vol. 26, no. 2, pp. 972-978, April 2011, doi:
10.1109/TPWRD.2010.2060369.

Int J Pow Elec & Dri Syst, Vol. 13, No. 1, March 2022: 200-215
Int J Pow Elec & Dri Syst ISSN: 2088-8694  215

[8] H. Halperin and K. W. Miller, “Reduction of Sheath Losses in Single-Conductor Cables,” in Transactions of the American
Institute of Electrical Engineers, vol. 48, no. 2, pp. 399-414, April 1929, doi: 10.1109/T-AIEE.1929.5055229.
[9] M. Asif, H.-Y. Lee, K.-H. Park, and B.-W. Lee, “Accurate Evaluation of Steady-State Sheath Voltage and Current in HVDC
Cable Using Electromagnetic Transient Simulation,” Energies, vol. 12, no. 21, 4161, 2019, doi: 10.3390/en12214161.
[10] B. H. Allison, “Reduction of Sheath Losses on High Voltage Cables,” WIPO Patent WO/2002/027890A1, 2002.
[11] C.-K. Jung, J.-B. Lee, and J.-W. Kang, “Transient Analysis and Reduction Method of Sheath Circulating Current in Underground
Power Cable Systems,” IFAC Power Plants and Power Systems Control, Seoul. Korea, pp. 867-872, 2003.
[12] H. Ma, J. Song, P. Ju, and R. Fang, “Research on compensation and protection of voltage in metal shield of 110 kV power cable
under three segments unsymmetrical state,” 2008 IEEE Power and Energy Society General Meeting - Conversion and Delivery of
Electrical Energy in the 21st Century, 2008, pp. 1-5, doi: 10.1109/PES.2008.4596478.
[13] O. E. Gouda and A. A. Farag, “Factors affecting the sheath losses in single-core underground power cables with two-points
bonding method,” International Journal of Electrical and Computer Engineering (IJECE), vol. 2, no. 1, pp. 7-16, February 2012,
doi: 10.11591/ijece.v2i1.115.
[14] M. Santos and M. A. Calafat, “Dynamic simulation of induced voltages in high voltage cable sheaths: Steady state approach,”
International Journal of Electrical Power & Energy Systems, vol. 105, 2019, pp. 1-16, doi: 10.1016/j.ijepes.2018.08.003.
[15] C.-K. Jung, J.-B. Lee, and J.-W. Kang, “Sheath circulating current analysis of a cross bonded power cable systems,” J. Electr.
Eng. Technol., vol. 2, no. 3, pp. 320-328, doi: 10.5370/JEET.2007.2.3.320.
[16] G. J. Anders, “Rating of electric power cables in unfavorable thermal environment”, New Jersey: Wiley-IEEE Press, 2004.
[17] B. Akbal, “Determination of the sheath current of high voltage underground cable line by using statistical methods,” Int J Eng Sci
Comput, vol. 6, no. 3, pp. 2188–2192, 2016, doi: 10.4010/2016.529.
[18] I. Sarajcev, M. Majstrovic, and I. Medic, “Calculation of losses in electric power cables as the base for cable temperature
analysis,” Advanced Computational Methods in Heat Transfer VI, vol. 27, pp. 529–537, 2000, doi: 10.2495/HT000491.
[19] P. Ocłoń, P. Cisek, D. Taler, M. Pilarczyk, and T. Szwarc, “Optimizing of the underground power cable bedding using
momentum-type particle swarm optimization method,” Energy, pp. 230-239, 2015, doi: 10.1016/j.energy.2015.04.100.
[20] M. Shaban, M. A. Salam, S. P. Ang, and W. Voon, “Calculation of sheath voltage of underground cables using various
configurations,” 5th Brunei Int. Conf. on Engineering and Technology (BICET 2014), 2014, pp. 1-6, doi: 10.1049/cp.2014.1074.
[21] F. de Leon, M. L. Marquez-Asensio, and G. Alvarez-Cordero, “Effects of Conductor Counter-Transposition on the Positive-
Sequence Impedance and Losses of Cross-Bonded Cables,” in IEEE Transactions on Power Delivery, vol. 26, no. 3, pp. 2060-
2063, July 2011, doi: 10.1109/TPWRD.2011.2123473.
[22] M. Rasoulpoor, M. Mirzaie, and S. M. Mirimani, “Electrical and thermal analysis of single conductor power cable considering the
lead sheath effect based on finite element method,” Iranian J. of Electr. & Electronic Eng., vol. 12, no. 1, pp. 73-81, March 2016.
[23] D. Enescu, P. Colella, and A. Russo, “Thermal assessment of power cables and impacts on cable current rating,” Energies, vol.
13, no. 20, 5319, 2020, doi: 10.3390/en13205319.
[24] G. F. Moore, “Electric Cables Handbook,” Third Edition, Victoria: Blackwell Publishing company, 1997.
[25] Y. Yang, D. M. Hepburn, C. Zhou, W. Zhou, W. Jiang, and Z. Tian, “On-line monitoring and analysis of the dielectric loss in
cross-bonded HV cable system,” Electric Power Systems Research, vol. 149, pp. 89–101, 2017, doi: 10.1016/j.epsr.2017.03.036.
[26] “Energy cables product catalog,” 2020. Accessed: Dec. 29, 2021. [Online]. Available: https://www.hes.com.tr/assets/doc/Katalog.pdf

BIOGRAPHIES OF AUTHORS

Mahmood Natiq Abed is an engineer Department of high voltage underground


cables test and detection their faults. He received bachelor's degree from the Northern Technical
University 2005 in Electrical Engineering, master's degree from the University of Turkish
Aeronautical Association in (2017) in electrical and electronic engineering. Currently, he is
working as an employee in Ninavah Electricity Distribution Directorate at General Directorate
Electricity for North- Mosul-Iraq. He can be contacted at email: [email protected].

Osamah Abdulsalam Suhry Electrical Engineering, Electronics and


Communications Department B.sc. Degree, July 2005, Mosul University, Iraq. Electrical and
Electronics Engineering. Master. Degree, Jan 2018, University of Turkish Aeronautical
Association. Over 15 years of experience in electricity (planning, designing, installation and
maintenance) between 33/11 kv substations, 11/0.4 kv substations, underground cables 33 & 11
kv, smart meters systems, streets lighting systems, solar power systems and planning &
Designing experience in all types of electricity distribution networks. Excellent academic and
professional record. He can be contacted at email: [email protected].

Mohammed Ahmed Ibrahim is a teacher in Department of Electrical Power


Technologies Engineering. The official university email: Bachelor's degree from the Northern
Technical University 2005 in Electrical Engineering. Master's degree from the Northern
Technical University in (2011) in Electrical Engineering. Research published in international
journals, Scopus containers and science Seven, and Five internal and sponsored conferences.
Currently, is a lecturer in the Electrical Power Engineering specializing, at Northern Technical
University, Technical College of Engineering-Mosul-Iraq. He can be contacted at email:
[email protected].

Simulation of sheath voltage, losses and loss factor of high voltage underground … (Mahmood Natiq Abed)

You might also like